Watlow 142 User Manual

Using This Retrofit Guide
This document is best viewed with Adobe Reader 6.0. To obtain the latest version of Adobe Reader, visit
http://www.adobe.com
Specification sheets on Watlow product may be obtained at http://www.watlow.com/literature/specsheets/ User Manuals on Watlow product may be obtained at http://www.watlow.com/literature/prodtechinfo/ Additional information on other Watlow products may be obtained by visiting http://www.watlow.com/
To locate a controller, search on the part number such as 965A-1CD0-00RG. Use the Help feature in Adobe Reader on how to search documents.
Before selecting a replacement controller:
1. Know the application.
Temperature range
Sensor type
Is the sensor upgradable if required?
Additional input requirements – remote set points, secondary sensor or events
Output required – control, alarm, event
Is the power-switching device upgradable?
Operating voltage of controller
Mounting requirements – panel space
Is a safety limit device required?
2. Know the product.
Inputs – type and number of
Control function – direct (cool) or reverse (heat )
Outputs – switched DC, SSR, or mechanical relay
Communication requirements
Which control features are required? (cascade, slidewire, differential, remote control, other)
3. Use your best judgment for selecting a replacement controller. All applications require close examination of input,
output and the control mode needs to have the controller function properly.
4. Safety: Remember to make sure all redundant safety equipment is in place and working when retrofitting equipment.
If a system has been retrofitted without the proper safety equipment, you could be liable if an accident occurs.
This is only a guide to replacement controllers. If you have doubts, please call (507) 454-5300 and ask for technical support or email wintechsupport@watlow.com. We’re here to help. The suggested replacement will differ in fit and form. Please review the replacement controller specifications for suitability. Carefully check the notes for additional information that may apply.
Your comments or suggestions on the Retrofit Guide are welcome. Please send comments or corrections to: Technical Writer, Watlow Controls, 1241 Bundy Boulevard, P.O. Box 5580, Winona, MN 55987-5580; phone (507) 454-5300; fax (507) 452-4507.
This Retrofit Guide is copyrighted by Watlow Winona, Inc., © February 2004 with all rights reserved. (1455)
Abbreviation & Terminology
(as used in this document)
0.5 – 0.5 amperes of current switching capability
2A – 2 amperes of current switching capability
5A - 5 amperes of current switching capability
10A – 10 amperes of current switching capability
15A – 15 amperes of current switching capability
12-24 – Supply voltage can be between 12 to 24 Volts
100-240 – Supply voltage can be between 100 to 240 Volts
100 ohm DIN – refers to 100-ohm platinum RTD that has a DIN curve.
100 ohm JIS – refers to 100-ohm platinum RTD that has a JIS curve.
1/32 DIN – Deutsche Industrial Norm standard for panel mounted controller, hole size is cut to 1.78”w x 0.88”h.
1/16 DIN – Deutsche Industrial Norm standard for panel mounted controller, hole size is cut to 1.78”w x 1.77”h.
1/8V DIN – Deutsche Industrial Norm standard for panel mounted controller, hole size is cut to 1.78”w x 3.63”h.
1/8H DIN – Deutsche Industrial Norm standard for panel mounted controller, hole size is cut to 3.63”w x 1.77”h”
1/8S DIN – Deutsche Industrial Norm standard for panel mounted controller, hole size is cut to 2.68”w x 2.68”h.
¼ DIN – Deutsche Industrial Norm standard for panel mounted controller, hole size is cut to 3.63”w x 3.63”h.
Action – determines the direction of control. Heat (reverse acting) or Cool (direct acting).
Auto Reset – the limit will automatically reset on a power cycle but requires manual reset on limit trip.
Cascade – a control algorithm in which the output of one control loop provides a set point for another loop. The second
loop, in turn, determines the control action.
Ch – Channel refers to an analog input. There are single and dual channel controllers.
Control Mode – the method that a controller uses to switch the outputs such as PID, ON/OFF, and Manual.
Differential - control algorithm in which the output is based on the difference of the inputs plus set point.
DIN – Deutsche Industrial Norm, a set of technical, scientific and dimensional standards developed in Germany. RTD
sensors with the DIN curve change resistance at a rate of 0.00385 ohms/ohms/C.
DIN Rail – standard DIN EN50022 mounting method for attaching devices onto a metal rail.
Fixed – refers to a set point that is fixed at one value.
High Limit - device will deactivate output on a temperature rise above set point.
Inductive Load – any device that has a wire winding such as solenoids, electromechanical relays or transformers.
Input – refers to the sensor types that may be connected.
Integral – the set point in integral (on board) to the controller.
JIS – Joint Industrial Standards, a set of technical, scientific and dimensional standards developed in Japan. RTD sensors
with the JIS curve change resistance at a rate of 0.00396 ohms/ohms/C.
Line Voltage – the voltage required powering the electronics of the controller.
Low Limit - device will deactivate output on a temperature drop below set point.
On/Off – a method of control that turns the output full on until set point is reached and then off until the process error
exceeds the hysteresis.
Open Brd – the form factor of this controller is an open circuit board mounted on four standoffs.
Manual Reset – the limit must be reset on a power cycle and requires manual reset on limit trip.
Multi RSP – multiple remote set potentiometers were supported. Each allowed the set point to be selected and adjusted.
Relay – refers to an electromechanical relay.
Remote – set point is adjusted using a remote potentiometer.
Panel – the form factor of this controller is mounted through a hole cut in the panel.
PI – Proportional and Integral, a control mode with two functions: proportional action dampens the systems response,
and integral corrects for droop.
PID – Proportional, Integral, and Derivative, a control mode with three functions: proportional action dampens the
systems response, integral corrects for droop, and derivative prevents overshoot and undershoot.
Potted – the circuit board and electronics are encased in epoxy.
Proc – Process input may accept 0-5, 1-5, 0-10 volts or 0-20 and 4-20 mA.
Profiling – Controller will perform a sequence of programmed steps.
Programmable – The feature is changeable in the field through jumpers and/or parameter selection.
RTD – Resistance Temperature Detector, a sensor that is 100 ohms at 0 degrees C and made of platinum material.
SSR – Solid State Relay, these devices will switch AC voltage only and require a load to latch on.
Sw DC – Switched DC, a time proportioning DC output used to drive DC input solid state relays.
t/c – Thermocouple sensor device made by joining two dissimilar metals whose standards is identified by a letter.
Temp Range – the range over which the controller could have the set point adjustment.
Thermistor – a sensor that changes resistance as the temperature changes. Similar but not the same as an RTD.
Universal – Input can be a thermocouple, 100 ohm DIN RTD or process (volts or milliamperes)
VAC – Volts Alternating Current
VAC/DC- Volts Alternating Current or Direct Current
VDC – Volts Direct Current
VTB Sw DC – Variable Time Base Switched Direct Current, a time proportioning DC output where the cycle time is
variable.
These notes are used to signify areas of concern in changing to a retrofit choice. These notes are also printed at the end of the retrofit listing.
Note 1: Retrofit controller requires a substitution of a 100 Ohm RTD sensor for the thermistor. Note 2: Mounting and dimensions of retrofit controller are different. Verify that sufficient panel space and depth is
available. Note 3: Retrofit controller outputs are different. Add external interposing mechanical or solid state relay if applicable. Note 4: Retrofit controller has a programmable, not fixed set point. Lock set point using controller's lockout parameter. Note 5: For DIN rail mounting or sub-panel mounting, purchase DIN rail adapter p/n 0822-0586-P001 for 1/32 DIN or
p/n 0822-0586-P002 for 1/16 DIN. Note 6: Add a suppressor, Watlow p/n 0804-0147-0000, for inductive loads. Note 7: Retrofit does not have equivalent action (as example, no manual reset) Note 8: Retrofit controller does not have dual dial scale. Note 9: Hardware lockout is not available on retrofit. Note 10:Retrofit controller does not have user selectable line voltage. Note 11:Retrofit does not support remote set point or retransmit. Check if pins 13, 14, 15 or 16 have termination. If
wires are on these pins, select a different retrofit. Note 12:Retrofit co ntroller does not have user selectable control action. Note 13:Solid state sensor required for humidity. See http://www.vaisala.com Note 14:Retrofit co ntroller does not have user selectable control mode. Note 15:Use auxiliary event board A007-1732-F4B8 Note 16:Retrofit communications are different, consult specifications. Note 17:Verify retrofit input range matches application.
Line
Series 142
142A-2676-1200 120 VAC J t/c 140 to 294°F High limit 142A-2676-1200 120 VAC J t/c 60 to 146°C High limit 142A-2676-1300 120 VAC J t/c 140 to 294°F High limit 142A-2676-1300 120 VAC J t/c 60 to 146°C High limit 142A-2676-1400 120 VAC J t/c 140 to 294°F On/Off 142A-2676-1400 120 VAC J t/c 60 to 146°C On/Off 142A-2676-2200 230 VAC J t/c 140 to 294°F High limit 142A-2676-2200 230 VAC J t/c 60 to 146°C High limit 142A-2676-2300 230 VAC J t/c 140 to 294°F High limit 142A-2676-2300 230 VAC J t/c 60 to 146°C High limit 142A-2676-2400 230 VAC J t/c 140 to 294°F On/Off 142A-2676-2400 230 VAC J t/c 60 to 146°C On/Off 142A-2686-1200 120 VAC J t/c 149°F High limit 142A-2686-1200 120 VAC J t/c 65°C High limit 142A-2686-1300 120 VAC J t/c 149°F High limit 142A-2686-1300 120 VAC J t/c 65°C High limit 142A-2686-1400 120 VAC J t/c 149°F On/Off 142A-2686-1400 120 VAC J t/c 65°C On/Off 142A-2686-2200 230 VAC J t/c 149°F High limit 142A-2686-2200 230 VAC J t/c 65°C High limit 142A-2686-2300 230 VAC J t/c 149°F High limit 142A-2686-2300 230 VAC J t/c 65°C High limit 142A-2686-2400 230 VAC J t/c 149°F On/Off 142A-2686-2400 230 VAC J t/c 65°C On/Off 142A-2696-1200 120 VAC J t/c 900°F High limit 142A-2696-1200 120 VAC J t/c 482°C High limit 142A-2696-1300 120 VAC J t/c 900°F High limit 142A-2696-1300 120 VAC J t/c 482°C High limit 142A-2696-1400 120 VAC J t/c 900°F On/Off 142A-2696-1400 120 VAC J t/c 482°C On/Off 142A-2696-2200 230 VAC J t/c 900°F High limit 142A-2696-2200 230 VAC J t/c 482°C High limit 142A-2696-2300 230 VAC J t/c 900°F High limit 142A-2696-2300 230 VAC J t/c 482°C High limit 142A-2696-2400 230 VAC J t/c 900°F On/Off 142A-2696-2400 230 VAC J t/c 482°C On/Off 142A-2702-1200 120 VAC J t/c 200 to 600°F High limit 142A-2702-1200 120 VAC J t/c 93 to 316°C High limit 142A-2702-1300 120 VAC J t/c 200 to 600°F High limit 142A-2702-1300 120 VAC J t/c 93 to 316°C High limit 142A-2702-1400 120 VAC J t/c 200 to 600°F On/Off
Voltage Input Temp Range Control Mode Action Output Set Point Mounting Retrofit
Series 142
Manual Reset
Manual Reset Automatic Reset Automatic Reset
Heat
Heat Manual Reset Manual Reset
Automatic Reset Automatic Reset
Heat
Heat Manual Reset Manual Reset
Automatic Reset Automatic Reset
Heat
Heat Manual Reset Manual Reset
Automatic Reset Automatic Reset
Heat
Heat Manual Reset Manual Reset
Automatic Reset Automatic Reset
Heat
Heat Manual Reset Manual Reset
Automatic Reset Automatic Reset
Heat
Heat Manual Reset Manual Reset
Automatic Reset Automatic Reset
Heat
See Notes
Below
3A Relay Remote Potted LV C1HU 0140 0294 A 2, 6, 8 3A Relay Remote Potted LV C1JU 0060 0146 A 2, 6, 8 3A Relay Remote Potted LV C1HW 0140 0294 A 2, 6, 8 3A Relay Remote Potted LV C1JW 0060 0146 A 2, 6, 8 3A Relay Remote Potted CV C1HH 0140 0294 A 2, 6, 8 3A Relay Remote Potted CV C1JH 0060 0146 A 2, 6, 8 3A Relay Remote Potted LV E1HU 0140 0294 A 2, 6, 8 3A Relay Remote Potted LV E1JU 0060 0146 A 2, 6, 8 3A Relay Remote Potted LV E1HW 0140 0294 A 2, 6, 8 3A Relay Remote Potted LV E1JW 0060 0146 A 2, 6, 8 3A Relay Remote Potted CV E1HH 0140 0294 A 2, 6, 8 3A Relay Remote Potted CV E1JH 0060 0146 A 2, 6, 8 3A Relay Fixed Potted LF C2HU 0149 AAAA A 6, 8 3A Relay Fixed Potted LF C2JU 0065 AAAA A 6, 8 3A Relay Fixed Potted LF C2HW 0149 AAAA A 6, 8 3A Relay Fixed Potted LF C2JW 0065 AAAA A 6, 8 3A Relay Fixed Potted CF C2HH 0149 AAAA A 6, 8 3A Relay Fixed Potted CF C2JH 0065 AAAA A 6, 8 3A Relay Fixed Potted LF E2HU 0149 AAAA A 6, 8 3A Relay Fixed Potted LF E2JU 0065 AAAA A 6, 8 3A Relay Fixed Potted LF E2HW 0149 AAAA A 6, 8 3A Relay Fixed Potted LF E2JW 0065 AAAA A 6, 8 3A Relay Fixed Potted CF E2HH 0149 AAAA A 6, 8 3A Relay Fixed Potted CF E2JH 0065 AAAA A 6, 8 3A Relay Fixed Potted LF C2HU 0900 AAAA A 6, 8 3A Relay Fixed Potted LF C2JU 0482 AAAA A 6, 8 3A Relay Fixed Potted LF C2HW 0900 AAAA A 6, 8 3A Relay Fixed Potted LF C2JW 0482 AAAA A 6, 8 3A Relay Fixed Potted CF C2HH 0900 AAAA A 6, 8 3A Relay Fixed Potted CF C2JH 0482 AAAA A 6, 8 3A Relay Fixed Potted LF E2HU 0900 AAAA A 6, 8 3A Relay Fixed Potted LF E2JU 0482 AAAA A 6, 8 3A Relay Fixed Potted LF E2HW 0900 AAAA A 6, 8 3A Relay Fixed Potted LF E2JW 0482 AAAA A 6, 8 3A Relay Fixed Potted CF E2HH 0900 AAAA A 6, 8 3A Relay Fixed Potted CF E2JH 0482 AAAA A 6, 8 3A Relay Remote Potted LV C1HU 0200 0600 A 2, 6, 8 3A Relay Remote Potted LV C1JU 0093 0316 A 2, 6, 8 3A Relay Remote Potted LV C1HW 0200 0600 A 2, 6, 8 3A Relay Remote Potted LV C1JW 0093 0316 A 2, 6, 8 3A Relay Remote Potted CV C1HH 0200 0600 A 2, 6, 8
Watlow Controls 1/31/2005 Page 1
Line
Series 142
142A-2702-1400 120 VAC J t/c 93 to 316°C On/Off 142A-2702-2200 230 VAC J t/c 200 to 600°F High limit 142A-2702-2200 230 VAC J t/c 93 to 316°C High limit 142A-2702-2300 230 VAC J t/c 200 to 600°F High limit 142A-2702-2300 230 VAC J t/c 93 to 316°C High limit 142A-2702-2400 230 VAC J t/c 200 to 600°F On/Off 142A-2702-2400 230 VAC J t/c 93 to 316°C On/Off 142A-2705-1200 120 VAC T t/c -328 to 662°F High limit 142A-2705-1200 120 VAC T t/c 200 to 350°C High limit 142A-2705-1300 120 VAC T t/c -328 to 662°F High limit 142A-2705-1300 120 VAC T t/c 200 to 350°C High limit 142A-2705-1400 120 VAC T t/c -328 to 662°F On/Off 142A-2705-1400 120 VAC T t/c 200 to 350°C On/Off 142A-2705-2200 230 VAC T t/c -328 to 662°F High limit 142A-2705-2200 230 VAC T t/c 200 to 350°C High limit 142A-2705-2300 230 VAC T t/c -328 to 662°F High limit 142A-2705-2300 230 VAC T t/c 200 to 350°C High limit 142A-2705-2400 230 VAC T t/c -328 to 662°F On/Off 142A-2705-2400 230 VAC T t/c 200 to 350°C On/Off 142A-2706-1200 120 VAC J t/c 32 to 600°F High limit 142A-2706-1200 120 VAC J t/c 0 to 316°C High limit 142A-2706-1300 120 VAC J t/c 32 to 600°F High limit 142A-2706-1300 120 VAC J t/c 0 to 316°C High limit 142A-2706-1400 120 VAC J t/c 32 to 600°F On/Off 142A-2706-1400 120 VAC J t/c 0 to 316°C On/Off 142A-2706-2200 230 VAC J t/c 32 to 600°F High limit 142A-2706-2200 230 VAC J t/c 0 to 316°C High limit 142A-2706-2300 230 VAC J t/c 32 to 600°F High limit 142A-2706-2300 230 VAC J t/c 0 to 316°C High limit 142A-2706-2400 230 VAC J t/c 32 to 600°F On/Off 142A-2706-2400 230 VAC J t/c 0 to 316°C On/Off 142A-2720-1200 120 VAC J t/c 32 to 302°F High limit 142A-2720-1200 120 VAC J t/c 0 to 150°C High limit 142A-2720-1300 120 VAC J t/c 32 to 302°F High limit 142A-2720-1300 120 VAC J t/c 0 to 150°C High limit 142A-2720-1400 120 VAC J t/c 32 to 302°F On/Off 142A-2720-1400 120 VAC J t/c 0 to 150°C On/Off 142A-2720-2200 230 VAC J t/c 32 to 302°F High limit 142A-2720-2200 230 VAC J t/c 0 to 150°C High limit 142A-2720-2300 230 VAC J t/c 32 to 302°F High limit 142A-2720-2300 230 VAC J t/c 0 to 150°C High limit
Voltage Input Temp Range Control Mode Action Output Set Point Mounting Retrofit
Series 142
Heat Manual Reset Manual Reset
Automatic Reset Automatic Reset
Heat
Heat Manual Reset Manual Reset
Automatic Reset Automatic Reset
Heat
Heat Manual Reset Manual Reset
Automatic Reset Automatic Reset
Heat
Heat Manual Reset Manual Reset
Automatic Reset Automatic Reset
Heat
Heat Manual Reset Manual Reset
Automatic Reset Automatic Reset
Heat
Heat Manual Reset Manual Reset
Automatic Reset Automatic Reset
Heat
Heat Manual Reset Manual Reset
Automatic Reset Automatic Reset
See Notes
Below
3A Relay Remote Potted CV C1JH 0093 0316 A 2, 6, 8 3A Relay Remote Potted LV E1HU 0200 0600 A 2, 6, 8 3A Relay Remote Potted LV E1JU 0093 0316 A 2, 6, 8 3A Relay Remote Potted LV E1HW 0200 0600 A 2, 6, 8 3A Relay Remote Potted LV E1JW 0093 0316 A 2, 6, 8 3A Relay Remote Potted CV E1HH 0200 0600 A 2, 6, 8 3A Relay Remote Potted CV E1JH 0093 0316 A 2, 6, 8 3A Relay Remote Potted LV C1MU -328 0662 A 2, 6, 8 3A Relay Remote Potted LV C1NU 0200 0350 A 2, 6, 8 3A Relay Remote Potted LV C1MW -328 0662 A 2, 6, 8 3A Relay Remote Potted LV C1NW 0200 0350 A 2, 6, 8 3A Relay Remote Potted CV C1MH -328 0662 A 2, 6, 8 3A Relay Remote Potted CV C1NH 0200 0350 A 2, 6, 8 3A Relay Remote Potted LV E1MU -328 0662 A 2, 6, 8 3A Relay Remote Potted LV E1NU 0200 0350 A 2, 6, 8 3A Relay Remote Potted LV E1MW -328 0662 A 2, 6, 8 3A Relay Remote Potted LV E1NW 0200 0350 A 2, 6, 8 3A Relay Remote Potted CV E1MH -328 0662 A 2, 6, 8 3A Relay Remote Potted CV E1NH 0200 0350 A 2, 6, 8 3A Relay Remote Potted LV C1HU 0032 0600 A 2, 6, 8 3A Relay Remote Potted LV C1JU 0000 0316 A 2, 6, 8 3A Relay Remote Potted LV C1HW 0032 0600 A 2, 6, 8 3A Relay Remote Potted LV C1JW 0000 0316 A 2, 6, 8 3A Relay Remote Potted CV C1HH 0032 0600 A 2, 6, 8 3A Relay Remote Potted CV C1JH 0000 0316 A 2, 6, 8 3A Relay Remote Potted LV E1HU 0032 0600 A 2, 6, 8 3A Relay Remote Potted LV E1JU 0000 0316 A 2, 6, 8 3A Relay Remote Potted LV E1HW 0032 0600 A 2, 6, 8 3A Relay Remote Potted LV E1JW 0000 0316 A 2, 6, 8 3A Relay Remote Potted CV E1HH 0032 0600 A 2, 6, 8 3A Relay Remote Potted CV E1JH 0000 0316 A 2, 6, 8 3A Relay Remote Potted LV C1HU 0032 0302 A 2, 6, 8 3A Relay Remote Potted LV C1JU 0000 0150 A 2, 6, 8 3A Relay Remote Potted LV C1HW 0032 0302 A 2, 6, 8 3A Relay Remote Potted LV C1JW 0000 0150 A 2, 6, 8 3A Relay Remote Potted CV C1HH 0032 0302 A 2, 6, 8 3A Relay Remote Potted CV C1JH 0000 0150 A 2, 6, 8 3A Relay Remote Potted LV E1HU 0032 0302 A 2, 6, 8 3A Relay Remote Potted LV E1JU 0000 0150 A 2, 6, 8 3A Relay Remote Potted LV E1HW 0032 0302 A 2, 6, 8 3A Relay Remote Potted LV E1JW 0000 0150 A 2, 6, 8
Watlow Controls 1/31/2005 Page 2
Line
Series 142
142A-2720-2400 230 VAC J t/c 32 to 302°F On/Off 142A-2720-2400 230 VAC J t/c 0 to 150°C On/Off 142A-2732-1200 120 VAC E t/c 68 to 617°F High limit 142A-2732-1200 120 VAC E t/c 20 to 325°C High limit 142A-2732-1300 120 VAC E t/c 68 to 617°F High limit 142A-2732-1300 120 VAC E t/c 20 to 325°C High limit 142A-2732-1400 120 VAC E t/c 68 to 617°F On/Off 142A-2732-1400 120 VAC E t/c 20 to 325°C On/Off 142A-2732-2200 230 VAC E t/c 68 to 617°F High limit 142A-2732-2200 230 VAC E t/c 20 to 325°C High limit 142A-2732-2300 230 VAC E t/c 68 to 617°F High limit 142A-2732-2300 230 VAC E t/c 20 to 325°C High limit 142A-2732-2400 230 VAC E t/c 68 to 617°F On/Off 142A-2732-2400 230 VAC E t/c 20 to 325°C On/Off 142A-2733-1200 120 VAC K t/c -200 to 1000°F High limit 142A-2733-1200 120 VAC K t/c -129 to 538°C High limit 142A-2733-1300 120 VAC K t/c -200 to 1000°F High limit 142A-2733-1300 120 VAC K t/c -129 to 538°C High limit 142A-2733-1400 120 VAC K t/c -200 to 1000°F On/Off 142A-2733-1400 120 VAC K t/c -129 to 538°C On/Off 142A-2733-2200 230 VAC K t/c -200 to 1000°F High limit 142A-2733-2200 230 VAC K t/c -129 to 538°C High limit 142A-2733-2300 230 VAC K t/c -200 to 1000°F High limit 142A-2733-2300 230 VAC K t/c -129 to 538°C High limit 142A-2733-2400 230 VAC K t/c -200 to 1000°F On/Off 142A-2733-2400 230 VAC K t/c -129 to 538°C On/Off 142A-2736-1200 120 VAC J t/c 0 to 450°F High limit 142A-2736-1200 120 VAC J t/c -18 to 450°C High limit 142A-2736-1300 120 VAC J t/c 0 to 450°F High limit 142A-2736-1300 120 VAC J t/c -18 to 450°C High limit 142A-2736-1400 120 VAC J t/c 0 to 450°F On/Off 142A-2736-1400 120 VAC J t/c -18 to 450°C On/Off 142A-2736-2200 230 VAC J t/c 0 to 450°F High limit 142A-2736-2200 230 VAC J t/c -18 to 450°C High limit 142A-2736-2300 230 VAC J t/c 0 to 450°F High limit 142A-2736-2300 230 VAC J t/c -18 to 450°C High limit 142A-2736-2400 230 VAC J t/c 0 to 450°F On/Off 142A-2736-2400 230 VAC J t/c -18 to 450°C On/Off 142A-3600-1300 120 VAC J t/c 250°F High limit 142A-3601-1200 120 VAC J t/c 225°F High limit 142A-3601-1200 120 VAC J t/c 107°C High limit
Voltage Input Temp Range Control Mode Action Output Set Point Mounting Retrofit
Series 142
Heat
Heat Manual Reset Manual Reset
Automatic Reset Automatic Reset
Heat
Heat Manual Reset Manual Reset
Automatic Reset Automatic Reset
Heat
Heat Manual Reset Manual Reset
Automatic Reset Automatic Reset
Heat
Heat Manual Reset Manual Reset
Automatic Reset Automatic Reset
Heat
Heat Manual Reset Manual Reset
Automatic Reset Automatic Reset
Heat
Heat Manual Reset Manual Reset
Automatic Reset Automatic Reset
Heat
Heat
Automatic Reset
Manual Reset Manual Reset
See Notes
Below
3A Relay Remote Potted CV E1HH 0032 0302 A 2, 6, 8 3A Relay Remote Potted CV E1JH 0000 0150 A 2, 6, 8 3A Relay Remote Potted LV C1SU 0068 0617 A 2, 6, 8 3A Relay Remote Potted LV C1TU 0020 0325 A 2, 6, 8 3A Relay Remote Potted LV C1SW 0068 0617 A 2, 6, 8 3A Relay Remote Potted LV C1TW 0020 0325 A 2, 6, 8 3A Relay Remote Potted CV C1SH 0068 0617 A 2, 6, 8 3A Relay Remote Potted CV C1TH 0020 0325 A 2, 6, 8 3A Relay Remote Potted LV E1SU 0068 0617 A 2, 6, 8 3A Relay Remote Potted LV E1TU 0020 0325 A 2, 6, 8 3A Relay Remote Potted LV E1SW 0068 0617 A 2, 6, 8 3A Relay Remote Potted LV E1TW 0020 0325 A 2, 6, 8 3A Relay Remote Potted CV E1SH 0068 0617 A 2, 6, 8 3A Relay Remote Potted CV E1TH 0020 0325 A 2, 6, 8 3A Relay Remote Potted LV C1KU -200 1000 A 2, 6, 8 3A Relay Remote Potted LV C1LU -129 0538 A 2, 6, 8 3A Relay Remote Potted LV C1KW -200 1000 A 2, 6, 8 3A Relay Remote Potted LV C1LW -129 0538 A 2, 6, 8 3A Relay Remote Potted CV C1KH -200 1000 A 2, 6, 8 3A Relay Remote Potted CV C1LH -129 0538 A 2, 6, 8 3A Relay Remote Potted LV E1KU -200 1000 A 2, 6, 8 3A Relay Remote Potted LV E1LU -129 0538 A 2, 6, 8 3A Relay Remote Potted LV E1KW -200 1000 A 2, 6, 8 3A Relay Remote Potted LV E1LW -129 0538 A 2, 6, 8 3A Relay Remote Potted CV E1KH -200 1000 A 2, 6, 8 3A Relay Remote Potted CV E1LH -129 0538 A 2, 6, 8 3A Relay Remote Potted LV C1HU 0000 0450 A 2, 6, 8 3A Relay Remote Potted LV C1JU 0-18 0450 A 2, 6, 8 3A Relay Remote Potted LV C1HW 0000 0450 A 2, 6, 8 3A Relay Remote Potted LV C1JW 0-18 0450 A 2, 6, 8 3A Relay Remote Potted CV C1HH 0000 0450 A 2, 6, 8 3A Relay Remote Potted CV C1JH 0-18 0450 A 2, 6, 8 3A Relay Remote Potted LV E1HU 0000 0450 A 2, 6, 8 3A Relay Remote Potted LV E1JU 0-18 0450 A 2, 6, 8 3A Relay Remote Potted LV E1HW 0000 0450 A 2, 6, 8 3A Relay Remote Potted LV E1JW 0-18 0450 A 2, 6, 8 3A Relay Remote Potted CV E1HH 0000 0450 A 6, 8 3A Relay Remote Potted CV E1JH 0-18 0450 A 6, 8 3A Relay Fixed Potted LF C4HW 0250 AAAA A 6, 8 3A Relay Fixed Potted LF C4HU 0225 AAAA A 6, 8 3A Relay Fixed Potted LF C4JU 0107 AAAA A 6, 8
Watlow Controls 1/31/2005 Page 3
Line
Series 142
142A-3601-1300 120 VAC J t/c 225°F High limit 142A-3601-1300 120 VAC J t/c 107°C High limit 142A-3601-1400 120 VAC J t/c 225°F On/Off 142A-3601-1400 120 VAC J t/c 107°C On/Off 142A-3601-2200 230 VAC J t/c 225°F High limit 142A-3601-2200 230 VAC J t/c 107°C High limit 142A-3601-2300 230 VAC J t/c 225°F High limit 142A-3601-2300 230 VAC J t/c 107°C High limit 142A-3601-2400 230 VAC J t/c 225°F On/Off 142A-3601-2400 230 VAC J t/c 107°C On/Off 142A-3602-1200 120 VAC J t/c 250°F High limit 142A-3602-1200 120 VAC J t/c 121°C High limit 142A-3602-1300 120 VAC J t/c 250°F High limit 142A-3602-1300 120 VAC J t/c 121°C High limit 142A-3602-1400 120 VAC J t/c 250°F On/Off 142A-3602-1400 120 VAC J t/c 121°C On/Off 142A-3602-2200 230 VAC J t/c 250°F High limit 142A-3602-2200 230 VAC J t/c 121°C High limit 142A-3602-2300 230 VAC J t/c 250°F High limit 142A-3602-2300 230 VAC J t/c 121°C High limit 142A-3602-2400 230 VAC J t/c 250°F On/Off 142A-3602-2400 230 VAC J t/c 121°C On/Off 142A-3603-1200 120 VAC J t/c 275°F High limit 142A-3603-1200 120 VAC J t/c 135°C High limit 142A-3603-1300 120 VAC J t/c 275°F High limit 142A-3603-1300 120 VAC J t/c 135°C High limit 142A-3603-1400 120 VAC J t/c 275°F On/Off 142A-3603-1400 120 VAC J t/c 135°C On/Off 142A-3603-2200 230 VAC J t/c 275°F High limit 142A-3603-2200 230 VAC J t/c 135°C High limit 142A-3603-2300 230 VAC J t/c 275°F High limit 142A-3603-2300 230 VAC J t/c 135°C High limit 142A-3603-2400 230 VAC J t/c 275°F On/Off 142A-3603-2400 230 VAC J t/c 135°C On/Off 142A-3604-1200 120 VAC J t/c 300°F High limit 142A-3604-1200 120 VAC J t/c 149°C High limit 142A-3604-1300 120 VAC J t/c 300°F High limit 142A-3604-1300 120 VAC J t/c 149°C High limit 142A-3604-1400 120 VAC J t/c 300°F On/Off 142A-3604-1400 120 VAC J t/c 149°C On/Off 142A-3604-2200 230 VAC J t/c 300°F High limit
