
Frequency Inverter
CFW-09
Convertidor de Frecuencia
CFW-09
Inversor de Freqüência
CFW-09
Frequenzumrichter
CFW-09
Variateur de Vitesse
CFW-09
Frequentie-Omzetter
CFW-09
Frekvensomriktare
CFW-09
Преобразователь частоты
CFW-09
User´s Guide
Manual del Usuario
Manual do Usuário
Bedienungsanleitung
Guide d'instalation et d'exploitation
Installatie en gebruikshandleiding
Bruksanvisning
Руководство по эксплуатации
Motors | Automation | Energy | Coatings

It is very important to check if the
inverter software version is the same

-2Inclusion of the functions Fieldbus and Serial Communication.
Inclusion of the Spare Part List.
Inclusion of thePID Regulator.
Inclusion of the German Language - Ride-through and Flying
Inclusionof DBW-01;KITKME; DC LinkInductor.
tem 3.3 -CE Installation.
Inclusion of new functions such as Ride-Through for Vector Control, Motor Phase Loss.
New I/O Expansion Boards EBB.04 and EBB.05.
-7Inclusion of the models from 2.9 to 32 A / 500-600 V.
3.2.1; 3.3; 4.2; 6.2; 6.3; 7.1;
7.2; 7.4; 7.5; 8.7.1; 8.10.1;
Inclusion of new functions:
Control Type of the Speed Regulator, SpeedRegulator Differential Gain, Stop Mode Selection,
Access to the parameters with different content than default, Hysteresis for Nx/Ny, kWh
Counter,Load User 1 and 2 the factory Hours Hx, via DIx, Parameter Setting Disable via DIx,
Help Message for E24, “P406 = 2 in Vector Control”, Automatic SensorLess Set of P525, Last
10 errors indication, Motor Torque indication via AOx.
New optional boards: EBC and PLC1.
Newmodel CFW-09 SHARKNEMA 4X/IP56.
New models for voltages, currents and powers: Models 500-600 V.
Inclusion of the items 8.14 Modbus-RTU,8.17 CFW-09 Supplied by the DC Link - Line HD,
8.18 CFW-09 RB Regenerative Converter.
Updating of the SparePart List.
79Inclusion of new functions:
Overcurrent Protection, Default factory reset 50 Hz, Timer Relay, Ramp Holding.
New lines of the current and
PID Regulator to “Academic” Changing.
-10General revision and update of the software version (2.6X to 3.1X):
Change on the maximum value of P156 and P401 for some models; Change on the maximum
value of P331; Change on the factory default value of P404.
Incorporation of the Mechanical Brake Logic for cranes, Load Detection Logic and addition of
Refer to items I, 6, 7 and 8
option “Indication of Torque Current Polarity” at the DOx and RLx outputs; VVW Control; DC
Braking for VVW and Sensorless; Flying Start function for the Sensorless Control; support for
EtherNet/IP communication board; read/write function for the PLC board parameters through
Modbus; Indication of the Analog Outputs values in read only parameters P027 to P030;
Simultaneous indication of the speed and current in parameter P070; P313 = 4 (Changes to
LOCAL mode keeping the commands);Regulation of the maximum torque current through
options AI1+AI2 and AI2+AI3; function F > Fx; function ready 2.
Updating of the software version to V4.0X.
Updating of the parameters P309 and P313.
Addition of new parameters: P335, P336, P337, P338, P340, P341, P342, P343, P344 and P346.
New options for fault Reset.
The table below describes all revisions made to this manual.

Quick Parameter Reference, Fault and Status Messages
.......................................................................................
....................................................................................
.................................................................................
1.1 Safety Notices in the Manual
.............................................................
1.2 Safety Notices on the Product
...........................................................
1.3PreliminaryRecommendations
..........................................................
..............................................................................
................................................................................
.............................................................................
2.4CFW-09IdentificationLabeland CodeNumber
..................................
.......................................................................
Installation and Connection
3.1Mechanical Installation
......................................................................
3.1.1EnvironmentConditions
...............................................................
3.1.2Dimensionalof CFW-09
...............................................................
3.1.3Mounting Specifications
...............................................................
3.1.3.1Mounting Inside a Panel
.....................................................
3.1.3.2Mounting onSurface
..........................................................
3.1.3.3Mounting withthe Heatsink Through aSurface
3.1.4Keypad(HMI)andCoverRemoval
................................................
3.2 Electrical Installation
..........................................................................
3.2.1Power/GroundingTerminals
.........................................................
3.2.2Locationof thePower/Grounding/ControlConnections
3.2.3 RatedVoltageSelection
..............................................................
Power/GroundingWiringand Fuses
............................................
.....................................................................
3.2.5.1AC InputConnection
...........................................................
3.2.5.2Output Connections
............................................................
3.2.5.3GroundingConnections
.......................................................
.........................................................................
..............................................................................
TypicalTerminalConnections
......................................................
3.3EuropeanEMC Directive- Requirementsfor ConformingInstallations
...................................................................................
...............................................................................
...........................................................................
3.3.4 EMC Filter Characteristics
...........................................................

..................................................................
....................................................................
........................................................................
"Read-Only"Variablesand Status
...............................................
ParameterViewingandProgramming
.........................................
............................................................................
.................................................................................
.............................................................................................
Type of Control:V/F60 Hz - Operation via Keypad(HMI)
5.3.2Typeof Control: Sensorless or Vector with Encoder
(OperationVia Keypad(HMI))
.....................................................
TypeofControl: VVW - KeypadOperation
.................................
Detailed Parameter Description
6.1Access and Read Only Parameters - P000 to P099
.........................
6.2 RegulationParameters - P100 to P199
.............................................
6.3Configuration Parameters-P200 to P399
.........................................
ParametersforCraneApplicationsand forTorqueMaster/Slave
..........................................................
6.4 Motor Parameters - P400 to P499
....................................................
6.5 SpecialFunctions Parameters - P500 to P699
.................................
.............................................................................
.................................................................................
Diagnostics and Troubleshooting
7.1 Faults and Possible Causes
.............................................................
................................................................................
...............................................................................
....................................................................
7.4.1CleaningInstructions
..................................................................
..................................................................................
CFW-09 Options and Accessories
.......................................................................
8.1.1 EBA(I/O Expansion BoardA)
.....................................................

8.1.2 EBB (I/O Expansion Board B)
....................................................
............................................................................................
.........................................................................
.......................................................................
................................................................................
8.3 Keypad with LEDs Only
....................................................................
8.4RemoteKeypad and Cables
.............................................................
....................................................................................
8.6RS-232 PC Communication Kit
........................................................
8.7Line Reactor/DC BusChoke
.............................................................
8.7.1Application Criteria
......................................................................
8.7.2 DC Link Inductor Built in
.............................................................
....................................................................................
...........................................................................................
............................................................................
8.10.1 DB Resistor Sizing
..................................................................
...............................................................................
8.10.3DynamicBraking Module-DBW-01and DBW-02
8.10.3.1DBW-01and DBW-02 IdentificationLabel
8.10.3.2Mechanical Installation
................................................
8.10.3.3Installation/Connection
................................................
ThroughSurfaceMountingKit
.........................................................
...........................................................................................
8.12.1 Installation of the
.................................................
.............................................................................
.......................................................................
................................................................................
8.12.5DeviceNetDriveProfile
............................................................
.............................................................................
8.12.7Use to the Fieldbus/RelatedParameters of the CFW-09
8.12.7.1VariablesReadfrom the Inverter
..................................
8.12.7.2VariablesWritten inthe Inverter
...................................
8.12.7.3 Fault Indications
..........................................................
8.12.7.4Addressing of the CFW-09Variables in the
.........................................................
.....................................................................
.............................................................................
8.13.2InterfacesDescription
..............................................................
.........................................................................
.........................................................................
8.13.3Protocol Definitions
.................................................................
..................................................................
8.13.3.2Parameters/VariablesResolution
..................................
........................................................
........................................................................
.......................................
......................................................
...............................................................
.................................................................
8.13.5Variablesand Errorsof the Serial Communication
............................................................
8.13.5.2Examples of Telegrams withBasic Variables
8.13.5.3Parameters Related tothe Serial Communication
8.13.5.4Errors Related to theSerial Communication

8.13.6Timesfor Read/Writeof Telegrams
..........................................
8.13.7 PhysicalConnectionof theRS-232and RS-485Interface
....................................................................................
8.14.1Introductionin theModbus-RTU Protocol
................................
8.14.1.1TransmissionModes
....................................................
8.14.1.2Message Structurein RTUMode
..................................
8.14.2Operationof theCFW-09 inthe Modbus-RTUNetwork
8.14.2.1Interface RS-232andRS-485Description
8.14.2.2InverterConfigurationinthe Modbus-RTUNetwork
8.14.2.3Access to the Inverter Data
...........................................
8.14.3Detailed FunctionDescription
...................................................
8.14.3.1 Function 01- Read Coils
..............................................
8.14.3.2Function 03 -Read Holding Register
............................
8.14.3.3 Function 05 - Write Single Coil
.....................................
8.14.3.4 Function 06 - Write SingleRegister
..............................
8.14.3.5 Function 15 - Write Multiple Coils
.................................
8.14.3.6 Function 16 - Write Multiple Registers
.........................
8.14.3.7Function43 - ReadDevice Identification
8.14.4CommunicationErrors
.............................................................
............................................................
8.15KIT KME (for ExtractableMounting)
................................................
.............................................................
8.16.1Enclosure Specifications
.........................................................
8.16.2Mechanical Installation
............................................................
8.16.3 Electrical Installation
...............................................................
..................................................................
........................................................................
8.17 CFW-09 Supplied by the DC Link - Line HD
...................................
8.18CFW-09RBRegenerativeConverter
...............................................
......................................................................................
......................................................................................
PowerSupplySpecifications
......................................................
9.1.2220-230V Power Supply
............................................................
9.1.3380-480V Power Supply
............................................................
9.1.4500-600V Power Supply
............................................................
9.1.5660-690V Power Supply
............................................................
9.2Electronics/General Data
..................................................................
9.2.1Applicable Standards
..................................................................
...............................................................................
9.3.1 I/O Expansion Board EBA
..........................................................
9.3.2 I/O Expansion Board EBB
..........................................................
...............................................................................

