Watts Tekmar Zone Valve Control 303V Series, Tekmar Zone Valve Control 303V-2, Tekmar Zone Valve Control 303V-1, Tekmar Zone Valve Control 303V-3 Installation Manual

Installation Manual
Call
Valve Open
Zone Valve Control 303V
Three Zones with Priority
Power
Priority
System
Pump
Zone 1
Zone 2 Zone 3
RoomResponse
TM
Zone Valve Control 303V
The Zone Valve Control 303V connects up to three thermostats and operates a circulator and zone valves to provide heating to a zoned hydronic heating system.
Features
• RoomResponseTM signal
• Compatible with all low voltage thermostats
• Unlimited zone expansion
• Zone priority
• Priority override
• Pump exercising
• Post purge
• Away signal shared between tekmar thermostats
• LED for each zone, priority, end switch and RoomResponse
TM
• Four ground screws
• Top, bottom and back conduit knockouts
• Fuses protect transformers and pumps
• Two spare fuses included
• CSA approved
Table of Contents
Important Safety Information ......................................... 2
Installation ...................................................................... 3
Packaging Contents ................................................... 3
Tools Required ........................................................... 3
Materials Required ..................................................... 3
Location ..................................................................... 3
Installing the Enclosure .............................................. 3
Application 303V-1 ..................................................... 4
Application 303V-2 ..................................................... 5
Application 303V-3 ..................................................... 6
User Interface ................................................................. 7
Indicator LED ............................................................. 7
Sequence of Operation .................................................. 7
Technical Data .............................................................. 11
Limited Warranty and Product Return Procedure ........ 12
Important Safety Information
It is your responsibility to ensure that this control is safely installed according to all applicable codes and standards. tekmar is not responsible for damages resulting from improper installation and/or maintenance.
This is a safety-alert symbol. The safety alert symbol is shown alone or used with a signal word (DANGER, WARNING, or CAUTION), a pictorial and/or a safety message to identify hazards. When you see this symbol alone or with a signal word on your equipment or in this manual, be alert to the potential for death or serious personal injury.
This pictorial alerts you to electricity, electrocution, and shock hazards.
This symbol identifies hazards which, if not avoided, could result in death or serious injury.
This symbol identifies hazards which, if not avoided, could result in minor or moderate injury.
This symbol identifies practices, actions, or failure to act which could result in property damage or damage to the equipment.
Read manual and all product labels BEFORE using the equipment. Do not use unless you know the safe and proper operation of this equipment. Keep this manual available for easy access by all users. Replacement manuals are available at tekmarControls.com
• It is the installer’s responsibility to ensure that this control is safely installed according to all applicable codes and standards.
• Improper installation and operation of this control could result in damage to the equipment and possibly even personal injury or death.
• This control is not intended for use as a primary limit control. Other controls that are intended and certified as safety limits must be placed into the control circuit.
The control includes fuses and transformer that are serviceable. Do not attempt to service any other parts on the control. Attempting to service the control voids the warranty.
• Strip all wiring to a length of 3/8 in. or 10 mm for all terminals.
• A circuit breaker or power disconnect that provides power to the control should be located nearby and clearly labeled.
• Refer to the current and voltage ratings at the back of this manual before connecting devices to this control.
2 of 12
Radio Frequency Interference
The installer must ensure that this control and its wiring are isolated and/or shielded from strong sources of electromagnetic noise. Conversely, this Class B digital apparatus complies with Part 15 of the FCC Rules and meets all requirements of the Canadian Interference­Causing Equipment Regulations. However, if this control does cause harmful interference to radio or television reception, which is determined by turning the control
Installation
Packaging Contents
• 1 Zone Valve Control 303V
• 2 Spare fuses (located in cover)
Tools Required
• tekmar or jeweler screwdriver
• Phillips head screwdriver
Materials Required
• 18 AWG LVT solid wire (low-voltage connections)
• 14 AWG solid wire (line-voltage connections)
off and on, the user is encouraged to try to correct the interference by re-orientating or relocating the receiving antenna, relocating the receiver with respect to this control, and/or connecting the control to a different circuit from that to which the receiver is connected.
Cet appareil numérique de la classe B respecte toutes les exigences du Règlement sur le matériel brouilleur du Canada.