Voltage Input Temp Range Control Mode Action Output Set Point Mounting Retrofit
Series 142
Automatic Reset Automatic Reset
Heat
Heat Manual Reset Manual Reset
Automatic Reset Automatic Reset
Heat
Heat Manual Reset Manual Reset
Automatic Reset Automatic Reset
Heat
Heat Manual Reset Manual Reset
Automatic Reset Automatic Reset
Heat
Heat Manual Reset Manual Reset
Automatic Reset Automatic Reset
Heat
Heat Manual Reset Manual Reset
Automatic Reset Automatic Reset
Heat
Heat Manual Reset Manual Reset
Automatic Reset Automatic Reset
Heat
Heat Manual Reset
See Notes
Below
3A Relay Fixed Potted LF C4HW 0225 AAAA A 6, 8 3A Relay Fixed Potted LF C4JW 0107 AAAA A 6, 8 3A Relay Fixed Potted CF C4HH 0225 AAAA A 6, 8 3A Relay Fixed Potted CF C4JH 0107 AAAA A 6, 8 3A Relay Fixed Potted LF E4HU 0225 AAAA A 6, 8 3A Relay Fixed Potted LF E4JU 0107 AAAA A 6, 8 3A Relay Fixed Potted LF E4HW 0225 AAAA A 6, 8 3A Relay Fixed Potted LF E4JW 0107 AAAA A 6, 8 3A Relay Fixed Potted CF E4HH 0225 AAAA A 6, 8 3A Relay Fixed Potted CF E4JH 0107 AAAA A 6, 8 3A Relay Fixed Potted LF C4HU 0250 AAAA A 6, 8 3A Relay Fixed Potted LF C4JU 0121 AAAA A 6, 8 3A Relay Fixed Potted LF C4HW 0250 AAAA A 6, 8 3A Relay Fixed Potted LF C4JW 0121 AAAA A 6, 8 3A Relay Fixed Potted CF C4HH 0250 AAAA A 6, 8 3A Relay Fixed Potted CF C4JH 0121 AAAA A 6, 8 3A Relay Fixed Potted LF E4HU 0250 AAAA A 6, 8 3A Relay Fixed Potted LF E4JU 0121 AAAA A 6, 8 3A Relay Fixed Potted LF E4HW 0250 AAAA A 6, 8 3A Relay Fixed Potted LF E4JW 0121 AAAA A 6, 8 3A Relay Fixed Potted CF E4HH 0250 AAAA A 6, 8 3A Relay Fixed Potted CF E4JH 0121 AAAA A 6, 8 3A Relay Fixed Potted LF C4HU 0275 AAAA A 6, 8 3A Relay Fixed Potted LF C4JU 0135 AAAA A 6, 8 3A Relay Fixed Potted LF C4HW 0275 AAAA A 6, 8 3A Relay Fixed Potted LF C4JW 0135 AAAA A 6, 8 3A Relay Fixed Potted CF C4HH 0275 AAAA A 6, 8 3A Relay Fixed Potted CF C4JH 0135 AAAA A 6, 8 3A Relay Fixed Potted LF E4HU 0275 AAAA A 6, 8 3A Relay Fixed Potted LF E4JU 0135 AAAA A 6, 8 3A Relay Fixed Potted LF E4HW 0275 AAAA A 6, 8 3A Relay Fixed Potted LF E4JW 0135 AAAA A 6, 8 3A Relay Fixed Potted CF E4HH 0275 AAAA A 6, 8 3A Relay Fixed Potted CF E4JH 0135 AAAA A 6, 8 3A Relay Fixed Potted LF C4HU 0300 AAAA A 6, 8 3A Relay Fixed Potted LF C4JU 0149 AAAA A 6, 8 3A Relay Fixed Potted LF C4HW 0300 AAAA A 6, 8 3A Relay Fixed Potted LF C4JW 0149 AAAA A 6, 8 3A Relay Fixed Potted CF C4HH 0300 AAAA A 6, 8 3A Relay Fixed Potted CF C4JH 0149 AAAA A 6, 8 3A Relay Fixed Potted LF E4HU 0300 AAAA A 6, 8
Watlow Controls 1/31/2005 Page 4
Line
Series 142
142A-3604-2200 230 VAC J t/c 149°C High limit 142A-3604-2300 230 VAC J t/c 300°F High limit 142A-3604-2300 230 VAC J t/c 149°C High limit 142A-3604-2400 230 VAC J t/c 300°F On/Off 142A-3604-2400 230 VAC J t/c 149°C On/Off 142A-3605-1200 120 VAC J t/c 325°F High limit 142A-3605-1200 120 VAC J t/c 163°C High limit 142A-3605-1300 120 VAC J t/c 325°F High limit 142A-3605-1300 120 VAC J t/c 163°C High limit 142A-3605-1400 120 VAC J t/c 325°F On/Off 142A-3605-1400 120 VAC J t/c 163°C On/Off 142A-3605-2200 230 VAC J t/c 325°F High limit 142A-3605-2200 230 VAC J t/c 163°C High limit 142A-3605-2300 230 VAC J t/c 325°F High limit 142A-3605-2300 230 VAC J t/c 163°C High limit 142A-3605-2400 230 VAC J t/c 325°F On/Off 142A-3605-2400 230 VAC J t/c 163°C On/Off 142A-3606-1200 120 VAC J t/c 350°F High limit 142A-3606-1200 120 VAC J t/c 177°C High limit 142A-3606-1300 120 VAC J t/c 350°F High limit 142A-3606-1300 120 VAC J t/c 177°C High limit 142A-3606-1400 120 VAC J t/c 350°F On/Off 142A-3606-1400 120 VAC J t/c 177°C On/Off 142A-3606-2200 230 VAC J t/c 350°F High limit 142A-3606-2200 230 VAC J t/c 177°C High limit 142A-3606-2300 230 VAC J t/c 350°F High limit 142A-3606-2300 230 VAC J t/c 177°C High limit 142A-3606-2400 230 VAC J t/c 350°F On/Off 142A-3606-2400 230 VAC J t/c 177°C On/Off 142A-3607-1200 120 VAC J t/c 375°F High limit 142A-3607-1200 120 VAC J t/c 191°C High limit 142A-3607-1300 120 VAC J t/c 375°F High limit 142A-3607-1300 120 VAC J t/c 191°C High limit 142A-3607-1400 120 VAC J t/c 375°F On/Off 142A-3607-1400 120 VAC J t/c 191°C On/Off 142A-3607-2200 230 VAC J t/c 375°F High limit 142A-3607-2200 230 VAC J t/c 191°C High limit 142A-3607-2300 230 VAC J t/c 375°F High limit 142A-3607-2300 230 VAC J t/c 191°C High limit 142A-3607-2400 230 VAC J t/c 375°F On/Off 142A-3607-2400 230 VAC J t/c 191°C On/Off
Voltage Input Temp Range Control Mode Action Output Set Point Mounting Retrofit
Series 142
Manual Reset
Automatic Reset Automatic Reset
Heat
Heat Manual Reset Manual Reset
Automatic Reset Automatic Reset
Heat
Heat Manual Reset Manual Reset
Automatic Reset Automatic Reset
Heat
Heat Manual Reset Manual Reset
Automatic Reset Automatic Reset
Heat
Heat Manual Reset Manual Reset
Automatic Reset Automatic Reset
Heat
Heat Manual Reset Manual Reset
Automatic Reset Automatic Reset
Heat
Heat Manual Reset Manual Reset
Automatic Reset Automatic Reset
Heat
Heat
See Notes
Below
3A Relay Fixed Potted LF E4JU 0149 AAAA A 6, 8 3A Relay Fixed Potted LF E4HW 0300 AAAA A 6, 8 3A Relay Fixed Potted LF E4JW 0149 AAAA A 6, 8 3A Relay Fixed Potted CF E4HH 0300 AAAA A 6, 8 3A Relay Fixed Potted CF E4JH 0149 AAAA A 6, 8 3A Relay Fixed Potted LF C4HU 0325 AAAA A 6, 8 3A Relay Fixed Potted LF C4JU 0163 AAAA A 6, 8 3A Relay Fixed Potted LF C4HW 0325 AAAA A 6, 8 3A Relay Fixed Potted LF C4JW 0163 AAAA A 6, 8 3A Relay Fixed Potted CF C4HH 0325 AAAA A 6, 8 3A Relay Fixed Potted CF C4JH 0163 AAAA A 6, 8 3A Relay Fixed Potted LF E4HU 0325 AAAA A 6, 8 3A Relay Fixed Potted LF E4JU 0163 AAAA A 6, 8 3A Relay Fixed Potted LF E4HW 0325 AAAA A 6, 8 3A Relay Fixed Potted LF E4JW 0163 AAAA A 6, 8 3A Relay Fixed Potted CF E4HH 0325 AAAA A 6, 8 3A Relay Fixed Potted CF E4JH 0163 AAAA A 6, 8 3A Relay Fixed Potted LF C4HU 0350 AAAA A 6, 8 3A Relay Fixed Potted LF C4JU 0177 AAAA A 6, 8 3A Relay Fixed Potted LF C4HW 0350 AAAA A 6, 8 3A Relay Fixed Potted LF C4JW 0177 AAAA A 6, 8 3A Relay Fixed Potted CF C4HH 0350 AAAA A 6, 8 3A Relay Fixed Potted CF C4JH 0177 AAAA A 6, 8 3A Relay Fixed Potted LF E4HU 0350 AAAA A 6, 8 3A Relay Fixed Potted LF E4JU 0177 AAAA A 6, 8 3A Relay Fixed Potted LF E4HW 0350 AAAA A 6, 8 3A Relay Fixed Potted LF E4JW 0177 AAAA A 6, 8 3A Relay Fixed Potted CF E4HH 0350 AAAA A 6, 8 3A Relay Fixed Potted CF E4JH 0177 AAAA A 6, 8 3A Relay Fixed Potted LF C4HU 0375 AAAA A 6, 8 3A Relay Fixed Potted LF C4JU 0191 AAAA A 6, 8 3A Relay Fixed Potted LF C4HW 0375 AAAA A 6, 8 3A Relay Fixed Potted LF C4JW 0191 AAAA A 6, 8 3A Relay Fixed Potted CF C4HH 0375 AAAA A 6, 8 3A Relay Fixed Potted CF C4JH 0191 AAAA A 6, 8 3A Relay Fixed Potted LF E4HU 0375 AAAA A 6, 8 3A Relay Fixed Potted LF E4JU 0191 AAAA A 6, 8 3A Relay Fixed Potted LF E4HW 0375 AAAA A 6, 8 3A Relay Fixed Potted LF E4JW 0191 AAAA A 6, 8 3A Relay Fixed Potted CF E4HH 0375 AAAA A 6, 8 3A Relay Fixed Potted CF E4JH 0191 AAAA A 6, 8
Watlow Controls 1/31/2005 Page 5
Line
Series 142
142A-3608-1200 120 VAC J t/c 400°F High limit 142A-3608-1200 120 VAC J t/c 204°C High limit 142A-3608-1300 120 VAC J t/c 400°F High limit 142A-3608-1300 120 VAC J t/c 204°C High limit 142A-3608-1400 120 VAC J t/c 400°F On/Off 142A-3608-1400 120 VAC J t/c 204°C On/Off 142A-3608-2200 230 VAC J t/c 400°F High limit 142A-3608-2200 230 VAC J t/c 204°C High limit 142A-3608-2300 230 VAC J t/c 400°F High limit 142A-3608-2300 230 VAC J t/c 204°C High limit 142A-3608-2400 230 VAC J t/c 400°F On/Off 142A-3608-2400 230 VAC J t/c 204°C On/Off 142A-3609-1200 120 VAC J t/c 155°F High limit 142A-3609-1200 120 VAC J t/c 68°C High limit 142A-3609-1300 120 VAC J t/c 155°F High limit 142A-3609-1300 120 VAC J t/c 68°C High limit 142A-3609-1400 120 VAC J t/c 155°F On/Off 142A-3609-1400 120 VAC J t/c 68°C On/Off 142A-3609-2200 230 VAC J t/c 155°F High limit 142A-3609-2200 230 VAC J t/c 68°C High limit 142A-3609-2300 230 VAC J t/c 155°F High limit 142A-3609-2300 230 VAC J t/c 68°C High limit 142A-3609-2400 230 VAC J t/c 155°F On/Off 142A-3609-2400 230 VAC J t/c 68°C On/Off 142A-3610-1200 120 VAC J t/c 135°F High limit 142A-3610-1200 120 VAC J t/c 57°C High limit 142A-3610-1300 120 VAC J t/c 135°F High limit 142A-3610-1300 120 VAC J t/c 57°C High limit 142A-3610-1400 120 VAC J t/c 135°F On/Off 142A-3610-1400 120 VAC J t/c 57°C On/Off 142A-3610-2200 230 VAC J t/c 135°F High limit 142A-3610-2200 230 VAC J t/c 57°C High limit 142A-3610-2300 230 VAC J t/c 135°F High limit 142A-3610-2300 230 VAC J t/c 57°C High limit 142A-3610-2400 230 VAC J t/c 135°F On/Off 142A-3610-2400 230 VAC J t/c 57°C On/Off 142A-3611-1200 120 VAC J t/c 240°F High limit 142A-3611-1200 120 VAC J t/c 116°C High limit 142A-3611-1300 120 VAC J t/c 240°F High limit 142A-3611-1300 120 VAC J t/c 116°C High limit 142A-3611-1400 120 VAC J t/c 240°F On/Off
Voltage Input Temp Range Control Mode Action Output Set Point Mounting Retrofit
Series 142
Manual Reset Manual Reset
Automatic Reset Automatic Reset
Heat
Heat Manual Reset Manual Reset
Automatic Reset Automatic Reset
Heat
Heat Manual Reset Manual Reset
Automatic Reset Automatic Reset
Heat
Heat Manual Reset Manual Reset
Automatic Reset Automatic Reset
Heat
Heat Manual Reset Manual Reset
Automatic Reset Automatic Reset
Heat
Heat Manual Reset Manual Reset
Automatic Reset Automatic Reset
Heat
Heat Manual Reset Manual Reset
Automatic Reset Automatic Reset
Heat
See Notes
Below
3A Relay Fixed Potted LF C4HU 0400 AAAA A 6, 8 3A Relay Fixed Potted LF C4JU 0204 AAAA A 6, 8 3A Relay Fixed Potted LF C4HW 0400 AAAA A 6, 8 3A Relay Fixed Potted LF C4JW 0204 AAAA A 6, 8 3A Relay Fixed Potted CF C4HH 0400 AAAA A 6, 8 3A Relay Fixed Potted CF C4JH 0204 AAAA A 6, 8 3A Relay Fixed Potted LF E4HU 0400 AAAA A 6, 8 3A Relay Fixed Potted LF E4JU 0204 AAAA A 6, 8 3A Relay Fixed Potted LF E4HW 0400 AAAA A 6, 8 3A Relay Fixed Potted LF E4JW 0204 AAAA A 6, 8 3A Relay Fixed Potted CF E4HH 0400 AAAA A 6, 8 3A Relay Fixed Potted CF E4JH 0204 AAAA A 6, 8 3A Relay Fixed Potted LF C4HU 0155 AAAA A 6, 8 3A Relay Fixed Potted LF C4JU 0068 AAAA A 6, 8 3A Relay Fixed Potted LF C4HW 0155 AAAA A 6, 8 3A Relay Fixed Potted LF C4JW 0068 AAAA A 6, 8 3A Relay Fixed Potted CF C4HH 0155 AAAA A 6, 8 3A Relay Fixed Potted CF C4JH 0068 AAAA A 6, 8 3A Relay Fixed Potted LF E4HU 0155 AAAA A 6, 8 3A Relay Fixed Potted LF E4JU 0068 AAAA A 6, 8 3A Relay Fixed Potted LF E4HW 0155 AAAA A 6, 8 3A Relay Fixed Potted LF E4JW 0068 AAAA A 6, 8 3A Relay Fixed Potted CF E4HH 0155 AAAA A 6, 8 3A Relay Fixed Potted CF E4JH 0068 AAAA A 6, 8 3A Relay Fixed Potted LF C4HU 0135 AAAA A 6, 8 3A Relay Fixed Potted LF C4JU 0057 AAAA A 6, 8 3A Relay Fixed Potted LF C4HW 0135 AAAA A 6, 8 3A Relay Fixed Potted LF C4JW 0057 AAAA A 6, 8 3A Relay Fixed Potted CF C4HH 0135 AAAA A 6, 8 3A Relay Fixed Potted CF C4JH 0057 AAAA A 6, 8 3A Relay Fixed Potted LF E4HU 0135 AAAA A 6, 8 3A Relay Fixed Potted LF E4JU 0057 AAAA A 6, 8 3A Relay Fixed Potted LF E4HW 0135 AAAA A 6, 8 3A Relay Fixed Potted LF E4JW 0057 AAAA A 6, 8 3A Relay Fixed Potted CF E4HH 0135 AAAA A 6, 8 3A Relay Fixed Potted CF E4JH 0057 AAAA A 6, 8 3A Relay Fixed Potted LF C4HU 0240 AAAA A 6, 8 3A Relay Fixed Potted LF C4JU 0116 AAAA A 6, 8 3A Relay Fixed Potted LF C4HW 0240 AAAA A 6, 8 3A Relay Fixed Potted LF C4JW 0116 AAAA A 6, 8 3A Relay Fixed Potted CF C4HH 0240 AAAA A 6, 8
Watlow Controls 1/31/2005 Page 6
Line
Series 142
142A-3611-1400 120 VAC J t/c 116°C On/Off 142A-3611-2200 230 VAC J t/c 240°F High limit 142A-3611-2200 230 VAC J t/c 116°C High limit 142A-3611-2300 230 VAC J t/c 240°F High limit 142A-3611-2300 230 VAC J t/c 116°C High limit 142A-3611-2400 230 VAC J t/c 240°F On/Off 142A-3611-2400 230 VAC J t/c 116°C On/Off 142A-3612-1200 120 VAC J t/c 475°F High limit 142A-3612-1200 120 VAC J t/c 246°C High limit 142A-3612-1300 120 VAC J t/c 475°F High limit 142A-3612-1300 120 VAC J t/c 246°C High limit 142A-3612-1400 120 VAC J t/c 475°F On/Off 142A-3612-1400 120 VAC J t/c 246°C On/Off 142A-3612-2200 230 VAC J t/c 475°F High limit 142A-3612-2200 230 VAC J t/c 246°C High limit 142A-3612-2300 230 VAC J t/c 475°F High limit 142A-3612-2300 230 VAC J t/c 246°C High limit 142A-3612-2400 230 VAC J t/c 475°F On/Off 142A-3612-2400 230 VAC J t/c 246°C On/Off 142A-3613-1200 120 VAC J t/c 500°F High limit 142A-3613-1200 120 VAC J t/c 260°C High limit 142A-3613-1300 120 VAC J t/c 500°F High limit 142A-3613-1300 120 VAC J t/c 260°C High limit 142A-3613-1400 120 VAC J t/c 500°F On/Off 142A-3613-1400 120 VAC J t/c 260°C On/Off 142A-3613-2200 230 VAC J t/c 500°F High limit 142A-3613-2200 230 VAC J t/c 260°C High limit 142A-3613-2300 230 VAC J t/c 500°F High limit 142A-3613-2300 230 VAC J t/c 260°C High limit 142A-3613-2400 230 VAC J t/c 500°F On/Off 142A-3613-2400 230 VAC J t/c 260°C On/Off 142A-3614-1200 120 VAC J t/c 525°F High limit 142A-3614-1200 120 VAC J t/c 274°C High limit 142A-3614-1300 120 VAC J t/c 525°F High limit 142A-3614-1300 120 VAC J t/c 274°C High limit 142A-3614-1400 120 VAC J t/c 525°F On/Off 142A-3614-1400 120 VAC J t/c 274°C On/Off 142A-3614-2200 230 VAC J t/c 525°F High limit 142A-3614-2200 230 VAC J t/c 274°C High limit 142A-3614-2300 230 VAC J t/c 525°F High limit 142A-3614-2300 230 VAC J t/c 274°C High limit
Voltage Input Temp Range Control Mode Action Output Set Point Mounting Retrofit
Series 142
Heat Manual Reset Manual Reset
Automatic Reset Automatic Reset
Heat
Heat Manual Reset Manual Reset
Automatic Reset Automatic Reset
Heat
Heat Manual Reset Manual Reset
Automatic Reset Automatic Reset
Heat
Heat Manual Reset Manual Reset
Automatic Reset Automatic Reset
Heat
Heat Manual Reset Manual Reset
Automatic Reset Automatic Reset
Heat
Heat Manual Reset Manual Reset
Automatic Reset Automatic Reset
Heat
Heat Manual Reset Manual Reset
Automatic Reset Automatic Reset
See Notes
Below
3A Relay Fixed Potted CF C4JH 0116 AAAA A 6, 8 3A Relay Fixed Potted LF E4HU 0240 AAAA A 6, 8 3A Relay Fixed Potted LF E4JU 0116 AAAA A 6, 8 3A Relay Fixed Potted LF E4HW 0240 AAAA A 6, 8 3A Relay Fixed Potted LF E4JW 0116 AAAA A 6, 8 3A Relay Fixed Potted CF E4HH 0240 AAAA A 6, 8 3A Relay Fixed Potted CF E4JH 0116 AAAA A 6, 8 3A Relay Fixed Potted LF C4HU 0475 AAAA A 6, 8 3A Relay Fixed Potted LF C4JU 0246 AAAA A 6, 8 3A Relay Fixed Potted LF C4HW 0475 AAAA A 6, 8 3A Relay Fixed Potted LF C4JW 0246 AAAA A 6, 8 3A Relay Fixed Potted CF C4HH 0475 AAAA A 6, 8 3A Relay Fixed Potted CF C4JH 0246 AAAA A 6, 8 3A Relay Fixed Potted LF E4HU 0475 AAAA A 6, 8 3A Relay Fixed Potted LF E4JU 0246 AAAA A 6, 8 3A Relay Fixed Potted LF E4HW 0475 AAAA A 6, 8 3A Relay Fixed Potted LF E4JW 0246 AAAA A 6, 8 3A Relay Fixed Potted CF E4HH 0475 AAAA A 6, 8 3A Relay Fixed Potted CF E4JH 0246 AAAA A 6, 8 3A Relay Fixed Potted LF C4HU 0500 AAAA A 6, 8 3A Relay Fixed Potted LF C4JU 0260 AAAA A 6, 8 3A Relay Fixed Potted LF C4HW 0500 AAAA A 6, 8 3A Relay Fixed Potted LF C4JW 0260 AAAA A 6, 8 3A Relay Fixed Potted CF C4HH 0500 AAAA A 6, 8 3A Relay Fixed Potted CF C4JH 0260 AAAA A 6, 8 3A Relay Fixed Potted LF E4HU 0500 AAAA A 6, 8 3A Relay Fixed Potted LF E4JU 0260 AAAA A 6, 8 3A Relay Fixed Potted LF E4HW 0500 AAAA A 6, 8 3A Relay Fixed Potted LF E4JW 0260 AAAA A 6, 8 3A Relay Fixed Potted CF E4HH 0500 AAAA A 6, 8 3A Relay Fixed Potted CF E4JH 0260 AAAA A 6, 8 3A Relay Fixed Potted LF C4HU 0525 AAAA A 6, 8 3A Relay Fixed Potted LF C4JU 0274 AAAA A 6, 8 3A Relay Fixed Potted LF C4HW 0525 AAAA A 6, 8 3A Relay Fixed Potted LF C4JW 0274 AAAA A 6, 8 3A Relay Fixed Potted CF C4HH 0525 AAAA A 6, 8 3A Relay Fixed Potted CF C4JH 0274 AAAA A 6, 8 3A Relay Fixed Potted LF E4HU 0525 AAAA A 6, 8 3A Relay Fixed Potted LF E4JU 0274 AAAA A 6, 8 3A Relay Fixed Potted LF E4HW 0525 AAAA A 6, 8 3A Relay Fixed Potted LF E4JW 0274 AAAA A 6, 8
Watlow Controls 1/31/2005 Page 7
Line
Series 142
142A-3614-2400 230 VAC J t/c 525°F On/Off 142A-3614-2400 230 VAC J t/c 274°C On/Off 142A-3615-1200 120 VAC J t/c 550°F High limit 142A-3615-1200 120 VAC J t/c 288°C High limit 142A-3615-1300 120 VAC J t/c 550°F High limit 142A-3615-1300 120 VAC J t/c 288°C High limit 142A-3615-1400 120 VAC J t/c 550°F On/Off 142A-3615-1400 120 VAC J t/c 288°C On/Off 142A-3615-2200 230 VAC J t/c 550°F High limit 142A-3615-2200 230 VAC J t/c 288°C High limit 142A-3615-2300 230 VAC J t/c 550°F High limit 142A-3615-2300 230 VAC J t/c 288°C High limit 142A-3615-2400 230 VAC J t/c 550°F On/Off 142A-3615-2400 230 VAC J t/c 288°C On/Off 142A-3616-1200 120 VAC J t/c 575°F High limit 142A-3616-1200 120 VAC J t/c 302°C High limit 142A-3616-1300 120 VAC J t/c 575°F High limit 142A-3616-1300 120 VAC J t/c 302°C High limit 142A-3616-1400 120 VAC J t/c 575°F On/Off 142A-3616-1400 120 VAC J t/c 302°C On/Off 142A-3616-2200 230 VAC J t/c 575°F High limit 142A-3616-2200 230 VAC J t/c 302°C High limit 142A-3616-2300 230 VAC J t/c 575°F High limit 142A-3616-2300 230 VAC J t/c 302°C High limit 142A-3616-2400 230 VAC J t/c 575°F On/Off 142A-3616-2400 230 VAC J t/c 302°C On/Off 142A-3617-1200 120 VAC J t/c 600°F High limit 142A-3617-1200 120 VAC J t/c 316°C High limit 142A-3617-1300 120 VAC J t/c 600°F High limit 142A-3617-1300 120 VAC J t/c 316°C High limit 142A-3617-1400 120 VAC J t/c 600°F On/Off 142A-3617-1400 120 VAC J t/c 316°C On/Off 142A-3617-2200 230 VAC J t/c 600°F High limit 142A-3617-2200 230 VAC J t/c 316°C High limit 142A-3617-2300 230 VAC J t/c 600°F High limit 142A-3617-2300 230 VAC J t/c 316°C High limit 142A-3617-2400 230 VAC J t/c 600°F On/Off 142A-3617-2400 230 VAC J t/c 316°C On/Off 142A-3618-1200 120 VAC J t/c 625°F High limit 142A-3618-1200 120 VAC J t/c 329°C High limit 142A-3618-1300 120 VAC J t/c 625°F High limit
Voltage Input Temp Range Control Mode Action Output Set Point Mounting Retrofit
Series 142
Heat
Heat Manual Reset Manual Reset
Automatic Reset Automatic Reset
Heat
Heat Manual Reset Manual Reset
Automatic Reset Automatic Reset
Heat
Heat Manual Reset Manual Reset
Automatic Reset Automatic Reset
Heat
Heat Manual Reset Manual Reset
Automatic Reset Automatic Reset
Heat
Heat Manual Reset Manual Reset
Automatic Reset Automatic Reset
Heat
Heat Manual Reset Manual Reset
Automatic Reset Automatic Reset
Heat
Heat Manual Reset Manual Reset
Automatic Reset
See Notes
Below
3A Relay Fixed Potted CF E4HH 0525 AAAA A 6, 8 3A Relay Fixed Potted CF E4JH 0274 AAAA A 6, 8 3A Relay Fixed Potted LF C4HU 0550 AAAA A 6, 8 3A Relay Fixed Potted LF C4JU 0288 AAAA A 6, 8 3A Relay Fixed Potted LF C4HW 0550 AAAA A 6, 8 3A Relay Fixed Potted LF C4JW 0288 AAAA A 6, 8 3A Relay Fixed Potted CF C4HH 0550 AAAA A 6, 8 3A Relay Fixed Potted CF C4JH 0288 AAAA A 6, 8 3A Relay Fixed Potted LF E4HU 0550 AAAA A 6, 8 3A Relay Fixed Potted LF E4JU 0288 AAAA A 6, 8 3A Relay Fixed Potted LF E4HW 0550 AAAA A 6, 8 3A Relay Fixed Potted LF E4JW 0288 AAAA A 6, 8 3A Relay Fixed Potted CF E4HH 0550 AAAA A 6, 8 3A Relay Fixed Potted CF E4JH 0288 AAAA A 6, 8 3A Relay Fixed Potted LF C4HU 0575 AAAA A 6, 8 3A Relay Fixed Potted LF C4JU 0302 AAAA A 6, 8 3A Relay Fixed Potted LF C4HW 0575 AAAA A 6, 8 3A Relay Fixed Potted LF C4JW 0302 AAAA A 6, 8 3A Relay Fixed Potted CF C4HH 0575 AAAA A 6, 8 3A Relay Fixed Potted CF C4JH 0302 AAAA A 6, 8 3A Relay Fixed Potted LF E4HU 0575 AAAA A 6, 8 3A Relay Fixed Potted LF E4JU 0302 AAAA A 6, 8 3A Relay Fixed Potted LF E4HW 0575 AAAA A 6, 8 3A Relay Fixed Potted LF E4JW 0302 AAAA A 6, 8 3A Relay Fixed Potted CF E4HH 0575 AAAA A 6, 8 3A Relay Fixed Potted CF E4JH 0302 AAAA A 6, 8 3A Relay Fixed Potted LF C4HU 0600 AAAA A 6, 8 3A Relay Fixed Potted LF C4JU 0316 AAAA A 6, 8 3A Relay Fixed Potted LF C4HW 0600 AAAA A 6, 8 3A Relay Fixed Potted LF C4JW 0316 AAAA A 6, 8 3A Relay Fixed Potted CF C4HH 0600 AAAA A 6, 8 3A Relay Fixed Potted CF C4JH 0316 AAAA A 6, 8 3A Relay Fixed Potted LF E4HU 0600 AAAA A 6, 8 3A Relay Fixed Potted LF E4JU 0316 AAAA A 6, 8 3A Relay Fixed Potted LF E4HW 0600 AAAA A 6, 8 3A Relay Fixed Potted LF E4JW 0316 AAAA A 6, 8 3A Relay Fixed Potted CF E4HH 0600 AAAA A 6, 8 3A Relay Fixed Potted CF E4JH 0316 AAAA A 6, 8 3A Relay Fixed Potted LF C4HU 0625 AAAA A 6, 8 3A Relay Fixed Potted LF C4JU 0329 AAAA A 6, 8 3A Relay Fixed Potted LF C4HW 0625 AAAA A 6, 8
Watlow Controls 1/31/2005 Page 8
Line
Series 142
142A-3618-1300 120 VAC J t/c 329°C High limit 142A-3618-1400 120 VAC J t/c 625°F On/Off 142A-3618-1400 120 VAC J t/c 329°C On/Off 142A-3618-2200 230 VAC J t/c 625°F High limit 142A-3618-2200 230 VAC J t/c 329°C High limit 142A-3618-2300 230 VAC J t/c 625°F High limit 142A-3618-2300 230 VAC J t/c 329°C High limit 142A-3618-2400 230 VAC J t/c 625°F On/Off 142A-3618-2400 230 VAC J t/c 329°C On/Off 142A-3619-1200 120 VAC K t/c 300°F High limit 142A-3619-1200 120 VAC K t/c 149°C High limit 142A-3619-1300 120 VAC K t/c 300°F High limit 142A-3619-1300 120 VAC K t/c 149°C High limit 142A-3619-1400 120 VAC K t/c 300°F On/Off 142A-3619-1400 120 VAC K t/c 149°C On/Off 142A-3619-2200 230 VAC K t/c 300°F High limit 142A-3619-2200 230 VAC K t/c 149°C High limit 142A-3619-2300 230 VAC K t/c 300°F High limit 142A-3619-2300 230 VAC K t/c 149°C High limit 142A-3619-2400 230 VAC K t/c 300°F On/Off 142A-3619-2400 230 VAC K t/c 149°C On/Off 142A-3620-1200 120 VAC J t/c 675°F High limit 142A-3620-1200 120 VAC J t/c 357°C High limit 142A-3620-1300 120 VAC J t/c 675°F High limit 142A-3620-1300 120 VAC J t/c 357°C High limit 142A-3620-1400 120 VAC J t/c 675°F On/Off 142A-3620-1400 120 VAC J t/c 357°C On/Off 142A-3620-2200 230 VAC J t/c 675°F High limit 142A-3620-2200 230 VAC J t/c 357°C High limit 142A-3620-2300 230 VAC J t/c 675°F High limit 142A-3620-2300 230 VAC J t/c 357°C High limit 142A-3620-2400 230 VAC J t/c 675°F On/Off 142A-3620-2400 230 VAC J t/c 357°C On/Off 142A-3621-1200 120 VAC J t/c 700°F High limit 142A-3621-1200 120 VAC J t/c 371°C High limit 142A-3621-1300 120 VAC J t/c 700°F High limit 142A-3621-1300 120 VAC J t/c 371°C High limit 142A-3621-1400 120 VAC J t/c 700°F On/Off 142A-3621-1400 120 VAC J t/c 371°C On/Off 142A-3621-2200 230 VAC J t/c 700°F High limit 142A-3621-2200 230 VAC J t/c 371°C High limit
Voltage Input Temp Range Control Mode Action Output Set Point Mounting Retrofit
Series 142
Automatic Reset
Heat
Heat Manual Reset Manual Reset
Automatic Reset Automatic Reset
Heat
Heat Manual Reset Manual Reset
Automatic Reset Automatic Reset
Heat
Heat Manual Reset Manual Reset
Automatic Reset Automatic Reset
Heat
Heat Manual Reset Manual Reset
Automatic Reset Automatic Reset
Heat
Heat Manual Reset Manual Reset
Automatic Reset Automatic Reset
Heat
Heat Manual Reset Manual Reset
Automatic Reset Automatic Reset
Heat
Heat Manual Reset Manual Reset
See Notes
Below
3A Relay Fixed Potted LF C4JW 0329 AAAA A 6, 8 3A Relay Fixed Potted CF C4HH 0625 AAAA A 6, 8 3A Relay Fixed Potted CF C4JH 0329 AAAA A 6, 8 3A Relay Fixed Potted LF E4HU 0625 AAAA A 6, 8 3A Relay Fixed Potted LF E4JU 0329 AAAA A 6, 8 3A Relay Fixed Potted LF E4HW 0625 AAAA A 6, 8 3A Relay Fixed Potted LF E4JW 0329 AAAA A 6, 8 3A Relay Fixed Potted CF E4HH 0625 AAAA A 6, 8 3A Relay Fixed Potted CF E4JH 0329 AAAA A 6, 8 3A Relay Fixed Potted LF C4KU 0300 AAAA A 6, 8 3A Relay Fixed Potted LF C4LU 0149 AAAA A 6, 8 3A Relay Fixed Potted LF C4KW 0300 AAAA A 6, 8 3A Relay Fixed Potted LF C4LW 0149 AAAA A 6, 8 3A Relay Fixed Potted CF C4KH 0300 AAAA A 6, 8 3A Relay Fixed Potted CF C4LH 0149 AAAA A 6, 8 3A Relay Fixed Potted LF E4KU 0300 AAAA A 6, 8 3A Relay Fixed Potted LF E4LU 0149 AAAA A 6, 8 3A Relay Fixed Potted LF E4KW 0300 AAAA A 6, 8 3A Relay Fixed Potted LF E4LW 0149 AAAA A 6, 8 3A Relay Fixed Potted CF E4KH 0300 AAAA A 6, 8 3A Relay Fixed Potted CF E4LH 0149 AAAA A 6, 8 3A Relay Fixed Potted LF C4HU 0675 AAAA A 6, 8 3A Relay Fixed Potted LF C4JU 0357 AAAA A 6, 8 3A Relay Fixed Potted LF C4HW 0675 AAAA A 6, 8 3A Relay Fixed Potted LF C4JW 0357 AAAA A 6, 8 3A Relay Fixed Potted CF C4HH 0675 AAAA A 6, 8 3A Relay Fixed Potted CF C4JH 0357 AAAA A 6, 8 3A Relay Fixed Potted LF E4HU 0675 AAAA A 6, 8 3A Relay Fixed Potted LF E4JU 0357 AAAA A 6, 8 3A Relay Fixed Potted LF E4HW 0675 AAAA A 6, 8 3A Relay Fixed Potted LF E4JW 0357 AAAA A 6, 8 3A Relay Fixed Potted CF E4HH 0675 AAAA A 6, 8 3A Relay Fixed Potted CF E4JH 0357 AAAA A 6, 8 3A Relay Fixed Potted LF C4HU 0700 AAAA A 6, 8 3A Relay Fixed Potted LF C4JU 0371 AAAA A 6, 8 3A Relay Fixed Potted LF C4HW 0700 AAAA A 6, 8 3A Relay Fixed Potted LF C4JW 0371 AAAA A 6, 8 3A Relay Fixed Potted CF C4HH 0700 AAAA A 6, 8 3A Relay Fixed Potted CF C4JH 0371 AAAA A 6, 8 3A Relay Fixed Potted LF E4HU 0700 AAAA A 6, 8 3A Relay Fixed Potted LF E4JU 0371 AAAA A 6, 8
Watlow Controls 1/31/2005 Page 9
Line
Series 142