QUICK PARAMETER REFERENCE, FAULT AND STATUS MESSAGES
DigitalInputsDI1 ... DI8Status
DigitalandRelayOutputsDO1,DO2,
0 = Inactive (Dropped-out)
A/D Conversion Value of AI4
A/D Conversion Value of Iv
A/D Conversion Value of Iw

P136 has different functions for V/F and Vector Control.
Motor Current and Motor Speed
JOG or JOG+ Speed Reference
Speedtransition to I/F Control

P151 has different function for V/F or Vector Control.
Intermediate Output Voltage
DC Link Voltage Regulation
DCLink VoltageRegulationMode
DC Link VoltageRegulation Level
(V/F Control / Vector Control
Overload Current 100 % Speed
Overload Current 50 % Speed
Overload Current 5 % Speed
Local Speed Reference Offset
Remote Speed Reference Offset

Speed Regulator Differential Gain
Maximum Output Current(V/FControl)
Maximum Forward Torque Current
Maximum Reverse Torque Current
Maximum ForwardTorque Current at
Maximum Reverse Torque Current at
Curve Type of the Max. Torque
5 = VVW (Voltage Vector WEG)
SpecialFunction Selection
5 = LoadsFactory Default-60Hz
6 = LoadsFactory Default-50Hz
P169 has different function for V/F or Vector Control.

Display Default Selection
4 = P006 (Inverter Status)
Reference Engineering Unit 1
Motor Phase Loss Detection
DecimalPoint of the SpeedIndication
Time Delay for Zero Speed Disable
Line Phase Loss Detection
Reference Engineering Unit 2
Reference Engineering Unit 3
Local/Remote Selection Source
2 = Keypad (Default Local)

Local Speed Reference Selection
7 = Fieldbus (Default FWD)
8 = Fieldbus (Default REV)
Local Start/Stop Selection

7 = Fieldbus (Default FWD)
8 = Fieldbus (Default REV)
RemoteStart/StopSelection
0 = (0 to 10) V / (0 to 20) mA
2 = (10 to 0) V / (20 to 0) mA
Analog Input AI2 Function

0 = (0 to 10) V / (0 to 20) mA
2 = (10 to 0) V / (20 to 0) mA
Analog Input AI3 Function
(Requires Optional I/O Expansion
0 = (0 to 10) V / (0 to 20) mA
2 = (10 to 0) V / (20 to 0) mA
0 = (0 to 10) V / (0 to 20) mA
(Requires Optional I/O Expansion
2 = (10 to 0) V / (20 to 0) mA
Analog OutputAO1 Function
4=Torque Current (Vector)
10=PositiveTorque Current
Analog OutputAO2 Function

4 = Torque Current (Vector)
10=PositiveTorque Current
Analog Output AO3 Function
(Requires Optional I/O Expansion
4=Torque Current (Vector)
15to 63= ExclusiveWEG use
Analog Output AO4 Function
(Requires optional I/O Expansion
4 = Torque Current (Vector)
15to 63= ExclusiveWEG use
Dead Zone for Speed Indication

DigitalInput DI1 Function
DigitalInput DI2 Function
DigitalInput DI3 Function
17 = Disables Flying Start
DigitalInput DI4 Function

17 = Disables Flying Start
18 = DC voltage regulator
DigitalInput DI5 Function
17 = Disables Flying Start
DigitalInput DI6 Function

17 = Disables Flying Start
18 = DC voltage regulator
DigitalInput DI7 Function
expansion board EBA or EBB)
17 = Disables Flying Start
DigitalInput DI8 Function
expansion board EBA or EBB)

17 = Disables Flying Start
expansion board EBA or EBB)
30 = Brake (Actual Speed)

DigitalOutputDO2 Function
expansion board EBA or EBB)
30 = Brake (Actual Speed)

Relay Output RL1 Function
30 = Brake (Actual Speed)
Relay Output RL2 Function

30 = Brake (Actual Speed)
Relay Output RL3 Function

30 = Brake (Actual Speed)
Nx, Ny, Ix, Zero Speed Zone, N = N* and Tx

QUICK PARAMETER REFERENCE
1 = Profibus DP/DP-V1 2 I/O
2 = Profibus DP/DP-V1 4 I/O
3 = Profibus DP/DP-V1 6 I/O
10 = DeviceNet Drive Profile
STOP Detection in a Profibus
1 = Modbus-RTU, 9600 bps,
2 = Modbus-RTU, 9600 bps,
3 = Modbus-RTU, 9600 bps,
4 = Modbus-RTU, 19200 bps,
5 = Modbus-RTU, 19200 bps,

Typeof disabling by E28/E29/E30
0 = Disable via Start/Stop
0 = Disablevia Start/Stop
Watchdog detection for the
Flying Start/Ride-Through

Ride-ThroughProportional Gain
PARAMETERS FOR CRANEAPPLICATIONS AND FOR MASTER/SLAVE FUNCTION
Logic for the Mechanical Braking Operation
Delay for N < Nx - Brake Activation
Delay for Resetting the Integrator
Indication of the Torque Current Polarity
Torque Current (Iq) Filter
Torque Current (Iq) Hysteresis
Parameters for Load Detection

0 to 7200 (P202 = 3 and 4)
0 to 300 (P202 = 0,1,2 and5)
30 to 120 (P202 = 3 and 4)

Motor Stator Resistance (Rs)
Motor Magnetizing Current (I
MotorFluxLeakage Inductance( LS)

Process Variable Scale Factor
Decimal Point of Proc. Var.
Engineering Unit of Proc. Var. 1
Engineering Unit of Proc. Var. 2
Engineering Unit of Proc. Var. 3
Automatic Setting of P525
Hysteresis for Set point =
Notes presented on Quick Parameter Description:
Parameter can be changed only with the inverter disabled
Values may change as a function of the “Motor Parameters”.
Values may change as a function of P413 (Tm Constant - obtained during
Values may change as a function of P409 and P411 (obtained during Self-
Values may change as a function of P412 (Tr Constant - obtained during
Values may change as a function of P296.
Values may change as a function of P295.
Values may change as a function of P203.
Values may change as a function of P320.
User’s Standard (for new inverters) = without parameter.
The inverter will be delivered with settings according to the market,
consideringthe HMI language,V/F 50 Hz or 60 Hz and the required voltage.
Thereset of the standard factorysetting may changethe parameters related
to the frequency (50 Hz/60 Hz). Valueswithin parenthesis mean the factory
The maximum value of P156 and P401 is 1.8 x P295 for model 4.2 A/500-
600 V and 1.6 xP295 for models 7 Aand 54A/220-230 V; 2.9A and7 A/500-
600V;107A, 147A and 247A/500-690 V;100A, 127Aand340A/660-690V.

- Interdependence among parameters: parameters that change the settings of
others when modified versus parameters that are automatically modified as a function of a
parameter setting (during start-up and/or normal operation)
Output Overcurrent/Short-Circuit
Power Supply Undervoltage/Phase Loss
Inverter Overtemperature/Pre-charge Circuit
Output Overload (I x t Function)
Valid for P202 = 4 (Vector with Encoder)
Error in the Copy Function
Dynamic Braking Resistor Overload
Motor or Encoder with Inverted Wires
(Self-Tuning) (Valid for P202 = 4)
Serial communication error
Long period at torque limitation
Internal DC Supply Undervoltage
E04 can be "Pre-charge Circuit Failure" only in the following models:
44 A/500-600 V and for all 500-690 V and
660-690 V models. E04 can also occur when signal with inverted polarity is applied
at analog inputsAI1/AI2. The E04 fault message can also occur in the models up to
130 A/ 200-230 V, 142 A/380-480 V and 63 A/500-600 V when the temperature at
the heatsink is lower than -10 ºC.
Condition where it occurs
Parameters that are affected
P223, P225, P226, P228, P237,
P156, P157, P158, P169 (V
P151, P153, P321, P322, P323
P122, P123, P124, P125, P126,
P127, P128, P129, P130, P131,

Inverter is Ready to be Enabled
Power Supply Voltage is Too Low for the Inverter Operation
Inverter in DC Braking Mode. (Refer to P300)

This Manual contains all necessary information for the correct installation
andoperationof theCFW-09VariableFrequency
The CFW-09 Instruction Manual has been written for qualified personnel
with suitable training or technical qualifications to operate this type of
The following Safety Notices will be used in this Manual:
Ifthe recommendedSafetyInstructionsarenotstrictlyobserved,it can lead
toserious or fatalinjuriesof personneland/or equipment damage.
Failureto observetherecommendedSafetyProcedurescanleadtomateri-
The content of this Manual supplies important information for the correct
understandingofoperationandproperperformanceof theequipment.
The following symbols may be attached to the product, serving as Safety
Components are sensitive to electrostatic discharge. Do not touch
them without following proper grounding procedures.
Mandatory connection to ground protection (PE).
Shield connection to ground.
Onlyqualified personnel should plan orimplement the installation,startup,
operation and maintenance of this equipment. Personnel must review this
entireManual before attempting to install,operate or troubleshoot the
These personnel must follow all safetyinstructions included in this Manual
and/ordefined bylocal regulations.
Failureto complywiththeseinstructionsmayresultin personnel injuryand/

