Westermo MA-21 User Manual

Strömslingeomvandlare
Current Loop Converter
Stromschleifenwandler
INSTALLATIONSANVISNING
INSTALLATION MANUAL
INSTALLATIONS ANLEITUNG
6021-2002
MA-21 AC
MA-21 DC
©
Westermo Teleindustri AB • 1998 • REV. A
Galvanic
Isolation
Transient
Protection
Balanced
TransmissionCEApproved
8 6021-2002
Switch settings
The MA-21 can through different switch settings be adapted to a vareity of running conditions. To set the switches, open the plastic case by placing and turning a screw­driver between top and bottom at the rear of the case.
DANGER! DO NOT OPEN CONNECTED UNIT
12345
V.24/RS-232-C CONNECTION
LINE
CONNECTION
MAINS
Specifications
Transmission Asynchronous, full/half duplex or simplex Interface 1 EIA RS-232-C/CCITT V.24
25-position D-sub female, DCE
Interface 2 20 mA current loop, selectable active or passive Data rate Up to 19.2 bit/s Indicators Power, RD, TD Isolation Galvanic isolation with opto-coupler (data transmission)
and transformer (supply)
Isolation voltage 1500V Overvoltage protection Mains: Breakdown voltage 440V at 230V AC
and 220V at 115V AC Interface 2: Breakdown voltage transmitter and receiver 37V Surge capacity 0.6 kW for 1ms
Power supply Switchable 115/230V +15/ –10% 48–62Hz Fuse 100mA fast 5x20 mm Power consumption Max 5VA at 230V AC Temperature range 5–50°C, ambient temperature Humidity 0–95% RH, non-condensing Dimensions WxHxD 161x53x139 mm Weight 0.5 kg Mounting With rubber pads or screws. Screws: remove
the two "keyholes" on the bottom of the case
96021-2002
ON OFF
S4
1 - 6
ON OFF
S5 S1
1 - 91 - 6 1 - 4
S2S3
S1 Selection of transmitted signal, selection
of signal controlling CTS
S2 Selection of transmitter/receiver
normal or inverted S3 Selection of receiver active/passive S4 Selection of transmitter active/passive S5 Selection of power supply
115/230V AC
Receiver active/passive
Factory settings
S3
S3
ON
123456
ON
123456
Transmitter active/passive
Passive
S4
Active
S4
ON
123456
ON
123456
Passive
Transmitted signal
Active
ON
123456789
TD
S1
ON
123456789
S1
ON
123456789
AUX
S1
ON
123456789
SRS
S1
ON
123456789
DTR
S1
CTS controlled by
ON
123456789
RTS
S1
ON
123456789
RD
S1
ON
123456789
Always high
S1
Inverted Transmitter/Receiver
Transmitter
Normal Normal
Normal
Inverted
Inverted
Inverted
Normal
Inverted
Receiver
S2
S2
S2
S2
ON
1234
ON
1234
ON
1234
ON
1234
S2
ON
1234
S3
ON
123456
S4
ON
123456
10 6021-2002
Cable
42pF/m
0.3mm
2
1200
5000m
600
6000m
2400
4000m
4800
3000m
9600
500m
19200
200m
I 2 103 TD/Transmitted Data
O 3 104 RD/Received Data
I 4 105 RTS/Request To Send O 5 106 CTS/Clear To Send O 6 107 DSR/Data Set Ready
7 102 SG/Signal Ground
O 8 109 DCD/Data Carrier Detect
I 11 AUX/Auxiliary
I 19 120 SRS/Secondary Request to Send
I 20 108/2 DTR/Data Terminal Ready
Receiver 1 R+ Receiver 2 R­Transmitter 3 T+ Transmitter 4 T-
5 Shield
No.
1) I= Input O= Output on MA-21
Direction
Description
Description
Direction 1)
Pin no.
CCITT V.24
Circuit no.
Connections
Line connection
(5-position screw-terminal)
Terminal connection (DCE) (RS-232-C/V.24, 25-position D-sub, female)
5
Line connection
Transmitter
Receiver
Receiver
Transmitter
Shield 1)
4
3
2
1
R+ R­T+ T-
T+ T­R+ R-
MA-21
Twisted pairs
20mA current loop
equipment
1) If shielded cable is used, connect the shield only at one end to avoid ground currents.
Transmission range (interface 2)
Transmission rate bit/s
116021-2002
1 – Voltage 2 + Voltage 3
MA-21 DC
Specifications Power supply 12–36V DC Power consumption Max 3W Insulation 1000V Fuse F1 1.6 A fast 5x20 mm
All other specifications according to MA-21 AC
Switch settings
According to MA-21 AC
Connections
According to MA-21 AC, except power supply
Connection
no.