142A-3621-2300 230 VAC J t/c 700°F High limit 142A-3621-2300 230 VAC J t/c 371°C High limit 142A-3621-2400 230 VAC J t/c 700°F On/Off 142A-3621-2400 230 VAC J t/c 371°C On/Off 142A-3622-1200 120 VAC J t/c 725°F High limit 142A-3622-1200 120 VAC J t/c 385°C High limit 142A-3622-1300 120 VAC J t/c 725°F High limit 142A-3622-1300 120 VAC J t/c 385°C High limit 142A-3622-1400 120 VAC J t/c 725°F On/Off 142A-3622-1400 120 VAC J t/c 385°C On/Off 142A-3622-2200 230 VAC J t/c 725°F High limit 142A-3622-2200 230 VAC J t/c 385°C High limit 142A-3622-2300 230 VAC J t/c 725°F High limit 142A-3622-2300 230 VAC J t/c 385°C High limit 142A-3622-2400 230 VAC J t/c 725°F On/Off 142A-3622-2400 230 VAC J t/c 385°C On/Off 142A-3623-1200 120 VAC J t/c 750°F High limit 142A-3623-1200 120 VAC J t/c 399°C High limit 142A-3623-1300 120 VAC J t/c 750°F High limit 142A-3623-1300 120 VAC J t/c 399°C High limit 142A-3623-1400 120 VAC J t/c 750°F On/Off 142A-3623-1400 120 VAC J t/c 399°C On/Off 142A-3623-2200 230 VAC J t/c 750°F High limit 142A-3623-2200 230 VAC J t/c 399°C High limit 142A-3623-2300 230 VAC J t/c 750°F High limit 142A-3623-2300 230 VAC J t/c 399°C High limit 142A-3623-2400 230 VAC J t/c 750°F On/Off 142A-3623-2400 230 VAC J t/c 399°C On/Off 142A-3624-1200 120 VAC J t/c 755°F High limit 142A-3624-1200 120 VAC J t/c 413°C High limit 142A-3624-1300 120 VAC J t/c 755°F High limit 142A-3624-1300 120 VAC J t/c 413°C High limit 142A-3624-1400 120 VAC J t/c 755°F On/Off 142A-3624-1400 120 VAC J t/c 413°C On/Off 142A-3624-2200 230 VAC J t/c 755°F High limit 142A-3624-2200 230 VAC J t/c 413°C High limit 142A-3624-2300 230 VAC J t/c 755°F High limit 142A-3624-2300 230 VAC J t/c 413°C High limit 142A-3624-2400 230 VAC J t/c 755°F On/Off 142A-3624-2400 230 VAC J t/c 413°C On/Off 142A-3625-1200 120 VAC J t/c 800°F High limit
Voltage Input Temp Range Control Mode Action Output Set Point Mounting Retrofit
Series 142
Automatic Reset Automatic Reset
Heat
Heat Manual Reset Manual Reset
Automatic Reset Automatic Reset
Heat
Heat Manual Reset Manual Reset
Automatic Reset Automatic Reset
Heat
Heat Manual Reset Manual Reset
Automatic Reset Automatic Reset
Heat
Heat Manual Reset Manual Reset
Automatic Reset Automatic Reset
Heat
Heat Manual Reset Manual Reset
Automatic Reset Automatic Reset
Heat
Heat Manual Reset Manual Reset
Automatic Reset Automatic Reset
Heat
Heat Manual Reset
See Notes
Below
3A Relay Fixed Potted LF E4HW 0700 AAAA A 6, 8 3A Relay Fixed Potted LF E4JW 0371 AAAA A 6, 8 3A Relay Fixed Potted CF E4HH 0700 AAAA A 6, 8 3A Relay Fixed Potted CF E4JH 0371 AAAA A 6, 8 3A Relay Fixed Potted LF C4HU 0725 AAAA A 6, 8 3A Relay Fixed Potted LF C4JU 0385 AAAA A 6, 8 3A Relay Fixed Potted LF C4HW 0725 AAAA A 6, 8 3A Relay Fixed Potted LF C4JW 0385 AAAA A 6, 8 3A Relay Fixed Potted CF C4HH 0725 AAAA A 6, 8 3A Relay Fixed Potted CF C4JH 0385 AAAA A 6, 8 3A Relay Fixed Potted LF E4HU 0725 AAAA A 6, 8 3A Relay Fixed Potted LF E4JU 0385 AAAA A 6, 8 3A Relay Fixed Potted LF E4HW 0725 AAAA A 6, 8 3A Relay Fixed Potted LF E4JW 0385 AAAA A 6, 8 3A Relay Fixed Potted CF E4HH 0725 AAAA A 6, 8 3A Relay Fixed Potted CF E4JH 0385 AAAA A 6, 8 3A Relay Fixed Potted LF C4HU 0750 AAAA A 6, 8 3A Relay Fixed Potted LF C4JU 0399 AAAA A 6, 8 3A Relay Fixed Potted LF C4HW 0750 AAAA A 6, 8 3A Relay Fixed Potted LF C4JW 0399 AAAA A 6, 8 3A Relay Fixed Potted CF C4HH 0750 AAAA A 6, 8 3A Relay Fixed Potted CF C4JH 0399 AAAA A 6, 8 3A Relay Fixed Potted LF E4HU 0750 AAAA A 6, 8 3A Relay Fixed Potted LF E4JU 0399 AAAA A 6, 8 3A Relay Fixed Potted LF E4HW 0750 AAAA A 6, 8 3A Relay Fixed Potted LF E4JW 0399 AAAA A 6, 8 3A Relay Fixed Potted CF E4HH 0750 AAAA A 6, 8 3A Relay Fixed Potted CF E4JH 0399 AAAA A 6, 8 3A Relay Fixed Potted LF C4HU 0755 AAAA A 6, 8 3A Relay Fixed Potted LF C4JU 0413 AAAA A 6, 8 3A Relay Fixed Potted LF C4HW 0755 AAAA A 6, 8 3A Relay Fixed Potted LF C4JW 0413 AAAA A 6, 8 3A Relay Fixed Potted CF C4HH 0755 AAAA A 6, 8 3A Relay Fixed Potted CF C4JH 0413 AAAA A 6, 8 3A Relay Fixed Potted LF E4HU 0755 AAAA A 6, 8 3A Relay Fixed Potted LF E4JU 0413 AAAA A 6, 8 3A Relay Fixed Potted LF E4HW 0755 AAAA A 6, 8 3A Relay Fixed Potted LF E4JW 0413 AAAA A 6, 8 3A Relay Fixed Potted CF E4HH 0755 AAAA A 6, 8 3A Relay Fixed Potted CF E4JH 0413 AAAA A 6, 8 3A Relay Fixed Potted LF C4HU 0800 AAAA A 6, 8
Watlow Controls 1/31/2005 Page 10
Line
Series 142
142A-3625-1200 120 VAC J t/c 427°C High limit 142A-3625-1300 120 VAC J t/c 800°F High limit 142A-3625-1300 120 VAC J t/c 427°C High limit 142A-3625-1400 120 VAC J t/c 800°F On/Off 142A-3625-1400 120 VAC J t/c 427°C On/Off 142A-3625-2200 230 VAC J t/c 800°F High limit 142A-3625-2200 230 VAC J t/c 427°C High limit 142A-3625-2300 230 VAC J t/c 800°F High limit 142A-3625-2300 230 VAC J t/c 427°C High limit 142A-3625-2400 230 VAC J t/c 800°F On/Off 142A-3625-2400 230 VAC J t/c 427°C On/Off 142A-3626-1200 120 VAC J t/c 50°F High limit 142A-3626-1200 120 VAC J t/c 10°C High limit 142A-3626-1300 120 VAC J t/c 50°F High limit 142A-3626-1300 120 VAC J t/c 10°C High limit 142A-3626-1400 120 VAC J t/c 50°F On/Off 142A-3626-1400 120 VAC J t/c 10°C On/Off 142A-3626-2200 230 VAC J t/c 50°F High limit 142A-3626-2200 230 VAC J t/c 10°C High limit 142A-3626-2300 230 VAC J t/c 50°F High limit 142A-3626-2300 230 VAC J t/c 10°C High limit 142A-3626-2400 230 VAC J t/c 50°F On/Off 142A-3626-2400 230 VAC J t/c 10°C On/Off 142A-3627-1200 120 VAC J t/c 850°F High limit 142A-3627-1200 120 VAC J t/c 454°C High limit 142A-3627-1300 120 VAC J t/c 850°F High limit 142A-3627-1300 120 VAC J t/c 454°C High limit 142A-3627-1400 120 VAC J t/c 850°F On/Off 142A-3627-1400 120 VAC J t/c 454°C On/Off 142A-3627-2200 230 VAC J t/c 850°F High limit 142A-3627-2200 230 VAC J t/c 454°C High limit 142A-3627-2300 230 VAC J t/c 850°F High limit 142A-3627-2300 230 VAC J t/c 454°C High limit 142A-3627-2400 230 VAC J t/c 850°F On/Off 142A-3627-2400 230 VAC J t/c 454°C On/Off 142A-3628-1200 120 VAC J t/c 875°F High limit 142A-3628-1200 120 VAC J t/c 468°C High limit 142A-3628-1300 120 VAC J t/c 875°F High limit 142A-3628-1300 120 VAC J t/c 468°C High limit 142A-3628-1400 120 VAC J t/c 875°F On/Off 142A-3628-1400 120 VAC J t/c 468°C On/Off
Voltage Input Temp Range Control Mode Action Output Set Point Mounting Retrofit
Series 142
Manual Reset
Automatic Reset Automatic Reset
Heat
Heat Manual Reset Manual Reset
Automatic Reset Automatic Reset
Heat
Heat Manual Reset Manual Reset
Automatic Reset Automatic Reset
Heat
Heat Manual Reset Manual Reset
Automatic Reset Automatic Reset
Heat
Heat Manual Reset Manual Reset
Automatic Reset Automatic Reset
Heat
Heat Manual Reset Manual Reset
Automatic Reset Automatic Reset
Heat
Heat Manual Reset Manual Reset
Automatic Reset Automatic Reset
Heat
Heat
See Notes
Below
3A Relay Fixed Potted LF C4JU 0427 AAAA A 6, 8 3A Relay Fixed Potted LF C4HW 0800 AAAA A 6, 8 3A Relay Fixed Potted LF C4JW 0427 AAAA A 6, 8 3A Relay Fixed Potted CF C4HH 0800 AAAA A 6, 8 3A Relay Fixed Potted CF C4JH 0427 AAAA A 6, 8 3A Relay Fixed Potted LF E4HU 0800 AAAA A 6, 8 3A Relay Fixed Potted LF E4JU 0427 AAAA A 6, 8 3A Relay Fixed Potted LF E4HW 0800 AAAA A 6, 8 3A Relay Fixed Potted LF E4JW 0427 AAAA A 6, 8 3A Relay Fixed Potted CF E4HH 0800 AAAA A 6, 8 3A Relay Fixed Potted CF E4JH 0427 AAAA A 6, 8 3A Relay Fixed Potted LF C4HU 0050 AAAA A 6, 8 3A Relay Fixed Potted LF C4JU 0010 AAAA A 6, 8 3A Relay Fixed Potted LF C4HW 0050 AAAA A 6, 8 3A Relay Fixed Potted LF C4JW 0010 AAAA A 6, 8 3A Relay Fixed Potted CF C4HH 0050 AAAA A 6, 8 3A Relay Fixed Potted CF C4JH 0010 AAAA A 6, 8 3A Relay Fixed Potted LF E4HU 0050 AAAA A 6, 8 3A Relay Fixed Potted LF E4JU 0010 AAAA A 6, 8 3A Relay Fixed Potted LF E4HW 0050 AAAA A 6, 8 3A Relay Fixed Potted LF E4JW 0010 AAAA A 6, 8 3A Relay Fixed Potted CF E4HH 0050 AAAA A 6, 8 3A Relay Fixed Potted CF E4JH 0010 AAAA A 6, 8 3A Relay Fixed Potted LF C4HU 0850 AAAA A 6, 8 3A Relay Fixed Potted LF C4JU 0454 AAAA A 6, 8 3A Relay Fixed Potted LF C4HW 0850 AAAA A 6, 8 3A Relay Fixed Potted LF C4JW 0454 AAAA A 6, 8 3A Relay Fixed Potted CF C4HH 0850 AAAA A 6, 8 3A Relay Fixed Potted CF C4JH 0454 AAAA A 6, 8 3A Relay Fixed Potted LF E4HU 0850 AAAA A 6, 8 3A Relay Fixed Potted LF E4JU 0454 AAAA A 6, 8 3A Relay Fixed Potted LF E4HW 0850 AAAA A 6, 8 3A Relay Fixed Potted LF E4JW 0454 AAAA A 6, 8 3A Relay Fixed Potted CF E4HH 0850 AAAA A 6, 8 3A Relay Fixed Potted CF E4JH 0454 AAAA A 6, 8 3A Relay Fixed Potted LF C4HU 0875 AAAA A 6, 8 3A Relay Fixed Potted LF C4JU 0468 AAAA A 6, 8 3A Relay Fixed Potted LF C4HW 0875 AAAA A 6, 8 3A Relay Fixed Potted LF C4JW 0468 AAAA A 6, 8 3A Relay Fixed Potted CF C4HH 0875 AAAA A 6, 8 3A Relay Fixed Potted CF C4JH 0468 AAAA A 6, 8
Watlow Controls 1/31/2005 Page 11
Line
Series 142
142A-3628-2200 230 VAC J t/c 875°F High limit 142A-3628-2200 230 VAC J t/c 468°C High limit 142A-3628-2300 230 VAC J t/c 875°F High limit 142A-3628-2300 230 VAC J t/c 468°C High limit 142A-3628-2400 230 VAC J t/c 875°F On/Off 142A-3628-2400 230 VAC J t/c 468°C On/Off 142A-3629-1200 120 VAC K t/c 800°F High limit 142A-3629-1200 120 VAC K t/c 427°C High limit 142A-3629-1300 120 VAC K t/c 800°F High limit 142A-3629-1300 120 VAC K t/c 427°C High limit 142A-3629-1400 120 VAC K t/c 800°F On/Off 142A-3629-1400 120 VAC K t/c 427°C On/Off 142A-3629-2200 230 VAC K t/c 800°F High limit 142A-3629-2200 230 VAC K t/c 427°C High limit 142A-3629-2300 230 VAC K t/c 800°F High limit 142A-3629-2300 230 VAC K t/c 427°C High limit 142A-3629-2400 230 VAC K t/c 800°F On/Off 142A-3629-2400 230 VAC K t/c 427°C On/Off 142A-3630-1200 120 VAC J t/c 925°F High limit 142A-3630-1200 120 VAC J t/c 496°C High limit 142A-3630-1300 120 VAC J t/c 925°F High limit 142A-3630-1300 120 VAC J t/c 496°C High limit 142A-3630-1400 120 VAC J t/c 925°F On/Off 142A-3630-1400 120 VAC J t/c 496°C On/Off 142A-3630-2200 230 VAC J t/c 925°F High limit 142A-3630-2200 230 VAC J t/c 496°C High limit 142A-3630-2300 230 VAC J t/c 925°F High limit 142A-3630-2300 230 VAC J t/c 496°C High limit 142A-3630-2400 230 VAC J t/c 925°F On/Off 142A-3630-2400 230 VAC J t/c 496°C On/Off 142A-3631-1200 120 VAC J t/c 950°F High limit 142A-3631-1200 120 VAC J t/c 510°C High limit 142A-3631-1300 120 VAC J t/c 950°F High limit 142A-3631-1300 120 VAC J t/c 510°C High limit 142A-3631-1400 120 VAC J t/c 950°F On/Off 142A-3631-1400 120 VAC J t/c 510°C On/Off 142A-3631-2200 230 VAC J t/c 950°F High limit 142A-3631-2200 230 VAC J t/c 510°C High limit 142A-3631-2300 230 VAC J t/c 950°F High limit 142A-3631-2300 230 VAC J t/c 510°C High limit 142A-3631-2400 230 VAC J t/c 950°F On/Off
Voltage Input Temp Range Control Mode Action Output Set Point Mounting Retrofit
Series 142
Manual Reset Manual Reset
Automatic Reset Automatic Reset
Heat
Heat Manual Reset Manual Reset
Automatic Reset Automatic Reset
Heat
Heat Manual Reset Manual Reset
Automatic Reset Automatic Reset
Heat
Heat Manual Reset Manual Reset
Automatic Reset Automatic Reset
Heat
Heat Manual Reset Manual Reset
Automatic Reset Automatic Reset
Heat
Heat Manual Reset Manual Reset
Automatic Reset Automatic Reset
Heat
Heat Manual Reset Manual Reset
Automatic Reset Automatic Reset
Heat
See Notes
Below
3A Relay Fixed Potted LF E4HU 0875 AAAA A 6, 8 3A Relay Fixed Potted LF E4JU 0468 AAAA A 6, 8 3A Relay Fixed Potted LF E4HW 0875 AAAA A 6, 8 3A Relay Fixed Potted LF E4JW 0468 AAAA A 6, 8 3A Relay Fixed Potted CF E4HH 0875 AAAA A 6, 8 3A Relay Fixed Potted CF E4JH 0468 AAAA A 6, 8 3A Relay Fixed Potted LF C4KU 0800 AAAA A 6, 8 3A Relay Fixed Potted LF C4LU 0427 AAAA A 6, 8 3A Relay Fixed Potted LF C4KW 0800 AAAA A 6, 8 3A Relay Fixed Potted LF C4LW 0427 AAAA A 6, 8 3A Relay Fixed Potted CF C4KH 0800 AAAA A 6, 8 3A Relay Fixed Potted CF C4LH 0427 AAAA A 6, 8 3A Relay Fixed Potted LF E4KU 0800 AAAA A 6, 8 3A Relay Fixed Potted LF E4LU 0427 AAAA A 6, 8 3A Relay Fixed Potted LF E4KW 0800 AAAA A 6, 8 3A Relay Fixed Potted LF E4LW 0427 AAAA A 6, 8 3A Relay Fixed Potted CF E4KH 0800 AAAA A 6, 8 3A Relay Fixed Potted CF E4LH 0427 AAAA A 6, 8 3A Relay Fixed Potted LF C4HU 0925 AAAA A 6, 8 3A Relay Fixed Potted LF C4JU 0496 AAAA A 6, 8 3A Relay Fixed Potted LF C4HW 0925 AAAA A 6, 8 3A Relay Fixed Potted LF C4JW 0496 AAAA A 6, 8 3A Relay Fixed Potted CF C4HH 0925 AAAA A 6, 8 3A Relay Fixed Potted CF C4JH 0496 AAAA A 6, 8 3A Relay Fixed Potted LF E4HU 0925 AAAA A 6, 8 3A Relay Fixed Potted LF E4JU 0496 AAAA A 6, 8 3A Relay Fixed Potted LF E4HW 0925 AAAA A 6, 8 3A Relay Fixed Potted LF E4JW 0496 AAAA A 6, 8 3A Relay Fixed Potted CF E4HH 0925 AAAA A 6, 8 3A Relay Fixed Potted CF E4JH 0496 AAAA A 6, 8 3A Relay Fixed Potted LF C4HU 0950 AAAA A 6, 8 3A Relay Fixed Potted LF C4JU 0510 AAAA A 6, 8 3A Relay Fixed Potted LF C4HW 0950 AAAA A 6, 8 3A Relay Fixed Potted LF C4JW 0510 AAAA A 6, 8 3A Relay Fixed Potted CF C4HH 0950 AAAA A 6, 8 3A Relay Fixed Potted CF C4JH 0510 AAAA A 6, 8 3A Relay Fixed Potted LF E4HU 0950 AAAA A 6, 8 3A Relay Fixed Potted LF E4JU 0510 AAAA A 6, 8 3A Relay Fixed Potted LF E4HW 0950 AAAA A 6, 8 3A Relay Fixed Potted LF E4JW 0510 AAAA A 6, 8 3A Relay Fixed Potted CF E4HH 0950 AAAA A 6, 8
Watlow Controls 1/31/2005 Page 12
Line
Series 142
142A-3631-2400 230 VAC J t/c 510°C On/Off 142A-3632-1200 120 VAC J t/c 975°F High limit 142A-3632-1200 120 VAC J t/c 524°C High limit 142A-3632-1300 120 VAC J t/c 975°F High limit 142A-3632-1300 120 VAC J t/c 524°C High limit 142A-3632-1400 120 VAC J t/c 975°F On/Off 142A-3632-1400 120 VAC J t/c 524°C On/Off 142A-3632-2200 230 VAC J t/c 975°F High limit 142A-3632-2200 230 VAC J t/c 524°C High limit 142A-3632-2300 230 VAC J t/c 975°F High limit 142A-3632-2300 230 VAC J t/c 524°C High limit 142A-3632-2400 230 VAC J t/c 975°F On/Off 142A-3632-2400 230 VAC J t/c 524°C On/Off 142A-3633-1200 120 VAC J t/c 1000°F High limit 142A-3633-1200 120 VAC J t/c 538°C High limit 142A-3633-1300 120 VAC J t/c 1000°F High limit 142A-3633-1300 120 VAC J t/c 538°C High limit 142A-3633-1400 120 VAC J t/c 1000°F On/Off 142A-3633-1400 120 VAC J t/c 538°C On/Off 142A-3633-2200 230 VAC J t/c 1000°F High limit 142A-3633-2200 230 VAC J t/c 538°C High limit 142A-3633-2300 230 VAC J t/c 1000°F High limit 142A-3633-2300 230 VAC J t/c 538°C High limit 142A-3633-2400 230 VAC J t/c 1000°F On/Off 142A-3633-2400 230 VAC J t/c 538°C On/Off 142A-3634-1200 120 VAC K t/c 1050°F High limit 142A-3634-1200 120 VAC K t/c 566°C High limit 142A-3634-1300 120 VAC K t/c 1050°F High limit 142A-3634-1300 120 VAC K t/c 566°C High limit 142A-3634-1400 120 VAC K t/c 1050°F On/Off 142A-3634-1400 120 VAC K t/c 566°C On/Off 142A-3634-2200 230 VAC K t/c 1050°F High limit 142A-3634-2200 230 VAC K t/c 566°C High limit 142A-3634-2300 230 VAC K t/c 1050°F High limit 142A-3634-2300 230 VAC K t/c 566°C High limit 142A-3634-2400 230 VAC K t/c 1050°F On/Off 142A-3634-2400 230 VAC K t/c 566°C On/Off 142A-3635-1200 120 VAC K t/c 1100°F High limit 142A-3635-1200 120 VAC K t/c 537°C High limit 142A-3635-1300 120 VAC K t/c 1100°F High limit 142A-3635-1300 120 VAC K t/c 537°C High limit
Voltage Input Temp Range Control Mode Action Output Set Point Mounting Retrofit
Series 142
Heat Manual Reset Manual Reset
Automatic Reset Automatic Reset
Heat
Heat Manual Reset Manual Reset
Automatic Reset Automatic Reset
Heat
Heat Manual Reset Manual Reset
Automatic Reset Automatic Reset
Heat
Heat Manual Reset Manual Reset
Automatic Reset Automatic Reset
Heat
Heat Manual Reset Manual Reset
Automatic Reset Automatic Reset
Heat
Heat Manual Reset Manual Reset
Automatic Reset Automatic Reset
Heat
Heat Manual Reset Manual Reset
Automatic Reset Automatic Reset
See Notes
Below
3A Relay Fixed Potted CF E4JH 0510 AAAA A 6, 8 3A Relay Fixed Potted LF C4HU 0975 AAAA A 6, 8 3A Relay Fixed Potted LF C4JU 0524 AAAA A 6, 8 3A Relay Fixed Potted LF C4HW 0975 AAAA A 6, 8 3A Relay Fixed Potted LF C4JW 0524 AAAA A 6, 8 3A Relay Fixed Potted CF C4HH 0975 AAAA A 6, 8 3A Relay Fixed Potted CF C4JH 0524 AAAA A 6, 8 3A Relay Fixed Potted LF E4HU 0975 AAAA A 6, 8 3A Relay Fixed Potted LF E4JU 0524 AAAA A 6, 8 3A Relay Fixed Potted LF E4HW 0975 AAAA A 6, 8 3A Relay Fixed Potted LF E4JW 0524 AAAA A 6, 8 3A Relay Fixed Potted CF E4HH 0975 AAAA A 6, 8 3A Relay Fixed Potted CF E4JH 0524 AAAA A 6, 8 3A Relay Fixed Potted LF C4HU 1000 AAAA A 6, 8 3A Relay Fixed Potted LF C4JU 0538 AAAA A 6, 8 3A Relay Fixed Potted LF C4HW 1000 AAAA A 6, 8 3A Relay Fixed Potted LF C4JW 0538 AAAA A 6, 8 3A Relay Fixed Potted CF C4HH 1000 AAAA A 6, 8 3A Relay Fixed Potted CF C4JH 0538 AAAA A 6, 8 3A Relay Fixed Potted LF E4HU 1000 AAAA A 6, 8 3A Relay Fixed Potted LF E4JU 0538 AAAA A 6, 8 3A Relay Fixed Potted LF E4HW 1000 AAAA A 6, 8 3A Relay Fixed Potted LF E4JW 0538 AAAA A 6, 8 3A Relay Fixed Potted CF E4HH 1000 AAAA A 6, 8 3A Relay Fixed Potted CF E4JH 0538 AAAA A 6, 8 3A Relay Fixed Potted LF C4KU 1050 AAAA A 6, 8 3A Relay Fixed Potted LF C4LU 0566 AAAA A 6, 8 3A Relay Fixed Potted LF C4KW 1050 AAAA A 6, 8 3A Relay Fixed Potted LF C4LW 0566 AAAA A 6, 8 3A Relay Fixed Potted CF C4KH 1050 AAAA A 6, 8 3A Relay Fixed Potted CF C4LH 0566 AAAA A 6, 8 3A Relay Fixed Potted LF E4KU 1050 AAAA A 6, 8 3A Relay Fixed Potted LF E4LU 0566 AAAA A 6, 8 3A Relay Fixed Potted LF E4KW 1050 AAAA A 6, 8 3A Relay Fixed Potted LF E4LW 0566 AAAA A 6, 8 3A Relay Fixed Potted CF E4KH 1050 AAAA A 6, 8 3A Relay Fixed Potted CF E4LH 0566 AAAA A 6, 8 3A Relay Fixed Potted LF C4KU 1100 AAAA A 6, 8 3A Relay Fixed Potted LF C4LU 0537 AAAA A 6, 8 3A Relay Fixed Potted LF C4KW 1100 AAAA A 6, 8 3A Relay Fixed Potted LF C4LW 0537 AAAA A 6, 8
Watlow Controls 1/31/2005 Page 13
Line
Series 142
142A-3635-1400 120 VAC K t/c 1100°F On/Off 142A-3635-1400 120 VAC K t/c 537°C On/Off 142A-3635-2200 230 VAC K t/c 1100°F High limit 142A-3635-2200 230 VAC K t/c 537°C High limit 142A-3635-2300 230 VAC K t/c 1100°F High limit 142A-3635-2300 230 VAC K t/c 537°C High limit 142A-3635-2400 230 VAC K t/c 1100°F On/Off 142A-3635-2400 230 VAC K t/c 537°C On/Off 142A-3636-1200 120 VAC K t/c 1150°F High limit 142A-3636-1200 120 VAC K t/c 621°C High limit 142A-3636-1300 120 VAC K t/c 1150°F High limit 142A-3636-1300 120 VAC K t/c 621°C High limit 142A-3636-1400 120 VAC K t/c 1150°F On/Off 142A-3636-1400 120 VAC K t/c 621°C On/Off 142A-3636-2200 230 VAC K t/c 1150°F High limit 142A-3636-2200 230 VAC K t/c 621°C High limit 142A-3636-2300 230 VAC K t/c 1150°F High limit 142A-3636-2300 230 VAC K t/c 621°C High limit 142A-3636-2400 230 VAC K t/c 1150°F On/Off 142A-3636-2400 230 VAC K t/c 621°C On/Off 142A-3637-1200 120 VAC K t/c 1200°F High limit 142A-3637-1200 120 VAC K t/c 649°C High limit 142A-3637-1300 120 VAC K t/c 1200°F High limit 142A-3637-1300 120 VAC K t/c 649°C High limit 142A-3637-1400 120 VAC K t/c 1200°F On/Off 142A-3637-1400 120 VAC K t/c 649°C On/Off 142A-3637-2200 230 VAC K t/c 1200°F High limit 142A-3637-2200 230 VAC K t/c 649°C High limit 142A-3637-2300 230 VAC K t/c 1200°F High limit 142A-3637-2300 230 VAC K t/c 649°C High limit 142A-3637-2400 230 VAC K t/c 1200°F On/Off 142A-3637-2400 230 VAC K t/c 649°C On/Off 142A-3638-1200 120 VAC K t/c 1250°F High limit 142A-3638-1200 120 VAC K t/c 677°C High limit 142A-3638-1300 120 VAC K t/c 1250°F High limit 142A-3638-1300 120 VAC K t/c 677°C High limit 142A-3638-1400 120 VAC K t/c 1250°F On/Off 142A-3638-1400 120 VAC K t/c 677°C On/Off 142A-3638-2200 230 VAC K t/c 1250°F High limit 142A-3638-2200 230 VAC K t/c 677°C High limit 142A-3638-2300 230 VAC K t/c 1250°F High limit
Voltage Input Temp Range Control Mode Action Output Set Point Mounting Retrofit
Series 142
Heat
Heat Manual Reset Manual Reset
Automatic Reset Automatic Reset
Heat
Heat Manual Reset Manual Reset
Automatic Reset Automatic Reset
Heat
Heat Manual Reset Manual Reset
Automatic Reset Automatic Reset
Heat
Heat Manual Reset Manual Reset
Automatic Reset Automatic Reset
Heat
Heat Manual Reset Manual Reset
Automatic Reset Automatic Reset
Heat
Heat Manual Reset Manual Reset
Automatic Reset Automatic Reset
Heat
Heat Manual Reset Manual Reset
Automatic Reset
See Notes
Below
3A Relay Fixed Potted CF C4KH 1100 AAAA A 6, 8 3A Relay Fixed Potted CF C4LH 0537 AAAA A 6, 8 3A Relay Fixed Potted LF E4KU 1100 AAAA A 6, 8 3A Relay Fixed Potted LF E4LU 0537 AAAA A 6, 8 3A Relay Fixed Potted LF E4KW 1100 AAAA A 6, 8 3A Relay Fixed Potted LF E4LW 0537 AAAA A 6, 8 3A Relay Fixed Potted CF E4KH 1100 AAAA A 6, 8 3A Relay Fixed Potted CF E4LH 0537 AAAA A 6, 8 3A Relay Fixed Potted LF C4KU 1150 AAAA A 6, 8 3A Relay Fixed Potted LF C4LU 0621 AAAA A 6, 8 3A Relay Fixed Potted LF C4KW 1150 AAAA A 6, 8 3A Relay Fixed Potted LF C4LW 0621 AAAA A 6, 8 3A Relay Fixed Potted CF C4KH 1150 AAAA A 6, 8 3A Relay Fixed Potted CF C4LH 0621 AAAA A 6, 8 3A Relay Fixed Potted LF E4KU 1150 AAAA A 6, 8 3A Relay Fixed Potted LF E4LU 0621 AAAA A 6, 8 3A Relay Fixed Potted LF E4KW 1150 AAAA A 6, 8 3A Relay Fixed Potted LF E4LW 0621 AAAA A 6, 8 3A Relay Fixed Potted CF E4KH 1150 AAAA A 6, 8 3A Relay Fixed Potted CF E4LH 0621 AAAA A 6, 8 3A Relay Fixed Potted LF C4KU 1200 AAAA A 6, 8 3A Relay Fixed Potted LF C4LU 0649 AAAA A 6, 8 3A Relay Fixed Potted LF C4KW 1200 AAAA A 6, 8 3A Relay Fixed Potted LF C4LW 0649 AAAA A 6, 8 3A Relay Fixed Potted CF C4KH 1200 AAAA A 6, 8 3A Relay Fixed Potted CF C4LH 0649 AAAA A 6, 8 3A Relay Fixed Potted LF E4KU 1200 AAAA A 6, 8 3A Relay Fixed Potted LF E4LU 0649 AAAA A 6, 8 3A Relay Fixed Potted LF E4KW 1200 AAAA A 6, 8 3A Relay Fixed Potted LF E4LW 0649 AAAA A 6, 8 3A Relay Fixed Potted CF E4KH 1200 AAAA A 6, 8 3A Relay Fixed Potted CF E4LH 0649 AAAA A 6, 8 3A Relay Fixed Potted LF C4KU 1250 AAAA A 6, 8 3A Relay Fixed Potted LF C4LU 0677 AAAA A 6, 8 3A Relay Fixed Potted LF C4KW 1250 AAAA A 6, 8 3A Relay Fixed Potted LF C4LW 0677 AAAA A 6, 8 3A Relay Fixed Potted CF C4KH 1250 AAAA A 6, 8 3A Relay Fixed Potted CF C4LH 0677 AAAA A 6, 8 3A Relay Fixed Potted LF E4KU 1250 AAAA A 6, 8 3A Relay Fixed Potted LF E4LU 0677 AAAA A 6, 8 3A Relay Fixed Potted LF E4KW 1250 AAAA A 6, 8
Watlow Controls 1/31/2005 Page 14
Line
Series 142
142A-3638-2300 230 VAC K t/c 677°C High limit 142A-3638-2400 230 VAC K t/c 1250°F On/Off 142A-3638-2400 230 VAC K t/c 677°C On/Off 142A-3639-1200 120 VAC K t/c 1300°F High limit 142A-3639-1200 120 VAC K t/c 704°C High limit 142A-3639-1300 120 VAC K t/c 1300°F High limit 142A-3639-1300 120 VAC K t/c 704°C High limit 142A-3639-1400 120 VAC K t/c 1300°F On/Off 142A-3639-1400 120 VAC K t/c 704°C On/Off 142A-3639-2200 230 VAC K t/c 1300°F High limit 142A-3639-2200 230 VAC K t/c 704°C High limit 142A-3639-2300 230 VAC K t/c 1300°F High limit 142A-3639-2300 230 VAC K t/c 704°C High limit 142A-3639-2400 230 VAC K t/c 1300°F On/Off 142A-3639-2400 230 VAC K t/c 704°C On/Off 142A-3640-1200 120 VAC K t/c 1350°F High limit 142A-3640-1200 120 VAC K t/c 732°C High limit 142A-3640-1300 120 VAC K t/c 1350°F High limit 142A-3640-1300 120 VAC K t/c 732°C High limit 142A-3640-1400 120 VAC K t/c 1350°F On/Off 142A-3640-1400 120 VAC K t/c 732°C On/Off 142A-3640-2200 230 VAC K t/c 1350°F High limit 142A-3640-2200 230 VAC K t/c 732°C High limit 142A-3640-2300 230 VAC K t/c 1350°F High limit 142A-3640-2300 230 VAC K t/c 732°C High limit 142A-3640-2400 230 VAC K t/c 1350°F On/Off 142A-3640-2400 230 VAC K t/c 732°C On/Off 142A-3641-1200 120 VAC K t/c 1400°F High limit 142A-3641-1200 120 VAC K t/c 760°C High limit 142A-3641-1300 120 VAC K t/c 1400°F High limit 142A-3641-1300 120 VAC K t/c 760°C High limit 142A-3641-1400 120 VAC K t/c 1400°F On/Off 142A-3641-1400 120 VAC K t/c 760°C On/Off 142A-3641-2200 230 VAC K t/c 1400°F High limit 142A-3641-2200 230 VAC K t/c 760°C High limit 142A-3641-2300 230 VAC K t/c 1400°F High limit 142A-3641-2300 230 VAC K t/c 760°C High limit 142A-3641-2400 230 VAC K t/c 1400°F On/Off 142A-3641-2400 230 VAC K t/c 760°C On/Off 142A-3642-1200 120 VAC K t/c 1450°F High limit 142A-3642-1200 120 VAC K t/c 788°C High limit
Voltage Input Temp Range Control Mode Action Output Set Point Mounting Retrofit
Series 142
Automatic Reset
Heat
Heat Manual Reset Manual Reset
Automatic Reset Automatic Reset
Heat
Heat Manual Reset Manual Reset
Automatic Reset Automatic Reset
Heat
Heat Manual Reset Manual Reset
Automatic Reset Automatic Reset
Heat
Heat Manual Reset Manual Reset
Automatic Reset Automatic Reset
Heat
Heat Manual Reset Manual Reset
Automatic Reset Automatic Reset
Heat
Heat Manual Reset Manual Reset
Automatic Reset Automatic Reset
Heat
Heat Manual Reset Manual Reset
See Notes
Below
3A Relay Fixed Potted LF E4LW 0677 AAAA A 6, 8 3A Relay Fixed Potted CF E4KH 1250 AAAA A 6, 8 3A Relay Fixed Potted CF E4LH 0677 AAAA A 6, 8 3A Relay Fixed Potted LF C4KU 1300 AAAA A 6, 8 3A Relay Fixed Potted LF C4LU 0704 AAAA A 6, 8 3A Relay Fixed Potted LF C4KW 1300 AAAA A 6, 8 3A Relay Fixed Potted LF C4LW 0704 AAAA A 6, 8 3A Relay Fixed Potted CF C4KH 1300 AAAA A 6, 8 3A Relay Fixed Potted CF C4LH 0704 AAAA A 6, 8 3A Relay Fixed Potted LF E4KU 1300 AAAA A 6, 8 3A Relay Fixed Potted LF E4LU 0704 AAAA A 6, 8 3A Relay Fixed Potted LF E4KW 1300 AAAA A 6, 8 3A Relay Fixed Potted LF E4LW 0704 AAAA A 6, 8 3A Relay Fixed Potted CF E4KH 1300 AAAA A 6, 8 3A Relay Fixed Potted CF E4LH 0704 AAAA A 6, 8 3A Relay Fixed Potted LF C4KU 1350 AAAA A 6, 8 3A Relay Fixed Potted LF C4LU 0732 AAAA A 6, 8 3A Relay Fixed Potted LF C4KW 1350 AAAA A 6, 8 3A Relay Fixed Potted LF C4LW 0732 AAAA A 6, 8 3A Relay Fixed Potted CF C4KH 1350 AAAA A 6, 8 3A Relay Fixed Potted CF C4LH 0732 AAAA A 6, 8 3A Relay Fixed Potted LF E4KU 1350 AAAA A 6, 8 3A Relay Fixed Potted LF E4LU 0732 AAAA A 6, 8 3A Relay Fixed Potted LF E4KW 1350 AAAA A 6, 8 3A Relay Fixed Potted LF E4LW 0732 AAAA A 6, 8 3A Relay Fixed Potted CF E4KH 1350 AAAA A 6, 8 3A Relay Fixed Potted CF E4LH 0732 AAAA A 6, 8 3A Relay Fixed Potted LF C4KU 1400 AAAA A 6, 8 3A Relay Fixed Potted LF C4LU 0760 AAAA A 6, 8 3A Relay Fixed Potted LF C4KW 1400 AAAA A 6, 8 3A Relay Fixed Potted LF C4LW 0760 AAAA A 6, 8 3A Relay Fixed Potted CF C4KH 1400 AAAA A 6, 8 3A Relay Fixed Potted CF C4LH 0760 AAAA A 6, 8 3A Relay Fixed Potted LF E4KU 1400 AAAA A 6, 8 3A Relay Fixed Potted LF E4LU 0760 AAAA A 6, 8 3A Relay Fixed Potted LF E4KW 1400 AAAA A 6, 8 3A Relay Fixed Potted LF E4LW 0760 AAAA A 6, 8 3A Relay Fixed Potted CF E4KH 1400 AAAA A 6, 8 3A Relay Fixed Potted CF E4LH 0760 AAAA A 6, 8 3A Relay Fixed Potted LF C4KU 1450 AAAA A 6, 8 3A Relay Fixed Potted LF C4LU 0788 AAAA A 6, 8