CHAPTER 1 - SAFETY NOTICES
In thisManual, qualified personnelare defined as people thataretrained to:
Install,ground,powerupandoperatetheCFW-09 accordingtothisManual
andthe local requiredsafety procedures;
Use of safety equipment according to the local regulations;
Administer Cardio PulmonaryResuscitation(CPR) and FirstAid.
Alwaysdisconnectthesupplyvoltagebeforetouching anyelectricalcomponent
Manycomponentsare chargedwithhighvoltages,even aftertheincomingAC
powersupplyhasbeendisconnectedorswitched OFF.Waitat least10minutes
for the totaldischargeof the power capacitors.
Alwaysconnect theframe of theequipment to theground (PE) at thesuitable
All electronic boards have components that are sensitive to electrostatic
discharges.Nevertouchanyoftheelectricalcomponentsorconnectorswithout
followingpropergroundingprocedures.Ifnecessarytodoso,touchtheproperly
groundedmetallicframe oruse a suitable groundstrap.
Inverterscan interferewithotherelectronic equipment.In order toreduce this
interference,adopt themeasuresrecommended in
ReadthisentireManualcarefullyand completelybeforeinstallingor operating
Do not apply High Voltage (High Pot) Test on the Inverter!
If this test is necessary, contact

Thischapterdefinesthecontentsandpurposeof thismanualanddescribes
themaincharacteristics ofthe CFW-09frequencyinverter.Identification of
theCFW-09,receivingandstorage requirementsare alsoprovided.
ThisManual isdividedinto 9Chapters, providinginformation tothe useron
howto receive, install, start-up andoperate the CFW-09:
GeneralInformationandReceivingtheCFW-09;
Information about the CFW-09 physical installation, electrical
connection(powerandcontrolcircuit)andinstallationofoptional
Keypad(HMI)Operation(Human-MachineInterface-keyboard-
DetailedProgramming ParametersDescription;
Diagnostics,troubleshooting,cleaninginstructions andpreventive
Technical description of CFW-09 optional devices and
Technical specifications (electricaland mechanical).
This Manual provides information for the correct use of the CFW-09. The
CFW-09is veryflexibleandallowsfortheoperationinmanydifferentmodes
as described in this manual.
As theCFW-09 can be applied in severalways,it is impossible to describe
here all of the application possibilities. WEG does not accept any
responsibilitywhen the CFW-09 is not used according to this Manual.
No part of this Manual may be reproduced in any form, without the written
It isimportantto note theSoftwareVersion installedin the VersionCFW-09,
sinceitdefinesthefunctionsandtheprogrammingparametersoftheinverter.
ThisManualrefersto theSoftwareversionindicatedontheinsidecover.For
example, the Version 1.0X applies to versions 1.00 to 1.09, where “X” is a
variable that will change due to minor software revisions. The operation of
theCFW-09withthese softwarerevisionsarestillcoveredbythisversionof
The SoftwareVersioncan be readin the Parameter P023.
TheCFW-09is ahighperformanceVariableFrequency
the control of speed and torque of a three-phase AC induction motor. The
technologicaladvantageof the CFW-09 is due to the “Vectrue”technology
thatprovidesthe followingbenefits:
Programmablescalar(volts/Hz)orVectorControlwiththesame product;
VectorControl can beprogrammed for“Sensorless” (that means that
standardmotorscanbecontrolledwithout encoderfeedback),or “Closed
Loop” (with an encoder attached to the motor shaft);

CHAPTER2 - GENERALINFORMATION
Internalelectronics powersuppliesand
Supply=DCLinkchokeconnection(optional)
=DB resistorconnection.Up tosize 7
only.Option for sizes4 to7.
The Sensorless Vector Control permits high torques and quick response,
evenat very lowspeedsandduring the starting of the motor;
The“OptimalBraking”functionallowscontrolledmotorbraking withoutusing
a Dynamic Braking (DB) resistor;
“Self-tuning”auto-tunefunctionwithVectorControl,permittingautomatic setting
of the control regulators and control parameters by means of the automatic
identification of the motor and the loadparameters.
Technical specifications for each modelof CFW-09 are describedin chapter 9.
Theblock diagram belowgives a generalviewof theCFW-09:

CHAPTER2 - GENERALINFORMATION
Locationofthe CFW-09Nameplate:
Nominal Output Current and
Switching Frequency for VT and
(Phase, Current and Frequency)

HOWTO SPECIFYTHE CFW-09MODEL:
0010 = 10A0013 = 13A0016 = 16 A
- For rated output current specification of variable torque (VT), refer to chapter 9.
- The rated output current indicated for the models 500-690 V is only valid for 500 V to 600 V supply.
- For rated output current specification (CT and VT) of the models with supply voltage higher than 600 V, refer to chapter 9.
The option field (S or O) defines if the CFW-09 is a standard version or if it is equipped with any optional devices. If the standard version is required, the code ends here. The model
code number always has the letter Z at the end. For example:
CFW090045T2223ESZ = Standard 45 A CFW-09 inverter - three phase input at 220-230 V, with the Manual in English.
If the CFW-09 is equipped with any optional devices, you must fill out the fields in accordance to the optional devices desired in the correct sequence up to the last optional device
desired, then the model code number is completed with the letter Z.
Thus, for instance, if a product of the example above is required with an EBA expansion board, indicate:
CFW090045T2223EOA1Z = 45 A CFW-09 inverter – three-phase input at 220-230 V, with the manual in English and with the optional EBA.01 board.

CHAPTER2 - GENERALINFORMATION
Thestandardproduct is definedas describedhere:
NEMA1/ IP20: 3.6 Ato 240 A/380-480 V models and all 220-230 V and
Protected chassis / IP20: 361Ato 600 A/380-480 V models and all 500-
HMI-CFW09-LCD(withLED andLCDdisplays)
DBTransistorforDBResistorbrakingincorporated inthefollowingmodels:
TheDC Link chokeisincludedin the standardproductfor 44A,53A, 63A
and 79A/500-600 V, all models 500-690 V and 660-690 V models.
DB Transistor can be incorporatedas anoptionin the following models:
Models 180A to 600A/380-480 V, 107 Ato 472 A/500-690 V and 100Ato
428A/660-690V, do not havethe capabilityto use an internal DBTransistor.
In this case, use the external DB Transistor option (refer to item 8.10.3 -
Dynamic Braking Module - DBW-01 and DBW-02).
It is necessary to connect an external braking resistor regardless if the DB
Transistor is built in, optional built in or an external module (DBW).
TheCFW-09issuppliedincardboardboxesuptosize3(
modelsabove,thepackingwillbe withwoodpalletandwoodbox.
Theoutsideofthepackingcontainerhasanameplatethatisidenticalto thaton
theCFW-09.Pleasecheckif thenameplate datamatchestheorderedones.
The boxesup to size7 must be placedandopened on atable (sizes above3
withthehelpof two persons).
Openthe box, remove thecardboard or expandedpolystyreneprotection.
Theboxes of sizesabove7mustbe openedonthefloor.Openthe
xpandedpolystyreneprotection
.The CFW-09mustbe handled
CFW-09 nameplatedata matches thepurchase order;
Theequipment hasnot beendamaged duringtransport.
If any problem is detected, contact the carrier immediately.
If the CFW-09 is not to be installed immediately, store it in a clean and dry
room (Storage temperatures between -25°C and 60°C). Cover it to prevent
dust,dirt or other contamination of theinverter.
If theinverter isstoredfor long periods,we recommend to powerit up oncea
yearduring1 hour. For220-230Vand 380-480Vmodelsapplysupplyvoltage
of approximately 220 Vac, three-phase or single-phase input, 50 or 60 Hz,
without connecting motor at output. After this energization, wait 24 hours
before installingit. For 500-600 V, 500-690 V and 660-690V models usethe
same procedureapplying a voltagebetween 300 and 330

INSTALLATION AND CONNECTION
This chapterdescribes the procedures for theelectricaland mechanical
installationof the CFW-09.
Theseguidelinesmust befollowedforproperCFW-09 operation.
The location of the CFW-09 installation is an important factor to assure
performanceand highproduct reliability.
For proper installation of the inverter, we make the following
Avoiddirect exposure to sunlight, rain, high moisture and sea air.
Avoidexposure togasesor explosiveor corrosive liquids.
Avoidexposure to excessive vibration,dust, oil or any(conductive
Allowed environmental conditions:
Temperature: 0 ºC to 40 ºC (32 ºF to 104 ºF) - nominal conditions.
From 40 ºC to 55 ºC (104 ºFto 131ºF) - with 2 % current derating for
(33.8 ºF)degreeabove 40 ºC (104 ºF).
RelativeAir Humidity: 5 % to 90 %, non-condensing.
MaximumAltitude: 1000 m (3.300 ft) – nominal conditions.
From 1000 m to 4000 m (3.300 ft to 13.200 ft) – with 1 % current
each100 m (330 ft) above1000 m (3.300ft).
Pollution Degree: 2 (according to EN50178 and UL508C) (It is not
the presence of water, condensation or conductive dust/
3.1.2Dimensional of CFW-09
Externaldimensionsand mountingholesare accordingto figure3.1 and
Sizes 3 to 10, 8E and 10E
- Mounting dimensional drawings of CFW-09

CHAPTER3- INSTALLATIONAND CONNECTION
Installation data – Refer to item 9.1
For installing the CFW-09, leave at least the minimum free spaces around the
inverteraccordingtofigure3.2.Thedimensionsofthesefreespacesaredescribed
Install the inverter in the vertical position according to the following
Installthe inverter ona flat surface.
Donotinstallheatsensitivecomponentsimmediatelyabovetheinverter.
For the inverters 45A to 130 A/220-230 V, 30 Ato 600A/380-480 V, 22 A
to 32 A/ 500-600 V, 44Ato 79A/500-600 V,107A to 472A/500-690 V and
100 A to 428 A/660-690 V:
First partially tighten the bolts on the surface, then install the inverter
For inverters 6 Ato 28A/220-230 V, 3.6 Ato 24A/380-480 V and 2.9Ato
Install the 2 bottom mounting bolts first, rest the inverter on the base and
then mount the 2 top bolts.