• Installation Manual 303V_D
• Needle-nose pliers
• Wire stripper
• Four 1/8” - 1” wood screws
Location
• Keep the control dry. Avoid potential leakage onto the control.
• Maintain relative humidity less than 90% in a non-condensing environment.
• Avoid exposure to extreme temperatures beyond 32-122°F (0-50°C).
• Install away from equipment, appliances, or other sources of electrical interference.
• Install to allow easy access for wiring, viewing, and adjusting the display screen.
• Install approximately 5 feet (1.5 m) off the finished floor.
• Locate the control near pumps and/or zones valves if possible.
• Provide a solid backing which the enclosure can be mounted to. Example: plywood or wall studs.
• Use the conduit knockouts provided on the upper, lower, and back of the enclosure for wiring.
Installing the Enclosure
To prevent the risk of personal injury and/or death, make sure power is not applied to the control until it is fully installed and ready for final testing. All work must be done with power to the circuit being worked on turned off.
Please be aware local codes may require this control to be installed or connected by an electrician.
3 of 12
N
Application 303V-1
Away
C R Rh W
Away
C R Rh W R W
MOD
XX
tN4
T1 T2 T3 T4 T5 T6
A
DHW CRW
BOILER T-STAT 1T-STAT 2T-STAT 3
-
+
tN4
A
CRW
tN4
A
CRW
T-STAT 4
tN4
A
CRW
T-STAT 5
tN4
A
CRW
T-STAT 6 EXPANSION
tN4
A
CRW
tN4
A
BCDE
FUSE 2 FUSE 1
END
SWITCH
MOTOR
POWER
PRIORITYSYS PUMP
ROOM
RESPONSE
ZONE 1
70 80
9060
50 100
MOD MAX %
END
SWITCH
MOTOR
ZONE 2
END
SWITCH
MOTOR
ZONE 3
END
SWITCH
MOTOR
ZONE 4
END
SWITCH
MOTOR
ZONE 5
END
SWITCH
MOTOR
ZONE 6
MASTER MEMBER
OFF OFF OFF
T-STAT 1 PRIORITY : ON
EXERCISING : ON POST PURGE : ON
MOD BOILER : 0-10V
SYSTEM PUMP DURING PRIORITY: ON
SYSTEM PUMP WITH MEMBER CALL: ON
ZONE VALVE END SWITCHES: ON
RESERVED
120 VAC POWER PUMP PUMP 1
SYSTEM PRIORITY
LNLNLN
OFF OFF OFF
4-20 mA
The Zone Valve Control 303V operates three heating zones. When the thermostat calls for heat, the zone valve opens, the system pump is turned on and the boiler is fired.
Mechanical
Legend
B1 = Boiler PS = System Pump T1 = WiFi Thermostat 561, 562 or 563 T2 = Thermostat 518 or 519 T3 = Generic Digital Power-Stealing Thermostat V1 to V3 = 2-Wire Zone Valves
303V
Electrical
B1
Included 510 Ω resistor must be installed when using power stealing thermostats (e.g. Thermostat T3)
B1
L N
PS
T1
PS
T2 T3
V1 V2 V3
4 of 12
V1 V2 V3
DIP Switches
Master T-stat 1 Priority Off Exercising On Post Purge On Mod Boiler - not applicable System Pump During Priority On System Pump With Member Calls Off Zone Valve End Switches Off
Application 303V-2
Away C R Rh W R W
MOD
XX
tN4
T1 T2 T3 T4 T5 T6
A
DHW CRW
BOILER T-STAT 1T-STAT 2T-STAT 3
-
+
tN4
A
CRW
tN4
A
CRW
T-STAT 4
tN4
A
CRW
T-STAT 5
tN4
A
CRW
T-STAT 6 EXPANSION
tN4
A
CRW
tN4
A
BCDE
FUSE 2 FUSE 1
END
SWITCH
MOTOR
POWER
PRIORITYSYS PUMP
ROOM
RESPONSE
ZONE 1
70 80
9060
50 100
MOD MAX %
END
SWITCH
MOTOR
ZONE 2
END
SWITCH
MOTOR
ZONE 3
END
SWITCH
MOTOR
ZONE 4
END
SWITCH
MOTOR
ZONE 5
END
SWITCH
MOTOR
ZONE 6
MASTER MEMBER
OFF OFF OFF
T-STAT 1 PRIORITY : ON
EXERCISING : ON POST PURGE : ON
MOD BOILER : 0-10V
SYSTEM PUMP DURING PRIORITY: ON
SYSTEM PUMP WITH MEMBER CALL: ON
ZONE VALVE END SWITCHES: ON
RESERVED
120 VAC POWER PUMP PUMP 1
SYSTEM PRIORITY
LNLNLN
OFF OFF OFF
4-20 mA
+T-T
DHW
-
The Zone Valve Control 303V operates a two heating zones and a domestic hot water tank. When a thermostat calls for heat, the zone valve opens and the system pump and the boiler turn on once the zone valve end switch closes. The domestic hot water tank is heated using a pump. When priority is selected, the heating zones are shut off while the hot water tank is heated.