Watlow Controls 1/31/2005 Page 15
Line
Series 142
142A-3642-1300 120 VAC K t/c 1450°F High limit 142A-3642-1300 120 VAC K t/c 788°C High limit 142A-3642-1400 120 VAC K t/c 1450°F On/Off 142A-3642-1400 120 VAC K t/c 788°C On/Off 142A-3642-2200 230 VAC K t/c 1450°F High limit 142A-3642-2200 230 VAC K t/c 788°C High limit 142A-3642-2300 230 VAC K t/c 1450°F High limit 142A-3642-2300 230 VAC K t/c 788°C High limit 142A-3642-2400 230 VAC K t/c 1450°F On/Off 142A-3642-2400 230 VAC K t/c 788°C On/Off 142A-3643-1200 120 VAC K t/c 1500°F High limit 142A-3643-1200 120 VAC K t/c 816°C High limit 142A-3643-1300 120 VAC K t/c 1500°F High limit 142A-3643-1300 120 VAC K t/c 816°C High limit 142A-3643-1400 120 VAC K t/c 1500°F On/Off 142A-3643-1400 120 VAC K t/c 816°C On/Off 142A-3643-2200 230 VAC K t/c 1500°F High limit 142A-3643-2200 230 VAC K t/c 816°C High limit 142A-3643-2300 230 VAC K t/c 1500°F High limit 142A-3643-2300 230 VAC K t/c 816°C High limit 142A-3643-2400 230 VAC K t/c 1500°F On/Off 142A-3643-2400 230 VAC K t/c 816°C On/Off 142A-3644-1200 120 VAC K t/c 1550°F High limit 142A-3644-1200 120 VAC K t/c 843°C High limit 142A-3644-1300 120 VAC K t/c 1550°F High limit 142A-3644-1300 120 VAC K t/c 843°C High limit 142A-3644-1400 120 VAC K t/c 1550°F On/Off 142A-3644-1400 120 VAC K t/c 843°C On/Off 142A-3644-2200 230 VAC K t/c 1550°F High limit 142A-3644-2200 230 VAC K t/c 843°C High limit 142A-3644-2300 230 VAC K t/c 1550°F High limit 142A-3644-2300 230 VAC K t/c 843°C High limit 142A-3644-2400 230 VAC K t/c 1550°F On/Off 142A-3644-2400 230 VAC K t/c 843°C On/Off 142A-3645-1200 120 VAC K t/c 1600°F High limit 142A-3645-1200 120 VAC K t/c 871°C High limit 142A-3645-1300 120 VAC K t/c 1600°F High limit 142A-3645-1300 120 VAC K t/c 871°C High limit 142A-3645-1400 120 VAC K t/c 1600°F On/Off 142A-3645-1400 120 VAC K t/c 871°C On/Off 142A-3645-2200 230 VAC K t/c 1600°F High limit
Voltage Input Temp Range Control Mode Action Output Set Point Mounting Retrofit
Series 142
Automatic Reset Automatic Reset
Heat
Heat Manual Reset Manual Reset
Automatic Reset Automatic Reset
Heat
Heat Manual Reset Manual Reset
Automatic Reset Automatic Reset
Heat
Heat Manual Reset Manual Reset
Automatic Reset Automatic Reset
Heat
Heat Manual Reset Manual Reset
Automatic Reset Automatic Reset
Heat
Heat Manual Reset Manual Reset
Automatic Reset Automatic Reset
Heat
Heat Manual Reset Manual Reset
Automatic Reset Automatic Reset
Heat
Heat Manual Reset
See Notes
Below
3A Relay Fixed Potted LF C4KW 1450 AAAA A 6, 8 3A Relay Fixed Potted LF C4LW 0788 AAAA A 6, 8 3A Relay Fixed Potted CF C4KH 1450 AAAA A 6, 8 3A Relay Fixed Potted CF C4LH 0788 AAAA A 6, 8 3A Relay Fixed Potted LF E4KU 1450 AAAA A 6, 8 3A Relay Fixed Potted LF E4LU 0788 AAAA A 6, 8 3A Relay Fixed Potted LF E4KW 1450 AAAA A 6, 8 3A Relay Fixed Potted LF E4LW 0788 AAAA A 6, 8 3A Relay Fixed Potted CF E4KH 1450 AAAA A 6, 8 3A Relay Fixed Potted CF E4LH 0788 AAAA A 6, 8 3A Relay Fixed Potted LF C4KU 1500 AAAA A 6, 8 3A Relay Fixed Potted LF C4LU 0816 AAAA A 6, 8 3A Relay Fixed Potted LF C4KW 1500 AAAA A 6, 8 3A Relay Fixed Potted LF C4LW 0816 AAAA A 6, 8 3A Relay Fixed Potted CF C4KH 1500 AAAA A 6, 8 3A Relay Fixed Potted CF C4LH 0816 AAAA A 6, 8 3A Relay Fixed Potted LF E4KU 1500 AAAA A 6, 8 3A Relay Fixed Potted LF E4LU 0816 AAAA A 6, 8 3A Relay Fixed Potted LF E4KW 1500 AAAA A 6, 8 3A Relay Fixed Potted LF E4LW 0816 AAAA A 6, 8 3A Relay Fixed Potted CF E4KH 1500 AAAA A 6, 8 3A Relay Fixed Potted CF E4LH 0816 AAAA A 6, 8 3A Relay Fixed Potted LF C4KU 1550 AAAA A 6, 8 3A Relay Fixed Potted LF C4LU 0843 AAAA A 6, 8 3A Relay Fixed Potted LF C4KW 1550 AAAA A 6, 8 3A Relay Fixed Potted LF C4LW 0843 AAAA A 6, 8 3A Relay Fixed Potted CF C4KH 1550 AAAA A 6, 8 3A Relay Fixed Potted CF C4LH 0843 AAAA A 6, 8 3A Relay Fixed Potted LF E4KU 1550 AAAA A 6, 8 3A Relay Fixed Potted LF E4LU 0843 AAAA A 6, 8 3A Relay Fixed Potted LF E4KW 1550 AAAA A 6, 8 3A Relay Fixed Potted LF E4LW 0843 AAAA A 6, 8 3A Relay Fixed Potted CF E4KH 1550 AAAA A 6, 8 3A Relay Fixed Potted CF E4LH 0843 AAAA A 6, 8 3A Relay Fixed Potted LF C4KU 1600 AAAA A 6, 8 3A Relay Fixed Potted LF C4LU 0871 AAAA A 6, 8 3A Relay Fixed Potted LF C4KW 1600 AAAA A 6, 8 3A Relay Fixed Potted LF C4LW 0871 AAAA A 6, 8 3A Relay Fixed Potted CF C4KH 1600 AAAA A 6, 8 3A Relay Fixed Potted CF C4LH 0871 AAAA A 6, 8 3A Relay Fixed Potted LF E4KU 1600 AAAA A 6, 8
Watlow Controls 1/31/2005 Page 16
Line
Series 142
142A-3645-2200 230 VAC K t/c 871°C High limit 142A-3645-2300 230 VAC K t/c 1600°F High limit 142A-3645-2300 230 VAC K t/c 871°C High limit 142A-3645-2400 230 VAC K t/c 1600°F On/Off 142A-3645-2400 230 VAC K t/c 871°C On/Off 142A-3646-1200 120 VAC K t/c 1650°F High limit 142A-3646-1200 120 VAC K t/c 899°C High limit 142A-3646-1300 120 VAC K t/c 1650°F High limit 142A-3646-1300 120 VAC K t/c 899°C High limit 142A-3646-1400 120 VAC K t/c 1650°F On/Off 142A-3646-1400 120 VAC K t/c 899°C On/Off 142A-3646-2200 230 VAC K t/c 1650°F High limit 142A-3646-2200 230 VAC K t/c 899°C High limit 142A-3646-2300 230 VAC K t/c 1650°F High limit 142A-3646-2300 230 VAC K t/c 899°C High limit 142A-3646-2400 230 VAC K t/c 1650°F On/Off 142A-3646-2400 230 VAC K t/c 899°C On/Off 142A-3647-1200 120 VAC K t/c 1700°F High limit 142A-3647-1200 120 VAC K t/c 927°C High limit 142A-3647-1300 120 VAC K t/c 1700°F High limit 142A-3647-1300 120 VAC K t/c 927°C High limit 142A-3647-1400 120 VAC K t/c 1700°F On/Off 142A-3647-1400 120 VAC K t/c 927°C On/Off 142A-3647-2200 230 VAC K t/c 1700°F High limit 142A-3647-2200 230 VAC K t/c 927°C High limit 142A-3647-2300 230 VAC K t/c 1700°F High limit 142A-3647-2300 230 VAC K t/c 927°C High limit 142A-3647-2400 230 VAC K t/c 1700°F On/Off 142A-3647-2400 230 VAC K t/c 927°C On/Off 142A-3648-1200 120 VAC K t/c 1750°F High limit 142A-3648-1200 120 VAC K t/c 954°C High limit 142A-3648-1300 120 VAC K t/c 1750°F High limit 142A-3648-1300 120 VAC K t/c 954°C High limit 142A-3648-1400 120 VAC K t/c 1750°F On/Off 142A-3648-1400 120 VAC K t/c 954°C On/Off 142A-3648-2200 230 VAC K t/c 1750°F High limit 142A-3648-2200 230 VAC K t/c 954°C High limit 142A-3648-2300 230 VAC K t/c 1750°F High limit 142A-3648-2300 230 VAC K t/c 954°C High limit 142A-3648-2400 230 VAC K t/c 1750°F On/Off 142A-3648-2400 230 VAC K t/c 954°C On/Off
Voltage Input Temp Range Control Mode Action Output Set Point Mounting Retrofit
Series 142
Manual Reset
Automatic Reset Automatic Reset
Heat
Heat Manual Reset Manual Reset
Automatic Reset Automatic Reset
Heat
Heat Manual Reset Manual Reset
Automatic Reset Automatic Reset
Heat
Heat Manual Reset Manual Reset
Automatic Reset Automatic Reset
Heat
Heat Manual Reset Manual Reset
Automatic Reset Automatic Reset
Heat
Heat Manual Reset Manual Reset
Automatic Reset Automatic Reset
Heat
Heat Manual Reset Manual Reset
Automatic Reset Automatic Reset
Heat
Heat
See Notes
Below
3A Relay Fixed Potted LF E4LU 0871 AAAA A 6, 8 3A Relay Fixed Potted LF E4KW 1600 AAAA A 6, 8 3A Relay Fixed Potted LF E4LW 0871 AAAA A 6, 8 3A Relay Fixed Potted CF E4KH 1600 AAAA A 6, 8 3A Relay Fixed Potted CF E4LH 0871 AAAA A 6, 8 3A Relay Fixed Potted LF C4KU 1650 AAAA A 6, 8 3A Relay Fixed Potted LF C4LU 0899 AAAA A 6, 8 3A Relay Fixed Potted LF C4KW 1650 AAAA A 6, 8 3A Relay Fixed Potted LF C4LW 0899 AAAA A 6, 8 3A Relay Fixed Potted CF C4KH 1650 AAAA A 6, 8 3A Relay Fixed Potted CF C4LH 0899 AAAA A 6, 8 3A Relay Fixed Potted LF E4KU 1650 AAAA A 6, 8 3A Relay Fixed Potted LF E4LU 0899 AAAA A 6, 8 3A Relay Fixed Potted LF E4KW 1650 AAAA A 6, 8 3A Relay Fixed Potted LF E4LW 0899 AAAA A 6, 8 3A Relay Fixed Potted CF E4KH 1650 AAAA A 6, 8 3A Relay Fixed Potted CF E4LH 0899 AAAA A 6, 8 3A Relay Fixed Potted LF C4KU 1700 AAAA A 6, 8 3A Relay Fixed Potted LF C4LU 0927 AAAA A 6, 8 3A Relay Fixed Potted LF C4KW 1700 AAAA A 6, 8 3A Relay Fixed Potted LF C4LW 0927 AAAA A 6, 8 3A Relay Fixed Potted CF C4KH 1700 AAAA A 6, 8 3A Relay Fixed Potted CF C4LH 0927 AAAA A 6, 8 3A Relay Fixed Potted LF E4KU 1700 AAAA A 6, 8 3A Relay Fixed Potted LF E4LU 0927 AAAA A 6, 8 3A Relay Fixed Potted LF E4KW 1700 AAAA A 6, 8 3A Relay Fixed Potted LF E4LW 0927 AAAA A 6, 8 3A Relay Fixed Potted CF E4KH 1700 AAAA A 6, 8 3A Relay Fixed Potted CF E4LH 0927 AAAA A 6, 8 3A Relay Fixed Potted LF C4KU 1750 AAAA A 6, 8 3A Relay Fixed Potted LF C4LU 0954 AAAA A 6, 8 3A Relay Fixed Potted LF C4KW 1750 AAAA A 6, 8 3A Relay Fixed Potted LF C4LW 0954 AAAA A 6, 8 3A Relay Fixed Potted CF C4KH 1750 AAAA A 6, 8 3A Relay Fixed Potted CF C4LH 0954 AAAA A 6, 8 3A Relay Fixed Potted LF E4KU 1750 AAAA A 6, 8 3A Relay Fixed Potted LF E4LU 0954 AAAA A 6, 8 3A Relay Fixed Potted LF E4KW 1750 AAAA A 6, 8 3A Relay Fixed Potted LF E4LW 0954 AAAA A 6, 8 3A Relay Fixed Potted CF E4KH 1750 AAAA A 6, 8 3A Relay Fixed Potted CF E4LH 0954 AAAA A 6, 8
Watlow Controls 1/31/2005 Page 17
Line
Series 142
142A-3649-1200 120 VAC K t/c 1800°F High limit 142A-3649-1200 120 VAC K t/c 982°C High limit 142A-3649-1300 120 VAC K t/c 1800°F High limit 142A-3649-1300 120 VAC K t/c 982°C High limit 142A-3649-1400 120 VAC K t/c 1800°F On/Off 142A-3649-1400 120 VAC K t/c 982°C On/Off 142A-3649-2200 230 VAC K t/c 1800°F High limit 142A-3649-2200 230 VAC K t/c 982°C High limit 142A-3649-2300 230 VAC K t/c 1800°F High limit 142A-3649-2300 230 VAC K t/c 982°C High limit 142A-3649-2400 230 VAC K t/c 1800°F On/Off 142A-3649-2400 230 VAC K t/c 982°C On/Off 142A-3650-1200 120 VAC K t/c 1850°F High limit 142A-3650-1200 120 VAC K t/c 1010°C High limit 142A-3650-1300 120 VAC K t/c 1850°F High limit 142A-3650-1300 120 VAC K t/c 1010°C High limit 142A-3650-1400 120 VAC K t/c 1850°F On/Off 142A-3650-1400 120 VAC K t/c 1010°C On/Off 142A-3650-2200 230 VAC K t/c 1850°F High limit 142A-3650-2200 230 VAC K t/c 1010°C High limit 142A-3650-2300 230 VAC K t/c 1850°F High limit 142A-3650-2300 230 VAC K t/c 1010°C High limit 142A-3650-2400 230 VAC K t/c 1850°F On/Off 142A-3650-2400 230 VAC K t/c 1010°C On/Off 142A-3651-1200 120 VAC K t/c 1900°F High limit 142A-3651-1200 120 VAC K t/c 1038°C High limit 142A-3651-1300 120 VAC K t/c 1900°F High limit 142A-3651-1300 120 VAC K t/c 1038°C High limit 142A-3651-1400 120 VAC K t/c 1900°F On/Off 142A-3651-1400 120 VAC K t/c 1038°C On/Off 142A-3651-2200 230 VAC K t/c 1900°F High limit 142A-3651-2200 230 VAC K t/c 1038°C High limit 142A-3651-2300 230 VAC K t/c 1900°F High limit 142A-3651-2300 230 VAC K t/c 1038°C High limit 142A-3651-2400 230 VAC K t/c 1900°F On/Off 142A-3651-2400 230 VAC K t/c 1038°C On/Off 142A-3652-1200 120 VAC K t/c 1950°F High limit 142A-3652-1200 120 VAC K t/c 1066°C High limit 142A-3652-1300 120 VAC K t/c 1950°F High limit 142A-3652-1300 120 VAC K t/c 1066°C High limit 142A-3652-1400 120 VAC K t/c 1950°F On/Off
Voltage Input Temp Range Control Mode Action Output Set Point Mounting Retrofit
Series 142
Manual Reset Manual Reset
Automatic Reset Automatic Reset
Heat
Heat Manual Reset Manual Reset
Automatic Reset Automatic Reset
Heat
Heat Manual Reset Manual Reset
Automatic Reset Automatic Reset
Heat
Heat Manual Reset Manual Reset
Automatic Reset Automatic Reset
Heat
Heat Manual Reset Manual Reset
Automatic Reset Automatic Reset
Heat
Heat Manual Reset Manual Reset
Automatic Reset Automatic Reset
Heat
Heat Manual Reset Manual Reset
Automatic Reset Automatic Reset
Heat
See Notes
Below
3A Relay Fixed Potted LF C4KU 1800 AAAA A 6, 8 3A Relay Fixed Potted LF C4LU 0982 AAAA A 6, 8 3A Relay Fixed Potted LF C4KW 1800 AAAA A 6, 8 3A Relay Fixed Potted LF C4LW 0982 AAAA A 6, 8 3A Relay Fixed Potted CF C4KH 1800 AAAA A 6, 8 3A Relay Fixed Potted CF C4LH 0982 AAAA A 6, 8 3A Relay Fixed Potted LF E4KU 1800 AAAA A 6, 8 3A Relay Fixed Potted LF E4LU 0982 AAAA A 6, 8 3A Relay Fixed Potted LF E4KW 1800 AAAA A 6, 8 3A Relay Fixed Potted LF E4LW 0982 AAAA A 6, 8 3A Relay Fixed Potted CF E4KH 1800 AAAA A 6, 8 3A Relay Fixed Potted CF E4LH 0982 AAAA A 6, 8 3A Relay Fixed Potted LF C4KU 1850 AAAA A 6, 8 3A Relay Fixed Potted LF C4LU 1010 AAAA A 6, 8 3A Relay Fixed Potted LF C4KW 1850 AAAA A 6, 8 3A Relay Fixed Potted LF C4LW 1010 AAAA A 6, 8 3A Relay Fixed Potted CF C4KH 1850 AAAA A 6, 8 3A Relay Fixed Potted CF C4LH 1010 AAAA A 6, 8 3A Relay Fixed Potted LF E4KU 1850 AAAA A 6, 8 3A Relay Fixed Potted LF E4LU 1010 AAAA A 6, 8 3A Relay Fixed Potted LF E4KW 1850 AAAA A 6, 8 3A Relay Fixed Potted LF E4LW 1010 AAAA A 6, 8 3A Relay Fixed Potted CF E4KH 1850 AAAA A 6, 8 3A Relay Fixed Potted CF E4LH 1010 AAAA A 6, 8 3A Relay Fixed Potted LF C4KU 1900 AAAA A 6, 8 3A Relay Fixed Potted LF C4LU 1038 AAAA A 6, 8 3A Relay Fixed Potted LF C4KW 1900 AAAA A 6, 8 3A Relay Fixed Potted LF C4LW 1038 AAAA A 6, 8 3A Relay Fixed Potted CF C4KH 1900 AAAA A 6, 8 3A Relay Fixed Potted CF C4LH 1038 AAAA A 6, 8 3A Relay Fixed Potted LF E4KU 1900 AAAA A 6, 8 3A Relay Fixed Potted LF E4LU 1038 AAAA A 6, 8 3A Relay Fixed Potted LF E4KW 1900 AAAA A 6, 8 3A Relay Fixed Potted LF E4LW 1038 AAAA A 6, 8 3A Relay Fixed Potted CF E4KH 1900 AAAA A 6, 8 3A Relay Fixed Potted CF E4LH 1038 AAAA A 6, 8 3A Relay Fixed Potted LF C4KU 1950 AAAA A 6, 8 3A Relay Fixed Potted LF C4LU 1066 AAAA A 6, 8 3A Relay Fixed Potted LF C4KW 1950 AAAA A 6, 8 3A Relay Fixed Potted LF C4LW 1066 AAAA A 6, 8 3A Relay Fixed Potted CF C4KH 1950 AAAA A 6, 8
Watlow Controls 1/31/2005 Page 18
Line
Series 142
142A-3652-1400 120 VAC K t/c 1066°C On/Off 142A-3652-2200 230 VAC K t/c 1950°F High limit 142A-3652-2200 230 VAC K t/c 1066°C High limit 142A-3652-2300 230 VAC K t/c 1950°F High limit 142A-3652-2300 230 VAC K t/c 1066°C High limit 142A-3652-2400 230 VAC K t/c 1950°F On/Off 142A-3652-2400 230 VAC K t/c 1066°C On/Off 142A-3653-1200 120 VAC J t/c 115°F High limit 142A-3653-1200 120 VAC J t/c 46°C High limit 142A-3653-1300 120 VAC J t/c 115°F High limit 142A-3653-1300 120 VAC J t/c 46°C High limit 142A-3653-1400 120 VAC J t/c 115°F On/Off 142A-3653-1400 120 VAC J t/c 46°C On/Off 142A-3653-2200 230 VAC J t/c 115°F High limit 142A-3653-2200 230 VAC J t/c 46°C High limit 142A-3653-2300 230 VAC J t/c 115°F High limit 142A-3653-2300 230 VAC J t/c 46°C High limit 142A-3653-2400 230 VAC J t/c 115°F On/Off 142A-3653-2400 230 VAC J t/c 46°C On/Off 142A-3654-1200 120 VAC K t/c 2050°F High limit 142A-3654-1200 120 VAC K t/c 1121°C High limit 142A-3654-1300 120 VAC K t/c 2050°F High limit 142A-3654-1300 120 VAC K t/c 1121°C High limit 142A-3654-1400 120 VAC K t/c 2050°F On/Off 142A-3654-1400 120 VAC K t/c 1121°C On/Off 142A-3654-2200 230 VAC K t/c 2050°F High limit 142A-3654-2200 230 VAC K t/c 1121°C High limit 142A-3654-2300 230 VAC K t/c 2050°F High limit 142A-3654-2300 230 VAC K t/c 1121°C High limit 142A-3654-2400 230 VAC K t/c 2050°F On/Off 142A-3654-2400 230 VAC K t/c 1121°C On/Off 142A-3655-1200 120 VAC K t/c 2100°F High limit 142A-3655-1200 120 VAC K t/c 1149°C High limit 142A-3655-1300 120 VAC K t/c 2100°F High limit 142A-3655-1300 120 VAC K t/c 1149°C High limit 142A-3655-1400 120 VAC K t/c 2100°F On/Off 142A-3655-1400 120 VAC K t/c 1149°C On/Off 142A-3655-2200 230 VAC K t/c 2100°F High limit 142A-3655-2200 230 VAC K t/c 1149°C High limit 142A-3655-2300 230 VAC K t/c 2100°F High limit 142A-3655-2300 230 VAC K t/c 1149°C High limit
Voltage Input Temp Range Control Mode Action Output Set Point Mounting Retrofit
Series 142
Heat Manual Reset Manual Reset
Automatic Reset Automatic Reset
Heat
Heat Manual Reset Manual Reset
Automatic Reset Automatic Reset
Heat
Heat Manual Reset Manual Reset
Automatic Reset Automatic Reset
Heat
Heat Manual Reset Manual Reset
Automatic Reset Automatic Reset
Heat
Heat Manual Reset Manual Reset
Automatic Reset Automatic Reset
Heat
Heat Manual Reset Manual Reset
Automatic Reset Automatic Reset
Heat
Heat Manual Reset Manual Reset
Automatic Reset Automatic Reset
See Notes
Below
3A Relay Fixed Potted CF C4LH 1066 AAAA A 6, 8 3A Relay Fixed Potted LF E4KU 1950 AAAA A 6, 8 3A Relay Fixed Potted LF E4LU 1066 AAAA A 6, 8 3A Relay Fixed Potted LF E4KW 1950 AAAA A 6, 8 3A Relay Fixed Potted LF E4LW 1066 AAAA A 6, 8 3A Relay Fixed Potted CF E4KH 1950 AAAA A 6, 8 3A Relay Fixed Potted CF E4LH 1066 AAAA A 6, 8 3A Relay Fixed Potted LF C4HU 0115 AAAA A 6, 8 3A Relay Fixed Potted LF C4JU 0046 AAAA A 6, 8 3A Relay Fixed Potted LF C4HW 0115 AAAA A 6, 8 3A Relay Fixed Potted LF C4JW 0046 AAAA A 6, 8 3A Relay Fixed Potted CF C4HH 0115 AAAA A 6, 8 3A Relay Fixed Potted CF C4JH 0046 AAAA A 6, 8 3A Relay Fixed Potted LF E4HU 0115 AAAA A 6, 8 3A Relay Fixed Potted LF E4JU 0046 AAAA A 6, 8 3A Relay Fixed Potted LF E4HW 0115 AAAA A 6, 8 3A Relay Fixed Potted LF E4JW 0046 AAAA A 6, 8 3A Relay Fixed Potted CF E4HH 0115 AAAA A 6, 8 3A Relay Fixed Potted CF E4JH 0046 AAAA A 6, 8 3A Relay Fixed Potted LF C4KU 2050 AAAA A 6, 8 3A Relay Fixed Potted LF C4LU 1121 AAAA A 6, 8 3A Relay Fixed Potted LF C4KW 2050 AAAA A 6, 8 3A Relay Fixed Potted LF C4LW 1121 AAAA A 6, 8 3A Relay Fixed Potted CF C4KH 2050 AAAA A 6, 8 3A Relay Fixed Potted CF C4LH 1121 AAAA A 6, 8 3A Relay Fixed Potted LF E4KU 2050 AAAA A 6, 8 3A Relay Fixed Potted LF E4LU 1121 AAAA A 6, 8 3A Relay Fixed Potted LF E4KW 2050 AAAA A 6, 8 3A Relay Fixed Potted LF E4LW 1121 AAAA A 6, 8 3A Relay Fixed Potted CF E4KH 2050 AAAA A 6, 8 3A Relay Fixed Potted CF E4LH 1121 AAAA A 6, 8 3A Relay Fixed Potted LF C4KU 2100 AAAA A 6, 8 3A Relay Fixed Potted LF C4LU 1149 AAAA A 6, 8 3A Relay Fixed Potted LF C4KW 2100 AAAA A 6, 8 3A Relay Fixed Potted LF C4LW 1149 AAAA A 6, 8 3A Relay Fixed Potted CF C4KH 2100 AAAA A 6, 8 3A Relay Fixed Potted CF C4LH 1149 AAAA A 6, 8 3A Relay Fixed Potted LF E4KU 2100 AAAA A 6, 8 3A Relay Fixed Potted LF E4LU 1149 AAAA A 6, 8 3A Relay Fixed Potted LF E4KW 2100 AAAA A 6, 8 3A Relay Fixed Potted LF E4LW 1149 AAAA A 6, 8
Watlow Controls 1/31/2005 Page 19
Line
Series 142
142A-3655-2400 230 VAC K t/c 2100°F On/Off 142A-3655-2400 230 VAC K t/c 1149°C On/Off 142A-3656-1200 120 VAC K t/c 2150°F High limit 142A-3656-1200 120 VAC K t/c 1177°C High limit 142A-3656-1300 120 VAC K t/c 2150°F High limit 142A-3656-1300 120 VAC K t/c 1177°C High limit 142A-3656-1400 120 VAC K t/c 2150°F On/Off 142A-3656-1400 120 VAC K t/c 1177°C On/Off 142A-3656-2200 230 VAC K t/c 2150°F High limit 142A-3656-2200 230 VAC K t/c 1177°C High limit 142A-3656-2300 230 VAC K t/c 2150°F High limit 142A-3656-2300 230 VAC K t/c 1177°C High limit 142A-3656-2400 230 VAC K t/c 2150°F On/Off 142A-3656-2400 230 VAC K t/c 1177°C On/Off 142A-3657-1200 120 VAC K t/c 2200°F High limit 142A-3657-1200 120 VAC K t/c 1204°C High limit 142A-3657-1300 120 VAC K t/c 2200°F High limit 142A-3657-1300 120 VAC K t/c 1204°C High limit 142A-3657-1400 120 VAC K t/c 2200°F On/Off 142A-3657-1400 120 VAC K t/c 1204°C On/Off 142A-3657-2200 230 VAC K t/c 2200°F High limit 142A-3657-2200 230 VAC K t/c 1204°C High limit 142A-3657-2300 230 VAC K t/c 2200°F High limit 142A-3657-2300 230 VAC K t/c 1204°C High limit 142A-3657-2400 230 VAC K t/c 2200°F On/Off 142A-3657-2400 230 VAC K t/c 1204°C On/Off 142A-3658-1200 120 VAC K t/c 2250°F High limit 142A-3658-1200 120 VAC K t/c 1232°C High limit 142A-3658-1300 120 VAC K t/c 2250°F High limit 142A-3658-1300 120 VAC K t/c 1232°C High limit 142A-3658-1400 120 VAC K t/c 2250°F On/Off 142A-3658-1400 120 VAC K t/c 1232°C On/Off 142A-3658-2200 230 VAC K t/c 2250°F High limit 142A-3658-2200 230 VAC K t/c 1232°C High limit 142A-3658-2300 230 VAC K t/c 2250°F High limit 142A-3658-2300 230 VAC K t/c 1232°C High limit 142A-3658-2400 230 VAC K t/c 2250°F On/Off 142A-3658-2400 230 VAC K t/c 1232°C On/Off 142A-3659-1200 120 VAC K t/c 2300°F High limit 142A-3659-1200 120 VAC K t/c 1260°C High limit 142A-3659-1300 120 VAC K t/c 2300°F High limit
Voltage Input Temp Range Control Mode Action Output Set Point Mounting Retrofit
Series 142
Heat
Heat Manual Reset Manual Reset
Automatic Reset Automatic Reset
Heat
Heat Manual Reset Manual Reset
Automatic Reset Automatic Reset
Heat
Heat Manual Reset Manual Reset
Automatic Reset Automatic Reset
Heat
Heat Manual Reset Manual Reset
Automatic Reset Automatic Reset
Heat
Heat Manual Reset Manual Reset
Automatic Reset Automatic Reset
Heat
Heat Manual Reset Manual Reset
Automatic Reset Automatic Reset
Heat
Heat Manual Reset Manual Reset
Automatic Reset
See Notes
Below
3A Relay Fixed Potted CF E4KH 2100 AAAA A 6, 8 3A Relay Fixed Potted CF E4LH 1149 AAAA A 6, 8 3A Relay Fixed Potted LF C4KU 2150 AAAA A 6, 8 3A Relay Fixed Potted LF C4LU 1177 AAAA A 6, 8 3A Relay Fixed Potted LF C4KW 2150 AAAA A 6, 8 3A Relay Fixed Potted LF C4LW 1177 AAAA A 6, 8 3A Relay Fixed Potted CF C4KH 2150 AAAA A 6, 8 3A Relay Fixed Potted CF C4LH 1177 AAAA A 6, 8 3A Relay Fixed Potted LF E4KU 2150 AAAA A 6, 8 3A Relay Fixed Potted LF E4LU 1177 AAAA A 6, 8 3A Relay Fixed Potted LF E4KW 2150 AAAA A 6, 8 3A Relay Fixed Potted LF E4LW 1177 AAAA A 6, 8 3A Relay Fixed Potted CF E4KH 2150 AAAA A 6, 8 3A Relay Fixed Potted CF E4LH 1177 AAAA A 6, 8 3A Relay Fixed Potted LF C4KU 2200 AAAA A 6, 8 3A Relay Fixed Potted LF C4LU 1204 AAAA A 6, 8 3A Relay Fixed Potted LF C4KW 2200 AAAA A 6, 8 3A Relay Fixed Potted LF C4LW 1204 AAAA A 6, 8 3A Relay Fixed Potted CF C4KH 2200 AAAA A 6, 8 3A Relay Fixed Potted CF C4LH 1204 AAAA A 6, 8 3A Relay Fixed Potted LF E4KU 2200 AAAA A 6, 8 3A Relay Fixed Potted LF E4LU 1204 AAAA A 6, 8 3A Relay Fixed Potted LF E4KW 2200 AAAA A 6, 8 3A Relay Fixed Potted LF E4LW 1204 AAAA A 6, 8 3A Relay Fixed Potted CF E4KH 2200 AAAA A 6, 8 3A Relay Fixed Potted CF E4LH 1204 AAAA A 6, 8 3A Relay Fixed Potted LF C4KU 2250 AAAA A 6, 8 3A Relay Fixed Potted LF C4LU 1232 AAAA A 6, 8 3A Relay Fixed Potted LF C4KW 2250 AAAA A 6, 8 3A Relay Fixed Potted LF C4LW 1232 AAAA A 6, 8 3A Relay Fixed Potted CF C4KH 2250 AAAA A 6, 8 3A Relay Fixed Potted CF C4LH 1232 AAAA A 6, 8 3A Relay Fixed Potted LF E4KU 2250 AAAA A 6, 8 3A Relay Fixed Potted LF E4LU 1232 AAAA A 6, 8 3A Relay Fixed Potted LF E4KW 2250 AAAA A 6, 8 3A Relay Fixed Potted LF E4LW 1232 AAAA A 6, 8 3A Relay Fixed Potted CF E4KH 2250 AAAA A 6, 8 3A Relay Fixed Potted CF E4LH 1232 AAAA A 6, 8 3A Relay Fixed Potted LF C4KU 2300 AAAA A 6, 8 3A Relay Fixed Potted LF C4LU 1260 AAAA A 6, 8 3A Relay Fixed Potted LF C4KW 2300 AAAA A 6, 8
Watlow Controls 1/31/2005 Page 20
Line
Series 142
142A-3659-1300 120 VAC K t/c 1260°C High limit 142A-3659-1400 120 VAC K t/c 2300°F On/Off 142A-3659-1400 120 VAC K t/c 1260°C On/Off 142A-3659-2200 230 VAC K t/c 2300°F High limit 142A-3659-2200 230 VAC K t/c 1260°C High limit 142A-3659-2300 230 VAC K t/c 2300°F High limit 142A-3659-2300 230 VAC K t/c 1260°C High limit 142A-3659-2400 230 VAC K t/c 2300°F On/Off 142A-3659-2400 230 VAC K t/c 1260°C On/Off 142A-3660-1200 120 VAC K t/c 2350°F High limit 142A-3660-1200 120 VAC K t/c 1288°C High limit 142A-3660-1300 120 VAC K t/c 2350°F High limit 142A-3660-1300 120 VAC K t/c 1288°C High limit 142A-3660-1400 120 VAC K t/c 2350°F On/Off 142A-3660-1400 120 VAC K t/c 1288°C On/Off 142A-3660-2200 230 VAC K t/c 2350°F High limit 142A-3660-2200 230 VAC K t/c 1288°C High limit 142A-3660-2300 230 VAC K t/c 2350°F High limit 142A-3660-2300 230 VAC K t/c 1288°C High limit 142A-3660-2400 230 VAC K t/c 2350°F On/Off 142A-3660-2400 230 VAC K t/c 1288°C On/Off 142A-3661-1200 120 VAC K t/c 2400°F High limit 142A-3661-1200 120 VAC K t/c 1316°C High limit 142A-3661-1300 120 VAC K t/c 2400°F High limit 142A-3661-1300 120 VAC K t/c 1316°C High limit 142A-3661-1400 120 VAC K t/c 2400°F On/Off 142A-3661-1400 120 VAC K t/c 1316°C On/Off 142A-3661-2200 230 VAC K t/c 2400°F High limit 142A-3661-2200 230 VAC K t/c 1316°C High limit 142A-3661-2300 230 VAC K t/c 2400°F High limit 142A-3661-2300 230 VAC K t/c 1316°C High limit 142A-3661-2400 230 VAC K t/c 2400°F On/Off 142A-3661-2400 230 VAC K t/c 1316°C On/Off 142A-3662-1200 120 VAC K t/c 2450°F High limit 142A-3662-1200 120 VAC K t/c 1343°C High limit 142A-3662-1300 120 VAC K t/c 2450°F High limit 142A-3662-1300 120 VAC K t/c 1343°C High limit 142A-3662-1400 120 VAC K t/c 2450°F On/Off 142A-3662-1400 120 VAC K t/c 1343°C On/Off 142A-3662-2200 230 VAC K t/c 2450°F High limit 142A-3662-2200 230 VAC K t/c 1343°C High limit
Voltage Input Temp Range Control Mode Action Output Set Point Mounting Retrofit
Series 142