CHAPTER3- INSTALLATIONAND CONNECTION
- Recommended free spaces
When inverters are installedin panelsor closed metallic boxes, adequate
cooling is required to ensure that the temperature around the inverter will
exceedthemaximum allowedtemperature.Referto DissipatedPower
Forreference,table 3.3shows the coolingairflowforeachinverter model.
3.1.3.1MountingInsidea Panel
When inverters are installed side by side, maintain the minimum
recommended distance B. When inverters are installed top and bottom,
maintainthe minimumrecommendeddistanceA+ Cand deflectthehot air
Provideindependentconduitsforsignal,controlandpowerconductors(Refer
to item 3.2: Electrical Installation).

CHAPTER3- INSTALLATIONAND CONNECTION
m3/min11990.5232150.9370332.0489422.55117553.36138653.97286
105 A and 130 A/220-230 V
- Cooling air flow requirements
Figure 3.3 shows the installationof the CFW-09 on a mounting plate.
3.1.3.2Mountingon Surface
- Mounting procedure for the CFW-09 on a surface
Internalfan, flowdirectionfromthe bottomto thetop.

CHAPTER3- INSTALLATIONAND CONNECTION
- Mounting procedure for the CFW-09 on a surface
d) Positioning (for all Sizes)
The CFW-09 can alsobe installed withthe heatsink throughthe mounting
plate, as shown in figure 3.4.
Inthiscase,refertoinstallationdrawingsshownin figure3.4c) andmaintain
the distances indicated in table 3.4.
When installing the heatsink through the mounting surface, according to
the degree of protection behind this surface is NEMA 1 / IP20.
does not protect against dust and water.

CHAPTER3- INSTALLATIONAND CONNECTION
- Mounting procedure for the CFW-09 with the heatsink through the mounting surface
c) Cutout Dimensions (Refer to table 3.4)

CHAPTER3- INSTALLATIONAND CONNECTION
SizemmmmmmmmmmmmmmThrough
The Through Surface Mounting kit (kit-KMF) is a set of supports for the CFW-09 as shown on
– Keypad (HMI) and cover removal procedure
- Cutout dimensions and kits for CFW-09 through surface mounting

CHAPTER3- INSTALLATIONAND CONNECTION
– Keypad (HMI) and cover removal procedure
The informationbelow willbea guide toachieve a proper installation.Follow
also all applicable local standards for electrical installations.
Be sure that theAC input power is disconnected before making any terminal
The CFW-09 frequencyinverter cannot be used as an emergencystop device.
Provideanother devicesfor thisfunction.
Thepower connectionterminalscan be of differentsizes andconfigurations,
dependingon theinverter model asshownin figure 3.6.
R, S, T:AC supply line. Models up to 10A at 220-230 V can be operated
withtwo phases (single-phaseoperation) withoutcurrentderating. In this
case the AC supply can be connected to any 2 of the 3 input terminals.
U, V, W: Motor connection.
-UD: Negativepole of the DC Link circuit.
BR: Dynamic Braking resistor connection.
+UD: Positive pole of the DC Link circuit.
DCR: Connectionto the external DC Linkchoke (optional).

CHAPTER3- INSTALLATIONAND CONNECTION
c) Size 3, 4 and 5 models
d) Size 6 and 7 (220-230 V and 380-480 V models)
g) Size 9 and 10 (380-480 V models)
f) Size 8 (380-480 V models)
e) Size 7 (500-600 V models)
h) Size 8E (500-690 V and 660-690 V models)

CHAPTER3- INSTALLATIONAND CONNECTION
i) Size10E (500-690 V and 660-690 V models)
b) Size 3, 4 and 5 models
No voltage selection needed for these models
- Location of the power/grounding/control connections and rated voltage

CHAPTER3- INSTALLATIONAND CONNECTION
- Location of the power/grounding/control connections and rated voltage

CHAPTER3- INSTALLATIONAND CONNECTION
Thefollowingmodelsof CFW-09inverterseries haveajumper forrated voltage
It isnecessaryto adjustthejumper in models380-480V when the power
voltageisdifferentfrom440V and460V.Alsoinmodels500-600 Vand500-690 V
whenthepower supplyvoltageis differentfrom550 V, 575 V and600 V.
Removejumperon the LVS1board (or from theCIP2 for models
frompositionXC60 (440-460V)and insertitontheproper positionaccording
to theapplication line voltage.
Removejumper on theLVS2 boardfrompositionXC62(550V, 575V,600V)
and insert it on the proper position according to the line voltage.
Removejumper ontheCIP3 boardfrom positionXC62 (550 V, 575 V,600 V)
and insert it on the proper position according to the line voltage.
a) LVS1(size 6 and 7, 380-480 V)
b) CIP2 (size 8, 9 and 10, 380-480 V)
- Rated voltage selection on boards LVS1, CIP2, LVS2 and CIP3

CHAPTER3- INSTALLATIONAND CONNECTION
d)–Rated voltage selection on
boards LVS1, CIP2, LVS2 and CIP3
c) LVS2 (size 7, 500-600 V)
d) CIP3 (size 8E and 10E, 500-690 V)
Sensitiveequipment(PLCs, temperaturecontrollers,thermocouples,etc.)
and its wiring must stay at a minimum distance of 10 in (0.25 m) from the
frequencyinverters,thereactorsandfromtheinputandmotorpowercables.
When flexible wires areusedforpower and grounding connectionsit is
necessarytoprovide appropriatecrimp terminals.
Use wire sizing and fuses as recommended in table 3.5.

CHAPTER3- INSTALLATIONAND CONNECTION
25*135*22535353535503535505050505063636380808080100
– Recommended wiring/fuses - Use 75 ºC copper wires only
- Three phase connection /
- Single phase connection

CHAPTER3- INSTALLATIONAND CONNECTION
The wire sizing indicatedintable3.5 are reference values only. The exact
wire sizing depends on the installation conditions and the maximum
acceptablelinevoltagedrop.
The tightening torque is as indicated in table 3.6. Use 75ºC copper wire
- Recommended tightening torque for power and
For protecting the input rectifier diodes and the wiring, use UR Type
(Ultra-Rapid) fuses with i
t equalor lower than indicated in table 3.5.
Standard fuses may be used optionally at the input with currents as
indicated in table 3.5, or circuit breakers dimensioned for 1.2 x rated
inverterinputcurrentforthe CTor the VToperation(refer toitems9.1.2
Howeverinthiscase,onlytheinstallationwillbeprotectedagainstshort-
circuit,butnot thediodes ofthe rectifierbridgeat theinverterinput.This
optionmaydamagethe inverterin caseof short-circuitof some internal

CHAPTER3- INSTALLATIONAND CONNECTION
- Power/grounding connections
Provide an AC input disconnecting switch to switch OFF input power to the
Thisdeviceshall disconnecttheinverterfrom theACinputsupplywhen required
(e.g.duringmaintenanceservices).Howeveritcannotbe usedasan emergency
TheneutralconductoroftheACinputfortheinvertermustbephysicallygrounded,
butdo not use itfor grounding purposeof the inverter(s).
Acontactor or another device that frequently disconnects and reapplies theAC
supplyto the inverter in order to start andstop themotor maycause damage to
theinverterpowersection.Thedriveisdesignedtouse controlsignalsfor starting
andstoppingthe motor.If used,theinput devicemust not exceedone operation
every6 minutes otherwisetheinverter may bedamaged.
Setjumper toselect therated linevoltage380-480V, for inverters86Aor
TheAC inputvoltagemustbecompatiblewiththe inverter ratedvoltage.
TheCFW-09is suitableforusein circuitscapableofsupplyingnotmorethan
30.000A(rms) symmetrical (230 V/480 V/600 V/690 V).
TheCFW-09canbeinstalledonpowersupplieswithahigherfaultlevelprovided
thatadequateprotection is provided by the fuses or circuit breaker.
DC Link Inductor/Line Reactor
item8.7 relatingto therequirement forusingthe LineReactor /DC Link
Capacitors for powerfactor correctionare not required at the input(R, S,
they MUST not be connected at the output (U, V, W).

