Weil-McLain Radiant Heater User Manual

Page 1
®
AlumiPex
Radiant Tubing
Above Floor
Installation Guide
These Instructions must be used only by a qualified installer/service technician. Read these instructions completely before beginning. Failure to follow these instructions can cause severe personal injury, death or substantial property damage.
Part No. 650-000-221/0298
Page 2
AlumiPe x Radiant Tubing
Hazard Definitions
Indicates presence of hazards that will cause severe personal injury, death or substantial property damage.
Indicates presence of hazards that will or can cause minor personal injury or property damage.
Codes and Standards
This guide is provided for general information only. The building or heating system designer is responsible for all design details and for compliance with all building codes, local and national.
Refer to AlumiPex Technical Information sheets for specific approvals and listings of AlumiPex Radiant Tubing.
Indicates presence of hazards that can cause severe personal injury, death or substantial property damage.
Indicates special instructions on installation, operation or maintenance that are important but not related to personal injury or property hazards.
AlumiPex Radiant Tubing is not approved for potable water applications.
Consult local requirements before installing a radiant heating system. Install AlumiPex tubing following all of the applicable codes and all specifications and methods prescribed by the building designer and heating system designer.
Do not use AlumiPex Radiant Tubing to conduct natural gas. Such an application could result in severe personal injury, death or substantial property damage.
Do not expose AlumiPex Radiant Tubing to petroleum products or solvents. Do not weld or glue AlumiPex. Do not secure AlumiPex tubing permanently with adhesive tape. The tubing could be damaged, resulting in risk of severe personal injury, death or substantial property damage.
Finished Flooring: Use only finished flooring rated by the flooring manufacturer for use with heated floors. Failure to follow this guideline could result in substantial property damage.
Do not use AlumiPex Radiant Tubing in potable water or combination space heating/ potable water heating applications. The tubing is not approved for domestic water use. In combination space heating/potable water heating applications, chemical or biological contamination in the system water is possible and could result in severe personal injury, death or substantial property damage.
Use only AlumiPex Fittings with AlumiPex Tubing. Use of any other method can result in severe personal injury, death or substantial property damage.
This installation guide covers both new construction and retrofit. For retrofit of a completed building review the Trade Guides with the building owner if there is no general contractor involved in the remodeling project.
2
Part Number 650-000-221/0298
Page 3
Above Floor Installation Guide
ALUMIPEX STEP-BY-STEP - - ­ABOVE FLOOR INSTALLATION
Page CONTENTS
4
7
8
9
10
11
11
12
Tube Layouts for Radiant Heating
Obtain Tube Layout Drawing
Meet with General Contractor
Obtain Materials
Obtain Special Equipment
Pre-Installation Check List
Mark Tube Layout on Subfloor
Mount Manifold(s)
Heating
Contractor
!
Set Tube Layout
!
Review Plans and Trade Guides with General Contractor
!
Purchase materials and equipment
TYPICAL SEQUENCE
Others
Calculate heat loss
!
and design radiant system
Site Preparation
!
Rough in utilities
!
Pour Foundation &
!
Main Slab Building Closure
!
Interior Framing,
!
Plumbing, Electrical
14
17
18
18
18
19
19
Part Number 650-000-221/0298
Install the Tubing
Pressure Test Tubing
Connect System Piping
Pressurize Tubing for Observation
Before Leaving the Jobsite . . .
Inspect Tubing Before Flooring Inst.
Inspection, Repair & Troubleshooting
Install and Test
!
AlumiPex Manifolds and Tubing Install System Piping
!
& Heating Components
! Inspect and Test
System After Building Completion
Drywall
!
Finish Carpentry
!
Finish Flooring
!
3
Page 4
AlumiPe x Radiant Tubing
A. Tube Layouts for Radiant Heating
1. Radiant Floor Heatng
a. Hot water flowing in the radiant tubing under the
finished flooring heats the flooring and the heat emission plates. The heat emission plates help spread the heat evenly across the flooring.
b. Heat must pass through the flooring and the
coverings on the floor (low pile carpeting and thermal pads, for example). See Figure 1.
The more the flooring and coverings act as insulators, the higher the tube water temperature has to be to cause the floor surface to heat up.
Heavy carpeting and pads resist heat transfer and are not recommended for use in radiant floor heating.
c. Heat will also try to move downward.