Automatic Reset
Heat
Heat Manual Reset Manual Reset
Automatic Reset Automatic Reset
Heat
Heat Manual Reset Manual Reset
Automatic Reset Automatic Reset
Heat
Heat Manual Reset Manual Reset
Automatic Reset Automatic Reset
Heat
Heat Manual Reset Manual Reset
Automatic Reset Automatic Reset
Heat
Heat Manual Reset Manual Reset
Automatic Reset Automatic Reset
Heat
Heat Manual Reset Manual Reset
Automatic Reset Automatic Reset
Heat
Heat Manual Reset Manual Reset
See Notes
Below
3A Relay Fixed Potted LF C4LW 1260 AAAA A 6, 8 3A Relay Fixed Potted CF C4KH 2300 AAAA A 6, 8 3A Relay Fixed Potted CF C4LH 1260 AAAA A 6, 8 3A Relay Fixed Potted LF E4KU 2300 AAAA A 6, 8 3A Relay Fixed Potted LF E4LU 1260 AAAA A 6, 8 3A Relay Fixed Potted LF E4KW 2300 AAAA A 6, 8 3A Relay Fixed Potted LF E4LW 1260 AAAA A 6, 8 3A Relay Fixed Potted CF E4KH 2300 AAAA A 6, 8 3A Relay Fixed Potted CF E4LH 1260 AAAA A 6, 8 3A Relay Fixed Potted LF C4KU 2350 AAAA A 6, 8 3A Relay Fixed Potted LF C4LU 1288 AAAA A 6, 8 3A Relay Fixed Potted LF C4KW 2350 AAAA A 6, 8 3A Relay Fixed Potted LF C4LW 1288 AAAA A 6, 8 3A Relay Fixed Potted CF C4KH 2350 AAAA A 6, 8 3A Relay Fixed Potted CF C4LH 1288 AAAA A 6, 8 3A Relay Fixed Potted LF E4KU 2350 AAAA A 6, 8 3A Relay Fixed Potted LF E4LU 1288 AAAA A 6, 8 3A Relay Fixed Potted LF E4KW 2350 AAAA A 6, 8 3A Relay Fixed Potted LF E4LW 1288 AAAA A 6, 8 3A Relay Fixed Potted CF E4KH 2350 AAAA A 6, 8 3A Relay Fixed Potted CF E4LH 1288 AAAA A 6, 8 3A Relay Fixed Potted LF C4KU 2400 AAAA A 6, 8 3A Relay Fixed Potted LF C4LU 1316 AAAA A 6, 8 3A Relay Fixed Potted LF C4KW 2400 AAAA A 6, 8 3A Relay Fixed Potted LF C4LW 1316 AAAA A 6, 8 3A Relay Fixed Potted CF C4KH 2400 AAAA A 6, 8 3A Relay Fixed Potted CF C4LH 1316 AAAA A 6, 8 3A Relay Fixed Potted LF E4KU 2400 AAAA A 6, 8 3A Relay Fixed Potted LF E4LU 1316 AAAA A 6, 8 3A Relay Fixed Potted LF E4KW 2400 AAAA A 6, 8 3A Relay Fixed Potted LF E4LW 1316 AAAA A 6, 8 3A Relay Fixed Potted CF E4KH 2400 AAAA A 6, 8 3A Relay Fixed Potted CF E4LH 1316 AAAA A 6, 8 3A Relay Fixed Potted LF C4KU 2450 AAAA A 6, 8 3A Relay Fixed Potted LF C4LU 1343 AAAA A 6, 8 3A Relay Fixed Potted LF C4KW 2450 AAAA A 6, 8 3A Relay Fixed Potted LF C4LW 1343 AAAA A 6, 8 3A Relay Fixed Potted CF C4KH 2450 AAAA A 6, 8 3A Relay Fixed Potted CF C4LH 1343 AAAA A 6, 8 3A Relay Fixed Potted LF E4KU 2450 AAAA A 6, 8 3A Relay Fixed Potted LF E4LU 1343 AAAA A 6, 8
Watlow Controls 1/31/2005 Page 21
Line
Series 142
142A-3662-2300 230 VAC K t/c 2450°F High limit 142A-3662-2300 230 VAC K t/c 1343°C High limit 142A-3662-2400 230 VAC K t/c 2450°F On/Off 142A-3662-2400 230 VAC K t/c 1343°C On/Off 142A-3663-1200 120 VAC K t/c 2500°F High limit 142A-3663-1200 120 VAC K t/c 1371°C High limit 142A-3663-1300 120 VAC K t/c 2500°F High limit 142A-3663-1300 120 VAC K t/c 1371°C High limit 142A-3663-1400 120 VAC K t/c 2500°F On/Off 142A-3663-1400 120 VAC K t/c 1371°C On/Off 142A-3663-2200 230 VAC K t/c 2500°F High limit 142A-3663-2200 230 VAC K t/c 1371°C High limit 142A-3663-2300 230 VAC K t/c 2500°F High limit 142A-3663-2300 230 VAC K t/c 1371°C High limit 142A-3663-2400 230 VAC K t/c 2500°F On/Off 142A-3663-2400 230 VAC K t/c 1371°C On/Off 142A-3664-1200 120 VAC E t/c 1050°F High limit 142A-3664-1200 120 VAC E t/c 566°C High limit 142A-3664-1300 120 VAC E t/c 1050°F High limit 142A-3664-1300 120 VAC E t/c 566°C High limit 142A-3664-1400 120 VAC E t/c 1050°F On/Off 142A-3664-1400 120 VAC E t/c 566°C On/Off 142A-3664-2200 230 VAC E t/c 1050°F High limit 142A-3664-2200 230 VAC E t/c 566°C High limit 142A-3664-2300 230 VAC E t/c 1050°F High limit 142A-3664-2300 230 VAC E t/c 566°C High limit 142A-3664-2400 230 VAC E t/c 1050°F On/Off 142A-3664-2400 230 VAC E t/c 566°C On/Off 142A-3665-1200 120 VAC K t/c 400°F High limit 142A-3665-1200 120 VAC K t/c 204°C High limit 142A-3665-1300 120 VAC K t/c 400°F High limit 142A-3665-1300 120 VAC K t/c 204°C High limit 142A-3665-1400 120 VAC K t/c 400°F On/Off 142A-3665-1400 120 VAC K t/c 204°C On/Off 142A-3665-2200 230 VAC K t/c 400°F High limit 142A-3665-2200 230 VAC K t/c 204°C High limit 142A-3665-2300 230 VAC K t/c 400°F High limit 142A-3665-2300 230 VAC K t/c 204°C High limit 142A-3665-2400 230 VAC K t/c 400°F On/Off 142A-3665-2400 230 VAC K t/c 204°C On/Off 142A-3666-1200 120 VAC J t/c 145°F High limit
Voltage Input Temp Range Control Mode Action Output Set Point Mounting Retrofit
Series 142
Automatic Reset Automatic Reset
Heat
Heat Manual Reset Manual Reset
Automatic Reset Automatic Reset
Heat
Heat Manual Reset Manual Reset
Automatic Reset Automatic Reset
Heat
Heat Manual Reset Manual Reset
Automatic Reset Automatic Reset
Heat
Heat Manual Reset Manual Reset
Automatic Reset Automatic Reset
Heat
Heat Manual Reset Manual Reset
Automatic Reset Automatic Reset
Heat
Heat Manual Reset Manual Reset
Automatic Reset Automatic Reset
Heat
Heat Manual Reset
See Notes
Below
3A Relay Fixed Potted LF E4KW 2450 AAAA A 6, 8 3A Relay Fixed Potted LF E4LW 1343 AAAA A 6, 8 3A Relay Fixed Potted CF E4KH 2450 AAAA A 6, 8 3A Relay Fixed Potted CF E4LH 1343 AAAA A 6, 8 3A Relay Fixed Potted LF C4KU 2500 AAAA A 6, 8 3A Relay Fixed Potted LF C4LU 1371 AAAA A 6, 8 3A Relay Fixed Potted LF C4KW 2500 AAAA A 6, 8 3A Relay Fixed Potted LF C4LW 1371 AAAA A 6, 8 3A Relay Fixed Potted CF C4KH 2500 AAAA A 6, 8 3A Relay Fixed Potted CF C4LH 1371 AAAA A 6, 8 3A Relay Fixed Potted LF E4KU 2500 AAAA A 6, 8 3A Relay Fixed Potted LF E4LU 1371 AAAA A 6, 8 3A Relay Fixed Potted LF E4KW 2500 AAAA A 6, 8 3A Relay Fixed Potted LF E4LW 1371 AAAA A 6, 8 3A Relay Fixed Potted CF E4KH 2500 AAAA A 6, 8 3A Relay Fixed Potted CF E4LH 1371 AAAA A 6, 8 3A Relay Fixed Potted LF C4SU 1050 AAAA A 6, 8 3A Relay Fixed Potted LF C4TU 0566 AAAA A 6, 8 3A Relay Fixed Potted LF C4SW 1050 AAAA A 6, 8 3A Relay Fixed Potted LF C4TW 0566 AAAA A 6, 8 3A Relay Fixed Potted CF C4SH 1050 AAAA A 6, 8 3A Relay Fixed Potted CF C4TH 0566 AAAA A 6, 8 3A Relay Fixed Potted LF E4SU 1050 AAAA A 6, 8 3A Relay Fixed Potted LF E4TU 0566 AAAA A 6, 8 3A Relay Fixed Potted LF E4SW 1050 AAAA A 6, 8 3A Relay Fixed Potted LF E4TW 0566 AAAA A 6, 8 3A Relay Fixed Potted CF E4SH 1050 AAAA A 6, 8 3A Relay Fixed Potted CF E4TH 0566 AAAA A 6, 8 3A Relay Fixed Potted LF C4KU 0400 AAAA A 6, 8 3A Relay Fixed Potted LF C4LU 0204 AAAA A 6, 8 3A Relay Fixed Potted LF C4KW 0400 AAAA A 6, 8 3A Relay Fixed Potted LF C4LW 0204 AAAA A 6, 8 3A Relay Fixed Potted CF C4KH 0400 AAAA A 6, 8 3A Relay Fixed Potted CF C4LH 0204 AAAA A 6, 8 3A Relay Fixed Potted LF E4KU 0400 AAAA A 6, 8 3A Relay Fixed Potted LF E4LU 0204 AAAA A 6, 8 3A Relay Fixed Potted LF E4KW 0400 AAAA A 6, 8 3A Relay Fixed Potted LF E4LW 0204 AAAA A 6, 8 3A Relay Fixed Potted CF E4KH 0400 AAAA A 6, 8 3A Relay Fixed Potted CF E4LH 0204 AAAA A 6, 8 3A Relay Fixed Potted LF C4HU 0145 AAAA A 6, 8
Watlow Controls 1/31/2005 Page 22
Line
Series 142
142A-3666-1200 120 VAC J t/c 63°C High limit 142A-3666-1300 120 VAC J t/c 145°F High limit 142A-3666-1300 120 VAC J t/c 63°C High limit 142A-3666-1400 120 VAC J t/c 145°F On/Off 142A-3666-1400 120 VAC J t/c 63°C On/Off 142A-3666-2200 230 VAC J t/c 145°F High limit 142A-3666-2200 230 VAC J t/c 63°C High limit 142A-3666-2300 230 VAC J t/c 145°F High limit 142A-3666-2300 230 VAC J t/c 63°C High limit 142A-3666-2400 230 VAC J t/c 145°F On/Off 142A-3666-2400 230 VAC J t/c 63°C On/Off 142A-3667-1200 120 VAC K t/c 460°F High limit 142A-3667-1200 120 VAC K t/c 328°C High limit 142A-3667-1300 120 VAC K t/c 460°F High limit 142A-3667-1300 120 VAC K t/c 328°C High limit 142A-3667-1400 120 VAC K t/c 460°F On/Off 142A-3667-1400 120 VAC K t/c 328°C On/Off 142A-3667-2200 230 VAC K t/c 460°F High limit 142A-3667-2200 230 VAC K t/c 328°C High limit 142A-3667-2300 230 VAC K t/c 460°F High limit 142A-3667-2300 230 VAC K t/c 328°C High limit 142A-3667-2400 230 VAC K t/c 460°F On/Off 142A-3667-2400 230 VAC K t/c 328°C On/Off 142A-3668-1200 120 VAC E t/c 428°F High limit 142A-3668-1200 120 VAC E t/c 155°C High limit 142A-3668-1300 120 VAC E t/c 428°F High limit 142A-3668-1300 120 VAC E t/c 155°C High limit 142A-3668-1400 120 VAC E t/c 428°F On/Off 142A-3668-1400 120 VAC E t/c 155°C On/Off 142A-3668-2200 230 VAC E t/c 428°F High limit 142A-3668-2200 230 VAC E t/c 155°C High limit 142A-3668-2300 230 VAC E t/c 428°F High limit 142A-3668-2300 230 VAC E t/c 155°C High limit 142A-3668-2400 230 VAC E t/c 428°F On/Off 142A-3668-2400 230 VAC E t/c 155°C On/Off 142A-3669-1200 120 VAC E t/c 383°F High limit 142A-3669-1200 120 VAC E t/c 110°C High limit 142A-3669-1300 120 VAC E t/c 383°F High limit 142A-3669-1300 120 VAC E t/c 110°C High limit 142A-3669-1400 120 VAC E t/c 383°F On/Off 142A-3669-1400 120 VAC E t/c 110°C On/Off
Voltage Input Temp Range Control Mode Action Output Set Point Mounting Retrofit
Series 142
Manual Reset
Automatic Reset Automatic Reset
Heat
Heat Manual Reset Manual Reset
Automatic Reset Automatic Reset
Heat
Heat Manual Reset Manual Reset
Automatic Reset Automatic Reset
Heat
Heat Manual Reset Manual Reset
Automatic Reset Automatic Reset
Heat
Heat Manual Reset Manual Reset
Automatic Reset Automatic Reset
Heat
Heat Manual Reset Manual Reset
Automatic Reset Automatic Reset
Heat
Heat Manual Reset Manual Reset
Automatic Reset Automatic Reset
Heat
Heat
See Notes
Below
3A Relay Fixed Potted LF C4JU 0063 AAAA A 6, 8 3A Relay Fixed Potted LF C4HW 0145 AAAA A 6, 8 3A Relay Fixed Potted LF C4JW 0063 AAAA A 6, 8 3A Relay Fixed Potted CF C4HH 0145 AAAA A 6, 8 3A Relay Fixed Potted CF C4JH 0063 AAAA A 6, 8 3A Relay Fixed Potted LF E4HU 0145 AAAA A 6, 8 3A Relay Fixed Potted LF E4JU 0063 AAAA A 6, 8 3A Relay Fixed Potted LF E4HW 0145 AAAA A 6, 8 3A Relay Fixed Potted LF E4JW 0063 AAAA A 6, 8 3A Relay Fixed Potted CF E4HH 0145 AAAA A 6, 8 3A Relay Fixed Potted CF E4JH 0063 AAAA A 6, 8 3A Relay Fixed Potted LF C4KU 0460 AAAA A 6, 8 3A Relay Fixed Potted LF C4LU 0328 AAAA A 6, 8 3A Relay Fixed Potted LF C4KW 0460 AAAA A 6, 8 3A Relay Fixed Potted LF C4LW 0328 AAAA A 6, 8 3A Relay Fixed Potted CF C4KH 0460 AAAA A 6, 8 3A Relay Fixed Potted CF C4LH 0328 AAAA A 6, 8 3A Relay Fixed Potted LF E4KU 0460 AAAA A 6, 8 3A Relay Fixed Potted LF E4LU 0328 AAAA A 6, 8 3A Relay Fixed Potted LF E4KW 0460 AAAA A 6, 8 3A Relay Fixed Potted LF E4LW 0328 AAAA A 6, 8 3A Relay Fixed Potted CF E4KH 0460 AAAA A 6, 8 3A Relay Fixed Potted CF E4LH 0328 AAAA A 6, 8 3A Relay Fixed Potted LF C4SU 0428 AAAA A 6, 8 3A Relay Fixed Potted LF C4TU 0155 AAAA A 6, 8 3A Relay Fixed Potted LF C4SW 0428 AAAA A 6, 8 3A Relay Fixed Potted LF C4TW 0155 AAAA A 6, 8 3A Relay Fixed Potted CF C4SH 0428 AAAA A 6, 8 3A Relay Fixed Potted CF C4TH 0155 AAAA A 6, 8 3A Relay Fixed Potted LF E4SU 0428 AAAA A 6, 8 3A Relay Fixed Potted LF E4TU 0155 AAAA A 6, 8 3A Relay Fixed Potted LF E4SW 0428 AAAA A 6, 8 3A Relay Fixed Potted LF E4TW 0155 AAAA A 6, 8 3A Relay Fixed Potted CF E4SH 0428 AAAA A 6, 8 3A Relay Fixed Potted CF E4TH 0155 AAAA A 6, 8 3A Relay Fixed Potted LF C4SU 0383 AAAA A 6, 8 3A Relay Fixed Potted LF C4TU 0110 AAAA A 6, 8 3A Relay Fixed Potted LF C4SW 0383 AAAA A 6, 8 3A Relay Fixed Potted LF C4TW 0110 AAAA A 6, 8 3A Relay Fixed Potted CF C4SH 0383 AAAA A 6, 8 3A Relay Fixed Potted CF C4TH 0110 AAAA A 6, 8
Watlow Controls 1/31/2005 Page 23
Line
Series 142
142A-3669-2200 230 VAC E t/c 383°F High limit 142A-3669-2200 230 VAC E t/c 110°C High limit 142A-3669-2300 230 VAC E t/c 383°F High limit 142A-3669-2300 230 VAC E t/c 110°C High limit 142A-3669-2400 230 VAC E t/c 383°F On/Off 142A-3669-2400 230 VAC E t/c 110°C On/Off 142A-3670-1200 120 VAC E t/c 423°F High limit 142A-3670-1200 120 VAC E t/c 150°C High limit 142A-3670-1300 120 VAC E t/c 423°F High limit 142A-3670-1300 120 VAC E t/c 150°C High limit 142A-3670-1400 120 VAC E t/c 423°F On/Off 142A-3670-1400 120 VAC E t/c 150°C On/Off 142A-3670-2200 230 VAC E t/c 423°F High limit 142A-3670-2200 230 VAC E t/c 150°C High limit 142A-3670-2300 230 VAC E t/c 423°F High limit 142A-3670-2300 230 VAC E t/c 150°C High limit 142A-3670-2400 230 VAC E t/c 423°F On/Off 142A-3670-2400 230 VAC E t/c 150°C On/Off 142A-3671-1200 120 VAC K t/c 550°F High limit 142A-3671-1200 120 VAC K t/c 288°C High limit 142A-3671-1300 120 VAC K t/c 550°F High limit 142A-3671-1300 120 VAC K t/c 288°C High limit 142A-3671-1400 120 VAC K t/c 550°F On/Off 142A-3671-1400 120 VAC K t/c 288°C On/Off 142A-3671-2200 230 VAC K t/c 550°F High limit 142A-3671-2200 230 VAC K t/c 288°C High limit 142A-3671-2300 230 VAC K t/c 550°F High limit 142A-3671-2300 230 VAC K t/c 288°C High limit 142A-3671-2400 230 VAC K t/c 550°F On/Off 142A-3671-2400 230 VAC K t/c 288°C On/Off 142A-3672-1200 120 VAC J t/c 185°F High limit 142A-3672-1200 120 VAC J t/c 85°C High limit 142A-3672-1300 120 VAC J t/c 185°F High limit 142A-3672-1300 120 VAC J t/c 85°C High limit 142A-3672-1400 120 VAC J t/c 185°F On/Off 142A-3672-1400 120 VAC J t/c 85°C On/Off 142A-3672-2200 230 VAC J t/c 185°F High limit 142A-3672-2200 230 VAC J t/c 85°C High limit 142A-3672-2300 230 VAC J t/c 185°F High limit 142A-3672-2300 230 VAC J t/c 85°C High limit 142A-3672-2400 230 VAC J t/c 185°F On/Off
Voltage Input Temp Range Control Mode Action Output Set Point Mounting Retrofit
Series 142
Manual Reset Manual Reset
Automatic Reset Automatic Reset
Heat
Heat Manual Reset Manual Reset
Automatic Reset Automatic Reset
Heat
Heat Manual Reset Manual Reset
Automatic Reset Automatic Reset
Heat
Heat Manual Reset Manual Reset
Automatic Reset Automatic Reset
Heat
Heat Manual Reset Manual Reset
Automatic Reset Automatic Reset
Heat
Heat Manual Reset Manual Reset
Automatic Reset Automatic Reset
Heat
Heat Manual Reset Manual Reset
Automatic Reset Automatic Reset
Heat
See Notes
Below
3A Relay Fixed Potted LF E4SU 0383 AAAA A 6, 8 3A Relay Fixed Potted LF E4TU 0110 AAAA A 6, 8 3A Relay Fixed Potted LF E4SW 0383 AAAA A 6, 8 3A Relay Fixed Potted LF E4TW 0110 AAAA A 6, 8 3A Relay Fixed Potted CF E4SH 0383 AAAA A 6, 8 3A Relay Fixed Potted CF E4TH 0110 AAAA A 6, 8 3A Relay Fixed Potted LF C4SU 0423 AAAA A 6, 8 3A Relay Fixed Potted LF C4TU 0150 AAAA A 6, 8 3A Relay Fixed Potted LF C4SW 0423 AAAA A 6, 8 3A Relay Fixed Potted LF C4TW 0150 AAAA A 6, 8 3A Relay Fixed Potted CF C4SH 0423 AAAA A 6, 8 3A Relay Fixed Potted CF C4TH 0150 AAAA A 6, 8 3A Relay Fixed Potted LF E4SU 0423 AAAA A 6, 8 3A Relay Fixed Potted LF E4TU 0150 AAAA A 6, 8 3A Relay Fixed Potted LF E4SW 0423 AAAA A 6, 8 3A Relay Fixed Potted LF E4TW 0150 AAAA A 6, 8 3A Relay Fixed Potted CF E4SH 0423 AAAA A 6, 8 3A Relay Fixed Potted CF E4TH 0150 AAAA A 6, 8 3A Relay Fixed Potted LF C4KU 0550 AAAA A 6, 8 3A Relay Fixed Potted LF C4LU 0288 AAAA A 6, 8 3A Relay Fixed Potted LF C4KW 0550 AAAA A 6, 8 3A Relay Fixed Potted LF C4LW 0288 AAAA A 6, 8 3A Relay Fixed Potted CF C4KH 0550 AAAA A 6, 8 3A Relay Fixed Potted CF C4LH 0288 AAAA A 6, 8 3A Relay Fixed Potted LF E4KU 0550 AAAA A 6, 8 3A Relay Fixed Potted LF E4LU 0288 AAAA A 6, 8 3A Relay Fixed Potted LF E4KW 0550 AAAA A 6, 8 3A Relay Fixed Potted LF E4LW 0288 AAAA A 6, 8 3A Relay Fixed Potted CF E4KH 0550 AAAA A 6, 8 3A Relay Fixed Potted CF E4LH 0288 AAAA A 6, 8 3A Relay Fixed Potted LF C4HU 0185 AAAA A 6, 8 3A Relay Fixed Potted LF C4JU 0085 AAAA A 6, 8 3A Relay Fixed Potted LF C4HW 0185 AAAA A 6, 8 3A Relay Fixed Potted LF C4JW 0085 AAAA A 6, 8 3A Relay Fixed Potted CF C4HH 0185 AAAA A 6, 8 3A Relay Fixed Potted CF C4JH 0085 AAAA A 6, 8 3A Relay Fixed Potted LF E4HU 0185 AAAA A 6, 8 3A Relay Fixed Potted LF E4JU 0085 AAAA A 6, 8 3A Relay Fixed Potted LF E4HW 0185 AAAA A 6, 8 3A Relay Fixed Potted LF E4JW 0085 AAAA A 6, 8 3A Relay Fixed Potted CF E4HH 0185 AAAA A 6, 8
Watlow Controls 1/31/2005 Page 24
Line
Series 142
142A-3672-2400 230 VAC J t/c 85°C On/Off 142A-3673-1200 120 VAC K t/c 1198°F High limit 142A-3673-1200 120 VAC K t/c 648°C High limit 142A-3673-1300 120 VAC K t/c 1198°F High limit 142A-3673-1300 120 VAC K t/c 648°C High limit 142A-3673-1400 120 VAC K t/c 1198°F On/Off 142A-3673-1400 120 VAC K t/c 648°C On/Off 142A-3673-2200 230 VAC K t/c 1198°F High limit 142A-3673-2200 230 VAC K t/c 648°C High limit 142A-3673-2300 230 VAC K t/c 1198°F High limit 142A-3673-2300 230 VAC K t/c 648°C High limit 142A-3673-2400 230 VAC K t/c 1198°F On/Off 142A-3673-2400 230 VAC K t/c 648°C On/Off 142A-3674-1200 120 VAC K t/c 700°F High limit 142A-3674-1200 120 VAC K t/c 371°C High limit 142A-3674-1300 120 VAC K t/c 700°F High limit 142A-3674-1300 120 VAC K t/c 371°C High limit 142A-3674-1400 120 VAC K t/c 700°F On/Off 142A-3674-1400 120 VAC K t/c 371°C On/Off 142A-3674-2200 230 VAC K t/c 700°F High limit 142A-3674-2200 230 VAC K t/c 371°C High limit 142A-3674-2300 230 VAC K t/c 700°F High limit 142A-3674-2300 230 VAC K t/c 371°C High limit 142A-3674-2400 230 VAC K t/c 700°F On/Off 142A-3674-2400 230 VAC K t/c 371°C On/Off 142A-3675-1200 120 VAC E t/c 500°F High limit 142A-3675-1200 120 VAC E t/c 260°C High limit 142A-3675-1300 120 VAC E t/c 500°F High limit 142A-3675-1300 120 VAC E t/c 260°C High limit 142A-3675-1400 120 VAC E t/c 500°F On/Off 142A-3675-1400 120 VAC E t/c 260°C On/Off 142A-3675-2200 230 VAC E t/c 500°F High limit 142A-3675-2200 230 VAC E t/c 260°C High limit 142A-3675-2300 230 VAC E t/c 500°F High limit 142A-3675-2300 230 VAC E t/c 260°C High limit 142A-3675-2400 230 VAC E t/c 500°F On/Off 142A-3675-2400 230 VAC E t/c 260°C On/Off 142A-3677-1200 120 VAC K t/c 788°F High limit 142A-3677-1200 120 VAC K t/c 420°C High limit 142A-3677-1300 120 VAC K t/c 788°F High limit 142A-3677-1300 120 VAC K t/c 420°C High limit
Voltage Input Temp Range Control Mode Action Output Set Point Mounting Retrofit
Series 142
Heat Manual Reset Manual Reset
Automatic Reset Automatic Reset
Heat
Heat Manual Reset Manual Reset
Automatic Reset Automatic Reset
Heat
Heat Manual Reset Manual Reset
Automatic Reset Automatic Reset
Heat
Heat Manual Reset Manual Reset
Automatic Reset Automatic Reset
Heat
Heat Manual Reset Manual Reset
Automatic Reset Automatic Reset
Heat
Heat Manual Reset Manual Reset
Automatic Reset Automatic Reset
Heat
Heat Manual Reset Manual Reset
Automatic Reset Automatic Reset
See Notes
Below
3A Relay Fixed Potted CF E4JH 0085 AAAA A 6, 8 3A Relay Fixed Potted LF C4KU 1198 AAAA A 6, 8 3A Relay Fixed Potted LF C4LU 0648 AAAA A 6, 8 3A Relay Fixed Potted LF C4KW 1198 AAAA A 6, 8 3A Relay Fixed Potted LF C4LW 0648 AAAA A 6, 8 3A Relay Fixed Potted CF C4KH 1198 AAAA A 6, 8 3A Relay Fixed Potted CF C4LH 0648 AAAA A 6, 8 3A Relay Fixed Potted LF E4KU 1198 AAAA A 6, 8 3A Relay Fixed Potted LF E4LU 0648 AAAA A 6, 8 3A Relay Fixed Potted LF E4KW 1198 AAAA A 6, 8 3A Relay Fixed Potted LF E4LW 0648 AAAA A 6, 8 3A Relay Fixed Potted CF E4KH 1198 AAAA A 6, 8 3A Relay Fixed Potted CF E4LH 0648 AAAA A 6, 8 3A Relay Fixed Potted LF C4KU 0700 AAAA A 6, 8 3A Relay Fixed Potted LF C4LU 0371 AAAA A 6, 8 3A Relay Fixed Potted LF C4KW 0700 AAAA A 6, 8 3A Relay Fixed Potted LF C4LW 0371 AAAA A 6, 8 3A Relay Fixed Potted CF C4KH 0700 AAAA A 6, 8 3A Relay Fixed Potted CF C4LH 0371 AAAA A 6, 8 3A Relay Fixed Potted LF E4KU 0700 AAAA A 6, 8 3A Relay Fixed Potted LF E4LU 0371 AAAA A 6, 8 3A Relay Fixed Potted LF E4KW 0700 AAAA A 6, 8 3A Relay Fixed Potted LF E4LW 0371 AAAA A 6, 8 3A Relay Fixed Potted CF E4KH 0700 AAAA A 6, 8 3A Relay Fixed Potted CF E4LH 0371 AAAA A 6, 8 3A Relay Fixed Potted LF C4SU 0500 AAAA A 6, 8 3A Relay Fixed Potted LF C4TU 0260 AAAA A 6, 8 3A Relay Fixed Potted LF C4SW 0500 AAAA A 6, 8 3A Relay Fixed Potted LF C4TW 0260 AAAA A 6, 8 3A Relay Fixed Potted CF C4SH 0500 AAAA A 6, 8 3A Relay Fixed Potted CF C4TH 0260 AAAA A 6, 8 3A Relay Fixed Potted LF E4SU 0500 AAAA A 6, 8 3A Relay Fixed Potted LF E4TU 0260 AAAA A 6, 8 3A Relay Fixed Potted LF E4SW 0500 AAAA A 6, 8 3A Relay Fixed Potted LF E4TW 0260 AAAA A 6, 8 3A Relay Fixed Potted CF E4SH 0500 AAAA A 6, 8 3A Relay Fixed Potted CF E4TH 0260 AAAA A 6, 8 3A Relay Fixed Potted LF C4KU 788 AAAA A 6, 8 3A Relay Fixed Potted LF C4LU 0420 AAAA A 6, 8 3A Relay Fixed Potted LF C4KW 788 AAAA A 6, 8 3A Relay Fixed Potted LF C4LW 0420 AAAA A 6, 8
Watlow Controls 1/31/2005 Page 25
Line
Series 142
142A-3677-1400 120 VAC K t/c 788°F On/Off 142A-3677-1400 120 VAC K t/c 420°C On/Off 142A-3677-2200 230 VAC K t/c 788°F High limit 142A-3677-2200 230 VAC K t/c 420°C High limit 142A-3677-2300 230 VAC K t/c 788°F High limit 142A-3677-2300 230 VAC K t/c 420°C High limit 142A-3677-2400 230 VAC K t/c 788°F On/Off 142A-3677-2400 230 VAC K t/c 420°C On/Off 142A-3678-1200 120 VAC E t/c 565°F High limit 142A-3678-1200 120 VAC E t/c 296°C High limit 142A-3678-1300 120 VAC E t/c 565°F High limit 142A-3678-1300 120 VAC E t/c 296°C High limit 142A-3678-1400 120 VAC E t/c 565°F On/Off 142A-3678-1400 120 VAC E t/c 296°C On/Off 142A-3678-2200 230 VAC E t/c 565°F High limit 142A-3678-2200 230 VAC E t/c 296°C High limit 142A-3678-2300 230 VAC E t/c 565°F High limit 142A-3678-2300 230 VAC E t/c 296°C High limit 142A-3678-2400 230 VAC E t/c 565°F On/Off 142A-3678-2400 230 VAC E t/c 296°C On/Off 142A-3679-1200 120 VAC E t/c 365°F High limit 142A-3679-1200 120 VAC E t/c 185°C High limit 142A-3679-1300 120 VAC E t/c 365°F High limit 142A-3679-1300 120 VAC E t/c 185°C High limit 142A-3679-1400 120 VAC E t/c 365°F On/Off 142A-3679-1400 120 VAC E t/c 185°C On/Off 142A-3679-2200 230 VAC E t/c 365°F High limit 142A-3679-2200 230 VAC E t/c 185°C High limit 142A-3679-2300 230 VAC E t/c 365°F High limit 142A-3679-2300 230 VAC E t/c 185°C High limit 142A-3679-2400 230 VAC E t/c 365°F On/Off 142A-3679-2400 230 VAC E t/c 185°C On/Off 142A-3680-1200 120 VAC T t/c 60°F High limit 142A-3680-1200 120 VAC T t/c 16°C High limit 142A-3680-1300 120 VAC T t/c 60°F High limit 142A-3680-1300 120 VAC T t/c 16°C High limit 142A-3680-1400 120 VAC T t/c 60°F On/Off 142A-3680-1400 120 VAC T t/c 16°C On/Off 142A-3680-2200 230 VAC T t/c 60°F High limit 142A-3680-2200 230 VAC T t/c 16°C High limit 142A-3680-2300 230 VAC T t/c 60°F High limit
Voltage Input Temp Range Control Mode Action Output Set Point Mounting Retrofit
Series 142
Heat
Heat Manual Reset Manual Reset
Automatic Reset Automatic Reset
Heat
Heat Manual Reset Manual Reset
Automatic Reset Automatic Reset
Heat
Heat Manual Reset Manual Reset
Automatic Reset Automatic Reset
Heat
Heat Manual Reset Manual Reset
Automatic Reset Automatic Reset
Heat
Heat Manual Reset Manual Reset
Automatic Reset Automatic Reset
Heat
Heat Manual Reset Manual Reset
Automatic Reset Automatic Reset
Heat
Heat Manual Reset Manual Reset
Automatic Reset
See Notes
Below
3A Relay Fixed Potted CF C4KH 788 AAAA A 6, 8 3A Relay Fixed Potted CF C4LH 0420 AAAA A 6, 8 3A Relay Fixed Potted LF E4KU 788 AAAA A 6, 8 3A Relay Fixed Potted LF E4LU 0420 AAAA A 6, 8 3A Relay Fixed Potted LF E4KW 788 AAAA A 6, 8 3A Relay Fixed Potted LF E4LW 0420 AAAA A 6, 8 3A Relay Fixed Potted CF E4KH 788 AAAA A 6, 8 3A Relay Fixed Potted CF E4LH 0420 AAAA A 6, 8 3A Relay Fixed Potted LF C4SU 0565 AAAA A 6, 8 3A Relay Fixed Potted LF C4TU 0296 AAAA A 6, 8 3A Relay Fixed Potted LF C4SW 0565 AAAA A 6, 8 3A Relay Fixed Potted LF C4TW 0296 AAAA A 6, 8 3A Relay Fixed Potted CF C4SH 0565 AAAA A 6, 8 3A Relay Fixed Potted CF C4TH 0296 AAAA A 6, 8 3A Relay Fixed Potted LF E4SU 0565 AAAA A 6, 8 3A Relay Fixed Potted LF E4TU 0296 AAAA A 6, 8 3A Relay Fixed Potted LF E4SW 0565 AAAA A 6, 8 3A Relay Fixed Potted LF E4TW 0296 AAAA A 6, 8 3A Relay Fixed Potted CF E4SH 0565 AAAA A 6, 8 3A Relay Fixed Potted CF E4TH 0296 AAAA A 6, 8 3A Relay Fixed Potted LF C4SU 0365 AAAA A 6, 8 3A Relay Fixed Potted LF C4TU 0185 AAAA A 6, 8 3A Relay Fixed Potted LF C4SW 0365 AAAA A 6, 8 3A Relay Fixed Potted LF C4TW 0185 AAAA A 6, 8 3A Relay Fixed Potted CF C4SH 0365 AAAA A 6, 8 3A Relay Fixed Potted CF C4TH 0185 AAAA A 6, 8 3A Relay Fixed Potted LF E4SU 0365 AAAA A 6, 8 3A Relay Fixed Potted LF E4TU 0185 AAAA A 6, 8 3A Relay Fixed Potted LF E4SW 0365 AAAA A 6, 8 3A Relay Fixed Potted LF E4TW 0185 AAAA A 6, 8 3A Relay Fixed Potted CF E4SH 0365 AAAA A 6, 8 3A Relay Fixed Potted CF E4TH 0185 AAAA A 6, 8 3A Relay Fixed Potted LF C4MU 0060 AAAA A 6, 8 3A Relay Fixed Potted LF C4NU 0016 AAAA A 6, 8 3A Relay Fixed Potted LF C4MW 0060 AAAA A 6, 8 3A Relay Fixed Potted LF C4NW 0016 AAAA A 6, 8 3A Relay Fixed Potted CF C4MH 0060 AAAA A 6, 8 3A Relay Fixed Potted CF C4NH 0016 AAAA A 6, 8 3A Relay Fixed Potted LF E4MU 0060 AAAA A 6, 8 3A Relay Fixed Potted LF E4NU 0016 AAAA A 6, 8 3A Relay Fixed Potted LF E4MW 0060 AAAA A 6, 8
Watlow Controls 1/31/2005 Page 26
Line
Series 142