Power Supply
12345
V.24/RS-232-C CONNECTION
LINE
CONNECTION
123
POWER
12-36VDC
12 6021-2002
Hints
The 20mA current loop interface, or TTY as it is sometimes known, is a popular industrial communications standard. The system relies on a current generator running on both the transmit and receive circuits. On each circuit it is important to have only one current generator supplying current into that circuit. For this reason the MA-21 can have it’s current generators set to be either active or passive. It is important to check the state of all attached equipment to ensure correct setting on the MA-21. The MA-21 has the same line interface as MD-21, MD-29 and are hence compatible.
The RS-232 interface is configured as DCE (Data Communication Equipment). Most printers, PC’s and terminals are set as DTE (Data Terminal Equipment). Some recomen­dation of cable configurations are given below.
If any problems do occur on set up of theMA-21, the LED’s will be helpful.
• PWR: The unit has power.
• RD: Data received on line interface.
• TD: Data received on RS-232 interface. A good way to check the MA-21 is to carry out a loop back test. Ensure that either the
transmitter or receiver are set to active, but not both active or passive. Connect T+ to R+ and T- to R-. Connect the RS-232 port to a terminal. When keys are pressed on the terminal you should receive the echo on screen. The TD & RD lights will both flicker simultaneously as you press the keys.
1 2 3 4 5 6 7 8
9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25
1 2 3 4 5 6 7 8
9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8
9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25
1 2 3 4 5 6 7 8
9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25
1 2 3 4 5 6 7 8
9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25
DTE MA-21 DTE MA-21 9-pos. PC MA-21
136021-2002
Connecting the MA-21 in a current loop
4 3
43
RD
21
2 1
43 21
TD TD
TD
S1: 1, 5, 7, 8 on S2: 1, 3 on S3: 3–6 on S4: 3–6 on
S1: 1, 5, 7, 8 on S2: 1, 3 on S3: 1, 2 on S4: 1, 2 on
RD
RD
Functional description
The TD led flashes on the master when transmitting from it. The RD led flashes on the slaves. When transmitting from a slave the TD led flashes only on that unit. The RD led flashes only on the master modem.
Functional description
When transmitting from the master, RD and TD flash. RD flashes on the slaves. When transmitting from a slave both RD and TD flash. On the other slaves and the master RD flashes.
Full duplex transmission
4 3
43
RD
21
2 1
43 21
TD
Slave Slave
SlaveSlave
TD
TD
S1: 1, 5, 7, 8 on S2: 1, 3 on S3: 1, 2 on S4: 3–6 on
S1: 1, 5, 7, 8 on S2: 1, 3 on S3: 1, 2 on S4: 1, 2 on
RD
RD
Half duplex transmission
Westermo Teleindustri AB • S-640 40 Stora Sundby, Sweden
Phone +46 16 612 00 Fax +46 16 611 80
E-mail: info@westermo.se • Westermo Web site: www.westermo.se
Westermo Teleindustri AB have distributors in several countries,
contact us for further information.
Westermo Data Communications GmbH Bruchsaler Straße 18, 68753 Waghäusel Tel.: +49(0)7254-95400-0 • Fax.:+49(0)7254-95400-9 E-Mail: westermo.germany@t-online.de
Westermo Data Communications Ltd Solent Business Centre • Millbrook Road West Millbrook, Southampton • SO15 0HW Phone: +44(0)1703-704 611 • Fax.:+44(0)1703 702 682 E-Mail: sales@westermo.co.uk
Subsidiaries
V.24/RS-232
PE
SG
Line
T+
T-
TD
AUX
SRS DTR
DSR DCD
PG
Power
Supply
R+
R-
CTS
RTS
RD
Shield
7
0V
+12V
6 8
3 420
19
1 211
2
TD
2)
S1
3
S2
R51
R47
+24VB
0V
0VB
+12V
-12V
Isolated power supply
F1
1
+12V
1 2
0VB
1 4 2 5
6
3
4
20mA
+24VB
R49
PE
1
0VB
1
4 2 5 6
3
2
20mA
+24VB
R50
PE
R48
PE
S4
RD
3 4
S2
8 74
5
9
S1
6 5
3
1)
1)
1)
1)
+12V
PWR
5
0VB
S3
Block diagram
1) 0 Ω resistors R48-R51 are normally not mounted.
2) Metal housing on D-sub is connected to PE