In suspended floor applications, heat will try to pass to the space underneath. So insulation is needed under the floor to prevent this heat movement.
2. Heat Output from Radiant Floors
a. The floor surface is usually heated to a maximum
temperature of about 85 oF - the surface temperature of human skin.
Higher floor temperatures in occupied areas could be uncomfortable.
Floor surface temperatures up to 92 oF are often used around the outside perimeter of rooms and in other areas where foot contact is limited.
b. The heat given off by the floor depends on the
difference between the room temperature and the floor temperature - the larger the difference in temperature, the greater the heat.
With the floor at 85 oF and room temperature at 70 oF, each square foot of the heated floor will give off about 30 Btu’s per hour.
c. The spacing of tubes affects how much heat can be
moved through the floor.
Closer spacing increases the heat per square foot of floor.
This is why tubes are often spaced closer together along outside walls with high heat losses - like next to large windows or patio doors.
Figure 1 - Heat flow from tube through slab
CarpetCarpet PadPad
SubfloorSubfloor
SleepersSleepers SleepersSleepers
SubfloorSubfloor
InsulationInsulation
TubeTube
Heat Emission PlateHeat Emission Plate
JoistJoist
3. Radiant Floor Heating Design
a. The heating system designer must determine:
The heat loss for each room.
Square feet of room floor surface available for floor heating.
The water temperature in the tubing and spacing between tubes - to match the heat given off by the floor to the heat lost from the room.
4. Tube Layout Patterns
a. The routing of the tubing in the room affects room
comfort and effectiveness of the floor heating system.
b. Figure 2 shows typical tube layouts for above floor
installations.
Where possible, the hottest water is usually routed along the outside walls.
Tube routing in above floor installations is limited by the practicality of variations in sleeper layouts. Sleepers are the boards used to separate the tubing and support the flooring.
c. Where the outside wall loss is particularly high,
such as caused by patio doors, the tubing will sometimes be spaced closer together for a few feet out from the wall as shown in Figure 2.
b. Pay close attention to the key information given in
these illustrations, such as:
flow direction
minimum bend diameters
spacing to walls
heat emission plates
passage under walls
use of closer spacing
4
Part Number 650-000-221/0298
Page 5
Above Floor Installation Guide
Figure 2 - Typical tube routing for an above floor installation
ABOVE FLOOR INSTALLATION
(One-Way Serpentine Patterns - Typical)
Outside Wall
Interior Partition
Supply
Constant Spacing
Outside Wall Concentrated Spacing
(Wall with large window area or cool wall)
Outside Wall
Interior Partition
Interior Partition
Return
These drawings are conceptual only. Consult Weil-McLain Radiant Guides or Software for actual project layout.
Interior Partition
Supply
Interior Partition
Return
Interior Partition
NOTE FLOW DIRECTION
!
The warmest water is directed next to the outside wall.
BEND DIAMETER
Maintain a MINIMUM bend diameter of:
!
1/2“ Tube - 6 inches 5/8“ Tube - 7 inches
!
3/4“ Tube - 8 inches
!
DISTANCE TO WALL
!
Keep the tubing 4 to 6 inches from the walls. This will reduce the chance of damage due to drilling,
!
sawing or nailing.
Part Number 650-000-221/0298
Bend
Diameter
USE HEAT EMISSION PLATES
!
Snap the tubing into AlumiPex Heat Emission Plates placed on the sleepers.
These plates spread the heat evenly to the floor and ensure
!
that the tubing is maintained in tight contact with the flooring above.
Staple the heat emission plates to the sleepers on one side
!
only to allow the plates to conform as the flooring or subfloor is installed.
PASSAGE UNDER WALLS
!
Avoid running tube under walls if possible. Where tubing must run under a wall, mark the framing
!
above for 6 inches on either side of this location so no fasteners will be driven into the framing near the tubing.
CLOSER SPACING
!
Tubing is often spaced closer near outside walls with cool surface temperatures or large window areas.
5
Page 6
AlumiPe x Radiant Tubing
Figure 6 - T ypical tube layout drawing
TUBE LAYOUT DRAWING - Typical
washer / dryer
DINING
LR1
KITCHEN
DK
LIVING ROOM
LR2
U T
I
L
I
T
UT
Y
Slab Control Joint
MANIFOLD
BEDROOM
BR1
BT
B A T H
BEDROOM
This drawing is conceptual only. Consult Weil-McLain Radiant Guides or Software for actual project layout.
