Weber SUMMIT GOLD D, SUMMIT SILVER A, SUMMIT SILVER D User Manual

®
Any Surface
Any Surface
24 inches Any Surface
24 inches
24 inches
Grill Frame
Note: For a countertop treatment: Recommended 3/4 inch ov
erhang. Notch front edge for frame to fully slide in.
27 inches min. for lid clearance
SUMMIT
SILVER A - SILVER D - GOLD D
BUILT - IN GAS GRILL DIMENSIONS
THIS GAS APPLIANCE IS DESIGNED FOR
OUTDOOR USE ONLY.
LOCATING YOUR GRILL
When determining a suitable location for your Summit® gas grill installation, give attention to concerns such as exposure to wind, proximity to trafc paths, and keeping any gas supply lines as short as possible. Never locate the Summit® gas grill in a garage, breezeway, shed, under an unprotected overhang, or other enclosed area. Locate the grill and structure so there is enough room to safely evacuate the area in case of a re.
CLEARANCE FROM SURFACES OR STRUCTURES
WARNING: Clearance from any surface or structure
is 24 inches from the back and sides of the grill. Refer to “Typical Gas Supply Installation” before starting installation.
WARNING: The structure, “island”, countertops, and
adjacent work areas for the built-in grill installation must be built from non-combustable materials only.
NOTE: If you have questions on what materials are considered non-combustable, contact you local building materials supplier or re department.
BUILT-IN STRUCTURE CUTOUT DIMENSIONS
ALL DIMENSIONS ARE TO FINISHED SURFACES.
WARNING: ALL COUNTERTOP FINISHED SURFACES
MUST BE CONSTRUCTED OF A NONCOMBUSTIBLE MATERIAL.
Built-In Cutout Dimensions
27" Grill 39" Grill Tolerances A B C
1
30
/
" 38
4
1
34
/
" 34
4
21" 21" +
1
/
" +
4
1
/
" +
4
1
1
1
/
" -
4
/
" -
4
/
" -
4
1
/
"
4
1
/
"
4
1
/
"
4
30
1
/
4
"
Built-In Fr
ame
34
1
/
4
"
24"
min.
21"
Access for electric on left hand side
6
1
/
4
"
3
3
/
4
"
Gas Inlet
28" GRILL
Note: For a countertop treatment: Recommended
3
/
4
" inch overhang.
Notch front edge for frame to fully slide in.
6
1
/
4
"
3
3
/
4
"
Gas Inlet
24"
min.
24"
min.
* Clearance from any surface or structure is at least 24 inches from the back and
sides of the grill.
27" inches min. distance from front edge of the cutout for open lid clearance
10
1/2"
min.
Side Burner Opening
36" GRILL
38
1
/
4
"
Built-In Frame
34
1
/
4
"
24"
min.
21"
Access for electric on left hand side
6
1
/
4
"
3
3
/
4
"
Gas Inlet
Note: For a countertop treatment: Recommended
3
/
4
" inch overhang.
Notch front edge for frame to fully slide in.
6
1
/
4
"
3
3
/
4
"
Gas Inlet
24"
min.
24"
min.
* Clearance from any surface or structure is at least 24 inches from the back and
sides of the grill.
27" inches min. distance from front edge of the cutout for open lid clearance
10
1/2"
min.
Side Burner Opening
BUILT-IN CUTOUT DIMENSIONS
GENERAL CONSTRUCTION DETAILS
Summit® Built-In unit and all other accessory units should be on site before contruction begins.
All dimensions have a tolerance of plus or minus +/-
1
/
" inch.
4
The grill frame rests directly on the Island Structure top nished surface. Make sure this surface is level. Do not support the grill from the bottom.
If the supporting structure is going to have an electrical outlet for a rotisserie, it should be on the left side of the structure.
Refer to Summit® Built-In Tank Drawer Installation Instructions for complete gas line locations.
2
6
1
/
4
"
3
3
/
4
"
Gas Inlet
B (6
1
/
4
")
A (3
3
/
4
")
C
Side view
Plan View Left Side
Gas Inlet
GAS SUPPLY
BUILT-IN GAS LINE LOCATIONS
Note: Leave an access in the “island” structure for gas supply and regulator service not inside the grill structure. Weber® has a gas line and regulator access door (part # 36311) available from your dealer or call Customer Service at 1-847-446-1071.
