Date of purchase: _________________________________
Date of installation: _______________________________
Installer: ________________________________________
Model number: ___________________________________
Serial number: ___________________________________
Table des matières
SÉCURITÉ DE LA SÉCHEUSE ........................................24
Date d’achat : _____________________________________
Date d’installation : ________________________________
Installateur : ______________________________________
Numéro de modèle : ________________________________
Numéro de série : __________________________________
Gather the required tools and parts before starting installation.
Tools needed for all installations:
Flat-blade screwdriver
1/4" nut driver or socket
wrench (recommended)
#2 Phillips screwdriver
Tin snips (new vent
installations)
Tools needed for gas installations:
8" or 10" pipe wrench
Pipe-joint compound
resistant to LP gas
8" or 10" adjustable wrench
(for gas connections)
Parts supplied:
Tape measure
Level
Adjustable wrench that
opens to 1" (25 mm) or
hex-head socket wrench
Utility knife
4
Vent clamps
Pliers
Caulking gun and
compound (for installing
new exhaust vent)
Putty knife
Leveling legs (4)
Parts supplied (steam models):
“Y” connector
Parts package is located in dryer drum. Check that all parts
are included.
Short inlet hose
Rubber washer
Parts needed (steam models):
5' (1.52 m) inlet hose
Parts needed
Check local codes. Check existing electrical supply and venting.
See “Electrical Requirements” and “Venting Requirements”
before purchasing parts.
Check code requirements. Some codes limit, or do not permit,
installing dryer in garages, closets, mobile homes, or sleeping
quarters. Contact your local building inspector.
Optional Equipment: (Not supplied with dryer)
Refer to your “Use and Care Guide” for information about
accessories available for your dryer.
Location Requirements
You will need:
■ A location allowing for proper exhaust installation.
See “Venting Requirements.”
■ A separate 30 amp circuit for electric dryers.
■ A separate 15 or 20 amp circuit for gas dryers.
■ If you are using power supply cord, a grounded electrical
outlet located within 2 ft. (610 mm) of either side of dryer.
See “Electrical Requirements.”
■ A sturdy oor to support dryer and a total weight (dryer
and load) of 200 lbs. (90.7 kg). The combined weight of a
companion appliance should also be considered.
■ Level oor with maximum slope of 1" (25 mm) under entire
dryer. If slope is greater than 1" (25 mm), install Extended
Dryer Feet Kit, Part Number 279810. If not level, clothes
may not tumble properly and automatic sensor cycles may
not operate correctly.
Do not operate your dryer at temperatures below 45°F (7°C).
At lower temperatures, the dryer might not shut off at the end
of an automatic cycle. Drying times can be extended.
The dryer must not be installed or stored in an area where it will
be exposed to water and/or weather.
Check code requirements. Some codes limit, or do not permit,
installation of the dryer in garages, closets, mobile homes, or
sleeping quarters. Contact your local building inspector.
NOTE: No other fuel-burning appliance can be installed in the
same closet as a dryer.
Installation clearances:
The location must be large enough to allow the dryer door to
open fully.
A minimum of 5½" (140 mm) clearance is required behind
the dryer for the exhaust vent with elbow. See “Venting
Requirements.”
29" Wide Models Dryer Dimensions
Front View
29"
(737 mm)
433/8"
(1102 mm)
1
/2"
(13 mm)
NOTE: Leveling legs should be 1/2" (13 mm) (to match height of
3.6 cu. ft. capacity washer) or 1½" (38 mm) (to match height of
3.8 cu. ft. capacity washer).
Side View
223/4"
(578 mm)
Back View
273/4"
(705 mm)
133/4"
(349 mm)
AB
A. Wide opening side-swing door
B. Wide opening hamper door
4"
(101 mm)
301/4"
(768 mm)
273/4"
(705 mm)
3
4
/4"
(121 mm)
1
14
/2"
(368 mm)
3
4
/4"
(121 mm)
141/2"
(368 mm)
Steam Non-Steam
5
Installation Spacing
3"*
Side View
14"* max.