BR3
BEDROOM
BR2
Tubing
Circuit
Finished Flooring
Tube Spacing
(Center to Center)
Circuit
Length
Leader Length
Length
Allowance
Normal Close
Inches Inches Feet Feet Feet Feet
LR1 Low pile carpet w/ thermal pad 8.5 178 43 10 231 LR2 Low pile carpet w/ thermal pad 8.5 6.5 192 22 10 224
DK Laminatedhardwood 12.5 6.5 227 28 10 265 UT Ceramic tile 6.5 45 4 10 59
BT Ceramic tile 6.5 79 12 10 101 BR1 Laminated hardwood 8.5 6.5 141 22 10 173 BR2 Laminated hardwood 8.5 6.5 163 22 10 195 BR3 Laminated hardwood 8.5 6.5 156 19 10 185
Coil
Number
Coil Length Tube Size
1 1000 feet 1/2" 974 2 300 feet 1/2" 286 3 300 feet 1/2" 173
Use for Circuits Listed
LR1, LR2, DK, UT & BR2
BT & BR3
BR1
Total Tube
Length
Total
Length
6
Part Number 650-000-221/0298
Page 7
Above Floor Installation Guide
B. Obtain Tube Layout Drawing
Floor Plan/Layout Should . . . . . . . . . .
!
Be drawn to scale using a CAD program so tube lengths can be calculated by the program.
!
Show complete floor plan, including all appliances, cabinets, fireplaces and any other details which could affect the routing of the tubing.
!
Show complete layout of all circuits.
!
Provide length of each circuit, including leader length. are the tubing runs connecting
Leaders
from the room circuits to the manifold(s).
The heating system designer may add an allowance to the total length to account for variations in actual installation. This might range from 3 to 10% depending on the type of installation. In the example shown at left, the designer used a length allowance of 10 feet.
!
Show tube spacing and flow directions.
!
State finished flooring assumed for each space.
Note Tube Routing
!
Run leaders (connecting tubing from manifolds to circuits) through hallways.
!
Run leaders and tubing under doorways.
!
Avoid running under walls to reduce chances of damage from fasteners.
!
Mark the framing above where tubing runs under walls so all trades will be aware.
!
If tubing must penetrate a firewall, follow local codes regarding sleeving and fire stopping requirements.
1. Do not start a radiant heating installation without a detailed tube layout drawing.
It provides critical information on:
tube routing
tube lengths
areas to be avoided
materials needed
2. Figure 3 includes the information and drawing detail for a typical tube layout drawing.
3. A complete, accurate drawing of the tube layout is the most important key to a successful job.
DO NOT Run Tubing:
!
Under cabinets, refrigerators, ranges, freezers. These items "block" the heat and the tubing would be wasted.
!
Within 8 inches of toilet flanges. The wax ring seal may soften and fail from the heat.
!
Under fireplaces, ovens, appliances or other heat sources.
!
Closer than 4" from walls.
!
Closer than 6" from appliance vents or flues.
Part Number 650-000-221/0298
7
Page 8
AlumiPe x Radiant Tubing
C. Meet with General Contractor
1. W e suggest you meet with the general contractor and follow this checklist:
q Review the AlumiPex Trade Guides with the
general contractor and ask him to provide the information and copies to each of the trades involved.
q Verify that the flooring system is rated by the
flooring manufacturer for use with heated floors.
q Verify architectural details affected by the
flooring system. Verify that the building designer has allowed for the following:
The rough openings for doors and windows
allow for the height of the flooring system.
Stair risers include allowance for the height
of the flooring system.
q Ensure that the tubing will be stored inside until
time for use.
AlumiPex is specially designed to protect the
tubing from damaging ultraviolet rays. However, avoid exposing the tubing to direct sunlight for extremely long periods.
Do not install AlumiPex tubing in
applications which will continuously expose the tubing to direct sunlight.
q Discuss the tube layout drawing with the general
contractor and verify:
q If the tubing passes under any interior walls, you
should mark these locations on the framing above.
Ask the general contractor to notify other
trades to watch for these markings to ensure tubing will not be damaged by fasteners.
q If the tubing passes through stud walls, the
framing carpenters should apply nail stops on both sides of the stud at these locations.