142A-3680-2300 230 VAC T t/c 16°C High limit 142A-3680-2400 230 VAC T t/c 60°F On/Off 142A-3680-2400 230 VAC T t/c 16°C On/Off 142A-3681-1200 120 VAC J t/c 175°F High limit 142A-3681-1200 120 VAC J t/c 79°C High limit 142A-3681-1300 120 VAC J t/c 175°F High limit 142A-3681-1300 120 VAC J t/c 79°C High limit 142A-3681-1400 120 VAC J t/c 175°F On/Off 142A-3681-1400 120 VAC J t/c 79°C On/Off 142A-3681-2200 230 VAC J t/c 175°F High limit 142A-3681-2200 230 VAC J t/c 79°C High limit 142A-3681-2300 230 VAC J t/c 175°F High limit 142A-3681-2300 230 VAC J t/c 79°C High limit 142A-3681-2400 230 VAC J t/c 175°F On/Off 142A-3681-2400 230 VAC J t/c 79°C On/Off 142A-3682-1200 120 VAC E t/c 575°F High limit 142A-3682-1200 120 VAC E t/c 302°C High limit 142A-3682-1300 120 VAC E t/c 575°F High limit 142A-3682-1300 120 VAC E t/c 302°C High limit 142A-3682-1400 120 VAC E t/c 575°F On/Off 142A-3682-1400 120 VAC E t/c 302°C On/Off 142A-3682-2200 230 VAC E t/c 575°F High limit 142A-3682-2200 230 VAC E t/c 302°C High limit 142A-3682-2300 230 VAC E t/c 575°F High limit 142A-3682-2300 230 VAC E t/c 302°C High limit 142A-3682-2400 230 VAC E t/c 575°F On/Off 142A-3682-2400 230 VAC E t/c 302°C On/Off 142A-3683-1200 120 VAC J t/c 150°F High limit 142A-3683-1200 120 VAC J t/c 66°C High limit 142A-3683-1300 120 VAC J t/c 150°F High limit 142A-3683-1300 120 VAC J t/c 66°C High limit 142A-3683-1400 120 VAC J t/c 150°F On/Off 142A-3683-1400 120 VAC J t/c 66°C On/Off 142A-3683-2200 230 VAC J t/c 150°F High limit 142A-3683-2200 230 VAC J t/c 66°C High limit 142A-3683-2300 230 VAC J t/c 150°F High limit 142A-3683-2300 230 VAC J t/c 66°C High limit 142A-3683-2400 230 VAC J t/c 150°F On/Off 142A-3683-2400 230 VAC J t/c 66°C On/Off 142A-3684-1200 120 VAC E t/c 450°F High limit 142A-3684-1200 120 VAC E t/c 232°C High limit
Voltage Input Temp Range Control Mode Action Output Set Point Mounting Retrofit
Series 142
Automatic Reset
Heat
Heat Manual Reset Manual Reset
Automatic Reset Automatic Reset
Heat
Heat Manual Reset Manual Reset
Automatic Reset Automatic Reset
Heat
Heat Manual Reset Manual Reset
Automatic Reset Automatic Reset
Heat
Heat Manual Reset Manual Reset
Automatic Reset Automatic Reset
Heat
Heat Manual Reset Manual Reset
Automatic Reset Automatic Reset
Heat
Heat Manual Reset Manual Reset
Automatic Reset Automatic Reset
Heat
Heat Manual Reset Manual Reset
See Notes
Below
3A Relay Fixed Potted LF E4NW 0016 AAAA A 6, 8 3A Relay Fixed Potted CF E4MH 0060 AAAA A 6, 8 3A Relay Fixed Potted CF E4NH 0016 AAAA A 6, 8 3A Relay Fixed Potted LF C4HU 0175 AAAA A 6, 8 3A Relay Fixed Potted LF C4JU 0079 AAAA A 6, 8 3A Relay Fixed Potted LF C4HW 0175 AAAA A 6, 8 3A Relay Fixed Potted LF C4JW 0079 AAAA A 6, 8 3A Relay Fixed Potted CF C4HH 0175 AAAA A 6, 8 3A Relay Fixed Potted CF C4JH 0079 AAAA A 6, 8 3A Relay Fixed Potted LF E4HU 0175 AAAA A 6, 8 3A Relay Fixed Potted LF E4JU 0079 AAAA A 6, 8 3A Relay Fixed Potted LF E4HW 0175 AAAA A 6, 8 3A Relay Fixed Potted LF E4JW 0079 AAAA A 6, 8 3A Relay Fixed Potted CF E4HH 0175 AAAA A 6, 8 3A Relay Fixed Potted CF E4JH 0079 AAAA A 6, 8 3A Relay Fixed Potted LF C4SU 0575 AAAA A 6, 8 3A Relay Fixed Potted LF C4TU 0302 AAAA A 6, 8 3A Relay Fixed Potted LF C4SW 0575 AAAA A 6, 8 3A Relay Fixed Potted LF C4TW 0302 AAAA A 6, 8 3A Relay Fixed Potted CF C4SH 0575 AAAA A 6, 8 3A Relay Fixed Potted CF C4TH 0302 AAAA A 6, 8 3A Relay Fixed Potted LF E4SU 0575 AAAA A 6, 8 3A Relay Fixed Potted LF E4TU 0302 AAAA A 6, 8 3A Relay Fixed Potted LF E4SW 0575 AAAA A 6, 8 3A Relay Fixed Potted LF E4TW 0302 AAAA A 6, 8 3A Relay Fixed Potted CF E4SH 0575 AAAA A 6, 8 3A Relay Fixed Potted CF E4TH 0302 AAAA A 6, 8 3A Relay Fixed Potted LF C4HU 0150 AAAA A 6, 8 3A Relay Fixed Potted LF C4JU 0066 AAAA A 6, 8 3A Relay Fixed Potted LF C4HW 0150 AAAA A 6, 8 3A Relay Fixed Potted LF C4JW 0066 AAAA A 6, 8 3A Relay Fixed Potted CF C4HH 0150 AAAA A 6, 8 3A Relay Fixed Potted CF C4JH 0066 AAAA A 6, 8 3A Relay Fixed Potted LF E4HU 0150 AAAA A 6, 8 3A Relay Fixed Potted LF E4JU 0066 AAAA A 6, 8 3A Relay Fixed Potted LF E4HW 0150 AAAA A 6, 8 3A Relay Fixed Potted LF E4JW 0066 AAAA A 6, 8 3A Relay Fixed Potted CF E4HH 0150 AAAA A 6, 8 3A Relay Fixed Potted CF E4JH 0066 AAAA A 6, 8 3A Relay Fixed Potted LF C4SU 0450 AAAA A 6, 8 3A Relay Fixed Potted LF C4TU 0232 AAAA A 6, 8
Watlow Controls 1/31/2005 Page 27
Line
Series 142
142A-3684-1300 120 VAC E t/c 450°F High limit 142A-3684-1300 120 VAC E t/c 232°C High limit 142A-3684-1400 120 VAC E t/c 450°F On/Off 142A-3684-1400 120 VAC E t/c 232°C On/Off 142A-3684-2200 230 VAC E t/c 450°F High limit 142A-3684-2200 230 VAC E t/c 232°C High limit 142A-3684-2300 230 VAC E t/c 450°F High limit 142A-3684-2300 230 VAC E t/c 232°C High limit 142A-3684-2400 230 VAC E t/c 450°F On/Off 142A-3684-2400 230 VAC E t/c 232°C On/Off 142A-3685-1200 120 VAC E t/c 265°F High limit 142A-3685-1200 120 VAC E t/c 129°C High limit 142A-3685-1300 120 VAC E t/c 265°F High limit 142A-3685-1300 120 VAC E t/c 129°C High limit 142A-3685-1400 120 VAC E t/c 265°F On/Off 142A-3685-1400 120 VAC E t/c 129°C On/Off 142A-3685-2200 230 VAC E t/c 265°F High limit 142A-3685-2200 230 VAC E t/c 129°C High limit 142A-3685-2300 230 VAC E t/c 265°F High limit 142A-3685-2300 230 VAC E t/c 129°C High limit 142A-3685-2400 230 VAC E t/c 265°F On/Off 142A-3685-2400 230 VAC E t/c 129°C On/Off 142A-3687-1200 120 VAC K t/c 1382°F High limit 142A-3687-1200 120 VAC K t/c 750°C High limit 142A-3687-1300 120 VAC K t/c 1382°F High limit 142A-3687-1300 120 VAC K t/c 750°C High limit 142A-3687-1400 120 VAC K t/c 1382°F On/Off 142A-3687-1400 120 VAC K t/c 750°C On/Off 142A-3687-2200 230 VAC K t/c 1382°F High limit 142A-3687-2200 230 VAC K t/c 750°C High limit 142A-3687-2300 230 VAC K t/c 1382°F High limit 142A-3687-2300 230 VAC K t/c 750°C High limit 142A-3687-2400 230 VAC K t/c 1382°F On/Off 142A-3687-2400 230 VAC K t/c 750°C On/Off 142A-3688-1200 120 VAC J t/c 215°F High limit 142A-3688-1200 120 VAC J t/c 102°C High limit 142A-3688-1300 120 VAC J t/c 215°F High limit 142A-3688-1300 120 VAC J t/c 102°C High limit 142A-3688-1400 120 VAC J t/c 215°F On/Off 142A-3688-1400 120 VAC J t/c 102°C On/Off 142A-3688-2200 230 VAC J t/c 215°F High limit
Voltage Input Temp Range Control Mode Action Output Set Point Mounting Retrofit
Series 142
Automatic Reset Automatic Reset
Heat
Heat Manual Reset Manual Reset
Automatic Reset Automatic Reset
Heat
Heat Manual Reset Manual Reset
Automatic Reset Automatic Reset
Heat
Heat Manual Reset Manual Reset
Automatic Reset Automatic Reset
Heat
Heat Manual Reset Manual Reset
Automatic Reset Automatic Reset
Heat
Heat Manual Reset Manual Reset
Automatic Reset Automatic Reset
Heat
Heat Manual Reset Manual Reset
Automatic Reset Automatic Reset
Heat
Heat Manual Reset
See Notes
Below
3A Relay Fixed Potted LF C4SW 0450 AAAA A 6, 8 3A Relay Fixed Potted LF C4TW 0232 AAAA A 6, 8 3A Relay Fixed Potted CF C4SH 0450 AAAA A 6, 8 3A Relay Fixed Potted CF C4TH 0232 AAAA A 6, 8 3A Relay Fixed Potted LF E4SU 0450 AAAA A 6, 8 3A Relay Fixed Potted LF E4TU 0232 AAAA A 6, 8 3A Relay Fixed Potted LF E4SW 0450 AAAA A 6, 8 3A Relay Fixed Potted LF E4TW 0232 AAAA A 6, 8 3A Relay Fixed Potted CF E4SH 0450 AAAA A 6, 8 3A Relay Fixed Potted CF E4TH 0232 AAAA A 6, 8 3A Relay Fixed Potted LF C4SU 0265 AAAA A 6, 8 3A Relay Fixed Potted LF C4TU 0129 AAAA A 6, 8 3A Relay Fixed Potted LF C4SW 0265 AAAA A 6, 8 3A Relay Fixed Potted LF C4TW 0129 AAAA A 6, 8 3A Relay Fixed Potted CF C4SH 0265 AAAA A 6, 8 3A Relay Fixed Potted CF C4TH 0129 AAAA A 6, 8 3A Relay Fixed Potted LF E4SU 0265 AAAA A 6, 8 3A Relay Fixed Potted LF E4TU 0129 AAAA A 6, 8 3A Relay Fixed Potted LF E4SW 0265 AAAA A 6, 8 3A Relay Fixed Potted LF E4TW 0129 AAAA A 6, 8 3A Relay Fixed Potted CF E4SH 0265 AAAA A 6, 8 3A Relay Fixed Potted CF E4TH 0129 AAAA A 6, 8 3A Relay Fixed Potted LF C4KU 1382 AAAA A 6, 8 3A Relay Fixed Potted LF C4LU 0750 AAAA A 6, 8 3A Relay Fixed Potted LF C4KW 1382 AAAA A 6, 8 3A Relay Fixed Potted LF C4LW 0750 AAAA A 6, 8 3A Relay Fixed Potted CF C4KH 1382 AAAA A 6, 8 3A Relay Fixed Potted CF C4LH 0750 AAAA A 6, 8 3A Relay Fixed Potted LF E4KU 1382 AAAA A 6, 8 3A Relay Fixed Potted LF E4LU 0750 AAAA A 6, 8 3A Relay Fixed Potted LF E4KW 1382 AAAA A 6, 8 3A Relay Fixed Potted LF E4LW 0750 AAAA A 6, 8 3A Relay Fixed Potted CF E4KH 1382 AAAA A 6, 8 3A Relay Fixed Potted CF E4LH 0750 AAAA A 6, 8 3A Relay Fixed Potted LF C4HU 0215 AAAA A 6, 8 3A Relay Fixed Potted LF C4JU 0102 AAAA A 6, 8 3A Relay Fixed Potted LF C4HW 0215 AAAA A 6, 8 3A Relay Fixed Potted LF C4JW 0102 AAAA A 6, 8 3A Relay Fixed Potted CF C4HH 0215 AAAA A 6, 8 3A Relay Fixed Potted CF C4JH 0102 AAAA A 6, 8 3A Relay Fixed Potted LF E4HU 0215 AAAA A 6, 8
Watlow Controls 1/31/2005 Page 28
Line
Series 142
142A-3688-2200 230 VAC J t/c 102°C High limit 142A-3688-2300 230 VAC J t/c 215°F High limit 142A-3688-2300 230 VAC J t/c 102°C High limit 142A-3688-2400 230 VAC J t/c 215°F On/Off 142A-3688-2400 230 VAC J t/c 102°C On/Off 142A-3689-1200 120 VAC J t/c 444°F High limit 142A-3689-1200 120 VAC J t/c 229°C High limit 142A-3689-1300 120 VAC J t/c 444°F High limit 142A-3689-1300 120 VAC J t/c 229°C High limit 142A-3689-1400 120 VAC J t/c 444°F On/Off 142A-3689-1400 120 VAC J t/c 229°C On/Off 142A-3689-2200 230 VAC J t/c 444°F High limit 142A-3689-2200 230 VAC J t/c 229°C High limit 142A-3689-2300 230 VAC J t/c 444°F High limit 142A-3689-2300 230 VAC J t/c 229°C High limit 142A-3689-2400 230 VAC J t/c 444°F On/Off 142A-3689-2400 230 VAC J t/c 229°C On/Off 142A-3690-1200 120 VAC K t/c 600°F High limit 142A-3690-1200 120 VAC K t/c 315°C High limit 142A-3690-1300 120 VAC K t/c 600°F High limit 142A-3690-1300 120 VAC K t/c 315°C High limit 142A-3690-1400 120 VAC K t/c 600°F On/Off 142A-3690-1400 120 VAC K t/c 315°C On/Off 142A-3690-2200 230 VAC K t/c 600°F High limit 142A-3690-2200 230 VAC K t/c 315°C High limit 142A-3690-2300 230 VAC K t/c 600°F High limit 142A-3690-2300 230 VAC K t/c 315°C High limit 142A-3690-2400 230 VAC K t/c 600°F On/Off 142A-3690-2400 230 VAC K t/c 315°C On/Off 142A-3691-1200 120 VAC K t/c 875°F High limit 142A-3691-1200 120 VAC K t/c 468°C High limit 142A-3691-1300 120 VAC K t/c 875°F High limit 142A-3691-1300 120 VAC K t/c 468°C High limit 142A-3691-1400 120 VAC K t/c 875°F On/Off 142A-3691-1400 120 VAC K t/c 468°C On/Off 142A-3691-2200 230 VAC K t/c 875°F High limit 142A-3691-2200 230 VAC K t/c 468°C High limit 142A-3691-2300 230 VAC K t/c 875°F High limit 142A-3691-2300 230 VAC K t/c 468°C High limit 142A-3691-2400 230 VAC K t/c 875°F On/Off 142A-3691-2400 230 VAC K t/c 468°C On/Off
Voltage Input Temp Range Control Mode Action Output Set Point Mounting Retrofit
Series 142
Manual Reset
Automatic Reset Automatic Reset
Heat
Heat Manual Reset Manual Reset
Automatic Reset Automatic Reset
Heat
Heat Manual Reset Manual Reset
Automatic Reset Automatic Reset
Heat
Heat Manual Reset Manual Reset
Automatic Reset Automatic Reset
Heat
Heat Manual Reset Manual Reset
Automatic Reset Automatic Reset
Heat
Heat Manual Reset Manual Reset
Automatic Reset Automatic Reset
Heat
Heat Manual Reset Manual Reset
Automatic Reset Automatic Reset
Heat
Heat
See Notes
Below
3A Relay Fixed Potted LF E4JU 0102 AAAA A 6, 8 3A Relay Fixed Potted LF E4HW 0215 AAAA A 6, 8 3A Relay Fixed Potted LF E4JW 0102 AAAA A 6, 8 3A Relay Fixed Potted CF E4HH 0215 AAAA A 6, 8 3A Relay Fixed Potted CF E4JH 0102 AAAA A 6, 8 3A Relay Fixed Potted LF C4HU 0444 AAAA A 6, 8 3A Relay Fixed Potted LF C4JU 0229 AAAA A 6, 8 3A Relay Fixed Potted LF C4HW 0444 AAAA A 6, 8 3A Relay Fixed Potted LF C4JW 0229 AAAA A 6, 8 3A Relay Fixed Potted CF C4HH 0444 AAAA A 6, 8 3A Relay Fixed Potted CF C4JH 0229 AAAA A 6, 8 3A Relay Fixed Potted LF E4HU 0444 AAAA A 6, 8 3A Relay Fixed Potted LF E4JU 0229 AAAA A 6, 8 3A Relay Fixed Potted LF E4HW 0444 AAAA A 6, 8 3A Relay Fixed Potted LF E4JW 0229 AAAA A 6, 8 3A Relay Fixed Potted CF E4HH 0444 AAAA A 6, 8 3A Relay Fixed Potted CF E4JH 0229 AAAA A 6, 8 3A Relay Fixed Potted LF C4KU 0600 AAAA A 6, 8 3A Relay Fixed Potted LF C4LU 0315 AAAA A 6, 8 3A Relay Fixed Potted LF C4KW 0600 AAAA A 6, 8 3A Relay Fixed Potted LF C4LW 0315 AAAA A 6, 8 3A Relay Fixed Potted CF C4KH 0600 AAAA A 6, 8 3A Relay Fixed Potted CF C4LH 0315 AAAA A 6, 8 3A Relay Fixed Potted LF E4KU 0600 AAAA A 6, 8 3A Relay Fixed Potted LF E4LU 0315 AAAA A 6, 8 3A Relay Fixed Potted LF E4KW 0600 AAAA A 6, 8 3A Relay Fixed Potted LF E4LW 0315 AAAA A 6, 8 3A Relay Fixed Potted CF E4KH 0600 AAAA A 6, 8 3A Relay Fixed Potted CF E4LH 0315 AAAA A 6, 8 3A Relay Fixed Potted LF C4KU 0875 AAAA A 6, 8 3A Relay Fixed Potted LF C4LU 0468 AAAA A 6, 8 3A Relay Fixed Potted LF C4KW 0875 AAAA A 6, 8 3A Relay Fixed Potted LF C4LW 0468 AAAA A 6, 8 3A Relay Fixed Potted CF C4KH 0875 AAAA A 6, 8 3A Relay Fixed Potted CF C4LH 0468 AAAA A 6, 8 3A Relay Fixed Potted LF E4KU 0875 AAAA A 6, 8 3A Relay Fixed Potted LF E4LU 0468 AAAA A 6, 8 3A Relay Fixed Potted LF E4KW 0875 AAAA A 6, 8 3A Relay Fixed Potted LF E4LW 0468 AAAA A 6, 8 3A Relay Fixed Potted CF E4KH 0875 AAAA A 6, 8 3A Relay Fixed Potted CF E4LH 0468 AAAA A 6, 8
Watlow Controls 1/31/2005 Page 29
Line
Series 142
142A-3692-1200 120 VAC K t/c 2000°F High limit 142A-3692-1200 120 VAC K t/c 1093°C High limit 142A-3692-1300 120 VAC K t/c 2000°F High limit 142A-3692-1300 120 VAC K t/c 1093°C High limit 142A-3692-1400 120 VAC K t/c 2000°F On/Off 142A-3692-1400 120 VAC K t/c 1093°C On/Off 142A-3692-2200 230 VAC K t/c 2000°F High limit 142A-3692-2200 230 VAC K t/c 1093°C High limit 142A-3692-2300 230 VAC K t/c 2000°F High limit 142A-3692-2300 230 VAC K t/c 1093°C High limit 142A-3692-2400 230 VAC K t/c 2000°F On/Off 142A-3692-2400 230 VAC K t/c 1093°C On/Off 142A-3693-1200 120 VAC J t/c 650°F High limit 142A-3693-1200 120 VAC J t/c 343°C High limit 142A-3693-1300 120 VAC J t/c 650°F High limit 142A-3693-1300 120 VAC J t/c 343°C High limit 142A-3693-1400 120 VAC J t/c 650°F On/Off 142A-3693-1400 120 VAC J t/c 343°C On/Off 142A-3693-2200 230 VAC J t/c 650°F High limit 142A-3693-2200 230 VAC J t/c 343°C High limit 142A-3693-2300 230 VAC J t/c 650°F High limit 142A-3693-2300 230 VAC J t/c 343°C High limit 142A-3693-2400 230 VAC J t/c 650°F On/Off 142A-3693-2400 230 VAC J t/c 343°C On/Off 142A-3694-1200 120 VAC T t/c 275°F High limit 142A-3694-1200 120 VAC T t/c 135°C High limit 142A-3694-1300 120 VAC T t/c 275°F High limit 142A-3694-1300 120 VAC T t/c 135°C High limit 142A-3694-1400 120 VAC T t/c 275°F On/Off 142A-3694-1400 120 VAC T t/c 135°C On/Off 142A-3694-2200 230 VAC T t/c 275°F High limit 142A-3694-2200 230 VAC T t/c 135°C High limit 142A-3694-2300 230 VAC T t/c 275°F High limit 142A-3694-2300 230 VAC T t/c 135°C High limit 142A-3694-2400 230 VAC T t/c 275°F On/Off 142A-3694-2400 230 VAC T t/c 135°C On/Off 142A-3695-1200 120 VAC K t/c 572°F High limit 142A-3695-1200 120 VAC K t/c 300°C High limit 142A-3695-1300 120 VAC K t/c 572°F High limit 142A-3695-1300 120 VAC K t/c 300°C High limit 142A-3695-1400 120 VAC K t/c 572°F On/Off
Voltage Input Temp Range Control Mode Action Output Set Point Mounting Retrofit
Series 142
Manual Reset Manual Reset
Automatic Reset Automatic Reset
Heat
Heat Manual Reset Manual Reset
Automatic Reset Automatic Reset
Heat
Heat Manual Reset Manual Reset
Automatic Reset Automatic Reset
Heat
Heat Manual Reset Manual Reset
Automatic Reset Automatic Reset
Heat
Heat Manual Reset Manual Reset
Automatic Reset Automatic Reset
Heat
Heat Manual Reset Manual Reset
Automatic Reset Automatic Reset
Heat
Heat Manual Reset Manual Reset
Automatic Reset Automatic Reset
Heat
See Notes
Below
3A Relay Fixed Potted LF C4KU 2000 AAAA A 6, 8 3A Relay Fixed Potted LF C4LU 1093 AAAA A 6, 8 3A Relay Fixed Potted LF C4KW 2000 AAAA A 6, 8 3A Relay Fixed Potted LF C4LW 1093 AAAA A 6, 8 3A Relay Fixed Potted CF C4KH 2000 AAAA A 6, 8 3A Relay Fixed Potted CF C4LH 1093 AAAA A 6, 8 3A Relay Fixed Potted LF E4KU 2000 AAAA A 6, 8 3A Relay Fixed Potted LF E4LU 1093 AAAA A 6, 8 3A Relay Fixed Potted LF E4KW 2000 AAAA A 6, 8 3A Relay Fixed Potted LF E4LW 1093 AAAA A 6, 8 3A Relay Fixed Potted CF E4KH 2000 AAAA A 6, 8 3A Relay Fixed Potted CF E4LH 1093 AAAA A 6, 8 3A Relay Fixed Potted LF C4HU 0650 AAAA A 6, 8 3A Relay Fixed Potted LF C4JU 0343 AAAA A 6, 8 3A Relay Fixed Potted LF C4HW 0650 AAAA A 6, 8 3A Relay Fixed Potted LF C4JW 0343 AAAA A 6, 8 3A Relay Fixed Potted CF C4HH 0650 AAAA A 6, 8 3A Relay Fixed Potted CF C4JH 0343 AAAA A 6, 8 3A Relay Fixed Potted LF E4HU 0650 AAAA A 6, 8 3A Relay Fixed Potted LF E4JU 0343 AAAA A 6, 8 3A Relay Fixed Potted LF E4HW 0650 AAAA A 6, 8 3A Relay Fixed Potted LF E4JW 0343 AAAA A 6, 8 3A Relay Fixed Potted CF E4HH 0650 AAAA A 6, 8 3A Relay Fixed Potted CF E4JH 0343 AAAA A 6, 8 3A Relay Fixed Potted LF C4MU 0275 AAAA A 6, 8 3A Relay Fixed Potted LF C4NU 0135 AAAA A 6, 8 3A Relay Fixed Potted LF C4MW 0275 AAAA A 6, 8 3A Relay Fixed Potted LF C4NW 0135 AAAA A 6, 8 3A Relay Fixed Potted CF C4MH 0275 AAAA A 6, 8 3A Relay Fixed Potted CF C4NH 0135 AAAA A 6, 8 3A Relay Fixed Potted LF E4MU 0275 AAAA A 6, 8 3A Relay Fixed Potted LF E4NU 0135 AAAA A 6, 8 3A Relay Fixed Potted LF E4MW 0275 AAAA A 6, 8 3A Relay Fixed Potted LF E4NW 0135 AAAA A 6, 8 3A Relay Fixed Potted CF E4MH 0275 AAAA A 6, 8 3A Relay Fixed Potted CF E4NH 0135 AAAA A 6, 8 3A Relay Fixed Potted LF C4KU 0572 AAAA A 6, 8 3A Relay Fixed Potted LF C4LU 0300 AAAA A 6, 8 3A Relay Fixed Potted LF C4KW 0572 AAAA A 6, 8 3A Relay Fixed Potted LF C4LW 0300 AAAA A 6, 8 3A Relay Fixed Potted CF C4KH 0572 AAAA A 6, 8
Watlow Controls 1/31/2005 Page 30
Line
Series 142
142A-3695-1400 120 VAC K t/c 300°C On/Off 142A-3695-2200 230 VAC K t/c 572°F High limit 142A-3695-2200 230 VAC K t/c 300°C High limit 142A-3695-2300 230 VAC K t/c 572°F High limit 142A-3695-2300 230 VAC K t/c 300°C High limit 142A-3695-2400 230 VAC K t/c 572°F On/Off 142A-3695-2400 230 VAC K t/c 300°C On/Off 142A-3697-1200 120 VAC J t/c 825°F High limit 142A-3697-1200 120 VAC J t/c 441°C High limit 142A-3697-1300 120 VAC J t/c 825°F High limit 142A-3697-1300 120 VAC J t/c 441°C High limit 142A-3697-1400 120 VAC J t/c 825°F On/Off 142A-3697-1400 120 VAC J t/c 441°C On/Off 142A-3697-2200 230 VAC J t/c 825°F High limit 142A-3697-2200 230 VAC J t/c 441°C High limit 142A-3697-2300 230 VAC J t/c 825°F High limit 142A-3697-2300 230 VAC J t/c 441°C High limit 142A-3697-2400 230 VAC J t/c 825°F On/Off 142A-3697-2400 230 VAC J t/c 441°C On/Off 142A-3698-1200 120 VAC J t/c 450°F High limit 142A-3698-1200 120 VAC J t/c 232°C High limit 142A-3698-1300 120 VAC J t/c 450°F High limit 142A-3698-1300 120 VAC J t/c 232°C High limit 142A-3698-1400 120 VAC J t/c 450°F On/Off 142A-3698-1400 120 VAC J t/c 232°C On/Off 142A-3698-2200 230 VAC J t/c 450°F High limit 142A-3698-2200 230 VAC J t/c 232°C High limit 142A-3698-2300 230 VAC J t/c 450°F High limit 142A-3698-2300 230 VAC J t/c 232°C High limit 142A-3698-2400 230 VAC J t/c 450°F On/Off 142A-3698-2400 230 VAC J t/c 232°C On/Off 142A-3699-1200 120 VAC J t/c 425°F High limit 142A-3699-1200 120 VAC J t/c 218°C High limit 142A-3699-1300 120 VAC J t/c 425°F High limit 142A-3699-1300 120 VAC J t/c 218°C High limit 142A-3699-1400 120 VAC J t/c 425°F On/Off 142A-3699-1400 120 VAC J t/c 218°C On/Off 142A-3699-2200 230 VAC J t/c 425°F High limit 142A-3699-2200 230 VAC J t/c 218°C High limit 142A-3699-2300 230 VAC J t/c 425°F High limit 142A-3699-2300 230 VAC J t/c 218°C High limit
Voltage Input Temp Range Control Mode Action Output Set Point Mounting Retrofit
Series 142
Heat Manual Reset Manual Reset
Automatic Reset Automatic Reset
Heat
Heat Manual Reset Manual Reset
Automatic Reset Automatic Reset
Heat
Heat Manual Reset Manual Reset
Automatic Reset Automatic Reset
Heat
Heat Manual Reset Manual Reset
Automatic Reset Automatic Reset
Heat
Heat Manual Reset Manual Reset
Automatic Reset Automatic Reset
Heat
Heat Manual Reset Manual Reset
Automatic Reset Automatic Reset
Heat
Heat Manual Reset Manual Reset
Automatic Reset Automatic Reset
See Notes
Below
3A Relay Fixed Potted CF C4LH 0300 AAAA A 6, 8 3A Relay Fixed Potted LF E4KU 0572 AAAA A 6, 8 3A Relay Fixed Potted LF E4LU 0300 AAAA A 6, 8 3A Relay Fixed Potted LF E4KW 0572 AAAA A 6, 8 3A Relay Fixed Potted LF E4LW 0300 AAAA A 6, 8 3A Relay Fixed Potted CF E4KH 0572 AAAA A 6, 8 3A Relay Fixed Potted CF E4LH 0300 AAAA A 6, 8 3A Relay Fixed Potted LF C4HU 0825 AAAA A 6, 8 3A Relay Fixed Potted LF C4JU 0441 AAAA A 6, 8 3A Relay Fixed Potted LF C4HW 0825 AAAA A 6, 8 3A Relay Fixed Potted LF C4JW 0441 AAAA A 6, 8 3A Relay Fixed Potted CF C4HH 0825 AAAA A 6, 8 3A Relay Fixed Potted CF C4JH 0441 AAAA A 6, 8 3A Relay Fixed Potted LF E4HU 0825 AAAA A 6, 8 3A Relay Fixed Potted LF E4JU 0441 AAAA A 6, 8 3A Relay Fixed Potted LF E4HW 0825 AAAA A 6, 8 3A Relay Fixed Potted LF E4JW 0441 AAAA A 6, 8 3A Relay Fixed Potted CF E4HH 0825 AAAA A 6, 8 3A Relay Fixed Potted CF E4JH 0441 AAAA A 6, 8 3A Relay Fixed Potted LF C4HU 0450 AAAA A 6, 8 3A Relay Fixed Potted LF C4JU 0232 AAAA A 6, 8 3A Relay Fixed Potted LF C4HW 0450 AAAA A 6, 8 3A Relay Fixed Potted LF C4JW 0232 AAAA A 6, 8 3A Relay Fixed Potted CF C4HH 0450 AAAA A 6, 8 3A Relay Fixed Potted CF C4JH 0232 AAAA A 6, 8 3A Relay Fixed Potted LF E4HU 0450 AAAA A 6, 8 3A Relay Fixed Potted LF E4JU 0232 AAAA A 6, 8 3A Relay Fixed Potted LF E4HW 0450 AAAA A 6, 8 3A Relay Fixed Potted LF E4JW 0232 AAAA A 6, 8 3A Relay Fixed Potted CF E4HH 0450 AAAA A 6, 8 3A Relay Fixed Potted CF E4JH 0232 AAAA A 6, 8 3A Relay Fixed Potted LF C4HU 0425 AAAA A 6, 8 3A Relay Fixed Potted LF C4JU 0218 AAAA A 6, 8 3A Relay Fixed Potted LF C4HW 0425 AAAA A 6, 8 3A Relay Fixed Potted LF C4JW 0218 AAAA A 6, 8 3A Relay Fixed Potted CF C4HH 0425 AAAA A 6, 8 3A Relay Fixed Potted CF C4JH 0218 AAAA A 6, 8 3A Relay Fixed Potted LF E4HU 0425 AAAA A 6, 8 3A Relay Fixed Potted LF E4JU 0218 AAAA A 6, 8 3A Relay Fixed Potted LF E4HW 0425 AAAA A 6, 8 3A Relay Fixed Potted LF E4JW 0218 AAAA A 6, 8
Watlow Controls 1/31/2005 Page 31
Line
Series 142
142A-3699-2400 230 VAC J t/c 425°F On/Off 142A-3699-2400 230 VAC J t/c 218°C On/Off 142A-3700-1200 120 VAC K t/c 200°F High limit 142A-3700-1200 120 VAC K t/c 93°C High limit 142A-3700-1300 120 VAC K t/c 200°F High limit 142A-3700-1300 120 VAC K t/c 93°C High limit 142A-3700-1400 120 VAC K t/c 200°F On/Off 142A-3700-1400 120 VAC K t/c 93°C On/Off 142A-3700-2200 230 VAC K t/c 200°F High limit 142A-3700-2200 230 VAC K t/c 93°C High limit 142A-3700-2300 230 VAC K t/c 200°F High limit 142A-3700-2300 230 VAC K t/c 93°C High limit 142A-3700-2400 230 VAC K t/c 200°F On/Off 142A-3700-2400 230 VAC K t/c 93°C On/Off 142A-3701-1200 120 VAC K t/c 150°F High limit 142A-3701-1200 120 VAC K t/c 66°C High limit 142A-3701-1300 120 VAC K t/c 150°F High limit 142A-3701-1300 120 VAC K t/c 66°C High limit 142A-3701-1400 120 VAC K t/c 150°F On/Off 142A-3701-1400 120 VAC K t/c 66°C On/Off 142A-3701-2200 230 VAC K t/c 150°F High limit 142A-3701-2200 230 VAC K t/c 66°C High limit 142A-3701-2300 230 VAC K t/c 150°F High limit 142A-3701-2300 230 VAC K t/c 66°C High limit 142A-3701-2400 230 VAC K t/c 150°F On/Off 142A-3701-2400 230 VAC K t/c 66°C On/Off 142A-3703-1200 120 VAC K t/c 140°F High limit 142A-3703-1200 120 VAC K t/c 60°C High limit 142A-3703-1300 120 VAC K t/c 140°F High limit 142A-3703-1300 120 VAC K t/c 60°C High limit 142A-3703-1400 120 VAC K t/c 140°F On/Off 142A-3703-1400 120 VAC K t/c 60°C On/Off 142A-3703-2200 230 VAC K t/c 140°F High limit 142A-3703-2200 230 VAC K t/c 60°C High limit 142A-3703-2300 230 VAC K t/c 140°F High limit 142A-3703-2300 230 VAC K t/c 60°C High limit 142A-3703-2400 230 VAC K t/c 140°F On/Off 142A-3703-2400 230 VAC K t/c 60°C On/Off 142A-3704-1200 120 VAC J t/c 465°F High limit 142A-3704-1200 120 VAC J t/c 241°C High limit 142A-3704-1300 120 VAC J t/c 465°F High limit
Voltage Input Temp Range Control Mode Action Output Set Point Mounting Retrofit
Series 142
Heat
Heat Manual Reset Manual Reset
Automatic Reset Automatic Reset
Heat
Heat Manual Reset Manual Reset
Automatic Reset Automatic Reset
Heat
Heat Manual Reset Manual Reset
Automatic Reset Automatic Reset
Heat
Heat Manual Reset Manual Reset
Automatic Reset Automatic Reset
Heat
Heat Manual Reset Manual Reset
Automatic Reset Automatic Reset
Heat
Heat Manual Reset Manual Reset
Automatic Reset Automatic Reset
Heat
Heat Manual Reset Manual Reset
Automatic Reset
See Notes
Below
3A Relay Fixed Potted CF E4HH 0425 AAAA A 6, 8 3A Relay Fixed Potted CF E4JH 0218 AAAA A 6, 8 3A Relay Fixed Potted LF C4KU 0200 AAAA A 6, 8 3A Relay Fixed Potted LF C4LU 0093 AAAA A 6, 8 3A Relay Fixed Potted LF C4KW 0200 AAAA A 6, 8 3A Relay Fixed Potted LF C4LW 0093 AAAA A 6, 8 3A Relay Fixed Potted CF C4KH 0200 AAAA A 6, 8 3A Relay Fixed Potted CF C4LH 0093 AAAA A 6, 8 3A Relay Fixed Potted LF E4KU 0200 AAAA A 6, 8 3A Relay Fixed Potted LF E4LU 0093 AAAA A 6, 8 3A Relay Fixed Potted LF E4KW 0200 AAAA A 6, 8 3A Relay Fixed Potted LF E4LW 0093 AAAA A 6, 8 3A Relay Fixed Potted CF E4KH 0200 AAAA A 6, 8 3A Relay Fixed Potted CF E4LH 0093 AAAA A 6, 8 3A Relay Fixed Potted LF C4KU 0150 AAAA A 6, 8 3A Relay Fixed Potted LF C4LU 0066 AAAA A 6, 8 3A Relay Fixed Potted LF C4KW 0150 AAAA A 6, 8 3A Relay Fixed Potted LF C4LW 0066 AAAA A 6, 8 3A Relay Fixed Potted CF C4KH 0150 AAAA A 6, 8 3A Relay Fixed Potted CF C4LH 0066 AAAA A 6, 8 3A Relay Fixed Potted LF E4KU 0150 AAAA A 6, 8 3A Relay Fixed Potted LF E4LU 0066 AAAA A 6, 8 3A Relay Fixed Potted LF E4KW 0150 AAAA A 6, 8 3A Relay Fixed Potted LF E4LW 0066 AAAA A 6, 8 3A Relay Fixed Potted CF E4KH 0150 AAAA A 6, 8 3A Relay Fixed Potted CF E4LH 0066 AAAA A 6, 8 3A Relay Fixed Potted LF C4KU 0140 AAAA A 6, 8 3A Relay Fixed Potted LF C4LU 0060 AAAA A 6, 8 3A Relay Fixed Potted LF C4KW 0140 AAAA A 6, 8 3A Relay Fixed Potted LF C4LW 0060 AAAA A 6, 8 3A Relay Fixed Potted CF C4KH 0140 AAAA A 6, 8 3A Relay Fixed Potted CF C4LH 0060 AAAA A 6, 8 3A Relay Fixed Potted LF E4KU 0140 AAAA A 6, 8 3A Relay Fixed Potted LF E4LU 0060 AAAA A 6, 8 3A Relay Fixed Potted LF E4KW 0140 AAAA A 6, 8 3A Relay Fixed Potted LF E4LW 0060 AAAA A 6, 8 3A Relay Fixed Potted CF E4KH 0140 AAAA A 6, 8 3A Relay Fixed Potted CF E4LH 0060 AAAA A 6, 8 3A Relay Fixed Potted LF C4HU 0465 AAAA A 6, 8 3A Relay Fixed Potted LF C4JU 0241 AAAA A 6, 8 3A Relay Fixed Potted LF C4HW 0465 AAAA A 6, 8