Built-In Gas Line Dimensions
28" Grill 36" Grill Tolerances
A B
Dimensions
C
3 6 2
3
/
" 3
4
1
/
" 6
4
1
/
" 2
2
3
/
"" +
4
1
/
" +
4
1
/
" +
2
1
1
1
/
" -
8
/
" -
8
/
" -
8
TYPICAL BULK PROPANE GAS SUPPLY INSTALLATION
We recommend that this installation be done by a LICENSED professional.
GENERAL SPECIFICATIONS FOR PIPING
Note - Contact your local municipality for building codes regulating outdoor gas grill installations. In absence of Local Codes, you must conform to the latest edition of the National Fuel Gas Code ANSI Z223.1/NFPA 54.
• This grill is designed to operate at 10.5 inches of water column pressure. A LP in line regulator may be necessary for this pressure.
CAUTION: IF YOUNG CHILDREN ARE IN
THE AREA, A LOCKING VALVE SHOULD BE CONSIDERED.
Pipe compound should be used which is resistant to the action of liquid propane gas when gas con­nections are made.
The gas connections must be rmly attached to rigid, permanent construction.
Note: The information provided in this manual is
1
/
"
8
1
/
"
8
1
/
"
8
general for typical installations. We cannot cover all possible installation ideas. We recommend, prior to installation, that you contact your municipality for local building codes and your local re department for installation verication.
If you have any questions, contact Customer
Note: Area should be kept clear of sharp, jagged, or
Service at 1-800-446-1071 extremely abrasive surfaces to avoid possible damage to gas supply lines. Exercise caution when pulling gas lines through built-in structure.
Table
10-1
Nominal
Iron Pipe
Size
(Inches)
1/4 .364 32 22 18 15 14 12 11 11 10 9 8 8 7 6
3/8 .493 72 49 40 34 30 27 25 23 22 21 18 17 15 14
1/2 .622 132 92 73 63 56 50 46 43 40 38 34 31 28 26
3/4 .824 278 190 152 130 115 105 96 90 84 79 72 64 59 55
1 1.049 520 350 285 245 215 195 180 170 160 150 130 120 110 100
1 1/4 1.380 1050 730 590 500 440 400 370 350 320 305 275 250 225 210
1 1/2 1.160 1600 1100 890 760 670 610 560 530 490 460 410 380 350 320
2 2.067 3050 2100 1650 1450 1270 1150 1050 990 930 870 780 710 650 610
2 1/2 2.469 4800 3300 2700 2300 2000 1850 1700 1600 1500 1400 1250 1130 1050 980
3 3.068 8500 5900 4700 4100 3600 3250 3000 2800 2600 2500 2200 2000 1850 1700
4 4.026 17500 12000 9700 8300 7400 6800 6200 5800 5400 5100 4500 4100 3800 3500
Maximum Capacity of Pipe in Cubic Feet of Gas per Hour for Gas Pressures of 0.5 psi or Less and a Pressure Drop of 0.3 Inch
Internal
Diameter
(Inches)
©1997 National Fire Protection Association, Inc., and International Approval Services - U.S., Inc. All Rights Reserved.
10 20 30 40 50 60 70 80 90 100 125 150 175 200
Water Column. (Based on a 0.60 Specic Gravity Gas)
Length of Pipe (Feet)
3
GAS SUPPLY
GAS LINE PIPING
Refer to the piping chart at the bottom of previous page.
The corrugated gas line from the manifold is 58 inches long. Do not extend the gas line.
We have provided the means to make an SAE 45° are connection. Do not use pipe sealant on this connection.
If the length of line required does not exceed 50 feet, use a 5/8” O.D. tube. One size larger should be used for lengths greater than 50 feet. Refer to piping chart.
Gas piping may be copper tubing, type K or L; polyethyl­ene plastic tube, with a minimum wall thickness of .062 inch; or standard weight (schedule 40) steel or wrought iron pipe.
Copper tubing must be tin-lined if the gas contains more than 0.3 grams of hydrogen sulde per 100 cubic feet of gas.
Plastic tubing is suitable only for outdoor, underground use.
Gas piping in contact with earth, or any other material which may corrode the piping, must be protected against corrosion in an approved manner.
Underground piping must have a minimum of 18” cover.