(356 mm)
51/2"*
(140 mm)
1"*
(25 mm)
*Required spacing
18"*
(457 mm)
1"*
(25 mm)
(76 mm)
3"*
(76 mm)
48 in.2*
(310 cm
24 in.
(155 cm
223/4"
(578 mm)
2
)
2
*
2
)
1
/2"
29
(749 mm)
133/4"
(349 mm)
(749 mm)
AB
291/2"
A. Wide opening side-swing door
B. Wide opening hamper door
Back View
27" Wide Models Dryer Dimensions
Front View
27"
(686 mm)
(1092 mm)
(13 mm)
43"
1
/2"
3
/8"
3
(85 mm)
14"
(356 mm)
Non-Steam
6
Installation Spacing
14"* max.
(356 mm)
18"*
(457 mm)
3"*
(76 mm)
48 in.2*
(310 cm
Installation spacing for recessed area
or closet
The dimensions shown are for the minimum spacing allowed.
■ Additional spacing should be considered for ease of
installation and servicing.
■ Additional clearances might be required for wall, door, and
oor moldings.
2
)
■ Additional spacing of 1" (25 mm) on all sides of the dryer is
recommended to reduce noise transfer.
■ For closet installation, with a door, minimum ventilation
openings in the top and bottom of the door are required.
Louvered doors with equivalent ventilation openings are
acceptable.
■ Companion appliance spacing should also be considered.
51/2"*
(140 mm)
1"*
(25 mm)
*Required spacing
1"*
(25 mm)
3"*
(76 mm)
2
24 in.
(155 cm2)
*
Mobile home – Additional installation
requirements
This dryer is suitable for mobile home installations. The
installation must conform to the Manufactured Home
Construction and Safety Standard, Title 24 CFR, Part 3280
(formerly the Federal Standard for Mobile Home Construction
and Safety, Title 24, HUD Part 280) or the Canadian
Manufactured Home Standard CAN/CSA-Z240 MH.
■ Metal exhaust system hardware, available for purchase.
For further information, please reference the “Assistance
or Service” section of the “Use and Care Guide.”
■ Special provisions must be made in mobile homes to
introduce outside air into the dryer. The opening (such
as a nearby window) should be at least twice as large
as the dryer exhaust opening.
7
Electric Dryer Power Hookup –
Canada Only
Electrical Requirements
GROUNDING INSTRUCTIONS
■
For a grounded, cord-connected dryer:
This dryer must be grounded. In the event of malfunction or
breakdown, grounding will reduce the risk of electric shock
by providing a path of least resistance for electric current.
This dryer is equipped with a cord having an equipmentgrounding conductor and a grounding plug. The plug must
be plugged into an appropriate outlet that is properly
installed and grounded in accordance with all local codes
and ordinances.
It is your responsibility:
■ To contact a qualied electrical installer.
■ To be sure that the electrical connection is adequate
and in conformance with the Canadian Electrical Code,
C22.1-latest edition and all local codes. A copy of the
above codes standard may be obtained from: Canadian
Standards Association, 178 Rexdale Blvd., Toronto, ON
M9W 1R3 CANADA.
■ To supply the required 4 wire, single phase, 120/240 volt,
60 Hz., AC only electrical supply on a separate 30-amp
circuit, fused on both sides of the line. A time-delay fuse or
circuit breaker is recommended. Connect to an individual
branch circuit.
■ This dryer is equipped with a CSA International Certied
Power Cord intended to be plugged into a standard 14-30R
wall receptacle. The cord is 5 ft. (1.52 m) in length. Be sure
wall receptacle is within reach of dryer’s nal location.
WARNING:
grounding conductor can result in a risk of electric shock.
Check with a qualied electrician or service representative
or personnel if you are in doubt as to whether the dryer is
properly grounded. Do not modify the plug provided with
the dryer: if it will not t the outlet, have a proper outlet
installed by a qualied electrician.
Improper connection of the equipment-
SAVE THESE INSTRUCTIONS
Gas Dryer Power Hookup
Electrical Requirements
4-wire receptacle (14-30R)
■ Do not use an extension cord.