Watlow Controls 1/31/2005 Page 32
Line
Series 142
142A-3704-1300 120 VAC J t/c 241°C High limit 142A-3704-1400 120 VAC J t/c 465°F On/Off 142A-3704-1400 120 VAC J t/c 241°C On/Off 142A-3704-2200 230 VAC J t/c 465°F High limit 142A-3704-2200 230 VAC J t/c 241°C High limit 142A-3704-2300 230 VAC J t/c 465°F High limit 142A-3704-2300 230 VAC J t/c 241°C High limit 142A-3704-2400 230 VAC J t/c 465°F On/Off 142A-3704-2400 230 VAC J t/c 241°C On/Off 142A-3707-1200 120 VAC J t/c 360°F High limit 142A-3707-1200 120 VAC J t/c 182°C High limit 142A-3707-1300 120 VAC J t/c 360°F High limit 142A-3707-1300 120 VAC J t/c 182°C High limit 142A-3707-1400 120 VAC J t/c 360°F On/Off 142A-3707-1400 120 VAC J t/c 182°C On/Off 142A-3707-2200 230 VAC J t/c 360°F High limit 142A-3707-2200 230 VAC J t/c 182°C High limit 142A-3707-2300 230 VAC J t/c 360°F High limit 142A-3707-2300 230 VAC J t/c 182°C High limit 142A-3707-2400 230 VAC J t/c 360°F On/Off 142A-3707-2400 230 VAC J t/c 182°C On/Off 142A-3708-1200 120 VAC T t/c -4°F High limit 142A-3708-1200 120 VAC T t/c -20°C High limit 142A-3708-1300 120 VAC T t/c -4°F High limit 142A-3708-1300 120 VAC T t/c -20°C High limit 142A-3708-1400 120 VAC T t/c -4°F On/Off 142A-3708-1400 120 VAC T t/c -20°C On/Off 142A-3708-2200 230 VAC T t/c -4°F High limit 142A-3708-2200 230 VAC T t/c -20°C High limit 142A-3708-2300 230 VAC T t/c -4°F High limit 142A-3708-2300 230 VAC T t/c -20°C High limit 142A-3708-2400 230 VAC T t/c -4°F On/Off 142A-3708-2400 230 VAC T t/c -20°C On/Off 142A-3709-1200 120 VAC K t/c 975°F High limit 142A-3709-1200 120 VAC K t/c 524°C High limit 142A-3709-1300 120 VAC K t/c 975°F High limit 142A-3709-1300 120 VAC K t/c 524°C High limit 142A-3709-1400 120 VAC K t/c 975°F On/Off 142A-3709-1400 120 VAC K t/c 524°C On/Off 142A-3709-2200 230 VAC K t/c 975°F High limit 142A-3709-2200 230 VAC K t/c 524°C High limit
Voltage Input Temp Range Control Mode Action Output Set Point Mounting Retrofit
Series 142
Automatic Reset
Heat
Heat Manual Reset Manual Reset
Automatic Reset Automatic Reset
Heat
Heat Manual Reset Manual Reset
Automatic Reset Automatic Reset
Heat
Heat Manual Reset Manual Reset
Automatic Reset Automatic Reset
Heat
Heat Manual Reset Manual Reset
Automatic Reset Automatic Reset
Heat
Heat Manual Reset Manual Reset
Automatic Reset Automatic Reset
Heat
Heat Manual Reset Manual Reset
Automatic Reset Automatic Reset
Heat
Heat Manual Reset Manual Reset
See Notes
Below
3A Relay Fixed Potted LF C4JW 0241 AAAA A 6, 8 3A Relay Fixed Potted CF C4HH 0465 AAAA A 6, 8 3A Relay Fixed Potted CF C4JH 0241 AAAA A 6, 8 3A Relay Fixed Potted LF E4HU 0465 AAAA A 6, 8 3A Relay Fixed Potted LF E4JU 0241 AAAA A 6, 8 3A Relay Fixed Potted LF E4HW 0465 AAAA A 6, 8 3A Relay Fixed Potted LF E4JW 0241 AAAA A 6, 8 3A Relay Fixed Potted CF E4HH 0465 AAAA A 6, 8 3A Relay Fixed Potted CF E4JH 0241 AAAA A 6, 8 3A Relay Fixed Potted LF C4HU 0360 AAAA A 6, 8 3A Relay Fixed Potted LF C4JU 0182 AAAA A 6, 8 3A Relay Fixed Potted LF C4HW 0360 AAAA A 6, 8 3A Relay Fixed Potted LF C4JW 0182 AAAA A 6, 8 3A Relay Fixed Potted CF C4HH 0360 AAAA A 6, 8 3A Relay Fixed Potted CF C4JH 0182 AAAA A 6, 8 3A Relay Fixed Potted LF E4HU 0360 AAAA A 6, 8 3A Relay Fixed Potted LF E4JU 0182 AAAA A 6, 8 3A Relay Fixed Potted LF E4HW 0360 AAAA A 6, 8 3A Relay Fixed Potted LF E4JW 0182 AAAA A 6, 8 3A Relay Fixed Potted CF E4HH 0360 AAAA A 6, 8 3A Relay Fixed Potted CF E4JH 0182 AAAA A 6, 8 3A Relay Fixed Potted LF C4MU 00-4 AAAA A 6, 8 3A Relay Fixed Potted LF C4NU 0-20 AAAA A 6, 8 3A Relay Fixed Potted LF C4MW 00-4 AAAA A 6, 8 3A Relay Fixed Potted LF C4NW 0-20 AAAA A 6, 8 3A Relay Fixed Potted CF C4MH 00-4 AAAA A 6, 8 3A Relay Fixed Potted CF C4NH 0-20 AAAA A 6, 8 3A Relay Fixed Potted LF E4MU 00-4 AAAA A 6, 8 3A Relay Fixed Potted LF E4NU 0-20 AAAA A 6, 8 3A Relay Fixed Potted LF E4MW 00-4 AAAA A 6, 8 3A Relay Fixed Potted LF E4NW 0-20 AAAA A 6, 8 3A Relay Fixed Potted CF E4MH 00-4 AAAA A 6, 8 3A Relay Fixed Potted CF E4NH 0-20 AAAA A 6, 8 3A Relay Fixed Potted LF C4KU 0975 AAAA A 6, 8 3A Relay Fixed Potted LF C4LU 0524 AAAA A 6, 8 3A Relay Fixed Potted LF C4KW 0975 AAAA A 6, 8 3A Relay Fixed Potted LF C4LW 0524 AAAA A 6, 8 3A Relay Fixed Potted CF C4KH 0975 AAAA A 6, 8 3A Relay Fixed Potted CF C4LH 0524 AAAA A 6, 8 3A Relay Fixed Potted LF E4KU 0975 AAAA A 6, 8 3A Relay Fixed Potted LF E4LU 0524 AAAA A 6, 8
Watlow Controls 1/31/2005 Page 33
Line
Series 142
142A-3709-2300 230 VAC K t/c 975°F High limit 142A-3709-2300 230 VAC K t/c 524°C High limit 142A-3709-2400 230 VAC K t/c 975°F On/Off 142A-3709-2400 230 VAC K t/c 524°C On/Off 142A-3710-1200 120 VAC T t/c 482°F High limit 142A-3710-1200 120 VAC T t/c 250°C High limit 142A-3710-1300 120 VAC T t/c 482°F High limit 142A-3710-1300 120 VAC T t/c 250°C High limit 142A-3710-1400 120 VAC T t/c 482°F On/Off 142A-3710-1400 120 VAC T t/c 250°C On/Off 142A-3710-2200 230 VAC T t/c 482°F High limit 142A-3710-2200 230 VAC T t/c 250°C High limit 142A-3710-2300 230 VAC T t/c 482°F High limit 142A-3710-2300 230 VAC T t/c 250°C High limit 142A-3710-2400 230 VAC T t/c 482°F On/Off 142A-3710-2400 230 VAC T t/c 250°C On/Off 142A-3711-1200 120 VAC K t/c 125°F High limit 142A-3711-1200 120 VAC K t/c 52°C High limit 142A-3711-1300 120 VAC K t/c 125°F High limit 142A-3711-1300 120 VAC K t/c 52°C High limit 142A-3711-1400 120 VAC K t/c 125°F On/Off 142A-3711-1400 120 VAC K t/c 52°C On/Off 142A-3711-2200 230 VAC K t/c 125°F High limit 142A-3711-2200 230 VAC K t/c 52°C High limit 142A-3711-2300 230 VAC K t/c 125°F High limit 142A-3711-2300 230 VAC K t/c 52°C High limit 142A-3711-2400 230 VAC K t/c 125°F On/Off 142A-3711-2400 230 VAC K t/c 52°C On/Off 142A-3712-1200 120 VAC T t/c 347°F High limit 142A-3712-1200 120 VAC T t/c 175°C High limit 142A-3712-1300 120 VAC T t/c 347°F High limit 142A-3712-1300 120 VAC T t/c 175°C High limit 142A-3712-1400 120 VAC T t/c 347°F On/Off 142A-3712-1400 120 VAC T t/c 175°C On/Off 142A-3712-2200 230 VAC T t/c 347°F High limit 142A-3712-2200 230 VAC T t/c 175°C High limit 142A-3712-2300 230 VAC T t/c 347°F High limit 142A-3712-2300 230 VAC T t/c 175°C High limit 142A-3712-2400 230 VAC T t/c 347°F On/Off 142A-3712-2400 230 VAC T t/c 175°C On/Off 142A-3713-1200 120 VAC T t/c 392°F High limit
Voltage Input Temp Range Control Mode Action Output Set Point Mounting Retrofit
Series 142
Automatic Reset Automatic Reset
Heat
Heat Manual Reset Manual Reset
Automatic Reset Automatic Reset
Heat
Heat Manual Reset Manual Reset
Automatic Reset Automatic Reset
Heat
Heat Manual Reset Manual Reset
Automatic Reset Automatic Reset
Heat
Heat Manual Reset Manual Reset
Automatic Reset Automatic Reset
Heat
Heat Manual Reset Manual Reset
Automatic Reset Automatic Reset
Heat
Heat Manual Reset Manual Reset
Automatic Reset Automatic Reset
Heat
Heat Manual Reset
See Notes
Below
3A Relay Fixed Potted LF E4KW 0975 AAAA A 6, 8 3A Relay Fixed Potted LF E4LW 0524 AAAA A 6, 8 3A Relay Fixed Potted CF E4KH 0975 AAAA A 6, 8 3A Relay Fixed Potted CF E4LH 0524 AAAA A 6, 8 3A Relay Fixed Potted LF C4MU 0482 AAAA A 6, 8 3A Relay Fixed Potted LF C4NU 0250 AAAA A 6, 8 3A Relay Fixed Potted LF C4MW 0482 AAAA A 6, 8 3A Relay Fixed Potted LF C4NW 0250 AAAA A 6, 8 3A Relay Fixed Potted CF C4MH 0482 AAAA A 6, 8 3A Relay Fixed Potted CF C4NH 0250 AAAA A 6, 8 3A Relay Fixed Potted LF E4MU 0482 AAAA A 6, 8 3A Relay Fixed Potted LF E4NU 0250 AAAA A 6, 8 3A Relay Fixed Potted LF E4MW 0482 AAAA A 6, 8 3A Relay Fixed Potted LF E4NW 0250 AAAA A 6, 8 3A Relay Fixed Potted CF E4MH 0482 AAAA A 6, 8 3A Relay Fixed Potted CF E4NH 0250 AAAA A 6, 8 3A Relay Fixed Potted LF C4KU 0125 AAAA A 6, 8 3A Relay Fixed Potted LF C4LU 0052 AAAA A 6, 8 3A Relay Fixed Potted LF C4KW 0125 AAAA A 6, 8 3A Relay Fixed Potted LF C4LW 0052 AAAA A 6, 8 3A Relay Fixed Potted CF C4KH 0125 AAAA A 6, 8 3A Relay Fixed Potted CF C4LH 0052 AAAA A 6, 8 3A Relay Fixed Potted LF E4KU 0125 AAAA A 6, 8 3A Relay Fixed Potted LF E4LU 0052 AAAA A 6, 8 3A Relay Fixed Potted LF E4KW 0125 AAAA A 6, 8 3A Relay Fixed Potted LF E4LW 0052 AAAA A 6, 8 3A Relay Fixed Potted CF E4KH 0125 AAAA A 6, 8 3A Relay Fixed Potted CF E4LH 0052 AAAA A 6, 8 3A Relay Fixed Potted LF C4MU 0347 AAAA A 6, 8 3A Relay Fixed Potted LF C4NU 0175 AAAA A 6, 8 3A Relay Fixed Potted LF C4MW 0347 AAAA A 6, 8 3A Relay Fixed Potted LF C4NW 0175 AAAA A 6, 8 3A Relay Fixed Potted CF C4MH 0347 AAAA A 6, 8 3A Relay Fixed Potted CF C4NH 0175 AAAA A 6, 8 3A Relay Fixed Potted LF E4MU 0347 AAAA A 6, 8 3A Relay Fixed Potted LF E4NU 0175 AAAA A 6, 8 3A Relay Fixed Potted LF E4MW 0347 AAAA A 6, 8 3A Relay Fixed Potted LF E4NW 0175 AAAA A 6, 8 3A Relay Fixed Potted CF E4MH 0347 AAAA A 6, 8 3A Relay Fixed Potted CF E4NH 0175 AAAA A 6, 8 3A Relay Fixed Potted LF C4MU 0392 AAAA A 6, 8
Watlow Controls 1/31/2005 Page 34
Line
Series 142
142A-3713-1200 120 VAC T t/c 200°C High limit 142A-3713-1300 120 VAC T t/c 392°F High limit 142A-3713-1300 120 VAC T t/c 200°C High limit 142A-3713-1400 120 VAC T t/c 392°F On/Off 142A-3713-1400 120 VAC T t/c 200°C On/Off 142A-3713-2200 230 VAC T t/c 392°F High limit 142A-3713-2200 230 VAC T t/c 200°C High limit 142A-3713-2300 230 VAC T t/c 392°F High limit 142A-3713-2300 230 VAC T t/c 200°C High limit 142A-3713-2400 230 VAC T t/c 392°F On/Off 142A-3713-2400 230 VAC T t/c 200°C On/Off 142A-3714-1200 120 VAC T t/c 175°F High limit 142A-3714-1200 120 VAC T t/c 79°C High limit 142A-3714-1300 120 VAC T t/c 175°F High limit 142A-3714-1300 120 VAC T t/c 79°C High limit 142A-3714-1400 120 VAC T t/c 175°F On/Off 142A-3714-1400 120 VAC T t/c 79°C On/Off 142A-3714-2200 230 VAC T t/c 175°F High limit 142A-3714-2200 230 VAC T t/c 79°C High limit 142A-3714-2300 230 VAC T t/c 175°F High limit 142A-3714-2300 230 VAC T t/c 79°C High limit 142A-3714-2400 230 VAC T t/c 175°F On/Off 142A-3714-2400 230 VAC T t/c 79°C On/Off 142A-3715-1200 120 VAC J t/c 265°F High limit 142A-3715-1200 120 VAC J t/c 129°C High limit 142A-3715-1300 120 VAC J t/c 265°F High limit 142A-3715-1300 120 VAC J t/c 129°C High limit 142A-3715-1400 120 VAC J t/c 265°F On/Off 142A-3715-1400 120 VAC J t/c 129°C On/Off 142A-3715-2200 230 VAC J t/c 265°F High limit 142A-3715-2200 230 VAC J t/c 129°C High limit 142A-3715-2300 230 VAC J t/c 265°F High limit 142A-3715-2300 230 VAC J t/c 129°C High limit 142A-3715-2400 230 VAC J t/c 265°F On/Off 142A-3715-2400 230 VAC J t/c 129°C On/Off 142A-3716-1200 120 VAC K t/c 122°F High limit 142A-3716-1200 120 VAC K t/c 50°C High limit 142A-3716-1300 120 VAC K t/c 122°F High limit 142A-3716-1300 120 VAC K t/c 50°C High limit 142A-3716-1400 120 VAC K t/c 122°F On/Off 142A-3716-1400 120 VAC K t/c 50°C On/Off
Voltage Input Temp Range Control Mode Action Output Set Point Mounting Retrofit
Series 142
Manual Reset
Automatic Reset Automatic Reset
Heat
Heat Manual Reset Manual Reset
Automatic Reset Automatic Reset
Heat
Heat Manual Reset Manual Reset
Automatic Reset Automatic Reset
Heat
Heat Manual Reset Manual Reset
Automatic Reset Automatic Reset
Heat
Heat Manual Reset Manual Reset
Automatic Reset Automatic Reset
Heat
Heat Manual Reset Manual Reset
Automatic Reset Automatic Reset
Heat
Heat Manual Reset Manual Reset
Automatic Reset Automatic Reset
Heat
Heat
See Notes
Below
3A Relay Fixed Potted LF C4NU 0200 AAAA A 6, 8 3A Relay Fixed Potted LF C4MW 0392 AAAA A 6, 8 3A Relay Fixed Potted LF C4NW 0200 AAAA A 6, 8 3A Relay Fixed Potted CF C4MH 0392 AAAA A 6, 8 3A Relay Fixed Potted CF C4NH 0200 AAAA A 6, 8 3A Relay Fixed Potted LF E4MU 0392 AAAA A 6, 8 3A Relay Fixed Potted LF E4NU 0200 AAAA A 6, 8 3A Relay Fixed Potted LF E4MW 0392 AAAA A 6, 8 3A Relay Fixed Potted LF E4NW 0200 AAAA A 6, 8 3A Relay Fixed Potted CF E4MH 0392 AAAA A 6, 8 3A Relay Fixed Potted CF E4NH 0200 AAAA A 6, 8 3A Relay Fixed Potted LF C4MU 0175 AAAA A 6, 8 3A Relay Fixed Potted LF C4NU 0079 AAAA A 6, 8 3A Relay Fixed Potted LF C4MW 0175 AAAA A 6, 8 3A Relay Fixed Potted LF C4NW 0079 AAAA A 6, 8 3A Relay Fixed Potted CF C4MH 0175 AAAA A 6, 8 3A Relay Fixed Potted CF C4NH 0079 AAAA A 6, 8 3A Relay Fixed Potted LF E4MU 0175 AAAA A 6, 8 3A Relay Fixed Potted LF E4NU 0079 AAAA A 6, 8 3A Relay Fixed Potted LF E4MW 0175 AAAA A 6, 8 3A Relay Fixed Potted LF E4NW 0079 AAAA A 6, 8 3A Relay Fixed Potted CF E4MH 0175 AAAA A 6, 8 3A Relay Fixed Potted CF E4NH 0079 AAAA A 6, 8 3A Relay Fixed Potted LF C4HU 00265 AAAA A 6, 8 3A Relay Fixed Potted LF C4JU 0129 AAAA A 6, 8 3A Relay Fixed Potted LF C4HW 00265 AAAA A 6, 8 3A Relay Fixed Potted LF C4JW 0129 AAAA A 6, 8 3A Relay Fixed Potted CF C4HH 00265 AAAA A 6, 8 3A Relay Fixed Potted CF C4JH 0129 AAAA A 6, 8 3A Relay Fixed Potted LF E4HU 00265 AAAA A 6, 8 3A Relay Fixed Potted LF E4JU 0129 AAAA A 6, 8 3A Relay Fixed Potted LF E4HW 00265 AAAA A 6, 8 3A Relay Fixed Potted LF E4JW 0129 AAAA A 6, 8 3A Relay Fixed Potted CF E4HH 00265 AAAA A 6, 8 3A Relay Fixed Potted CF E4JH 0129 AAAA A 6, 8 3A Relay Fixed Potted LF C4KU 0122 AAAA A 6, 8 3A Relay Fixed Potted LF C4LU 0050 AAAA A 6, 8 3A Relay Fixed Potted LF C4KW 0122 AAAA A 6, 8 3A Relay Fixed Potted LF C4LW 0050 AAAA A 6, 8 3A Relay Fixed Potted CF C4KH 0122 AAAA A 6, 8 3A Relay Fixed Potted CF C4LH 0050 AAAA A 6, 8
Watlow Controls 1/31/2005 Page 35
Line
Series 142
142A-3716-2200 230 VAC K t/c 122°F High limit 142A-3716-2200 230 VAC K t/c 50°C High limit 142A-3716-2300 230 VAC K t/c 122°F High limit 142A-3716-2300 230 VAC K t/c 50°C High limit 142A-3716-2400 230 VAC K t/c 122°F On/Off 142A-3716-2400 230 VAC K t/c 50°C On/Off 142A-3717-1200 120 VAC K t/c 1382°F High limit 142A-3717-1200 120 VAC K t/c 750°C High limit 142A-3717-1300 120 VAC K t/c 1382°F High limit 142A-3717-1300 120 VAC K t/c 750°C High limit 142A-3717-1400 120 VAC K t/c 1382°F On/Off 142A-3717-1400 120 VAC K t/c 750°C On/Off 142A-3717-2200 230 VAC K t/c 1382°F High limit 142A-3717-2200 230 VAC K t/c 750°C High limit 142A-3717-2300 230 VAC K t/c 1382°F High limit 142A-3717-2300 230 VAC K t/c 750°C High limit 142A-3717-2400 230 VAC K t/c 1382°F On/Off 142A-3717-2400 230 VAC K t/c 750°C On/Off 142A-3718-1200 120 VAC J t/c 61°F High limit 142A-3718-1200 120 VAC J t/c 16°C High limit 142A-3718-1300 120 VAC J t/c 61°F High limit 142A-3718-1300 120 VAC J t/c 16°C High limit 142A-3718-1400 120 VAC J t/c 61°F On/Off 142A-3718-1400 120 VAC J t/c 16°C On/Off 142A-3718-2200 230 VAC J t/c 61°F High limit 142A-3718-2200 230 VAC J t/c 16°C High limit 142A-3718-2300 230 VAC J t/c 61°F High limit 142A-3718-2300 230 VAC J t/c 16°C High limit 142A-3718-2400 230 VAC J t/c 61°F On/Off 142A-3718-2400 230 VAC J t/c 16°C On/Off 142A-3719-1200 120 VAC J t/c 230°F High limit 142A-3719-1200 120 VAC J t/c 110°C High limit 142A-3719-1300 120 VAC J t/c 230°F High limit 142A-3719-1300 120 VAC J t/c 110°C High limit 142A-3719-1400 120 VAC J t/c 230°F On/Off 142A-3719-1400 120 VAC J t/c 110°C On/Off 142A-3719-2200 230 VAC J t/c 230°F High limit 142A-3719-2200 230 VAC J t/c 110°C High limit 142A-3719-2300 230 VAC J t/c 230°F High limit 142A-3719-2300 230 VAC J t/c 110°C High limit 142A-3719-2400 230 VAC J t/c 230°F On/Off
Voltage Input Temp Range Control Mode Action Output Set Point Mounting Retrofit
Series 142
Manual Reset Manual Reset
Automatic Reset Automatic Reset
Heat
Heat Manual Reset Manual Reset
Automatic Reset Automatic Reset
Heat
Heat Manual Reset Manual Reset
Automatic Reset Automatic Reset
Heat
Heat Manual Reset Manual Reset
Automatic Reset Automatic Reset
Heat
Heat Manual Reset Manual Reset
Automatic Reset Automatic Reset
Heat
Heat Manual Reset Manual Reset
Automatic Reset Automatic Reset
Heat
Heat Manual Reset Manual Reset
Automatic Reset Automatic Reset
Heat
See Notes
Below
3A Relay Fixed Potted LF E4KU 0122 AAAA A 6, 8 3A Relay Fixed Potted LF E4LU 0050 AAAA A 6, 8 3A Relay Fixed Potted LF E4KW 0122 AAAA A 6, 8 3A Relay Fixed Potted LF E4LW 0050 AAAA A 6, 8 3A Relay Fixed Potted CF E4KH 0122 AAAA A 6, 8 3A Relay Fixed Potted CF E4LH 0050 AAAA A 6, 8 3A Relay Fixed Potted LF C4KU 1382 AAAA A 6, 8 3A Relay Fixed Potted LF C4LU 0750 AAAA A 6, 8 3A Relay Fixed Potted LF C4KW 1382 AAAA A 6, 8 3A Relay Fixed Potted LF C4LW 0750 AAAA A 6, 8 3A Relay Fixed Potted CF C4KH 1382 AAAA A 6, 8 3A Relay Fixed Potted CF C4LH 0750 AAAA A 6, 8 3A Relay Fixed Potted LF E4KU 1382 AAAA A 6, 8 3A Relay Fixed Potted LF E4LU 0750 AAAA A 6, 8 3A Relay Fixed Potted LF E4KW 1382 AAAA A 6, 8 3A Relay Fixed Potted LF E4LW 0750 AAAA A 6, 8 3A Relay Fixed Potted CF E4KH 1382 AAAA A 6, 8 3A Relay Fixed Potted CF E4LH 0750 AAAA A 6, 8 3A Relay Fixed Potted LF C4HU 0061 AAAA A 6, 8 3A Relay Fixed Potted LF C4JU 0016 AAAA A 6, 8 3A Relay Fixed Potted LF C4HW 0061 AAAA A 6, 8 3A Relay Fixed Potted LF C4JW 0016 AAAA A 6, 8 3A Relay Fixed Potted CF C4HH 0061 AAAA A 6, 8 3A Relay Fixed Potted CF C4JH 0016 AAAA A 6, 8 3A Relay Fixed Potted LF E4HU 0061 AAAA A 6, 8 3A Relay Fixed Potted LF E4JU 0016 AAAA A 6, 8 3A Relay Fixed Potted LF E4HW 0061 AAAA A 6, 8 3A Relay Fixed Potted LF E4JW 0016 AAAA A 6, 8 3A Relay Fixed Potted CF E4HH 0061 AAAA A 6, 8 3A Relay Fixed Potted CF E4JH 0016 AAAA A 6, 8 3A Relay Fixed Potted LF C4HU 0230 AAAA A 6, 8 3A Relay Fixed Potted LF C4JU 0110 AAAA A 6, 8 3A Relay Fixed Potted LF C4HW 0230 AAAA A 6, 8 3A Relay Fixed Potted LF C4JW 0110 AAAA A 6, 8 3A Relay Fixed Potted CF C4HH 0230 AAAA A 6, 8 3A Relay Fixed Potted CF C4JH 0110 AAAA A 6, 8 3A Relay Fixed Potted LF E4HU 0230 AAAA A 6, 8 3A Relay Fixed Potted LF E4JU 0110 AAAA A 6, 8 3A Relay Fixed Potted LF E4HW 0230 AAAA A 6, 8 3A Relay Fixed Potted LF E4JW 0110 AAAA A 6, 8 3A Relay Fixed Potted CF E4HH 0230 AAAA A 6, 8
Watlow Controls 1/31/2005 Page 36
Line
Series 142
142A-3719-2400 230 VAC J t/c 110°C On/Off 142A-3721-1200 120 VAC J t/c 100°F High limit 142A-3721-1200 120 VAC J t/c 38°C High limit 142A-3721-1300 120 VAC J t/c 100°F High limit 142A-3721-1300 120 VAC J t/c 38°C High limit 142A-3721-1400 120 VAC J t/c 100°F On/Off 142A-3721-1400 120 VAC J t/c 38°C On/Off 142A-3721-2200 230 VAC J t/c 100°F High limit 142A-3721-2200 230 VAC J t/c 38°C High limit 142A-3721-2300 230 VAC J t/c 100°F High limit 142A-3721-2300 230 VAC J t/c 38°C High limit 142A-3721-2400 230 VAC J t/c 100°F On/Off 142A-3721-2400 230 VAC J t/c 38°C On/Off 142A-3722-1200 120 VAC J t/c 75°F High limit 142A-3722-1200 120 VAC J t/c 24°C High limit 142A-3722-1300 120 VAC J t/c 75°F High limit 142A-3722-1300 120 VAC J t/c 24°C High limit 142A-3722-1400 120 VAC J t/c 75°F On/Off 142A-3722-1400 120 VAC J t/c 24°C On/Off 142A-3722-2200 230 VAC J t/c 75°F High limit 142A-3722-2200 230 VAC J t/c 24°C High limit 142A-3722-2300 230 VAC J t/c 75°F High limit 142A-3722-2300 230 VAC J t/c 24°C High limit 142A-3722-2400 230 VAC J t/c 75°F On/Off 142A-3722-2400 230 VAC J t/c 24°C On/Off 142A-3723-1200 120 VAC J t/c 140°F High limit 142A-3723-1200 120 VAC J t/c 60°C High limit 142A-3723-1300 120 VAC J t/c 140°F High limit 142A-3723-1300 120 VAC J t/c 60°C High limit 142A-3723-1400 120 VAC J t/c 140°F On/Off 142A-3723-1400 120 VAC J t/c 60°C On/Off 142A-3723-2200 230 VAC J t/c 140°F High limit 142A-3723-2200 230 VAC J t/c 60°C High limit 142A-3723-2300 230 VAC J t/c 140°F High limit 142A-3723-2300 230 VAC J t/c 60°C High limit 142A-3723-2400 230 VAC J t/c 140°F On/Off 142A-3723-2400 230 VAC J t/c 60°C On/Off 142A-3724-1200 120 VAC J t/c 160°F High limit 142A-3724-1200 120 VAC J t/c 71°C High limit 142A-3724-1300 120 VAC J t/c 160°F High limit 142A-3724-1300 120 VAC J t/c 71°C High limit
Voltage Input Temp Range Control Mode Action Output Set Point Mounting Retrofit
Series 142
Heat Manual Reset Manual Reset
Automatic Reset Automatic Reset
Heat
Heat Manual Reset Manual Reset
Automatic Reset Automatic Reset
Heat
Heat Manual Reset Manual Reset
Automatic Reset Automatic Reset
Heat
Heat Manual Reset Manual Reset
Automatic Reset Automatic Reset
Heat
Heat Manual Reset Manual Reset
Automatic Reset Automatic Reset
Heat
Heat Manual Reset Manual Reset
Automatic Reset Automatic Reset
Heat
Heat Manual Reset Manual Reset
Automatic Reset Automatic Reset
See Notes
Below
3A Relay Fixed Potted CF E4JH 0110 AAAA A 6, 8 3A Relay Fixed Potted LF C4HU 0100 AAAA A 6, 8 3A Relay Fixed Potted LF C4JU 0038 AAAA A 6, 8 3A Relay Fixed Potted LF C4HW 0100 AAAA A 6, 8 3A Relay Fixed Potted LF C4JW 0038 AAAA A 6, 8 3A Relay Fixed Potted CF C4HH 0100 AAAA A 6, 8 3A Relay Fixed Potted CF C4JH 0038 AAAA A 6, 8 3A Relay Fixed Potted LF E4HU 0100 AAAA A 6, 8 3A Relay Fixed Potted LF E4JU 0038 AAAA A 6, 8 3A Relay Fixed Potted LF E4HW 0100 AAAA A 6, 8 3A Relay Fixed Potted LF E4JW 0038 AAAA A 6, 8 3A Relay Fixed Potted CF E4HH 0100 AAAA A 6, 8 3A Relay Fixed Potted CF E4JH 0038 AAAA A 6, 8 3A Relay Fixed Potted LF C4HU 0075 AAAA A 6, 8 3A Relay Fixed Potted LF C4JU 0024 AAAA A 6, 8 3A Relay Fixed Potted LF C4HW 0075 AAAA A 6, 8 3A Relay Fixed Potted LF C4JW 0024 AAAA A 6, 8 3A Relay Fixed Potted CF C4HH 0075 AAAA A 6, 8 3A Relay Fixed Potted CF C4JH 0024 AAAA A 6, 8 3A Relay Fixed Potted LF E4HU 0075 AAAA A 6, 8 3A Relay Fixed Potted LF E4JU 0024 AAAA A 6, 8 3A Relay Fixed Potted LF E4HW 0075 AAAA A 6, 8 3A Relay Fixed Potted LF E4JW 0024 AAAA A 6, 8 3A Relay Fixed Potted CF E4HH 0075 AAAA A 6, 8 3A Relay Fixed Potted CF E4JH 0024 AAAA A 6, 8 3A Relay Fixed Potted LF C4HU 0140 AAAA A 6, 8 3A Relay Fixed Potted LF C4JU 0060 AAAA A 6, 8 3A Relay Fixed Potted LF C4HW 0140 AAAA A 6, 8 3A Relay Fixed Potted LF C4JW 0060 AAAA A 6, 8 3A Relay Fixed Potted CF C4HH 0140 AAAA A 6, 8 3A Relay Fixed Potted CF C4JH 0060 AAAA A 6, 8 3A Relay Fixed Potted LF E4HU 0140 AAAA A 6, 8 3A Relay Fixed Potted LF E4JU 0060 AAAA A 6, 8 3A Relay Fixed Potted LF E4HW 0140 AAAA A 6, 8 3A Relay Fixed Potted LF E4JW 0060 AAAA A 6, 8 3A Relay Fixed Potted CF E4HH 0140 AAAA A 6, 8 3A Relay Fixed Potted CF E4JH 0060 AAAA A 6, 8 3A Relay Fixed Potted LF C4HU 0160 AAAA A 6, 8 3A Relay Fixed Potted LF C4JU 0071 AAAA A 6, 8 3A Relay Fixed Potted LF C4HW 0160 AAAA A 6, 8 3A Relay Fixed Potted LF C4JW 0071 AAAA A 6, 8
Watlow Controls 1/31/2005 Page 37
Line
Series 142
142A-3724-1400 120 VAC J t/c 160°F On/Off 142A-3724-1400 120 VAC J t/c 71°C On/Off 142A-3724-2200 230 VAC J t/c 160°F High limit 142A-3724-2200 230 VAC J t/c 71°C High limit 142A-3724-2300 230 VAC J t/c 160°F High limit 142A-3724-2300 230 VAC J t/c 71°C High limit 142A-3724-2400 230 VAC J t/c 160°F On/Off 142A-3724-2400 230 VAC J t/c 71°C On/Off 142A-3725-1200 120 VAC J t/c 130°F High limit 142A-3725-1200 120 VAC J t/c 54°C High limit 142A-3725-1300 120 VAC J t/c 130°F High limit 142A-3725-1300 120 VAC J t/c 54°C High limit 142A-3725-1400 120 VAC J t/c 130°F On/Off 142A-3725-1400 120 VAC J t/c 54°C On/Off 142A-3725-2200 230 VAC J t/c 130°F High limit 142A-3725-2200 230 VAC J t/c 54°C High limit 142A-3725-2300 230 VAC J t/c 130°F High limit 142A-3725-2300 230 VAC J t/c 54°C High limit 142A-3725-2400 230 VAC J t/c 130°F On/Off 142A-3725-2400 230 VAC J t/c 54°C On/Off 142A-3726-1200 120 VAC K t/c 325°F High limit 142A-3726-1200 120 VAC K t/c 163°C High limit 142A-3726-1300 120 VAC K t/c 325°F High limit 142A-3726-1300 120 VAC K t/c 163°C High limit 142A-3726-1400 120 VAC K t/c 325°F On/Off 142A-3726-1400 120 VAC K t/c 163°C On/Off 142A-3726-2200 230 VAC K t/c 325°F High limit 142A-3726-2200 230 VAC K t/c 163°C High limit 142A-3726-2300 230 VAC K t/c 325°F High limit 142A-3726-2300 230 VAC K t/c 163°C High limit 142A-3726-2400 230 VAC K t/c 325°F On/Off 142A-3726-2400 230 VAC K t/c 163°C On/Off 142A-3727-1200 120 VAC J t/c 158°F High limit 142A-3727-1200 120 VAC J t/c 70°C High limit 142A-3727-1300 120 VAC J t/c 158°F High limit 142A-3727-1300 120 VAC J t/c 70°C High limit 142A-3727-1400 120 VAC J t/c 158°F On/Off 142A-3727-1400 120 VAC J t/c 70°C On/Off 142A-3727-2200 230 VAC J t/c 158°F High limit 142A-3727-2200 230 VAC J t/c 70°C High limit 142A-3727-2300 230 VAC J t/c 158°F High limit
Voltage Input Temp Range Control Mode Action Output Set Point Mounting Retrofit
Series 142
Heat
Heat Manual Reset Manual Reset
Automatic Reset Automatic Reset
Heat
Heat Manual Reset Manual Reset
Automatic Reset Automatic Reset
Heat
Heat Manual Reset Manual Reset
Automatic Reset Automatic Reset
Heat
Heat Manual Reset Manual Reset
Automatic Reset Automatic Reset
Heat
Heat Manual Reset Manual Reset
Automatic Reset Automatic Reset
Heat
Heat Manual Reset Manual Reset
Automatic Reset Automatic Reset
Heat
Heat Manual Reset Manual Reset
Automatic Reset
See Notes
Below