Ask the general contractor to notify other
trades to watch for these locations to ensure tubing will not be damaged by fasteners.
q A copy of the tube layout drawing should be
given to the general contractor to ensure a trouble-free installation.
You will probably want to provide a final
copy after the installation is complete.
The final copy should show special
notations, any changes from the original plan, and locations of any repairs.
floor plan design has not been changed. finished floorings (and coverings) shown by
heating system designer are correct per final design.
8
Part Number 650-000-221/0298
Page 9
Above Floor Installation Guide
D. Obtain Materials
1. AlumiPex Tubing
In rolls and sizes specified on tube layout drawing.
2. AlumiPex Tube Fittings
Refer to AlumiPex Fitting Instructions for part numbers and procedures.
Use only AlumiPex Fittings with AlumiPex Tubing. Use of any other method can result in severe personal injury, death or substantial property damage. Refer to AlumiPex Fitting Instructions for selection and application of fittings.
3. AlumiPex Manifolds
Available in three sizes (2, 3 and 4 takeoff) in nickel-plated brass (shown above), with or without integral balancing valves .
Copper manifolds (not shown) are also available.
Refer to AlumiPex Manifold Instructions for part numbers and procedures.
4. Additional Materials
a. AlumiPex Heat Emission Plates
These are sized and designed specifically for
use with AlumiPex ½” tubing.
See Figure 11, Page 16.
Do not apply tubing in above floor
installations without heat emission plates. Heat will be uneven and could cause shrinkage or damage to flooring.
b. Staples
Use staples sized so as not to penetrate deeper
than the subfloor. Usually, 5/8” staples will work well.
c. Poly-wrapped insulation (if not already installed in
joist bays below)
e. Manifold Enclosure(s) (Optional)
30” x 27” or 30” x 37”.
Part Number 650-000-221/0298
9
Page 10
AlumiPe x Radiant Tubing
E. Obtain Special Equipment
3. AlumiPex Reamer/Sizer(s)
The reamer/sizer is specific to tube diameter.  Make sure to have the right reamer/sizer for each
size of tubing being installed.
1. Tubing Uncoiler
Assists in tube installation.
2. AlumiPex Tube Cutter
4. Pressure Gauge
With a scale range of 150 psig. For pressure testing and tubing pressurization.
10
Part Number 650-000-221/0298
Page 11
Above Floor Installation Guide
F. Pre-Installation Check List
q Subfloor must be installed.
q Make provision for pressure testing:
W ater if no freeze concern.
q Interior framing should be completed, but drywall
and finish carpentry not in place if possible.
Otherwise, air compressor and hoses for air test and pressurization.
q Read this installation guide, the AlumiPex Fitting
q Review AlumiPex T rade Guides with general
contractor to ensure other trades will be informed.
Instructions and AlumiPex Manifold Instructions thoroughly .
G. Mark Floor Plan and Tube Layout on Subfloor
1. Use the T ube Layout Plan to mark the following on the subfloor . Use several colors if possible to define different elements and circuits.
See Figure 7 for typical layout markings for the
system shown in Figure 6, page 6.
Mark wall lines and door openings (if interior
framing is not already installed).
Mark outlines of kitchen and bath cabinets,
appliances, etc.
Mark areas to be avoided (fireplaces, toilet
flanges, etc.).
Then mark key portions of the tube layout,
showing tube bend locations and flow direction.
Mark locations of penetration holes in rooms and hallways, if any.
Figure 7 - Possible layout markings on subfloor for portion of system shown in Figure 6
Penetration Hole (Typical)
Areas (Typical)
Areas (Typical)
Counters and Avoidance
Counters and Avoidance
Leader Routing
(typical)
Return Bends (typical)
(Typical)
Penetration Holes
Manifold
Leader Routing
(typical)
Return Bends (typical)
Part Number 650-000-221/0298
This drawing is conceptual only. Consult heating system designer for actual job details.
11
Page 12
AlumiPe x Radiant Tubing
H. Mount Manifold(s)
1. Accurately measure the location of the manifold mounting wall (if not already installed).
Placement of the manifold and the tube
penetrations is critical.
Take extra care in laying out these locations so all
items will be in proper position for the interior framing of the building.
2. Attach the manifold to a plywood panel.
Size the panel to fit between the finished studs if
the panel is to be recess mounted.