If using a replacement power supply cord, it is recommended
that you use Power Supply Cord Replacement Part Number
8579325. For further information, please reference the
“Assistance or Service” section of the “Use and Care Guide.”
8
■ 120 Volt, 60 Hz., AC only, 15- or 20-amp fused electrical
supply is required. A time-delay fuse or circuit breaker is
recommended. It is also recommended that a separate
circuit serving only this dryer be provided.
GROUNDING INSTRUCTIONS
■
For a grounded, cord-connected dryer:
This dryer must be grounded. In the event of malfunction or
breakdown, grounding will reduce the risk of electric shock
by providing a path of least resistance for electric current.
This dryer is equipped with a cord having an equipmentgrounding conductor and a grounding plug. The plug must
be plugged into an appropriate outlet that is properly
installed and grounded in accordance with all local codes
and ordinances.
WARNING:
grounding conductor can result in a risk of electric shock.
Check with a qualied electrician or service representative
or personnel if you are in doubt as to whether the dryer is
properly grounded. Do not modify the plug provided with
the dryer: if it will not t the outlet, have a proper outlet
installed by a qualied electrician.
Improper connection of the equipment-
SAVE THESE INSTRUCTIONS
Gas Supply Requirements
LP gas conversion:
Conversion must be made by a qualified technician.
No attempt shall be made to convert the dryer from the gas
specied on the model/serial rating plate for use with a different
gas without consulting the serving gas supplier.
IMPORTANT: The gas installation must conform with local codes,
or in the absence of local codes, with the National Fuel Gas
Code, ANSI Z223.1/NFPA 54 or the Canadian Natural Gas and
Propane Installation Code, CSA B149.1.
Gas supply line
■ 1/2" NPT pipe is recommended.
■ 3/8" approved tubing is acceptable for lengths under
20 ft. (6.1 m) if local codes and gas supplier permit.
■ Must include 1/8" NPT minimum plugged tapping accessible
for test gauge connection, immediately upstream of the gas
connection to the dryer (see illustration).
■ Must include a shut-off valve:
In the U.S.A.:
An individual manual shut-off valve must be installed within
six (6) feet (1.8 m) of the dryer in accordance with the National
Fuel Gas Code, ANSI Z223.1.
In Canada:
An individual manual shut-off valve must be installed in
accordance with the B149.1, Natural Gas and Propane
Installation Code. It is recommended that an individual manual
shut-off valve be installed within six (6) feet (1.8 m)
of the dryer.
The shut-off valve location should be easy to reach for opening
and closing.
Gas type
Natural gas:
This dryer is equipped for use with Natural Gas. It is designcertied by CSA International for LP (propane or butane) gases
with appropriate conversion.
■ Your dryer must have the correct burner for the type of gas
in your home. Burner information is located on the rating
plate in the door well of your dryer. If this information does
not agree with the type of gas available, please reference the
“Assistance or Service” section of the “Use and Care Guide.”
C
BA
A. 3/8" flexible gas connector
B. 3/8" pipe to flare adapter fitting
C. 1/8" NPT minimum plugged tapping
D. 1/2" NPT gas supply line
E. Gas shut-off valve
E
Gas supply connection requirements
There are many methods by which your gas dryer can be
connected to the gas supply. Listed here are some guidelines
for two different methods of connection.
This dryer must be connected to the gas supply line with
a listed exible gas connector that complies with the standard
for connectors for gas appliances, ANSI Z21.24 or CSA 6.10.
Option 1 (Recommended Method)
Flexible stainless steel gas connector:
■ If local codes permit, use a new exible stainless steel gas
connector (Design Certied by the American Gas Association
or CSA International) to connect your dryer to the rigid gas
supply line. Use an elbow and a 3/8" are x 3/8" NPT adapter
tting between the stainless steel gas connector and the dryer
gas pipe, as needed to prevent kinking.
D
9
Option 2 (Alternate Method)
Approved aluminum or copper tubing:
■ Lengths under 20 ft. (6.1 m) can use 3/8" approved tubing
(if codes and gas supplier permit).