Mechanical
Legend
A1 = DHW Tank Aquastat B1 = Modulating Condensing Boiler BP = Boiler Pump PS = System Pump P1 = Zone 1 DHW Tank Pump T1 = WiFi Thermostat 561, 562or 563 T2 = Generic Bi-Metallic Strip
Thermostat V1 = 2-Wire Zone Valve V2 = 4-Wire Zone Valve
Electrical
B1
BP
A1
303V
Power
LN
LN
A1
P1 V1 V2
PS
T1
T2
DIP Switches
Master T-stat 1 Priority On Exercising On Post Purge On Mod Boiler - depends on boiler System Pump During Priority Off System Pump With Member Calls Off Zone Valve End Switches On
Included 510 Ω resistor must be installed when using power stealing thermostats (e.g. Thermostat T2)
B1
P1L N PS
5 of 12
V1
V2
End switch jumper required for Zone 1 when using a pump and Zone Valve End Switch DIP = On
Application 303V-3
Away
C R Rh W
+TT
-
Away
C R Rh W
MOD
XX
tN4
T1 T2 T3 T4 T5 T6
A
DHW CRW
BOILER T-STAT 1T-STAT 2T-STAT 3
-
+
tN4
A
CRW
tN4
A
CRW
T-STAT 4
tN4
A
CRW
T-STAT 5
tN4
A
CRW
T-STAT 6 EXPANSION
tN4
A
CRW
tN4
A
BCDE
FUSE 2 FUSE 1
END
SWITCH
MOTOR
POWER
PRIORITYSYS PUMP
ROOM
RESPONSE
ZONE 1
70 80
9060
50 100
MOD MAX %
END
SWITCH
MOTOR
ZONE 2
END
SWITCH
MOTOR
ZONE 3
END
SWITCH
MOTOR
ZONE 4
END
SWITCH
MOTOR
ZONE 5
END
SWITCH
MOTOR
ZONE 6
MASTER MEMBER
OFF OFF OFF
T-STAT 1 PRIORITY : ON
EXERCISING : ON POST PURGE : ON
MOD BOILER : 0-10V
SYSTEM PUMP DURING PRIORITY: ON
SYSTEM PUMP WITH MEMBER CALL: ON
ZONE VALVE END SWITCHES: ON
RESERVED
120 VAC POWER PUMP PUMP 1
SYSTEM PRIORITY
LNLNLN
OFF OFF OFF
4-20 mA
Away
C R Rh W
Away
C R Rh W R W R W
MOD
XX
tN4
T1 T2 T3 T4 T5 T6
A
DHW CRW
BOILER T-STAT 1T-STAT 2T-STAT 3
-
+
tN4
A
CRW
tN4
A
CRW
T-STAT 4
tN4
A
CRW
T-STAT 5
tN4
A
CRW
T-STAT 6 EXPANSION
tN4
A
CRW
tN4
A
BCDE
FUSE 2 FUSE 1
END
SWITCH
MOTOR
POWER
PRIORITYSYS PUMP
ROOM
RESPONSE
ZONE 1
70 80
9060
50 100
MOD MAX %
END
SWITCH
MOTOR
ZONE 2
END
SWITCH
MOTOR
ZONE 3
END
SWITCH
MOTOR
ZONE 4
END
SWITCH
MOTOR
ZONE 5
END
SWITCH
MOTOR
ZONE 6
MASTER MEMBER
OFF OFF OFF
T-STAT 1 PRIORITY : ON
EXERCISING : ON POST PURGE : ON
MOD BOILER : 0-10V
SYSTEM PUMP DURING PRIORITY: ON
SYSTEM PUMP WITH MEMBER CALL: ON
ZONE VALVE END SWITCHES: ON
RESERVED
120 VAC POWER PUMP PUMP 1
SYSTEM PRIORITY
LNLNLN
OFF OFF OFF
4-20 mA
Two Zone Valve Controls operate six heating zones and a domestic hot water tank. When a thermostat calls for heat, the zone valve opens. The hot water tank is heated using a pump when the tank aquastat calls for heat. The master control operates the system pump and the boiler when there is a call for heat on either the master or member control.