Longer manifolds will require spanning more than
one stud spacing.
For a complete metal cabinet enclosure, use
AlumiPex Wall Cabinets.
See Figure 8 for a typical manifold mounting
arrangement.
3. Prepare holes for tube routing.
Drill 1½” holes through the studs to route tubing
to upper floors. See Figure 9 for drilling penetration holes in the rooms above.
Drill 1½” holes through the sole plate in the
manifold stud cavity for penetrations to route tubing to same floor or lower floor heating circuits.
Route same floor tubing through the joist bays
below and then up through holes in each room unless the tubing will be routed through a hallway as in Figure 6. Here, the tubing would be routed to the joist bay below, then up to the proper locations in the hallway to route to the rooms. This method provides a neat installation while allowing ample room for tube bending.
When drilling the holes for tube penetration into
the rooms or hallway, drill the holes at a 45 degree angle to provide the proper minimum bend diameter for the tubing. See Figure 9, Page 14.
12
Part Number 650-000-221/0298
Page 13
Above Floor Installation Guide
Figure 8 - Mounting of manifold(s), typical
MANIFOLD MOUNTING
4“
Cover
(Above Floor System)
RETURN
SUPPLY
RETURNRETURN
SUPPLYSUPPLY
Studs
24“ Min
Dry Wall
Dry Wall
Joists
AlumiPex Manifold, Typical
!
Refer to AlumiPex Manifold Instructions for details of mounting, assembly and application.
Mounting Configuration
!
The installed depth of the manifold assembly is approximately 4 inches.
!
If mounted on 3/4“ plywood as shown, the complete assembly would fit in a 5” deep enclosure.
!
This can be done by using 2 x 6 studs in the vicinity of the manifold or building out from 2 x 4 studs.
Part Number 650-000-221/0298
Lower Plate
Subfloor
Joist Bays
The details shown are representative only. Other mounting configurations are possible.
Junction Box
!
Junction box for manifold valve actuator wiring, if needed.
Protect Tubing at Penetrations
!
Where tubing passes through stud walls, make sure nail stoppers are installed on both sides of the stud to protect tubing from damage by fasteners.
!
Make sure the drywall installers and finish carpenters are aware of the tubing in the walls and floors.
AlumiPex Manifold Fittings
!
Refer to AlumiPex Fitting Instructions for selection and application of AlumiPex fittings.
13
Page 14
AlumiPe x Radiant Tubing
I. Install the T ubing
Always wear safety glasses for eye protection when handling AlumiPex tubing. The tubing can spring back when pulled. Failure to follow this guideline could result in serious personal injury.
1. Install the sleepers.
Beginning from one side of each room, use your
floor markings and the tube layout drawing to place the sleepers.
Glue and nail each sleeper in place as shown in
Figure 10.
Bend routing sleepers can be made using a router
and fixture as shown or using a saber saw to cut semicircles.
2. Drill tube penetration holes.
If the tubing will penetrate the floor in the room,
drill a 1½” hole at a 45 degree angle for each penetration as shown in Figure 9.
Make sure the tube can be routed through the hole
from below and provide a minimum 6 inch bend diameter (3 inch bend radius) for 1/2” tubing.
3. Install heat emission plates.
Install AlumiPex Heat Emission Plates in the
sleeper spaces, centered in the 1” gap.
Secure heat emission plates on one side only to the
sleeper below using 5/8” staples.
Leave the other side of the heat emission plates
free to move so the plates can conform to the floor as the upper subfloor or finished flooring is installed.
See Figure 11 for typical details.
7. Attach tube fitting to manifold SUPPLY connection (bottom manifold).
8. Feed the tubing to the room as shown on the heating system designer’s tube layout drawing, feeding the outer (SUPPL Y) tubing first.
9. Complete the layout for the circuit and route the tubing back to the return manifold as shown on the tube layout drawing.
10. Carefully cut the tubing to the correct height at the return manifold. Apply an AlumiPex fitting for attachment to the manifold.
11. Then attach the fitting to the RETURN (top) manifold.
12. Continue the process for each circuit.
13. See Figure 11, page 16, for an above floor construction example.
Figure 9 - Tubing penetration hole, typical
45
degrees
Drill penetration holes 1½" diameter on 45 degree angle.