■ If you are using Natural Gas, do not use copper tubing.
■ 3/8" are x 3/8" NPT adapter tting between dryer pipe
and 3/8" approved tubing.
■ Lengths over 20 ft. (6.1 m) should use larger tubing and
a different size adapter tting.
■ If your dryer has been converted to use LP gas, 3/8" LP
compatible copper tubing can be used. If the total length
of the supply line is more than 20 ft. (6.1 m), use larger pipe.
NOTE: Pipe joint compounds that resist the action of LP
gas must be used. Do not use TEFLON®† tape.
Burner input requirements
Elevations up to 10,000 ft. (3,048 m):
■ The design of this dryer is certied by CSA International for
use at altitudes up to 10,000 ft. (3,048 m) above sea level at
the B.T.U. rating indicated on the model/serial number plate.
Burner input adjustments are not required when the dryer is
operated up to this elevation.
Elevations above 10,000 ft. (3,048 m):
■ When installed above 10,000 ft. (3,048 m), a 4% reduction
of the burner B.T.U. rating shown on the model/serial
number plate is required for each 1,000 ft. (305 m)
increase in elevation.
Gas supply pressure testing
■ The dryer must be disconnected from the gas supply piping
system during pressure testing at pressures greater than
1/2 psi.
Dryer gas pipe
■ The gas pipe that comes out through the rear of your dryer
has a 3/8" male pipe thread.
29" Wide Model
Install Leveling Legs
1.
Prepare dryer for leveling legs
To avoid damaging oor, use a large at piece of cardboard
from dryer carton; place under entire back edge of dryer.
Firmly grasp dryer body (not console panel) and gently lay
dryer down on cardboard.
2.
Screw in leveling legs
(235 mm)
3/8" NPT dryer pipe
27" Wide Model
1
/2"
1
53/4"
(146 mm)
(38 mm)
3/8" NPT dryer pipe
†®TEFLON is a registered trademark of E.I. Du Pont De Nemours and Company.
10
91/4"
1
/4"
1
(32 mm)
Using a wrench and tape measure, screw legs into leg holes
until bottom of foot is approximately 1/2" (13 mm) (to match
height of 3.6 cu. ft. capacity washer) or 1½" (38 mm) (to
match height of 3.8 cu. ft. capacity washer) from bottom of
dryer.
Now stand the dryer on its legs. Slide the dryer until it is
close to its nal location. Leave enough room for electrical
connection and to connect the exhaust vent.
For mobile home use
Gas dryers must be securely fastened to the oor.
Mobile home installations require a Mobile Home Installation
Hold-down Kit. For ordering information, please reference the
“Use and Care Guide.”
A
B
D
C
A
B
Make Gas Connection
Closed valve
Open valve
Venting
Connect gas supply to dryer
1.
Flared
male tting
Remove red cap from gas pipe. Using a wrench to tighten,
connect gas supply to dryer. Use pipe-joint compound
on threads of all non-ared male ttings. If exible metal
tubing is used, be sure there are no kinks.
NOTE: For LP gas connections, you must use pipe-joint
compound resistant to action of LP gas. Do not use
TEFLON®† tape.
Plan pipe tting connection
2.
Non-ared
male tting
Venting Requirements
WARNING: To reduce the risk of re, this dryer MUST BE
EXHAUSTED OUTDOORS.
IMPORTANT: Observe all governing codes and ordinances.
Dryer exhaust must not be connected into any gas vent,
chimney, wall, ceiling, attic, crawlspace, or a concealed space
of a building. Only rigid or exible metal vent shall be used for
exhausting.
A. 3/8" exible gas connector
B. 3/8" dryer pipe
A combination of pipe ttings must be used to connect dryer
to existing gas line. A recommended connection is shown.
Your connection may be different, according to supply line
type, size, and location.
Open shut-off valve
3.
Open shut-off valve in supply line; valve is open when handle
is parallel to gas pipe. Then, test all connections by brushing
on an approved noncorrosive leak-detection solution.
Bubbles will show a leak. Correct any leaks found.