TEST CONNECTIONS
All connections and joints must be thoroughly tested for leaks in accordance with local codes and all listed procedures
in the latest edition of the National Fuel Gas Code ANSI
Z223.1/NFPA 54.
DANGER
Do not use an open ame to check for gas leaks. Be sure there are no sparks or open ames in the area while you check for gas leaks. This will result in a re or explosion which can cause serious bodily injury or death, and damage to property.
Typical 20 LP propane gas supply Instal­lation
We strongly recommend that you use the Summit® Built-In Tank Cabinet (#21280) for installations using a 20 lb LP cylin­der, mounted remotely in an “island” structure. The Summit® Built-In Tank Cabinet is a CSA listed acces­sory for installing a remote mounted 20 lb LP cylinder, in an “island” structure. Summit® Built-In Tank Cabinet has a hose and regulator assembly and gas connections, for connecting a remote mounted LP cylinder to the Summit® Built-In gas grill. The hose and regulator is listed as a required part of the CSA listed Summit® Built-In gas grill.
The Summit® Built-In Tank Cabinet also meets the require­ments for venting, tank retention and separation of the LP cylinder from a heat source as outlined in the ANSI Standard for Outdoor Cooking Gas Appliances, Z21.58/CSA 1.6 for LP enclosures.
The Summit® Built-In Tank Cabinet has its own installation guide. If you do not use the Summit® Built-In Tank Cabinet, you need to hire a licensed contractor or licensed plumber and they need to follow the requirements described in the ANSI Standard for Outdoor Cooking Gas Appliances, Z21.58/CSA
1.6 for LP enclosures. The requirements described in the Standard for Outdoor Cooking Gas Appliances, Z21.58/CSA 1.6. are as follows; A remote enclosure for an LP gas cylinder shall be ventilated by openings at both the upper and lower levels of the cylinder. This shall be accomplished by one of the following:
a). One side of the remote LP cylinder enclosure shall be
completely open; or
b). If the remote LP cylinder enclosure is designed to have
four sides, a top and a bottom, ventilation is required for the remote LP cylinder enclosure;
1). There should be at least two ventilation openings, (a hole or group of holes, for the purpose of ventila­tion) in the sidewalls of the enclosure. The openings should be located within 5 inches (127mm) of the top of the enclosure. The ventilation openings should be equally sized and spaced at a minimum of 90 degrees, and be unobstructed. The openings shall have a total free open area of not less than 20 square inches. (This relates to1 square inch of ventilation area, per pound of stored fuel capacity).
2). Ventilation openings (a hole or group of holes, for the purpose of ventilation) should be provided at oor level. The ventilation openings should have a total free area of not less than 10 square inches. (This relates to square of ventilation area, per pound of stored fuel capacity). There should be at least two ventilation openings if the ventilation openings at oor level are in the sidewall. The ventilation openings should be within 5 inches (127mm) of the oor. The ventilation openings should be of equal size and be spaced at a minimum of 90 degrees, and should be unobstructed.
3). The minimum size of the ventilation hole (s) should not be less than inch.
4). The ventilation openings in the sidewalls should not allow venting into the empty or “hollow” area of the “island”. If a gas leak should occur or the LP cylinder should vent in the LP cylinder enclosure, the gas should not be allowed to vent or migrate into the empty or “hollow” area of the “island”. Ventilation openings in the sidewalls of the enclosure should only communicate with the outside of the “island” structure, so that the gas can dissipate outside of the “island” structure.
c). If the remote LP cylinder enclosure has four sides, a top
and a bottom, and is intended for installation in a built-in “island” enclosure;
4
1). At least one ventilation opening (a hole or group of holes, for the purpose of ventilation) needs to be on one side of the enclosure that communicates with the outside of the “island” structure. If a gas leak should occur or the LP cylinder should vent in the LP cylinder enclosure, the gas should not be allowed to vent or migrate into the empty or “hollow” area of the “island”. Ventilation openings should only communi­cate with the outside of the “island” structure, so that the gas can dissipate outside of the “island” structure. The ventilation opening should be located within 5 inches (127mm) of the top of the enclosure, and should have a total free area of 20 square inches. (This relates to 1 square inch of ventilation area, per pound of stored fuel).