CHAPTER3- INSTALLATIONAND CONNECTION
Theinverteris providedwithelectronicprotection againstmotoroverload.
This protection must be set according the specific motor.When the same
inverterdrivesseveral motors,useindividualoverloadrelaysfor each
motor. Maintainthe electrical continuity of the motor cable shield.
If a disconnect switch or a contactor is inserted in the motor supply line,
DO NOT operate the disconnect switch with the motor running or when
is enabled. Maintain the electrical continuity of the motor cable
With the Dynamic Braking (DB) option, the DB resistor shall be mounted
externally. Figure 8.22 shows how to connect the DB resistor. Size it
according to the application, not exceeding the maximum current of the
Use twisted cable for the connection between inverter
Providephysical separationbetween this cable andthe
cables. When the DB resistor is mounted inside the
watt loss generated when the enclosure size and
Invertersmust begrounded forsafety purposes(PE).Theearth orground
connectionmustcomplywiththelocalregulations.Forgroundinguse
with cross section as indicated in table 3.5. Make the ground
toa groundingbar ortothegeneralgroundingpoint(resistance
Do not share the ground wiring with other equipment that operates with
highcurrent (for instance, highvoltagemotors, welding
severalinvertersareused together, referto figure3.10.
- Grounding connections for more than one inverter

CHAPTER3- INSTALLATIONAND CONNECTION
Do notuse the neutral from the main power supplyto ground the inverter.
When electromagnetic interference (EMI), generated by the inverter,
problems with other equipment, use shielded wires or install the
metallic conduits. Connect one end of the shielding to the
point andthe other end to the motor frame.
Alwaysgroundthemotorframe. Groundthemotorinthepanelwhere
is installed or ground it to the inverter. The inverter output
separatelyfrom the input wiring, as well as from the
control and signal cables.
ForIT networks (alsoknown asungrounded orhigh earthingimpedance
networks) it is necessary to consider the following:
Models 180 A to 600 A/380-480 V,2.9 A to 79 A/500-600 V, 107A to 472 A/
500-690 V and 100 A to 428 A/660-690 V have a varistor and capacitor
connectedbetween inputphase and groundthat must be disconnectedif
IT networkis used for that, remove the jumper as shown infigure 3.11.
In 500-600V/500-690V/660-690 V models, the jumper is accessible taking
out (models 2.9A to 14 A/500-600 V) or opening (models 22 Ato 79A/500-
600 V, 107 A to 211 A/500-690 V and 100 A to 179 A/660-690 V) the front
coveror takingouttheconnectionscover(247Ato 472A/500-600Vand 225A
In models 180Ato600A/380-480 V, besides opening or
cover(s),it is required toremovethe control board
The externalRFIfiltersthat are necessary in orderto fulfill the requirements
of European EMC Directive as stated in item 3.3, cannot be used with IT
The user must check and assume the responsibilityof personnel electrical
shock risk when usinginverters in IT networks.
Aboutthe useof a differential relayat the inverter input:
-The indicationof phase-to-groundshort-circuitmust beprocessedby
in order to indicate onlya fault message or to turn off the
-Check withthe relaymanufacturerits properoperationwith frequency
becauseof the existinghigh-frequencyleakage currents flowing
inverter, cable and motor parasitic capacitancestotheearth.

CHAPTER3- INSTALLATIONAND CONNECTION
g) Models 247 A to 472 A/500-600 V and 225 A to 428 A/660-690 V
- Location of jumper to disconnect the varistor and capacitor between input phase and ground -
necessary only in models when IT network is used
a) Models 180 A to 240 A/380-480 V
b) Models 312 A to 600 A/380-480 V
c) Models 2.9 A to 14 A/500-600 V
d) Models 22 A to 32 A/500-600 V
e) Models 44 A to 79 A/500-600 V
f) Models 107 A to 211A/500-600 V and 100 A to 179 A/660-690 V

CHAPTER3- INSTALLATIONAND CONNECTION
Thecontrolwiring(analoginputs/outputs,digitalinputs/outputsandrelayoutputs)
is made on the following terminal blocks of the Electronic Control Board CC9
(refer to location in figures 3.7, item 3.2.2).
Digital and Analog Signals
- XC1/XC1A control terminals description (CC9 board) - Active high digital inputs
= normally closed contact,
FWD / REV Section (RemoteMode)
Digital inputs 24 Vdc source
0 V Reference of the 24 Vdc Source
Positive Reference for Potentiometer
Speed Reference (Remote Mode)
Negative Reference for Potentiometer
0 V Reference for Analog Outputs
Analog Output: Motor Current
0 V Reference for Analog Outputs
Relay Output - Speed > P288 (N > Nx)
Relay Output - Speed > P288 (N > Nx)
Relay Output - Speed Reference >
AI1+13AI1-14-REF15AI2+16AI2-17AO1
Minimum High Level: 18 Vdc
Grounded by a 249 resistor
+ 5.4 Vdc 5 %, Capacity: 2 mA
Valid for AI1 and AI2 differential,
resolution: 10 bits, (0 to 10) Vdc or
(0 to 20) mA / (4 to 20) mA
500[(0 to 20) mA / (4 to 20) mA]
Grounded by a 5.1 resistor
The following diagram shows the control wiring with the digital inputs as active
highas setonfactory(jumper betweenXC1:8 andXC1:10).

CHAPTER3- INSTALLATIONAND CONNECTION
- XC1/XC1A control terminals description (CC9 board) - active low digital inputs
= normally closed contact,
FWD / REV Section (RemoteMode)
Digital inputs 24 Vdc source
0 V Reference of the 24 Vdc Source
Positive Reference for Potentiometer
Speed Reference (Remote Mode)
Negative Reference for Potentiometer
0 V Reference for Analog Outputs
Analog Output: Motor Current
0 V Reference for Analog Outputs
Relay Output - Speed > P288 (N > Nx)
Relay Output - Speed > P288 (N > Nx)
Relay Output - Speed Reference > P288
DI12DI23DI34DI45DI56DI67COM8COM924 Vdc
AI1-14-REF15AI2+16AI2-17AO118GND(AO1)
Minimum High Level: 18 Vdc
Grounded by a 249 resistor
differential, resolution: (0 to 10) Vdc or
(0 to 20) mA / (4 to 20) mA
Impedance: 400 k [(0 to 10) Vdc]
500 [(0 to 20) mA / (4 to 20) mA]
Thefollowingdiagramshowsthe controlwiringwith thedigitalinputs asactive
low(withouta jumperbetweenXC1:8 andXC1:10).
Forusing the digitalinputs asactivelowit is necessaryto remove thejumper
betweenXC1:8 andXC1:10andplaceit betweenXC1:7 andXC1:9.

CHAPTER3- INSTALLATIONAND CONNECTION
Related Parameters: P221, P222, P234 to P240.
During the signal and control wire installation you must follow these
Cable Cross Section: 0.5 mm² (20AWG) to 1.5 mm² (14 AWG );
Max.Torque:0.50 N.m (4.50 lbf.in);
XC1 wiringmust be connectedwith shielded cables and installed
separatelyfrom other wiring (power, control at 110V/220 Vac,etc.),
- Wiring separation distances
- Dip switch position for
(0 to 10) V or (0 to 20) mA/(4 to 20) mA selection
- Dip switch configuration
If the crossing of these cables is unavoidable, install them perpendicular,
maintaining a minimum separation distance of 5 cm (2 in) at the crossing
*Can be usedfor grounding
)ON(4 to 20) mA / (0 to 20) mA
)ON(4 to 20) mA / (0 to 20) mA
As a default the analogue inputs are selected as (0 to 10) V. This can be

CHAPTER3- INSTALLATIONAND CONNECTION
For wiring distances longer than 50 m (150 ft), it is necessary to use
galvanicisolatorsfor theXC1:11to
Relays, contactors, solenoids or electromagnetic braking coils installed
near inverters can generate interference in the control circuit. In order to
eliminate this interference, connect RC suppressors in parallel with the
coils of ACrelays.Connect a free - wheeling diode in case of DC relays/
When anexternal keypad(HMI) isused (Refer tochapter 8),separate the
cable thatconnectsthekeypadtotheinverterfromothercables,maintaining
a minimum distance of 10 cm (4 in) between them.
– Keypad Start/Stop (LocalMode)
, you can operate the inverter in the local
mode.Thisoperationmodeis recommended foruserswho areoperating the
inverter for the first time; without additional control connections. For start-up
according tothis operation mode,followchapter 5.
Connect the shield as shown in figure 3.14.
Screw located on the CC9 Board and on support plate of the CC9 Board
2-Wire ControlStart/Stop(RemoteMode)
thefactory default programming, the selectionof the operationmode(Local/
Remote) is made via the key (default is Local).

CHAPTER3- INSTALLATIONAND CONNECTION
-3-Wire ControlStart/Stop
Selection of function Start/Stop with 3 wire control.
Parameterstobe programmed:
Program P224 = 1 (DIx) if you want the 3 wire control in local mode.
Program P227 = 1 (DIx) if you want the 3 wire control in remote mode.
To program therotationselectionvia DI2
NO contact for Start and NC contact
Thespeed referencecanbe viaAnalogInputAI (as in
(HMI) (as in Connection 1),
or via any other source. The function Start/Stop is
DI12DI23DI34DI45DI56DI67COM8COM924 Vdc
GND11+REF12AI1 +13AI1 -14-REF
- XC1 (CC9) wiring for connection 3
DI12DI23DI34DI45DI56DI67COM8COM924 Vdc

CHAPTER3- INSTALLATIONAND CONNECTION
SelectionfunctionFWD/REV.
Parameterstobe programmed:
When the FWD Run / REV Run Function is programmed, the function is
alwaysactive, in both local and remote operation modes.
At the same time, the keys
remaininactive (even when
The direction of rotationis defined automatically by the FWD Run / REV Run
Clockwiserotationfor Forwardand CounterClockwise rotationfor Reverse.
The speedreference can befrom anysource (as inConnection 3).
- XC1 (CC9) wiring for connection 4