Mechanical
Legend
A1 = DHW Tank Aquastat B1 = Modulating Condensing Boiler BP = Boiler Pump PS = System Pump
P1 = Zone 1 DHW Tank Pump T1, T2 = WiFi Thermostat 561, 562 or 563 T3, T4 = Thermostat 518 or 519
T5 = Generic Power-Stealing Thermostat T6 = Generic Bi-Metallic Strip Thermostat V1 to V6 = 4-Wire Zone Valves
303V 304V
N LN
Expansion
Power
A1
LN
B1
P1
BP
Electrical
End switch jumper required for Zone 1 when using a pump and Zone Valve End Switch DIP = On
T1
T2
B1
A1
PS
V1 V2 V3 V4 V5 V6
T3 T4 T5 T6
DIP Switches
Master T-stat 1 Priority On Exercising On Post Purge On
PSLLN
P1
Mod Boiler - depends on boiler System Pump During Priority Off System Pump With Member Calls On Zone Valve End Switches On
V1 V2 V3 V4 V5 V6
DIP Switches
N
Member T-stat 1 Priority Off Exercising On Post Purge On
Mod Boiler - not applicable System Pump During Priority Off System Pump With Member Calls Off Zone Valve End Switches On
6 of 12
User Interface - Indicator LED
Power
• On when 115 V (ac) is applied.
• Off when power disconnected or transformer fuse is blown.
Priority
• On when zone 1 has priority over zones 2 and 3.
• Flashing while in priority override.
RoomResponse
• On when modulating condensing boiler is operating below maximum setting.
System Pump
• On when zone valve end switches are closed (valve open).
• Off when zone valve end switches are open circuit (valve closed).
TM
Sequence of Operation
Zone 1 Call
• On when thermostat 1 calls for heat.
• Off when thermostat 1 stops calling for heat.
Zones 2 and 3 Call
• On when the corresponding thermostat calls for heat.
• Off during priority operation.
• Off when corresponding thermostat stops calling for heat.
Zones 1 to 3 Valve Open
• On when corresponding thermostat calls for heat and the zone valve is open (end switch closed).
• Off when zone valve closed (end switch open circuit).
• Off when corresponding thermostat stops calling for heat.
Zone Operation
When a thermostat calls for heat by closing the R and W terminals:
• 24 V (ac) is applied to the corresponding zone valve.
• The corresponding zone indicator LED is turned on.
Boiler Operation
When a thermostat calls for heat by closing the R and W terminals:
• The boiler end switch XX is closed to fire the boiler. This requires the control DIP switch to be set to Maste r.
• The RoomResponseTM 0-10 V (dc) or 4-20 mA signal is sent to a modulating-condensing boiler.
DHW Operation
Many modulating-condensing boilers have multiple temperature call inputs. Wire the DHW end switch to input recommended in the boiler’s manual.
When a zone 1 calls for heat by closing the R and W terminals:
• The DHW end switch is closed to fire the boiler at the DHW temperature.
• The Mod Boiler output is changed to 10 V (dc) or 20 mA.
Priority Override
• The Priority LED light flashes when priority override is in effect.
• Priority for zone 1 is in effect for 60 minutes after which priority override starts by shutting off zone 1 and resumes heating on zones 2 and 3 and expansion zones.
• During priority override, the mod max dial setting limits the RoomResponseTM signal to the boiler.