C. 3/8" to 3/8" pipe elbow
D. 3/8" pipe-to-are adapter tting
4"
(102 mm)
4" (102 mm) heavy metal exhaust vent
■ Only a 4" (102 mm) heavy metal exhaust vent and clamps may
be used.
■ Do not use plastic or metal foil vent.
Rigid metal vent:
■ Recommended for best drying performance and to avoid
crushing and kinking.
Flexible metal vent: (Acceptable only if accessible to
clean)
■ Must be fully extended and supported in nal dryer location.
■ Remove excess to avoid sagging and kinking that may result
in reduced airow and poor performance.
■ Do not install in enclosed walls, ceilings, or oors.
■ The total length should not exceed 7
NOTE: If using an existing vent system, clean lint from entire
length of the system and make sure exhaust hood is not plugged
with lint. Replace plastic or metal foil vents with rigid metal
or exible metal vents. Review “Vent System Chart” and, if
necessary, modify existing vent system to achieve best drying
performance.
3
/4 ft. (2.4 m).
†®TEFLON is a registered trademark of E.I. Dupont De Nemours and Company.
11
Exhaust hoods:
A
■ Must be at least 12" (305 mm) from ground or any object that
may obstruct exhaust (such as owers, rocks, bushes, or
snow).
Recommended Styles:
Plan Vent System
Recommended exhaust installations
Typical installations vent the dryer from the rear of the dryer.
Other installations are possible.
B
C
D
E
Louvered hood Box hood
Acceptable Style:
Angled hood
Elbows:
■ 45° elbows provide better airow than 90° elbows.
Good
Better
Clamps:
■ Use clamps to seal all joints.
■ Exhaust vent must not be connected or secured with screws
or other fastening devices that extend into interior of duct
and catch lint. Do not use duct tape.
F
G
B
H
A. Dryer
B. Elbow
C. Wall
D. Exhaust hood
I
F. Rigid metal or flexible metal vent
G. Vent length necessary to connect elbows
H. Exhaust outlet
I. Optional side exhaust outlet
E. Clamps
Optional exhaust installations:
27" Wide Models can be converted to exhaust out the right side,
left side, or through the bottom (4-way vent kit). Each kit includes
step-by-step instructions. For ordering information, see “Venting
Kits.”
See “Venting Kits” for more information.
12
A B C
A. Standard rear offset exhaust installation
B. Left- or right-side exhaust installation (27" wide models only)
C. Bottom exhaust installation (27" wide models only)
Alternate installations for close clearances
Venting systems come in many varieties. Select the type best
for your installation. Two close-clearance installations are shown.
Refer to the manufacturer’s instructions.
Over-The-Top installation
(also available with one offset elbow)
Periscope installation
NOTE: The following kits for close clearance alternate
installations are available for purchase.
Venting Kits
For more information, call 1-800-901-2042, or visit us at
www.applianceaccessories.com. In Canada, call
1-800-807-6777 or visit us at www.whirlpoolparts.ca.
Part Number Descriptions
8171587RP0–5" Metal vent periscope
4396037RP0"-18" Metal vent periscope
4396011RP18" - 29" Metal vent periscope
439601429" - 50" Metal vent periscope
4392892In-Wall metal DuraVent™ Periscope
4396028Sure Connect™ venting kit
The exhaust vent must be securely fastened to a noncombustible
portion of the mobile home structure and must not terminate
beneath the mobile home. Terminate the exhaust vent outside.
Determine vent path:
■ Select route that will provide straightest and most direct path
outdoors.
■ Plan installation to use fewest number of elbows and turns.
■ When using elbows or making turns, allow as much room
as possible.
■ Bend vent gradually to avoid kinking.
■ Use as few 90° turns as possible.
Determine vent length and elbows needed for
best drying performance:
■ Use following “Vent System Chart” to determine type of vent
material and hood combinations acceptable to use.
NOTE: Do not use vent runs longer than those specied
in “Vent System Chart.” Exhaust systems longer than those
specied will:
■ Shorten life of dryer.
■ Reduce performance, resulting in longer drying times and
increased energy usage.