2). At least one ventilation opening (a hole or group of holes, for the purpose of ventilation) needs to be on one side of the enclosure that communicates with the outside of the “island” structure, at the bottom. If a gas leak should occur or the LP cylinder should vent in the LP cylinder enclosure, the gas should not be allowed to vent or migrate into the empty or “hollow” area of the “island”. Ventilation openings should only communicate with the outside of the “island” structure, so that the gas can dissipate outside of the “island” structure. The ventilation opening should be located within 5 inches (127mm) of the bottom of the enclosure, and should have a total free area of 10 square inches. (This relates to 1/4 square inch of ventilation area, per pound of stored fuel).
3). The minimum size of the ventilation hole (s) should not be less than inch.
d). The remote LP cylinder enclosure should be constructed
with non-combustible materials. The remote LP cylinder enclosure should isolate the LP cylinder from the burner compartment, so that it provides shielding from radiation, be a ame barrier and provide protection from foreign material such as hot drippings.
e). There should be a minimum of 2 inches (50.8mm) be-
tween the ground and the oor of the remote LP cylinder enclosure.
f). The LP cylinder valve should be readily accessible for
hand operation. A door on the remote LP cylinder enclo­sure to gain access to the LP cylinder valve is acceptable, provided it is non- locking and can be opened without the use of tools.
If your, licensed contractor or licensed plumber, builds an LP cylinder enclosure following the guidelines in the ANSI Stan­dard for Outdoor Cooking Gas Appliances, Z21.58 CSA 1.6, you need to order kit number (#21287), which will contain the hose and regulator assembly, mount­ing bracket for the regulator, connection ttings and LP tank bracket for retaining the LP cylinder that must be used with the Summit® Built-In gas grill. The hose and regulator in the kit (#21287) is listed as part of the CSA listed Summit® Built­In gas grill.
DANGER
Use of any other hose and regulator assembly could be dangerous, and may not provide adequate gas supply to the Summit® Built-In gas grill, and could result in a re or an explosion causing serious bodily injury or death and damage to property.
DANGER
Failure to use the the Summit® Built-In Tank Cabinet for a 20 lb cylinder or failure to build a LP cylinder enclo­sure for a 20 lb cylinder following the requirements for ventilation, cylinder retention and separation of the LP cylinder from a heat source, listed in the ANSI Stan­dard for Outdoor Cooking Gas Appliances, ANSI Z21.58 CSA 1.6, could be dangerous, and could result in a re or an explosion causing serious bodily injury or death and damage to property.
If you do not follow the DANGER statements exactly, the Warranty on the Summit® Built-In gas grill will be voided.
5
 
 
 

GAS SUPPLY
Typical tank cabinet or tank enclosure location
CONNECT GAS SUPPLY
A 58" inch corrugated gas line is supplied with the grill. This line needs to pass through the gas inlet opening to the main gas supply.
1) Connect the corregated gas line to the manifold located on the right hand side of grill under the control panel.
Note: Leave an access in the “island” structure for gas supply and regulator service not inside the grill structure. Weber® has a gas line and regulator access door (part # 36311) available from your dealer or call Customer Service at 1-847-446-1071.
The corrugated line passes through the "Island Structure" cavity to the regulator connection inside the Summit® Built-In tank cabinet (#21280) or the hose and regulator connection from kit # 21287. (Shown below)
VENTILATION
WARNING: Air holes must be provided in the structure at the top and bottom to provide ventilation in the event of a gas leak.
Air holes can be located in a low visibility area and should be protected by screening material to prevent rodents and insects from entering the structure. Air holes will also help dry moisture. Summit® Built- In cabinet vents (part # 36312 / #61429) are available from your dealer or call Customer Service at 1-800-466-1071.
Note: These drawings are only a reference.
Cross ventilation must be incorporated in the supporting structure. We recommend a minimum of 100 square inches of venting per side.
Vents should be on two sides of the structure.
The above drawings are for reference only.
Location of the vents should be from the center, outward.
Locate the vents at both the bottom of the structure and at the top of the structure.
The bottom vents should be as close to ground level as possible. Make sure the vent area is not blocked by interior supports of the structure.
We recommend vents with screens.
Access doors to the structure are not considered vents.
Clean the vents periodically.
DANGER: Failure to follow recommended minimum
venting instructions can cause gas to collect in the structure in the event of a gas leak. This may result in a re or an explosion which can cause serious bodily injury or death, and damage to property.
6
Loading...