Master / Member DIP Switch
• Allows for unlimited expansion using additional Switching Relays and/or Zone Valve Controls.
• The Master Switching Relay is wired and operates the boiler.
• If using a single Switching Relay set to Master.
• When using multiple Switching Relays and/or Zone Valve Controls, set one control to Master and set all other controls to Member.
• The boiler end switch XX only closes when the DIP switch is set to Master and does not close when set to Member.
T-Stat 1 Priority DIP Switch
When T-Stat 1 is calling for heat by closing the R and W terminals:
• 115 V (ac) is applied to the Priority Pump 1.
• Zone 1 indicator LED is turned on.
• Priority indicator LED is turned on.
• Zones 2 and 3 zone valves and LEDs are turned off.
• Expansion Member controls shut off their zones.
• After 60 minutes of continuous zone 1 call for DHW heating the control goes into priority override. This prevents building freeze up if the DHW tank aquastat fails in the closed position.
• A jumper wire must be installed on the zone 1 end switch if a pump is installed and the Zone Valve End Switches DIP switch is set on.
Exercising DIP Switch
• ON: Each circulator pump is energized for 30 seconds every 72 hours.
• OFF: Circulator pump exercising disabled.
Post Purge DIP Switch
• ON: After thermostat 1 stops calling for heat, the zone 1 priority pump and zone valve remain on for 2 minutes to purge heat from the boiler to the zone.
• OFF: Post purge disabled.
Mod Boiler DIP Switch
Select either 0-10 V (dc) or 4-20 mA signal to the modulating condensing boiler. Consult the boiler manual to determine the signal type. The DIP switch position does not matter if the modulating boiler output is not used.
System Pump During Priority DIP Switch
• On: System pump operates when zone 1 calls for heat.
• Off: System pump shuts off when zone 1 calls for heat. Typically set off when using a pump for heating a domestic hot water tank.
System Pump With Member Call DIP Switch
• On: System pump on the master control runs when a zone on a member control calls for heat.
• Off: System pump on the master control does not turn on when a zone on a member control calls for heat.
Zone Valve End Switches DIP Switch
• On: System pump and boiler will not turn on until the zone valve end switch is closed. Select this option when using 3 or 4-wire zone valves.
• Off: System pump and boiler turn on immediately when a thermostat calls for heat. Select this option when using 2-wire zone valves.
Fuses
• All fuses are T5A 250V slow blow, glass 5 x 20 mm.
• Fuses 1 and 2 correspond to the 24 V (ac) transformer power supply. If a fuse is blown, first check that the thermostat wiring is not shorted. Then replace the fuse.
7 of 12
70 80
9060
50 100
MOD MAX %
Expansion Terminals
• Connect the five wires of the expansion bus from the master to the member controls.
Termi n al
A/tN4 Away signal connecting tekmar thermostats B C Power common D Demand signal. 0 Vdc = demand. 2 Vdc = no
E
RoomResponseTM Signal
The RoomResponseTM signal adjusts the temperature of a modulating condensing boiler that accepts a 0-10 V(dc) or 4-20 mA input. It works by continually adjusting boiler water temperatures to the lowest possible value to meet comfort without wasting energy. This is done by monitoring each thermostat's on and off time pattern and determines the ideal water temperature for each zone. The control then chooses the highest water temperature requirement of all the thermostats and provides a 0-10 V (dc) or 4-20 mA signal proportional to the boiler operating temperature. The RoomResponseTM signal is a DOE compliant method of controlling boiler temperature to building load. The RoomResponseTM signal is not available to on/off boilers. Benefits of the RoomResponseTM signal include:
• Increase in boiler efficiency
• Reduction in room temperature swing
• Reduction in expansion noises from heating pipes
Description
RoomResponse
demand Priority signal. 0 Vdc = priority. 2 Vdc = no priority
TM
signal from member controls
Mod Max % dial set to 100% in the illustration.
Mod Max % Dial
The upper limit of the 0-10 V (dc) or 4 -20 mA signal to the modulating condensing boiler can be set using the Mod Max % Dial.
This sets the upper temperature limit for the boiler.
The dial is only applicable to controls set as the Master.