CHAPTER3- INSTALLATIONAND CONNECTION
TheCFW-09 inverterserieswas designedtaking inconsiderationsafetyand
EMC aspects. The CFW-09 units do not have an intrinsic function until
connectedwithothercomponents(e.g.a motor).Therefore,thebasicproduct
isnot CE marked for compliancewith theEMCDirective. Theend user takes
personal responsibility for the EMC compliance of the whole installation.
However, when installedaccording tothe recommendations described inthe
product manual and including the recommended filters/EMC measures the
CFW-09 fulfillallrequirementsof the EMCDirective(89/336/EEC)asdefined
bythe ProductStandardEN61800-3“Adjustablespeedelectricalpowerdrives
systems”, specific for variable speed drives systems.
Compliance of the whole series of the CFW-09 is based on testing some
representative models. A Technical Construction File was checked and
approvedbya Competent Body.
The CFW-09 inverter series are intended for professional applications only.
Therefore,theharmoniccurrentemissionsdefinedbythestandardsEN61000-
3-2 and EN61000-3-2/A14do not apply.
The 500-600 V models are intended to be connected to an industrial low
voltage power supply network, or public network which does not supply
buildings used for domestic purpose - second environment according to
Thefiltersspecifiedin items 3.3.2and 3.3.3 donot applyto the 500-600V
For installing the frequency inverters in accordance to the
EN61800-3the followingitemsarerequired:
Output cables (motor wiring) must be flexible armored or to be installed
inside a metallic conduit or in a tray with equivalent attenuation.
The control (inputs and outputs) and signal wiring must be shielded or
installed inside a metallic conduit or a tray with equivalent attenuation.
It is essential to follow the grounding recommendations presented in this
Forfirst environment(low-voltage public network)
(radio-frequencyinterferencefilter)atinverterinput.
For second environment (industrial areas) and unrestricted
:install anRFI filter at inverterinput.
Theuse of a filterrequires:
Thecable’sshieldingmust besolidly connectedtothecommon backplane,
The inverterandthe filter must be mounted incloseproximity, electrically
connected, to one another, on the same metallic backplane. The wiring
between them should be kept as short as possible.
Twofiltersaresuggested:EpcosandSchaffner,detailedonthefollowingitems
3.3.2and3.3.3.Figures3.18 and3.19presenta connectiondiagramfor EMC
filters,Epcos and Schaffnerrespectively.

CHAPTER3- INSTALLATIONAND CONNECTION
For installation with inverters that complies class A1 (first environment
restricted distribution), note that this is a product of the restricted sales
distribution class according to IEC/EN61800-3 (1996) +A11 (2000). In a
domestic environment this productmaycause radio interference in which
case the user may be required to take adequate measures.
Forinstallationwith invertersthatcompliesclassA2 (second environment
unrestricted distribution), note that this product is not intendedtobeused
ona low-voltagepublic networkwhich suppliesdomestic premises. Radio
frequencyinterference is expectedif usedonsuchanetwork.
Descriptionofconductedemissionclassesaccordingto thestandard
ClassB:first environment, unrestricted distribution
ClassA1:first environment,restricted distribution
ClassA2: second environment,unrestricted distribution
The followingtables 3.9,3.10 and 3.11showthe Epcos filters forCFW-09
frequencyinverterswith380-480V,500-600Vand660-690V powersupply
respectively,themaximummotorcablelengthforconductedemissionclas-
ses A1, A2 and B (according to EN61800-3) and the electromagnetic
radiationdisturbancelevel.
- Epcos EMC filters connection in CFW-09 frequency inverters
Controlingand Signal Wiring
Panel or MetallicEnclosure
Protective Grounding - PE

CHAPTER3- INSTALLATIONAND CONNECTION
N/A = Not Applicable – The inverters were not tested with these limits.
The RFI filter suggested above for model 600 A/380-480 V considers a power supply with 2 % voltage drop. For a power supply with 4 %
voltage drop it’s possible to use B84143B600S20 RFI filter. In this case, consider the same motor cable lengths and radiated emission data
Minimum output frequency = 2.9 Hz.
Minimum output frequency = 2.4 Hz.
Epcos filters list for CFW-09 inverter series with 380-480 V power supply
Maximum motor cable length
according to conducted emission
Electromagnetic radiation
disturbance level (Product
First environment, restricted
unrestricted distribution
unrestricted distribution
100m50m20mSecond environment,
unrestricted distribution
First environment, restricted
First environment, restricted
100m35mFirst environment, res
First environment, restricted
First environment, restricted
First environment, restricted
CT60AVTSecond environment,
unrestricted distribution
unrestricted distribution
First environment, restricted
First environment, restricted
100m25mFirst environment, restricted
First environment, restricted
First environment, restricted
100mFirst environment, restricted
First environment, restricted
First environment, restricted
First environment, restricted
First environment, restricted

CHAPTER3- INSTALLATIONAND CONNECTION
Maximum motor cable length
ClassA2ClassA1ClassBInside metallic
Electromagnetic radiation
unrestricted distribution
unrestricted distribution
unrestricted distribution
unrestricted distribution
- Epcos filters list for CFW-09 inverter series with 500-600 V power supply
N/A = Not Applicable – The inverters were not tested with these limits.
Minimum output frequency = 2.4 Hz.
unrestricted distribution
unrestricted distribution
unrestricted distribution
unrestricted distribution
unrestricted distribution
- Epcos filters list for CFW-09 inverter series with 660-690 V power supply
N/A = Not Applicable – The inverters were not tested with these limits.
Minimum output frequency = 2.4 Hz.

CHAPTER3- INSTALLATIONAND CONNECTION
The following tables 3.12 and 3.13 show the Schaffner filters list for CFW-09
inverterseries with 380-480V and 220-230V power supply, respectively.
- Schaffner EMC filters connection in CFW-09 frequency inverters
Controlingand Signal Wiring
Panel or MetallicEnclosure
Protective Grounding - PE
EL3L2L1PEXRTSInputCMChoke
NoNoNoNoNoNoNoNoNoNoNoNoNo
PanelElectromagnetic radiation
First environment, restricted
unrestricted distribution
unrestricted distribution
First environment, restricted
First environment, restricted
First environment, restricted
First environment, restricted
First environment, restricted
- Schaffner filters list for CFW-09 inverter series with 380-480 V power supply

CHAPTER3- INSTALLATIONAND CONNECTION
First environment, restricted
First environment, restricted
First environment, restricted
unrestricted distribution
First environment, restricted
First environment, restricted
First environment, restricted
First environment, restricted
First environment, restricted
First environment, restricted
- Schaffner filters list for CFW-09 inverter series with 380-480 V power supply
Electromagnetic radiation
(1) - First environment/restricted distribution (Basic Standard CISPR 11):
30 to 230 MHz: 30 dB (uV/m) in 30 m
230 to 1000 MHz: 37 dB (uV/m) in 30 m
Second environment/unrestricted distribution (Basic Standard CISPR 11: Group 2, class A):
30 to 230 MHz: 40 dB (uV/m) in 30 m
230 to 1000 MHz: 50 dB (uV/m) in 30 m
(2) - Motor shielded cable length:

CHAPTER3- INSTALLATIONAND CONNECTION
Electromagnetic radiation
(Product StandardEN61800-
NoNoNoNo2 x Schaffner 203
BBBA1A1A1A1A1A1A1A1A1First environment, restricted
First environment, restricted
First environment, restricted
First environment, restricted
First environment, restricted
First environment, restricted
First environment, restricted
First environment, restricted
unrestricted distribution
First environment, restricted
First environment, restricted
First environment, restricted
(1) - First environment/restricted distribution (Basic Standard CISPR 11):
30 to 230 MHz: 30 dB (uV/m) in 30 m
230 to 1000 MHz: 37 dB (uV/m) in 30 m
Second environment/unrestricted distribution (Basic Standard CISPR 11: Group 2, class A):
30 to 230 MHz: 40 dB (uV/m) in 30 m
230 to 1000 MHz: 50 dB (uV/m) in 30 m
(2) - Motor shielded cable length:
- Schaffner filters list for CFW-09 inverter series with 220-230 V power supply

CHAPTER3- INSTALLATIONAND CONNECTION
Table 3.14showsthe maintechnicalcharacteristicsof Epcosand Shaffner
filters used in CFW-09 inverter series. Figure 3.20 presents drawings of
EMC Filter Characteristics
- Technical specifications of EMC filters for the CFW-09 inverter series
According to the manufacturer, this filter can be used up to 331 A.

CHAPTER3- INSTALLATIONAND CONNECTION
a)EPCOS B84143A8R105Filter
- EMC filters for CFW-09 inverter series [dimensions in mm]
b)EPCOS B84143A16R105Filter

CHAPTER3- INSTALLATIONAND CONNECTION
c)EPCOS B84143A25R105 Filter
- EMC filters for CFW-09 inverter series [dimensions in mm]
d) EPCOS B84143A36R105 and B84143A50R105Filter

CHAPTER3- INSTALLATIONAND CONNECTION
e)EPCOS B84143A66R105Filter
f) EPCOS B84143A90R105 Filter
- EMC filters for CFW-09 inverter series [dimensions in mm]

CHAPTER3- INSTALLATIONAND CONNECTION
g)EPCOS B84143A120R105Filter
h)EPCOSB84143G150R110Filter
- EMC filters for CFW-09 inverter series [dimensions in mm]

CHAPTER3- INSTALLATIONAND CONNECTION
i)EPCOSB84143G220R110 Filter
j) EPCOS B84143B320S20and B84143B400S20 Filters
- EMC filters for CFW-09 inverter series [dimensions in mm]

CHAPTER3- INSTALLATIONAND CONNECTION
k)EPCOSB84143B600S20Filter
l)EPCOSB84143B1000S20Filter
- EMC filters for CFW-09 inverter series [dimensions in mm]

CHAPTER3- INSTALLATIONAND CONNECTION
n) EPCOS B84143B250S21 Filter
- EMC filters for CFW-09 inverter series [dimensions in mm]
m) EPCOS B84143B150S21andB84143B180S21Filters
1242±1152 x M6 / 6 mm deep

CHAPTER3- INSTALLATIONAND CONNECTION
o)EPCOS B84143B400S125Filter
- EMC filters for CFW-09 inverter series [dimensions in mm]

CHAPTER3- INSTALLATIONAND CONNECTION
p)EPCOS B84143B600S125Filter
- EMC filters for CFW-09 inverter series [dimensions in mm]

CHAPTER3- INSTALLATIONAND CONNECTION
q) Schaffner FN3258-7-45, FN3258-16-45, FN3258-30-47, FN3258-55-52, FN3258-100-35 and FN3258-130-35 filters
Type/35- Terminalblockforflexibleand
Type/45-Terminal blockfor6 mm
Type/47-Terminal blockfor 16mm
Type/52- Dimesionsinmm(inch)
- EMC filters for CFW-09 inverter series [dimensions in mm (in)]

CHAPTER3- INSTALLATIONAND CONNECTION
r) Schaffner FN3359-150-28, FN3359-250-28, FN3359-400-99, FN3359-600-99 and FN3359-1000-99 filters
Bus bar connection(Type/99)
These filters are supplied with M12
bolts for the grounding connection.
- EMC filters for CFW-09 inverter series [dimensions in mm]
Thedeclaration ofconformityCEisavailableonthewebsitewww.weg.net
or on the CD, which comes with the products.