4. Place tube roll on uncoiler.
5. Route free end of tubing to manifold.
Feed the free end of the tubing through any
penetration holes to the manifold.
6. Install manifold fitting on free end of tube.
a. AlumiPex Nickel-Plated Brass Manifolds:
Use only AlumiPex Euro conical fittings. Refer to AlumiPex Manifold Instructions for
details and part numbers.
b. AlumiPex Copper Manifolds:
Use only AlumiPex tubing to NPT connectors.
14
SleeperSleeper
SubfloorSubfloor
1/2" Tubing, Typical
(With 6" bend diameter)
Joist, Typical
Part Number 650-000-221/0298
Page 15
Above Floor Installation Guide
Figure 10 - T ypical sleeper layout and installation
SLEEPER LAYOUT - ABOVE FLOOR
(Typical)
5
3
4
1
4
1
4
1
4
3
1
2
4
2
1
4
1
4
4
1
4
5 5
These drawings are conceptual only. Consult Weil-McLain Radiant Guides or Software for actual project layout.
1
SLEEPERS
!
Typically sleepers are 1 x __ lumber or .
(Width of sleeper is equal to the required tube spacing less 1 inch.)
!
Space 1" apart as shown to provide room for heat emission plate tubing channel and for thermal expansion.
!
Begin at one side of the room. Place a 1 x 4 spacer (item 3)
" from wall as shown.
¼
!
Leave a 1" gap between spacer and first sleeper. Then glue and nail sleepers in place.
2
END SUPPORT SLEEPERS
!
Typically cut from 3/4" plywood.
should equal tube bend radius plus 4 inches.)
!
Use a router and circle cutting template or fixture to route 3/4" wide x 5/8" deep channels as shown..
!
Place the end supports about " from the wall to allow room for expansion. Then glue and nail in place.
Part Number 650-000-221/0298
¾" CDX plywood
(Width of end sleepers
¼
3
SPACERS
!
Typically 1 x 4 furring strips.
!
Place spacers about from the wall to allow room for expansion. Then glue and nail in place.
!
Use a spacer between the wall and one of the end support sleepers to provide a channel for the tubing to leave the room as shown.
4
TUBING PATH
!
Provide a 1" gap between spacer and end support sleeper for routing tubing out of room. This will allow placement of a heat emission plate along this route.
5
PROVIDE GAP AROUND PERIMETER
!
Provide " gap around entire perimeter of room to allow for expansion.
¼
¼"
15
Page 16
AlumiPe x Radiant Tubing
Figure 11 - Typical above floor installation
ABOVE FLOOR INSTALLATION
J
E
I
F
G
This drawing is conceptual only. Consult Weil-McLain Radiant Guides or Software for actual project layout.
AlumiPex Tubing, 1/2”
A
!
Use AlumiPex tubing, 1/2”, commonly spaced on 6½-inch centers as shown (equal to 5½" for the sleeper plus 1" gap).
B
AlumiPex Heat Emission Plates
!
Use AlumiPex Heat Emission Plates to distribute the heat evenly to the floor above. Space plates from 1/4” to 1” apart end to end to allow for thermal expansion.
C
Sleepers
!
Glue and nail 1 x __ wood sleepers to the subflooring, starting from one side of the room and working toward the other.
Leave a 1" gap between sleepers to provide room for the
!
heat emission plate groove.
Staples
D
!
Secure each 2-foot long plate to the sleepers with 5/8" staples. Staple one side only to allow the plates to level out as the top subfloor or finish wood flooring is applied..
C
B
A
E
F
G
H
I
J
D
H
Cover Sheet
!
A cover sheet must be used if the finished flooring will be carpet, tile, vinyl or laminated hardwood.
Mark the Tubing Locations
!
Always mark the top subfloor with a chalk line or other mark to clearly show the location of the tubing underneath, ensuring the tubing won't be penetrated by fasteners.
Pay extra attention to marking the tubing bend
!
locations as well.
Poly-wrapped Insulation
Joists Subflooring
Finished Flooring
16
Part Number 650-000-221/0298
Page 17
Above Floor Installation Guide
J . Pressure T est the Finished Tubing Installation
1. After all tubing has been routed and connected to the manifold, pressure test all tubing circuits before finished flooring is installed. Refer to AlumiPex Manifold Instructions.