Mod Max % Max Voltage Max mA
50 5 12 60 6 13.6 70 7 15.2 80 8 16.8 90 9 18.4
100 10 20
Setting the Max Mod % Dial
Required Adapter
Boiler Make/Model
Aerco AM series Not required 0-10 V 50% 65% 80% 100%
Bosch Greenstar ICM Module 0-10 V 55% 70% 80% 100% Buderus GB142, GB162 EM10 Module 0 -10 V 50% 60% 75% 90%
Burnham® Alpine Camus® Modulating Micoflame HTP Elite Not required 0-10 V 50% 65% 80% 90%
*
®
(Supplied by boiler
manufacturer)
Not required 4-20 mA 50% 70% 85% 100%
Not required 0-10 V 50% 60% 70% 85%
0-10 V (dc) /
4-20 mA
DIP Switch
Mod Max % Dial for Boiler Design Temperature
120 ° F 140°F 16 0°F 180°F
IBC VFC and SL series* Laars® Mascot LX Not required 0-10 V 55% 70% 85% 100% Laars® Mascot FT Not required 0-10 V 50% 65% 80% 10 0% Lochinvar® Knight
Lochinvar
NTI Trinity Fire Tube and LX Not required 4-20 mA 55% 65% 75% 90% Peerless PureFire PFA-1 Adapter 0-10 V 55% 65% 75% 90% Raypak Xfyre, Xtherm, MVB, XPakFT Not required 0-10 V 55% 65% 80% 90%
Riverside HeatStation*
Viessmann 100-W, WB1B
®
FTXL*
Not required 0-10 V 65% 75% 85% 100%
Not required 0-10 V 55% 70% 85% 100%
Not required 0-10 V 55% 70% 85% 100%
Not required 0-10 V 50% 65% 85% 100%
OpenTherm Module
0-10 V 55% 70% 85% 100%
Viessmann 200-W, B2HB and 300 CU3A
Weil-McLain
* Requires changes to boiler's settings
®
Evergreen*
Not required 0-10 V 50% 60% 70% 80%
Not required 0-10 V 50% 70% 85% 100%
8 of 12
91
91
Aerco AM Series Camus Modulating MicoFlame
303V
+
22+23
Aerco AM
• No changes to the boiler are required.
Bosch Greenstar
+
303V
• Install the Bosch ICM as per the directions.
• Set ICM jumper to the left position to enable system supply water temperature (VT) mode.
9+10
Bosch ICM
Buderus GB142 and GB162
303V
+
5+6
Camus Micoflame
• Change control to mode 6 in the control parameters.
Heat Transfer Products Elite
+
303V
• Move jumper on connection board from A to B.
• Set function 17 to temperature.
16–17
+
HTP Elite
IBC VFC and SL Series
2
+
303V
Buderus EM10 Module
• Install the Buderus EM10 module as per the directions.
• Do NOT install the jumper between U terminals 1 and 3 on the EM10 module.
1
X
+
On the V10 controller:
• Set Load 1 to External Control
• Change "Max Control @ 9.5 Vdc" to 190°F (88°C)
• Change "Min Control @ 2.1 Vdc" to 32°F (0°C)
Burnham Alpine Laars Mascot LX
X
+
X
303V
• Change Parameter 9 Remote 4-20 mA to Setpoint Source.
• Change "Energy Management" setting "Central Heat Modulation Source" to 4-20 mA.
• Change "Energy Management" setting "Central Heat 4-20 mA Setup, 4 mA Water Temperature" to 80°F (26.5°C).
TT +
12
0
Burnham Alpine
X
+
• Change Installer Parameter 25 "0-10V to Power" to Disabled.
• Change Installer Parameter 26 "0-10V to outlet setpoint" to Disabled.
X
TT +
12
0
IBC V10 Control303V
X
TT +
5611 12
Laars Mascot LX303V
9 of 12
45
12
Laars Mascot FT
Peerless Pinnacle PF-200, 210, 300, 399
303V
+
16–17
+
Laars Mascot FT
• No changes to the boiler are required.
Lochinvar Knight
X
+
X
303V
• Set BMS Type to Setpoint. This is the factory default setting.
WR +
1237 38
Lochinvar Knight
Lochinvar FTXL
X
+
X
303V
• Set BMS parameter to ACTIVE.