ThischapterdescribestheCFW-09operationviathestandardKeypador
Human-MachineInterface(HMI),providingthefollowinginformation:
GeneralKeypadDescription;
Description of the StatusIndicators.
Thestandard CFW-09Keypadhas tworeadout displays:a LED readout
witha 4 digit,seven-segmentdisplay anda LCDdisplay withtwo linesof
16alphanumeric characters.Therearealso4indicatorLEDsand 8keys.
Figure4.1 shows the frontview of theKeypadandindicates the position
of the readouts, keys and status LEDs.
Functionsof the LEDDisplay:
The LED Display shows the fault codes, inverter status, the parameter
numberandits value.For unitsof current, voltageor frequency, the LED
display shows the unit in the right side digit (L.S.D.) as shown here.
speedand other parameters
Whenthe indicationis higherthan 9999 (forinstanceinrpm)thenumber
corresponding to the ten of thousand will not be displayed (ex.: 12345
rpm will be read as 2345 rpm). The correct indication will be displayed
Functionsof the LCD Display:
The LCD Display shows the parameter number and its value
simultaneously, without requiringthe toggling of the
provides a brief description of each parameter function, fault code and

CHAPTER4 - KEYPAD (HMI)OPERATION
- Direction of rotation (FWD / REV) LEDs
Green LEDONand Red LED OFF.
GreenLED OFF and Red LED ON.
DirectionofRotation (FWD/REV)LEDs:
BasicFunctionsof the Keys:
The functions describedbelow are validfor factory default programming and
LocalModeoperation. Theactual functionof thekeysmayvary ifparameters
P220throughP228are re-programmed.
Startstheinvertervia accelerationramp.Afterstarting,thedisplaysequences
through these units at each touch of the Start key in the order shown here
Stops (disables) the inverter via deceleration ramp. Also resets the inverter
after afault has occurred.
TogglestheLEDdisplaybetweentheparameternumberanditsvalue(Number/
Increasesthe speed,the parameternumber or theparameter value.
Decreasesthe speed,the parameternumber or theparameter value.
Reversesthe directionofmotor rotationbetweenForward/Reverse.
Toggles betweentheLOCALand REMOTEmodesof operation.
Performsthe JOG functionwhenpressed.
Any DIx programmed for General Enable must be closed (and the CFW-09
must be stopped)toenable JOG function.
FWD / REVCommand (Key orDI2)

CHAPTER4 - KEYPAD (HMI)OPERATION
The keypadis used for programmingand operating the CFW-09allowingthe
Indicationof theinverterstatus andoperationvariables;
FaultIndicationand Diagnostics;
Viewingandprogrammingparameters;
Allfunctions relatingto the CFW-09 operation (Start,Stop,Motor Direction of
Rotation,JOG,Increment/Decrementof theSpeedReferenceandSelectionof
LocalMode/RemoteMode)canbe performedthroughthe Keypad.This isvalid
withthefactorydefaultprogrammingof theinverter.Allkeypadkeysareenabled
when the Local Mode has been selected. These same functions can be
performed in Remote Modeby means of digitaland analog inputs.
Flexibilityis providedthroughthe abilityto programthe parameters thatdefine
the input and outputfunctions.
Keypad keys operation description:
keysare enabledwhenP224= 0 (I,O Key)for LocalMode
and/or P227 = 0 (I, O Key) for Remote Mode.
Startsinverter via Acceleration Ramp.
StopstheinverterviaDecelerationRamp.
Itresets theinverter after a FaultTrip (alwaysactive).
When the Jog key is pressed, it accelerates the motor according to the
AccelerationRampup to theJOG speed programmed inP122 (defaultis 150
rpm). When released, the motor decelerates according to the Deceleration
EnabledwhenP225= 1(Keypad)for LocalModeand/orP228=1(Keypad)for
Ifa DigitalInput isset to GeneralEnable(P263toP270= 2) ithas to beclosed
to allowthe JOG function.
Selects the control input and speed reference source, toggling between LO-
EnabledwhenP220 = 2 (Keypad LOC) or 3 (Keypad REM).
Reversesthe motor directionof rotation.
Enabled when P223 = 2 (Keypad FWD) or 3 (Keypad REV) for Local Mode
and/or P226= 2 (KeypadFWD) or 3 (Keypad REV) for Remote Mode.
The keys described below are enabled when P221 = 0 (Keypad) for Local
Modeand/orP222=0(Keypad)forRemoteMode.TheparameterP121 contains
the speed reference set by the keypad.
When pressed it increasesthe speed reference.
When pressed itdecreases the speed reference.

CHAPTER4 - KEYPAD (HMI)OPERATION
ParametersP002to P099arereservedforthe displayof “read-only”values.The
factorydefaultdisplaywhen poweris appliedto theinverterisP002.Motor speed
inrpm.The usercan scroll through thevarious read-onlyparametersor use the
factory configured display of the key values. This is done by pressing the start
Someselected“read-only” variablescan beviewedfollowingthe
The “read-only” variable to be shown afterAC power is applied to the inverter
InitialMonitoringParameter
P070 (motor speed and motor current)
P040 (PID process variable)
- Choosing the initial monitoring parameter
The last frequency Reference set by the keys and is stored
AC power is removed, provided P120= 1
Backup activeis the factorydefault).Tochangethe frequency reference before
startingthe inverter,the valueof parameter P121 must bechanged.
6 =runMotorFrequencyP005=60.0Hz

CHAPTER4 - KEYPAD (HMI)OPERATION
InverterisREADY to be started
Linevoltagein toolowfor inverteroperation
The displayflashes in the following conditions:
Duringthe DCInjection braking;
Tryingto change a parameter value when itis not allowed;
Inverterin acurrent overloadcondition(Referto chapter7 - Diagnostics
Inverterin Fault condition(Referto chapter 7 - Diagnosticsand
All CFW-09 settings are made through the parameters. The parameters are
shown on the display with the letter
Eachparameter isassociatedto a numerical value(parametercontent),that
correspondsto an optionselected among thoseoptions thatareavailablefor
Thevaluesof theparametersdefinethe inverterprogrammingorthe valueof
avariable(e.g. current,frequency,voltage).For inverterprogramming you
shouldchangetheparameter content(s).
To allow the reprogramming of any parameter value it is required to change
parameterP000 tothepasswordvalue.The factorydefaultpasswordvalueis
5.Otherwiseyoucanonlyreadtheparametervaluesandnotreprogramthem.
P000 descriptionin chapter 6.

CHAPTER4 - KEYPAD (HMI)OPERATION
Selectthe desiredparameter
Numeric valueassociated to the
Setsthe new desired value.
For parameters that can be changed with the motor running, the inverter
will use the new value immediatelyafter it has been set. For the parameters
that can be changed only with motor stopped, the inverter will use this new
set value only after the key is pressed.
Bypressing the keyafter the reprogramming, the new programmed
value will be stored automatically and will remain stored until a new value is
Ifthelastvalueprogrammedin theparameteris notfunctionallycompatible
withotherparametervaluesalreadyprogrammed,anE24-ProgrammingError
Exampleof programmingerror:
Programming two digital inputs (DIx) with the same function. Refer to table
4.2 forthe list of programmingerrors that will generate anE24 Programming