2. Isolate the AlumiPex manifolds and tubing from any other piping.
3. Attach a pressure gauge with a 150 psig scale range to the manifold using a high pressure hose.
Locate the gauge so it can be read during all
phases of construction.
4. Fill the system for pressure test with water only if there is no freeze potential.
You will need to keep the system pressurized as
discussed in the next section.
So the fluid used for testing would have to remain
in place.
You must be sure, if using water, that no freeze
potential would exist from time of installing pipe until time for you to complete the system piping and fill the system for start-up.
5. If there is freeze potential, fill the system with air and perform the pressure test using air .
If using air, remove all air vents from the manifolds
and plug the openings.
b. The pressure should not drop unless testing with
air on a cold day.
On cold days, air pressure testing will show a drop as the air in the tubing cools off. But the pressure should reach a steady level and drop no further.
If the pressure does drop, check the connections at the manifolds first.
c. Examine the system for leaks. Repair any leaks
found and repeat the test.
d. Check threaded joints with leak detection fluid
(soap mixture if using air).
When pressure testing with air, or when air is left anywhere in the system being pressurized, there is a risk of explosive discharge of compressed air or water if a leak or break occurs. Do not leave these pressure tests unattended while others are present. Remove all non-essential persons from the area during pressure testing. Failure to follow these guidelines could lead to severe personal injury, death or substantial property damage.
6. Pressurize the system to between 70 and 100 psig for 30 minutes.
a. Observe the pressure on the gauge.
Failure to check for and repair leaks can result in damage to system components and the premises, causing severe personal injury, death or substantial property damage.
Part Number 650-000-221/0298
17
Page 18
AlumiPe x Radiant Tubing
L. Connect System Piping & Heating System Components
1. Install piping and heating system components if framing is in place.
3. Don’t solder within 18 inches of tubing.
3. Cover tubing to protect it from solder drip.
K. Pressurize T ubing for Observation
1. After the system has been proven leak free, pressurize all tubing circuits to 30 psig.
Maintain this pressure on the tubing for the
remainder of the building construction.
Pressurizing the tubing allows use of the pressure
gauge to verify the integrity of the tubing and connections.
4. Never apply an open flame to AlumiPex tubing.
5. Pressure test sytem piping to verify there are no leaks.
Periodically observe the pressure gauge to make
sure no major drop in pressure occurs. A pressure drop would indicate a puncture or leak.
M. Before Leaving the Jobsite . . .
1. Before leaving the jobsite, we recommend you meet with the general contractor to review the AlumiPex T rade Guides.
q Make special note of the pressure gauge. It can be
used by all trades to check the integrity of the tubing throughout the construction of the building.
q Review traffic recommendations. q Ask for early notification of the schedule for
installing finished flooring so you can inspect the installation a day before this starts.
q If possible, get an agreement that the flooring
won’t be installed until you have inspected the installation and given your release.
2. Make a record of your installation
We suggest you take photographs of the tubing
and manifolds.
Use the photographs and notes on the tube layout
drawing to document installation details.
18
Part Number 650-000-221/0298
Page 19
Above Floor Installation Guide
N . Inspect T ubing Before Finished Flooring Installation
1. Arrange to inspect the installation a day before the scheduled finished flooring installation starts.
q Check the pressure gauge to verify the system is
still pressurized at or near 30 psig.
q Visually inspect all tubing to verify there is no
damage.
q Repair any damage you find. q Advise the general contractor of your findings and
release for finished flooring installation.
O. Inspection, Repair and T roubleshooting
1. Inspect the tubing connections and piping as the job is completed.
2. Perform a final pressure test on the system after all flooring is in place and building is ready for occupancy to verify all joints are tight and no damage has occurred to the tubing during construction.
3. Repair of kinked or crushed tubing:
Use a copper pipe truer to restore the tubing
roundness.
If the damage is so severe that this cannot be done,
cut out the damaged section of tubing.
Cut a new length of tubing long enough to span the gap.
At each end of the splice section, install an AlumiPex coupling.
Slip a length of heat shrink tubing over each end before tightening the couplings.
Tighten couplings. Then seal them with the heat shrink tubing.
Route a groove in the subflooring deep enough to accommodate the finished repair section.
Mark the location of any such repairs on the tube layout drawing
Part Number 650-000-221/0298
19
Page 20
AlumiPe x Radiant Tubing
20
Part Number 650-000-221/0298
Loading...