• Set BMS Type to SETPOINT.
WR +
21 22 35 36
Lochinvar FTXL
+
303V J5 J8 J18
15+16
Peerless Pinnacle Terminal
Strip
2–8+12
Peerless PFA-1
Interface Adapter
Peerless Pinnacle
Control
Board
• Install the Peerless PFA-1 Interface Adapter
• On the boiler display, change Central Heating Mode to 4 for 0-10 VDC Input to Modulate Setpoint
Riverside HeatStation
+
303V
Riverside HeatStation
• Set boiler PIM DIP switch 2 to Off.
• Set boiler PIM DIP switch 5 to On.
• Set boiler PIM DIP switch 6 to Off.
• Set APP parameter to EMS.
• Set SIGNAL parameter to 0-10Vdc.
• Set SETP LO to 70°F.
• Set SETP HI to 180°F.
EMS 8
+
9
NTI Trinity LX
X
+
X
303V
• Enter boiler password.
• Set Parameter "Setpoint source" to 4-20mA
CH1R +
3511 12
NTI Trinity LX
NTI Trinity FireTube
X
+
X
303V
• Enter boiler password.
• Set Parameter "Setpoint source" to 4-20mA
CH1R +
35
Sensor I/O24Vac I/O
NTI Trinity Fire Tube
Raypak MVB and XTherm
X
+
X
303V
• Set boiler PIM DIP switch 2 to Down.
• Set boiler PIM DIP switch 5 to Up.
10 of 12
Raypak MVB or XTherm
+
13 14 17 18
Raypak XFyre and XPakFT
91
Viessmann Vitodens 200-W, B2HP and Vitocrossal 300 CU3A
+ XX
+ TT
89
0
J2 J1
303V
Raypak XFyre or XPakFT
• Set boiler PIM DIP switch 2 to Down.
• Set boiler PIM DIP switch 5 to Up.
Viessmann Vitodens 100-W, WB1B
+
303V
• Install the OpenTherm Module as per the boiler manufacturer's instructions.
1–4
+
Viessmann
OpenTherm Module
Technical Data
+
1–2
+
Viessmann
303V
Extension Module EA1
Plug 0-10V
• Connect to the Viessmann Extension Module EA1 Pl ug 0 -10V.
Weil-McLain Evergreen
+
303V
• Use Local Priority 1 for DHW tank heating.
• Use Local Priority 2 for the RoomResponseTM signal.
• Set Local Priority 2 Supply Min to 60°F.
• Set Local Priority 2 Supply Max to 180°F.
• Set Local Priority 2 Volts For Min to 2 V.
• Set Local Priority 2 Volts For Max to 10 V.
5+6
Weil-McLain
Evergreen P15
Zone Valve Control 303V Three Zones with Priority
Literature Submittal 303V_C, Installation Manual 303V_D, Job Record 303V_J
Packaged weight 5.0 lb. (2250 g)
Dimensions 8-3/16” H x 10-11/16” W x 2-3/8” D (208 x 271 x 60 mm)
Enclosure Cover: ABS plastic, Base: galvanized steel, NEMA type 1
Approvals CSA C US, RoHS
Ambient conditions Indoor use only, 32 to 122°F (0 to 50°C), RH ≤90% non-condensing
Power supply 115 V (ac) ±10%, 60 Hz, 11 A
Transformer
Control load 7 VA at 24 V (ac)
Fuses T5A 250 V slow blow 5 x 20 mm glass fuse, two spare fuses included
Zone valve outputs 24 V (ac), 2 A max each, one transformer 33 VA, two transformer 73 VA
Zone valve end switch 24 V (ac)
Pump relays 230 V (ac), 5 A, 1/3 hp
Boiler XX end switch 24 V (ac), 5 A
DHW end switch 24 V (ac), 5 A
Mod boiler output 0-10 V (dc) 500 Ω min load impedance / 4-20 mA 1 kΩ max load impedance
40 VA at 24 V (ac), expandable to 80 VA with additional transformer M3069 (sold separately)
11 of 12
Warranty
Limited Warranty The liability of tekmar under this warranty is limited. The Purchaser, by taking receipt of any tekmar product (“Product”), acknowledges the terms of the Limited Warranty in effect at the time of such Product sale and acknowledges that it has read and understands same.