CHAPTER4 - KEYPAD (HMI)OPERATION
- Incompatibility between parameters - E24
To allowthereprogrammingofanyparametervalueit isrequiredtochange
parameterP000 tothepasswordvalue.The factorydefaultpasswordvalueis
5.Otherwiseyoucanonlyreadtheparametervaluesandnotreprogramthem.
P000 descriptionin chapter 6.
Twoor more parameters between P264 or P265 or P266 or P267 or P268 or P269 and P270 equal to 1 (LOC/REM).
Twoor more parameters between P265 or P266 or P267 or P268 or P269 and P270 equal to 6 (Ramp 2).
Two or more parameters between P265 or P266 or P267 or P268 or P269 and P270 equal to 9 (Speed/Torque).
P265 equal to 8 and P266 different than 8 or vice versa (FWD Run / REV Run).
P221 or P222 equal to 8 (Multispeed) and P266
[P221 = 7 or P222 = 7] and [(P265
(with reference = E.P. and without DIx = increase E.P. or without DIx = decrease E.P.).
P264 and P266 equal to 8 (Reverse Run).
7] and [(P265 = 5 or P267 = 5 or P266 = 5 or P268 = 5)].
(without reference = E.P. and with DIx = increase E.P. or with DIx = decrease E.P.).
P265 or P267 or P269 equal to 14 and P266 and P268 and P270 different than 14 (with DIx = Start and DIx
P266 or P268 or P270 equal to 14 and P265 and P267 and P269 different than 14 (with DIx
P220 > 1 and P224 = P227 = 1 without any DIx set for Start/Stop or DIx = Fast Stop or General Enable.
P220 = 0 and P224 = 1 and without DIx = Start/Stop or Fast Stop and without DIx = General Enable.
P220 = 1 and P227 = 1 and without DIx = Start/Stop or Fast Stop and without DIx = General Enable.
DIx = STARTand DIx = STOP, but P224
Twoor more parameters between P265 or P266 or P267 or P268 or P269 and P270 equal to 15 (MAN/AUT).
Two or more parameters between P265 or P266 or P267 or P268 or P269 and P270 equal to 17 (Disables
Twoor more parameters between P265 or P266 or P267 or P268 or P269 and P270 equal to 18 (DC Voltage Regulator).
Two or more parameters between
P265 or P266 or P267 or P268 or P269 and P270
equal to 19 (ParameterSetting Disable)
Two or more parameters between P265, P266, P267, P268 and P269 equal to 20 (Load user via DIx).
P296 = 8 and P295 = 4, 6, 39, 40, 41, 42, 43, 44, 45, 46, 47, 48, or 49 (P295 incompatible with inverter model – To avoid damages
of the internal inverter components).
P296 = 5, 6, 7 or 8 and P297 = 3 (P297 incompatible with inverter model).
Twoor more parameters between P265 or P266 or P267 or P268 or P269 and P270 equal to 21 (Timer RL2).
Twoor more parameters between P265 or P266 or P267 or P268 or P269 and P270 equal to 22 (Timer RL3).
P265 or P266 or P267 or P268 or P269 or P270 = 21 and P279
P265 or P266 or P267 or P268 or P269 or P270 = 22 and P280
P279 = 28 and P265 or P266 or P267 or P268 or P269 or P270
P280 = 28 and P265 or P266 or P267 or P268 or P269 or P270
P2022 and P237 = 1 or P241 = 1 or P265 to P270 = JOG+ or P265 to P270 = JOG-.
P203 = 1 and P211 = 1 and [P224 = 0 or P227 = 0]
P220 = 0 and P224 = 1 and P227 = 0 or P227 = 1 and P263 = 0
P220 = 1 and P224 = 0 or P224 = 1 and P227 = 1 and P263 = 0
P220 = 2 and P224 = 0 or P224 = 1and P227 = 0 or P227 = 1 and P263 = 0
E24 - Incompatibility between parameters

Thischapterprovidesthefollowinginformation:
Howtocheckand preparetheinverterbefore power-up;
Howto power-upandcheck for properoperation;
Howto operatetheinverter.
Theinvertershallbeinstalledaccordingtochapter3:Installation
DisconnecttheACinputpowerbefore making anyconnections.Evenwhen the
inverter project is different from the suggested connections, the following
recommendationsare applicable.
Check if thepower,grounding and controlconnections are correct and
Clean the inside of the inverter
Removeall shippingmaterialfrom the insideofthe inverter orcabinet.
Check if theselectedinverterAC poweris correct(
Check allmotor connectionsand verify if itsvoltage, current and frequency
match theinverter specifications.
Whenthemotordataissetproperlyduringthefirstpower-uproutine,
the inverter automatically sets the additional parameters used for
the correct operationunder this control mode.
Uncouple the load from the motor
If the motor cannot be uncoupled, make sure that the direction of rotation
(FWD/REV) cannot cause damage to the machine.
Close the inverter cover or cabinet doors
After theinverter has been checked,AC power canbe applied:
Measurethe linevoltage andcheck if it iswithinthespecified range(referto
Close the input circuit breaker or disconnect switch.
3) Check if the power-up has been successful
When the inverterispowered upforthe first timeorwhen thefactory default
parameter values areloaded (P204 = 5),astart-upsub-routineis run. This
sub-routinerequests theuser toprogramsomebasic parameters toensure
properoperationandmotorprotection.
Astart-up programming exampleisshown below:
Rated Voltage: 380 V to 480 V

Initial Power-up - Programming via Keypad (HMI) (Based on the example above):
After power-up,the displayshows
Press the key to enter the
Press the key to save the
selected option and exit the
InverterRated VoltageSelection:
Press the key to go to the
Press the key to enter the
languageP201=EnglishlanguageP201=EnglishlanguageP201=EnglishVFDRated Volt.P296=440/

SelectedInverterRatedVoltage:
ProgrammedMotorRated Voltage:
Press the key to save the
selected option and exit the
Press the key to go to the next
Press the key to enter the
thecorrect motorrated voltagevalue
Press the key to save the
programmed value and exit the
Press the key to go to the next
Press the key to enter the
MotorRatedVoltP400=440VMotorRatedCur.P401=9.0A
selecttheinverterpowersupplyvoltage
MotorRatedVoltP400=440VMotorRatedVoltP400=

thecorrect motor ratedcurrent value
Press the key to save the
programmed value and exit the
Press the key to go to the next
Press the key to enter the
Use the and keysto set the
correctmotor ratedfrequencyvalue
Press the key to save the
programmedvalueand exitthe
Press the key to go to the next
Press the key to enter the
ProgrammedMotor RatedCurrent:
MotorRatedFrequencyRange:
ProgrammedMotorRated Frequency:
P401=7.9 AMotorRatedCur.P401=7.
9 AMotorRated FreqP403=60HzMotorRated Fre
d FreqP403=60HzMotorRated

thecorrect motor ratedrpmvalue
Press the key to save the
programmed value and exit the
Press the key to go to the next
Press the key to enter the
Use the and keys to select
Press the key to save the
selected option and exit the
Press the key to go to the next
Press the key to enter the
SelectedMotor Rated Power:
Motor VentilationTypeSelection:
= 1730rpmMotorRatedHPP404=0.33HPMotorRatedHPP404=5.0HPMotorRatedHPP404=5.0HPMotor

Opentheinputcircuitbreakerordisconnectswitchtoshutdownthe CFW-09.
To repeatthe initialpower-upprocedure:
(this loads the factorydefault parameters)
andfollow theinitialpower-up sub-routineagain;
The initial power-up sub-routine described above automatically sets some
parameters accordingtotheentereddata.Formore details,referto chapter6.
Modificationof motor characteristics after thefirstpower up:
Insert the motor data at parameters P400 to P407;
Foroperationin the vector mode runthe self-tuning routine (P408 >0);
Set P156, P157, P158, P169, P170, P171, and P172;
Powerthe inverter down and up for the new settingsto take place andfor
Modificationof motorcharacteristics after thefirst powerup, for operation in
Followthe previous procedures and also set parameter P297 to 2.5 kHz.
describes thestart-upprocedurewhenoperatingviatheKeypad(HMI).
Four types of control willbe considered:
V/F 60 Hz, Sensorless Vector, Vector
with Encoder Feedback and VVW (Voltage Vector
Even after theAC input is disconnected, high voltages may still be present.
Wait at least 10 minutes after powering down to allow a full discharge of the
SelectedMotor VentilationType:
Thefirst power-uproutine isfinished.
Inverteris readytooperate
Use the and keysto select
Press the key to save the
selected option and exit the
P401 maximum value is 1.8 x P295 for model 4.2 A/500-600 V and 1.6 x
P295for models7Aand 54A/220-230V;2.9Aand
and 247A/500-690 V; 100A, 127 Aand 340 A/660-690 V.

Press the key. Press the keys
programmedvalueand exitthe
Inverteris readyto beoperated
Enablestheaccesstochangeparameters
With the factory default programming
[P200= 1 (PasswordActive)],P000must
be set to 5 to allow parameters changes
Passwordvalue(factorydefault =5)
Typeof Control Selection:
VFDreadyParameterAccessP00
rolP202=V/F60HzParameterAccessP000 = 5
Control is recommended in the following cases:
Severalmotorsdriven bythesameinverter;
Motorrated current lowerthan 1/3 of theinverter ratedcurrent;
For test purposes, without a motor connected to the inverter.
TheV/F Controlcan alsobe usedinapplicationsthat donotrequire fastdynamic
responses,accuratespeedregulationorhigh startingtorque(speederror willbe
a function of the motor slip).
(RatedSlip)is programmed,speedaccuracy of1 % can
Thesequencebelowis validfortheConnection1(referto
mustbealreadyinstalledandpowered upaccordingto

Press the key to enter the
select the type of control
Press the key to save the
selected option and exit the
If the option V/F 60 Hz (value = 0) is
already programmed, ignore this
Thisis a read-onlyparameter
Motor accelerates from 0 to 90 rpm*
(Minimum Speed), in the Forward (CW)
Motoraccelerates upto 1800
thenreverses thedirectionof rotation
acceleratingback up to 1800rpm
Press the key and hold until
whether the motor is running FWD

Press the key and hold it
Motor deceleratesdown to 0 rpm
Motor accelerates from 0 rpm up to
the JOG speed set at P122
Motor deceleratesdown to 0 rpm
The last frequencyreferencevalueset via the and keysis saved.
Ifyouwishtochangethisvaluebeforeenabling theinverter, changeparameter
If the rotation direction of the motor is not correct, switch off the inverter.
Wait 10 minutes toallow acomplete dischargeof the capacitors andthen
swap any two wires at the motor output.
If the acceleration current becomes too high,speciallyat low frequencies
(< 15 Hz), adjust the TorqueBoost at
Increase/decrease the content of
graduallyuntil youobtain an
operationwithconstant current overthe entirefrequencyrange.
Refer to P136 inchapter 6.
If E01faultoccurs duringdeceleration,increase the deceleration time at