The “Vent System Chart” provides venting requirements that
will help achieve best drying performance.
Vent System Chart
Number of
90° turns
or elbows
0Rigid metal64 ft. (20 m)58 ft. (17.7 m)
1Rigid metal54 ft. (16.5 m) 48 ft. (14.6 m)
2Rigid metal44 ft. (13.4 m) 38 ft. (11.6 m)
3Rigid metal35 ft. (10.7 m)29 ft. (8.8 m)
4Rigid metal27 ft. (8.2 m)21 ft. (6.4 m)
NOTE: Side and bottom exhaust installations for 27" wide
models have a 90º turn inside the dryer. To determine
maximum exhaust length, add one 90º turn to the chart.
Type
of vent
Box/louvered
hoods
Angled
hoods
13
12" min.
(305 mm)
12" min.
(305 mm)
Vent System Chart
(Long Vent Models Only)
Number of
90° turns
or elbows
0Rigid metal120 ft. (36.6 m)
1Rigid metal110 ft. (33.5 m)
2Rigid metal100 ft. (30.5 m)
3Rigid metal90 ft. (27.4 m)
4Rigid metal80 ft. (24.4 m)
5Rigid metal70 ft. (21.3 m)
Type
of vent
Install Vent System
Install exhaust hood
1.
Box/louvered, or
Angled hoods
Connect Inlet Hoses
(Steam Models Only)
For non-steam models, skip to “Connect Vent.”
The dryer must be connected to the cold water faucet using
the new inlet hoses. Do not use old hoses.
Turn cold water off, remove and
1.
replace rubber washer
Turn cold water faucet off and remove washer inlet hose.
Remove old rubber washer from inlet hose and replace
with new rubber washer.
Attach short hose and
2.
“Y” connector
Install exhaust hood and use caulking compound to seal
exterior wall opening around exhaust hood.
Connect vent to exhaust hood
2.
Vent must t over the exhaust hood. Secure vent to exhaust
hood with 4" (102 mm) clamp. Run vent to dryer location
using straightest path possible. Avoid 90° turns. Use clamps
to seal all joints. Do not use duct tape, screws, or other
fastening devices that extend into interior of vent to secure
vent, because they can catch lint.
Attach 2 ft (0.6 m) inlet hose to cold water faucet. Screw on
coupling by hand until it is seated on faucet. Then attach
“Y” connector to end of the 2 ft (0.6 m) inlet hose. Screw on
coupling by hand until it is seated on “Y” connector.
Tighten couplings
3.
Using pliers, tighten the couplings with additional two-thirds
turn.
NOTE: Do not overtighten. Damage to the coupling can result.
14
Attach long hose to “Y”
4.
connector and tighten couplings
Attach dryer 5 ft (1.5 m) inlet hose ends to the “Y” connector.
Attach washer cold inlet hose to other side of “Y” connector.
Screw on coupling by hand until it is seated on connector.
Using pliers, tighten the couplings an additional two-thirds
turn.
NOTE: Do not overtighten. Damage to the coupling can result.
Attach long hose to dryer ll
5.
valve and tighten coupling
1
/4"
30
(768 mm)
7.
Check for leaks
Check for leaks around “Y” connector, faucet, and hoses.
Connect Vent
Connect vent to exhaust outlet
1.
(101 mm)
Attach other end of long hose to
ll valve at top of dryer back panel.
Screw on coupling by hand until
it is seated on ll valve connector.
Using pliers, tighten the coupling
an additional two-thirds turn.
NOTE: Do not overtighten. Damage
to the coupling can result.
Turn on cold water faucet
6.
4"
Using a 4" (102 mm) clamp, connect vent to exhaust outlet
in dryer. If connecting to existing vent, make sure vent is
clean. Dryer vent must t over dryer exhaust outlet and inside
exhaust hood. Check that vent is secured to exhaust hood
with a 4" (102 mm) clamp.
Move dryer to nal location
2.
Move dryer to nal location. Avoid crushing or kinking vent.
Check that the water faucet is turned on.
15
Loading...
+ 33 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.