The tekmar Limited Warranty to the Purchaser on the Products sold hereunder is a manufacturer’s pass-through warranty which the Purchaser is authorized to pass through to its customers. Under the Limited Warranty, each tekmar Product is warranted against defects in workmanship and materials if the Product is installed and used in compliance with tekmar’s instructions, ordinary wear and tear excepted. The pass-through warranty period is for a period of twenty-four (24) months from the production date if the Product is not installed during that period, or twelve (12) months from the documented date of installation if installed within twenty-four (24) months from the production date.
The liability of tekmar under the Limited Warranty shall be limited to, at tekmar’s sole discretion: the cost of parts and labor provided by tekmar to repair defects in materials and / or workmanship of the defective product; or to the exchange of the defective product for a warranty replacement product; or to the granting of credit limited to the original cost of the defective product, and such repair, exchange or credit shall be the sole remedy available from tekmar, and, without limiting the foregoing in any way, tekmar is not responsible, in contract, tort or strict product liability, for any other losses, costs, expenses, inconve­nienc es, or damages , whe the r dire ct, indirect, speci al, secon dary, inci­dental or consequential, arising from ownership or use of the product, or from defects in workmanship or materials, including any liability for fundamental breach of contract.
The pass-through Limited Warranty applies only to those defective Products returned to tekmar during the warranty period. This Limited Warranty does not cover the cost of the parts or labor to remove or transport the defective Product, or to reinstall the repaired or replace­ment Product, all such costs and expenses being subject to Purchas­er’s agreement and warranty with its customers.
Any representations or warranties about the Products made by Pur­chaser to its customers which are different from or in excess of the
tekmar Limited Warranty are the Purchaser’s sole responsibility and obligation. Purchaser shall indemnify and hold tekmar harmless from and against any and all claims, liabilities and damages of any kind or nature which arise out of or are related to any such representations or warranties by Purchaser to its customers.
The pass-through Limited Warranty does not apply if the returned Prod­uct has been damaged by negligence by persons other than tekmar, accident, fire, Act of God, abuse or misuse; or has been damaged by modifications, alterations or attachments made subsequent to purchase which have not been authorized by tekmar; or if the Product was not installed in compliance with tekmar’s instructions and / or the local codes and ordinances; or if due to defective installation of the Product; or if the Product was not used in compliance with tekmar’s instructions.
THIS WARRANTY IS IN LIEU OF ALL OTHER WARRANTIES, EXPRESS OR IMPLIED, WHICH THE GOVERNING LAW ALLOWS PARTIES TO CONTRACTUALLY EXCLUDE, INCLUDING, WITHOUT LIMITATION, IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE, DURABILITY OR DESCRIPTION OF THE PRODUCT, ITS NON-INFRINGEMENT OF ANY RELEVANT PATENTS OR TRADEMARKS, AND ITS COMPLIANCE WITH OR NON-VIOLA­TION OF ANY APPLICABLE ENVIRONMENTAL, HEALTH OR SAFETY LEGISLATION; THE TERM OF ANY OTHER WARRANTY NOT HEREBY CONTRACTUALLY EXCLUDED IS LIMITED SUCH THAT IT SHALL NOT EXTEND BEYOND TWENTY-FOUR (24) MONTHS FROM THE PRODUCTION DATE, TO THE EXTENT THAT SUCH LIMITATION IS ALLOWED BY THE GOVERNING LAW.
Product Warranty Return Procedure All Products that are believed to have defects in workmanship or materials must be returned, together with a written description of the defect, to the tekmar Representative assigned to the territory in which such Product is located. If tekmar receives an inquiry from someone other than a tekmar Representative, including an inquiry from Purchaser (if not a tekmar Representative) or Purchaser’s customers, regarding a potential warranty claim, tekmar’s sole obligation shall be to provide the address and other contact infor­mation regarding the appropriate Representative.
Need help? Go to our website or contact us.
tekmarControls.com | tekmar.customerservice@wattswater.com | 1-800-438-3903
All specications are subject to change without notice
Tel: 1-800-438-3903 • Fax: (250) 984-0815
tekmarControls.com
303V_D - 10/19 © 2019 tekmar
Loading...