3A Relay Fixed Potted CF C4HH 0160 AAAA A 6, 8 3A Relay Fixed Potted CF C4JH 0071 AAAA A 6, 8 3A Relay Fixed Potted LF E4HU 0160 AAAA A 6, 8 3A Relay Fixed Potted LF E4JU 0071 AAAA A 6, 8 3A Relay Fixed Potted LF E4HW 0160 AAAA A 6, 8 3A Relay Fixed Potted LF E4JW 0071 AAAA A 6, 8 3A Relay Fixed Potted CF E4HH 0160 AAAA A 6, 8 3A Relay Fixed Potted CF E4JH 0071 AAAA A 6, 8 3A Relay Fixed Potted LF C4HU 0130 AAAA A 6, 8 3A Relay Fixed Potted LF C4JU 0054 AAAA A 6, 8 3A Relay Fixed Potted LF C4HW 0130 AAAA A 6, 8 3A Relay Fixed Potted LF C4JW 0054 AAAA A 6, 8 3A Relay Fixed Potted CF C4HH 0130 AAAA A 6, 8 3A Relay Fixed Potted CF C4JH 0054 AAAA A 6, 8 3A Relay Fixed Potted LF E4HU 0130 AAAA A 6, 8 3A Relay Fixed Potted LF E4JU 0054 AAAA A 6, 8 3A Relay Fixed Potted LF E4HW 0130 AAAA A 6, 8 3A Relay Fixed Potted LF E4JW 0054 AAAA A 6, 8 3A Relay Fixed Potted CF E4HH 0130 AAAA A 6, 8 3A Relay Fixed Potted CF E4JH 0054 AAAA A 6, 8 3A Relay Fixed Potted LF C4KU 0325 AAAA A 6, 8 3A Relay Fixed Potted LF C4LU 0163 AAAA A 6, 8 3A Relay Fixed Potted LF C4KW 0325 AAAA A 6, 8 3A Relay Fixed Potted LF C4LW 0163 AAAA A 6, 8 3A Relay Fixed Potted CF C4KH 0325 AAAA A 6, 8 3A Relay Fixed Potted CF C4LH 0163 AAAA A 6, 8 3A Relay Fixed Potted LF E4KU 0325 AAAA A 6, 8 3A Relay Fixed Potted LF E4LU 0163 AAAA A 6, 8 3A Relay Fixed Potted LF E4KW 0325 AAAA A 6, 8 3A Relay Fixed Potted LF E4LW 0163 AAAA A 6, 8 3A Relay Fixed Potted CF E4KH 0325 AAAA A 6, 8 3A Relay Fixed Potted CF E4LH 0163 AAAA A 6, 8 3A Relay Fixed Potted LF C4HU 0158 AAAA A 6, 8 3A Relay Fixed Potted LF C4JU 0070 AAAA A 6, 8 3A Relay Fixed Potted LF C4HW 0158 AAAA A 6, 8 3A Relay Fixed Potted LF C4JW 0070 AAAA A 6, 8 3A Relay Fixed Potted CF C4HH 0158 AAAA A 6, 8 3A Relay Fixed Potted CF C4JH 0070 AAAA A 6, 8 3A Relay Fixed Potted LF E4HU 0158 AAAA A 6, 8 3A Relay Fixed Potted LF E4JU 0070 AAAA A 6, 8 3A Relay Fixed Potted LF E4HW 0158 AAAA A 6, 8
Watlow Controls 1/31/2005 Page 38
Line
Series 142
142A-3727-2300 230 VAC J t/c 70°C High limit 142A-3727-2400 230 VAC J t/c 158°F On/Off 142A-3727-2400 230 VAC J t/c 70°C On/Off 142A-3728-1200 120 VAC K t/c 350°F High limit 142A-3728-1200 120 VAC K t/c 177°C High limit 142A-3728-1300 120 VAC K t/c 350°F High limit 142A-3728-1300 120 VAC K t/c 177°C High limit 142A-3728-1400 120 VAC K t/c 350°F On/Off 142A-3728-1400 120 VAC K t/c 177°C On/Off 142A-3728-2200 230 VAC K t/c 350°F High limit 142A-3728-2200 230 VAC K t/c 177°C High limit 142A-3728-2300 230 VAC K t/c 350°F High limit 142A-3728-2300 230 VAC K t/c 177°C High limit 142A-3728-2400 230 VAC K t/c 350°F On/Off 142A-3728-2400 230 VAC K t/c 177°C On/Off 142A-3729-1200 120 VAC J t/c 40°F High limit 142A-3729-1200 120 VAC J t/c 4°C High limit 142A-3729-1300 120 VAC J t/c 40°F High limit 142A-3729-1300 120 VAC J t/c 4°C High limit 142A-3729-1400 120 VAC J t/c 40°F On/Off 142A-3729-1400 120 VAC J t/c 4°C On/Off 142A-3729-2200 230 VAC J t/c 40°F High limit 142A-3729-2200 230 VAC J t/c 4°C High limit 142A-3729-2300 230 VAC J t/c 40°F High limit 142A-3729-2300 230 VAC J t/c 4°C High limit 142A-3729-2400 230 VAC J t/c 40°F On/Off 142A-3729-2400 230 VAC J t/c 4°C On/Off 142A-3730-1200 120 VAC J t/c 180°F High limit 142A-3730-1200 120 VAC J t/c 82°C High limit 142A-3730-1300 120 VAC J t/c 180°F High limit 142A-3730-1300 120 VAC J t/c 82°C High limit 142A-3730-1400 120 VAC J t/c 180°F On/Off 142A-3730-1400 120 VAC J t/c 82°C On/Off 142A-3730-2200 230 VAC J t/c 180°F High limit 142A-3730-2200 230 VAC J t/c 82°C High limit 142A-3730-2300 230 VAC J t/c 180°F High limit 142A-3730-2300 230 VAC J t/c 82°C High limit 142A-3730-2400 230 VAC J t/c 180°F On/Off 142A-3730-2400 230 VAC J t/c 82°C On/Off 142A-3731-1200 120 VAC K t/c 950°F High limit 142A-3731-1200 120 VAC K t/c 510°C High limit
Voltage Input Temp Range Control Mode Action Output Set Point Mounting Retrofit
Series 142
Automatic Reset
Heat
Heat Manual Reset Manual Reset
Automatic Reset Automatic Reset
Heat
Heat Manual Reset Manual Reset
Automatic Reset Automatic Reset
Heat
Heat Manual Reset Manual Reset
Automatic Reset Automatic Reset
Heat
Heat Manual Reset Manual Reset
Automatic Reset Automatic Reset
Heat
Heat Manual Reset Manual Reset
Automatic Reset Automatic Reset
Heat
Heat Manual Reset Manual Reset
Automatic Reset Automatic Reset
Heat
Heat Manual Reset Manual Reset
See Notes
Below
3A Relay Fixed Potted LF E4JW 0070 AAAA A 6, 8 3A Relay Fixed Potted CF E4HH 0158 AAAA A 6, 8 3A Relay Fixed Potted CF E4JH 0070 AAAA A 6, 8 3A Relay Fixed Potted LF C4KU 0350 AAAA A 6, 8 3A Relay Fixed Potted LF C4LU 0177 AAAA A 6, 8 3A Relay Fixed Potted LF C4KW 0350 AAAA A 6, 8 3A Relay Fixed Potted LF C4LW 0177 AAAA A 6, 8 3A Relay Fixed Potted CF C4KH 0350 AAAA A 6, 8 3A Relay Fixed Potted CF C4LH 0177 AAAA A 6, 8 3A Relay Fixed Potted LF E4KU 0350 AAAA A 6, 8 3A Relay Fixed Potted LF E4LU 0177 AAAA A 6, 8 3A Relay Fixed Potted LF E4KW 0350 AAAA A 6, 8 3A Relay Fixed Potted LF E4LW 0177 AAAA A 6, 8 3A Relay Fixed Potted CF E4KH 0350 AAAA A 6, 8 3A Relay Fixed Potted CF E4LH 0177 AAAA A 6, 8 3A Relay Fixed Potted LF C4HU 0040 AAAA A 6, 8 3A Relay Fixed Potted LF C4JU 0004 AAAA A 6, 8 3A Relay Fixed Potted LF C4HW 0040 AAAA A 6, 8 3A Relay Fixed Potted LF C4JW 0004 AAAA A 6, 8 3A Relay Fixed Potted CF C4HH 0040 AAAA A 6, 8 3A Relay Fixed Potted CF C4JH 0004 AAAA A 6, 8 3A Relay Fixed Potted LF E4HU 0040 AAAA A 6, 8 3A Relay Fixed Potted LF E4JU 0004 AAAA A 6, 8 3A Relay Fixed Potted LF E4HW 0040 AAAA A 6, 8 3A Relay Fixed Potted LF E4JW 0004 AAAA A 6, 8 3A Relay Fixed Potted CF E4HH 0040 AAAA A 6, 8 3A Relay Fixed Potted CF E4JH 0004 AAAA A 6, 8 3A Relay Fixed Potted LF C4HU 0180 AAAA A 6, 8 3A Relay Fixed Potted LF C4JU 0082 AAAA A 6, 8 3A Relay Fixed Potted LF C4HW 0180 AAAA A 6, 8 3A Relay Fixed Potted LF C4JW 0082 AAAA A 6, 8 3A Relay Fixed Potted CF C4HH 0180 AAAA A 6, 8 3A Relay Fixed Potted CF C4JH 0082 AAAA A 6, 8 3A Relay Fixed Potted LF E4HU 0180 AAAA A 6, 8 3A Relay Fixed Potted LF E4JU 0082 AAAA A 6, 8 3A Relay Fixed Potted LF E4HW 0180 AAAA A 6, 8 3A Relay Fixed Potted LF E4JW 0082 AAAA A 6, 8 3A Relay Fixed Potted CF E4HH 0180 AAAA A 6, 8 3A Relay Fixed Potted CF E4JH 0082 AAAA A 6, 8 3A Relay Fixed Potted LF C4KU 0950 AAAA A 6, 8 3A Relay Fixed Potted LF C4LU 0510 AAAA A 6, 8
Watlow Controls 1/31/2005 Page 39
Line
Series 142
142A-3731-1300 120 VAC K t/c 950°F High limit 142A-3731-1300 120 VAC K t/c 510°C High limit 142A-3731-1400 120 VAC K t/c 950°F On/Off 142A-3731-1400 120 VAC K t/c 510°C On/Off 142A-3731-2200 230 VAC K t/c 950°F High limit 142A-3731-2200 230 VAC K t/c 510°C High limit 142A-3731-2300 230 VAC K t/c 950°F High limit 142A-3731-2300 230 VAC K t/c 510°C High limit 142A-3731-2400 230 VAC K t/c 950°F On/Off 142A-3731-2400 230 VAC K t/c 510°C On/Off 142A-3734-1200 120 VAC E t/c 400°F High limit 142A-3734-1200 120 VAC E t/c 204°C High limit 142A-3734-1300 120 VAC E t/c 400°F High limit 142A-3734-1300 120 VAC E t/c 204°C High limit 142A-3734-1400 120 VAC E t/c 400°F On/Off 142A-3734-1400 120 VAC E t/c 204°C On/Off 142A-3734-2200 230 VAC E t/c 400°F High limit 142A-3734-2200 230 VAC E t/c 204°C High limit 142A-3734-2300 230 VAC E t/c 400°F High limit 142A-3734-2300 230 VAC E t/c 204°C High limit 142A-3734-2400 230 VAC E t/c 400°F On/Off 142A-3734-2400 230 VAC E t/c 204°C On/Off 142A-3735-1200 120 VAC J t/c 333°F High limit 142A-3735-1200 120 VAC J t/c 60°C High limit 142A-3735-1300 120 VAC J t/c 333°F High limit 142A-3735-1300 120 VAC J t/c 60°C High limit 142A-3735-1400 120 VAC J t/c 333°F On/Off 142A-3735-1400 120 VAC J t/c 60°C On/Off 142A-3735-2200 230 VAC J t/c 333°F High limit 142A-3735-2200 230 VAC J t/c 60°C High limit 142A-3735-2300 230 VAC J t/c 333°F High limit 142A-3735-2300 230 VAC J t/c 60°C High limit 142A-3735-2400 230 VAC J t/c 333°F On/Off 142A-3735-2400 230 VAC J t/c 60°C On/Off
Voltage Input Temp Range Control Mode Action Output Set Point Mounting Retrofit
Series 142
Automatic Reset Automatic Reset
Heat
Heat Manual Reset Manual Reset
Automatic Reset Automatic Reset
Heat
Heat Manual Reset Manual Reset
Automatic Reset Automatic Reset
Heat
Heat Manual Reset Manual Reset
Automatic Reset Automatic Reset
Heat
Heat Manual Reset Manual Reset
Automatic Reset Automatic Reset
Heat
Heat Manual Reset Manual Reset
Automatic Reset Automatic Reset
Heat
Heat
See Notes
Below
3A Relay Fixed Potted LF C4KW 0950 AAAA A 6, 8 3A Relay Fixed Potted LF C4LW 0510 AAAA A 6, 8 3A Relay Fixed Potted CF C4KH 0950 AAAA A 6, 8 3A Relay Fixed Potted CF C4LH 0510 AAAA A 6, 8 3A Relay Fixed Potted LF E4KU 0950 AAAA A 6, 8 3A Relay Fixed Potted LF E4LU 0510 AAAA A 6, 8 3A Relay Fixed Potted LF E4KW 0950 AAAA A 6, 8 3A Relay Fixed Potted LF E4LW 0510 AAAA A 6, 8 3A Relay Fixed Potted CF E4KH 0950 AAAA A 6, 8 3A Relay Fixed Potted CF E4LH 0510 AAAA A 6, 8 3A Relay Fixed Potted LF C4SU 0400 AAAA A 6, 8 3A Relay Fixed Potted LF C4TU 0204 AAAA A 6, 8 3A Relay Fixed Potted LF C4SW 0400 AAAA A 6, 8 3A Relay Fixed Potted LF C4TW 0204 AAAA A 6, 8 3A Relay Fixed Potted CF C4SH 0400 AAAA A 6, 8 3A Relay Fixed Potted CF C4TH 0204 AAAA A 6, 8 3A Relay Fixed Potted LF E4SU 0400 AAAA A 6, 8 3A Relay Fixed Potted LF E4TU 0204 AAAA A 6, 8 3A Relay Fixed Potted LF E4SW 0400 AAAA A 6, 8 3A Relay Fixed Potted LF E4TW 0204 AAAA A 6, 8 3A Relay Fixed Potted CF E4SH 0400 AAAA A 6, 8 3A Relay Fixed Potted CF E4TH 0204 AAAA A 6, 8 3A Relay Fixed Potted LF C4HU 0333 AAAA A 6, 8 3A Relay Fixed Potted LF C4JU 0060 AAAA A 6, 8 3A Relay Fixed Potted LF C4HW 0333 AAAA A 6, 8 3A Relay Fixed Potted LF C4JW 0060 AAAA A 6, 8 3A Relay Fixed Potted CF C4HH 0333 AAAA A 6, 8 3A Relay Fixed Potted CF C4JH 0060 AAAA A 6, 8 3A Relay Fixed Potted LF E4HU 0333 AAAA A 6, 8 3A Relay Fixed Potted LF E4JU 0060 AAAA A 6, 8 3A Relay Fixed Potted LF E4HW 0333 AAAA A 6, 8 3A Relay Fixed Potted LF E4JW 0060 AAAA A 6, 8 3A Relay Fixed Potted CF E4HH 0333 AAAA A 6, 8 3A Relay Fixed Potted CF E4JH 0060 AAAA A 6, 8
Note 1: Retrofit controller requires a substitution of a 100 Ohm DIN RTD sensor. Note 2: Mounting and dimensions of retrofit controller are different. Verify that sufficient panel space and depth is available. Note 3: Retrofit controller outputs are different. Add external interposing mechanical or solid state relay if applicable. Note 4: Retrofit controller has a programmable, not fixed set point. Lock set point using controller's lockout parameter. Note 5: For DIN rail mounting or sub-panel mounting, purchase DIN rail adapter p/n 0822-0586-P001 for 1/32 DIN or p/n 0822-0586-P002 for 1/16 DIN. Note 6: Add a quencharc suppressor, Watlow p/n 0804-0147-0000, for inductive loads.
Note 7: Retrofit does not have equivalent action (as example, no manual reset)
Watlow Controls 1/31/2005 Page 40
Series 142
8
Line
Series 142 Note 8: Retrofit controller does not have dual dial scale. Note 9: Hardware lockout is not available on retrofit. Note 10: Retrofit controller does not have user selectable line voltage.
Note 11: Retrofit does not support remote set point or retransmit. If wires are on these pins, select a different retrofit. Note 12: Retrofit controller does not have user selectable control action. Note 13: Solid state sensor required for humidity. See http://www.vaisala.com Note 14: Retrofit controller does not have user selectable control mode. Note 15: Use auxiliay event board A007-1732-F4B Note 16: Retrofit communications are different, consult specifications. Note 17: Verify retrofit input range matches application.
Voltage Input Temp Range Control Mode Action Output Set Point Mounting Retrofit
See Notes
Below
Watlow Controls 1/31/2005 Page 41
Series 142
User’s Manual
Safety Limit or On-Off
Controller
Watlow Controls
1241 Bundy Boulevard, P.O. Box 5580, Winona, Minnesota USA 55987-5580
Phone: 507/454-5300, Fax: 507/452-4507, Internet: http://www.watlow.com
The Watlow Series 142 is a compact, environmentally protected safety limit temperature controller. The limit has a single thermocouple input and is available in several common ranges.
The 142 has a single mechanical relay output, and operates as a high limit, latching control with manual and/or auto-power reset. Fixed set points are available.
The Series 142 safety limit controller is ideally suited for limit applications requiring tamper-proof operation, agency approvals and immunity to hostile environments.
• The factory-fixed set point cannot be altered by operator
action or neglect.
• Agency approvals ensure compliance with recognized
standards.
• Epoxy potting makes the Series 142 resistant to envi-
ronments with vibration or humid/corrosive conditions.
Compact size and sub-panel mounting make the Series 142 readily adaptable to many applications. Its single, factory-fixed set point thermocouple input and Form C, 3 amp electromechanical relay output provides simplicity and reliability for many applications. Sensor break protection ensures fail-safe process shut down upon input failure.
We use note, caution and warning symbols through­out this manual to draw your attention to important oper­ational and safety information.
A “NOTE” marks a short message to alert you to an important detail.
A “CAUTION” safety alert appears with information that is important for protecting your equipment and per­formance. Be especially careful to read and follow all cautions that apply to your application.
A “WARNING” safety alert appears with information that is important for protecting you, others and equipment from damage. Pay very close attention to all warnings that apply to your application.
The safety alert symbol, ç, (an exclamation point in a triangle) precedes a general CAUTION or WARNING statement.
The electrical hazard symbol, Ó, (a lightning bolt in a triangle) precedes an electric shock hazard CAUTION or WARNING safety statement.
Safety Information
General Description
0600-0023-0000 Rev D August 1999 Supersedes 0600-0023-0000 Rev C
$5.00
Made in the U.S.A.
Printed on Recycled Paper
10% Postconsumer Waste
97
TOT AL
CUSTO MER
SA TISFACTI ON
3 Y ear Warranty
2 User’s Manual Watlow Series 142
Figure 2a — Series 142 dimensions.
Installation Procedure
1. Drill two 0.187 in. (5mm) diameter holes in the desired panel location.
2. Mount the unit with two 6-32 screws, 0.25 in. (6mm) hex nut and #6 internal tooth lock washer.
3. Use the correct thermocouple type per the model num­ber on the unit sticker. See the side of the case.
• Use correct thermocouple polarity. Red is negative.
• Insulate the thermocouple mounting from the mount-
ing surface to prevent heat migration input errors.
• Thermocouple leads should be twisted pair wire and
routed separately from any other lines.
• In electrically-noisy environments (heavy switching
contactors, motors, solenoids, etc.), use shielded ther­mocouple lead wire with the shield connected at the sensor end only.
• Use a separate thermocouple to maintain the limit
function of this controller; do not parallel thermocou­ple input from the primary controller.
4. All wiring and fusing must conform to the National Electric Code (NEC) NFPA70 and any other locally applicable codes.
5. Fuse the independent load voltage on the L1 (hot) side and connect it to the common (C) side of the relay.
NOTE: For applications where the CE mark is required, all quick connect and spade terminals must be pre-insulated to meet IEC 730 specifications.
Units With Remote Setpot Assembly
1. Drill two 2.0 in. (51mm) diameter holes in the desired remote setpot assembly location. See Figure 2b.
2. Using the dial scale as a location template, center and mark all four mounting holes on the dial scale with a center punch.
3. For bolted dial scale assembly, drill four 0.125 in. (3mm) diameter clearance holes. If you are using a screw assembly, use a tap drill. Tap drill sizes used are:
Tap Drill Size Screw/Thread Size
#44 - 0.086 in. dia. (2mm) #4.36 #43 - 0.089 in. dia. (2mm) #4.40 #42 - 0.093 in. dia. (2mm) #4.48
4. Drill four 0.189 in. (5mm) diameter holes in desired panel location. See Figure 2b.
5. Mount the Series 142 with four screws.
6. Connect sensor, load and remote setpot assembly per Wiring Diagram. See the wiring pages.
Figure 2b — Setpot dimensions and mechanical zero location.
Dial Scale Alignment to Mechanical Zero
1. Turn the dial scale knob completely counterclockwise (to mechanical zero).
2. If the “Indicator” line on the setpot knob skirt, and “Mechanical Zero” (represented by a small line beyond the low end of the scale) are not aligned, loosen both set screws on the setpot knob, and rotate the knob until both lines meet.
3. Tighten both set screws.
4.05 in.
Installation
(103mm)
3.50 in. (89mm)
Use a 0.25 in. (6mm) hex nut
for proper clearance.
1.38 in. (35mm)
Two 0.187 in. (5mm) dia.
2.76 in. (70mm)
mounting holes
1.38 in. (35mm)
1.13 in. (29mm)
0.53 in.
4 mounting holes
0.9 in.
(23mm)
1.72 in. (43mm)
Mechanical Zero
3.00 in. sq.
2.69 in. sq. (68mm)
(76mm)
(13mm)
Watlow Series 142 User’s Manual 3
NOTE: All terminals are 1/4 in. (4mm) quick connects.
Figure 3a — 120V~ power wiring (142A - _ _ _ _ - 1 _ 00).
Figure 3b — 208/240V~ power wiring (142A - _ _ _ _ - 2 _
00).
Figure 3c — Reset switch.
NOTE: Jumpering the reset terminals does not convert from limit to an on-off control mode.
Figure 3d — 3A mechanical relay wiring.
Figure 3e — Thermocouple wiring.
NOTE: Extension wire for thermocouples must be of the same alloy as the thermocouple itself to limit errors.
Figure 3f — Remote setpot (142A - 2 _ _ _ - _ _ 00).
Remote Setpot
Green
Black
Red
P3
P2
P1
N.O.
N.C.
Reset
L2
L1
COM
Thermocouple +
Thermocouple -
P3
P2
P1
N.O.
N.C.
Reset
L2
L1
Red
COM
Thermocouple +
Thermocouple -
P3
P2
P1
N.O.
N.C.
Reset
L2
L1
Temperature
Control Output
Fuse
L1
External
Load
L2
COM
Thermocouple +
Thermocouple -
P3
P2
P1
N.O.
N.C.
Reset
L2
L1
Customer Supplied N.O. Momentary Switch
COM
Thermocouple +
Thermocouple -
P3
P2
P1
N.O.
N.C.
Reset
L2
L1
Fuses 208/240V~
COM
Thermocouple +
Thermocouple -
P3
P2
P1
N.O.
N.C.
Thermocouple +
Thermocouple -
Reset
L2
L1
120V~ Fuse
COM
Neutral
Hot
Wiring
4 User’s Manual Watlow Series 142
Figure 4 — System wiring example.
WARNING: Install high or low temperature limit control protection in sys-
tems where an overtemperature fault condition could present a fire hazard or other hazard. Failure to install temperature limit control protection where a potential hazard exists could result in damage to equipment and property, and injury or death to personnel.
ç
CAUTION: Watlow mercury relay loads must have a unity power factor.
For RESISTIVE LOADS ONLY.
Series 142
142A - 3 _ _ _ - 1200
Safety Limit Control
988A-2BA0-0000
Rear View
9 10
12 13
21 22 11
N.O.
High Limit
Mechanical
Contactor
N.C. N.O. COM
L2
Load
Power
Heat Load
(+)
(-)
Fuse
L1 L2
Momentary Switch
Manual Reset for Limit Control
Fuses
L1
Load
Power
N.O.
COM
Earth
Ground
Indicator turns on when limit trips
Process
Sensor
L2 L1
Limit Sensor
Limit Power
- +
Thermo-
couple
System Wiring Example
Watlow Series 142 User’s Manual 5
(1599)
Limit Control Mode
• High limit control
• Latched manual reset with ±3°F (1.7°C) hysteresis
• Can only be reset when process temperature drops below limit set point. Terminals are provided for remote reset in the event of an overtemperature condition. (Reset switch supplied by user.)
On/off Temperature Control Mode
• Off — when process temperature exceeds factory-fixed or remote adjustable set point
• On — when process temperature is less than factory-fixed or remote adjustable set point
• Hysteresis (switching differential) ±3°F (1.7°C) nominal
Agency Approvals
• UL and C-UL, File #E43684 197 Commercial Cooking Appliances 873 Temperature Indicating and Regulating Equipment 991 Test for Safety Related Controls Employing Solid State Devices
• A.G.A., Report #C3236001
• CE 89/336/EEC Electromagnetic Compatibility Directive EN50082-1, Immunity EN50081-1, Emissions
• CE 73/23/EEC Low Voltage Directive EN60730-1, EN60730-2-9, Safety
Operator Interface
• Non-adjustable, factory-fixed or remote adjustable set point
Remote Set Point
• Dial scale calibrated to compensate for sensor non-linearity
• Dual °F/°C scales
Accuracy
• Calibration accuracy: ±1% of span, at 77°F ± 5°F (25°C ± 3°C) ambient and rated line voltage ±1%
• Accuracy span: ±2.5% of range or 1000°F (540°C) minimum, whichever is greater
• Thermocouple temperature stability: Typically ±5µV/°F (9µV/°C) ambient
• Voltage stability: ±0.01% of span /% of rated line voltage
Thermocouple Input
• Grounded or ungrounded Type E, J, K or T. Sensor break protec­tion de-energizes output.
• Factory-set, thermocouple ranges
Output
• Electromechanical relay1, SPDT, 3A @ 120/240V~ or 3A @ 30VÎ (dc), Form C, with RC suppression on on-off temperature con­troller version. Off-state output impedance is 20kwith RC suppression.
Output Relay Status Upon Power Restoration
(Assuming process temperature is not above set point.)
• Auto reset: Output relay automatically re-energizes
• Manual reset: Manual reset is required to re-energize output relay
Line Voltage/Power
• 120V~, ±10%; (108-132V~), 50/60Hz, ±5%
• 208/240V~, ±10%; (187-264V~), 50/60Hz, ±5%
• Power consumption 4VA maximum
Operating Environment
• 32 to 149°F (0 to 65°C)
• 0 to 90% RH, non-condensing
Storage Temperature
• -40 to 185°F (-40 to 85°C)
Terminals
• 1⁄4 inch quick connect lugs (spade/ appliance)
Dimensions Controller
• Length 4 in. (102mm)
• Width 2.8 in. (70mm)
• Height 4.05 in. (103mm)
• Controller Weight 0.79 lb. (0.36kg)
• Shipping Weight 1.25 lbs. (0.57kg)
Set Point Assembly
• Dial Scale 3 in. sq. (76mm)
• Pot Depth Behind 1.0 in. (25mm)
• Knob Depth in Front 1.2 in. (31mm)
• Lead Length 24 in. (610mm)
• Weight 0.2 lb. (0.09kg)
1
Electromechanical relays are warranted for 100,000 closures
only. UL® is a registered trademark of Underwriter’s Laboratories, Inc. Note: Specifications subject to change without notice.
• Call or fax Customer Service for a Return Material Authorization (RMA) number before returning a con­troller.
• Put the RMA number on the shipping label, and also on a description of the problem.
• 20% of net price restocking charge applies to all stan­dard units returned to stock.
If you encounter a problem with your Watlow con­troller, review all of your configuration information to verify that your selections are consistent with your application: inputs; outputs; alarms; limits; etc. If the problem persists after checking the above, you can get technical support by dialing 507/494-5656, 7 AM to 7 PM Central Standard Time, or e-mail to wintechsupport@watlow.com. An applica­tions engineer will discuss your application with you.
Please have the following information available when calling:
• Complete model number • Serial Number
• All configuration information • User’s Manual
The Watlow Series 142 is warranted to be free of defects in material and workmanship for 36 months after delivery to the first purchaser for use, providing that the units have not been misapplied. Since Watlow has no con­trol over their use, and sometimes misuse, we cannot guar­antee against failure. Watlow's obligations hereunder, at Watlow's option, are limited to replacement, repair or refund of purchase price, and parts which upon examina­tion prove to be defective within the warranty period speci­fied. This warranty does not apply to damage resulting from transportation, alteration, misuse, or abuse.
Your comments or suggestions on this manual are welcome. Please send them to: Technical Writer, Watlow Controls, 1241 Bundy Boulevard, P.O. Box 5580, Winona, Minnesota 55987-5580; phone: 507/454-5300; fax: 507/452-
4507. The Series 142 User’s Manual is copyrighted by Watlow Winona, Inc., © August 1999, with all rights reserved. (1816)
Your Feedback
Warranty
Technical Assistance
Returns
Specifications
6 User’s Manual Watlow Series 142
(1817)
To order, complete the code number
to the right with the information below: 1 4 2 A - _ _ _ _ - _ _ 0 0 Series 142 = Temperature safety limit,
limit, latching 3A relay, environmentally sealed controller, or basic on-off temperature controller
Output Type
A = Electromechanical relay
1
, Form C, 3A, with RC suppression on on-off temperature controller, without contact suppression on limit controller
Set Point
2 = Remote/Adjustable
2
3 = Fixed (See below for available factory-fixed set points)
Input (Thermocouple) ANSI Type E
669 = 230°F (110°C) 679 = 365°F (185°C) 682 = 575°F (302°C) 685 = 265°F (129°C) 684 = 450°F (232°C) 664 = 1050°F (566°C) 670 = 302°F (150°C) 675 = 500°F (260°C) 668 = 311°F (155°C) 678 = 565°F (296°C)
Ordering Information
1
Electromechanical relays war­ranted for 100,000 closures only. 2
User selectable range. Consult factory for details. Setpot required, sold separately. 3
A.G.A. Certified 4
Not within calibration toler­ance range per ANSI circular MC96.1.
Note: User documentation may be available in French, German, Spanish, Italian, and Dutch, as well as English. Check Watlow’s website (www.watlow.com/) for availability. Specify language at time of order.
ANSI Type J
706 = 32 to 600°F
(0 to 315°C) 626 = 50°F (10°C) 718 = 61°F (16°C) 653 = 115°F (46°C) 666 = 145°F (63°C) 686 = 149°F (65°C) 6093= 155°F (68°C) 681 = 175°F (79°C) 672 = 185°F (85°C) 6003= 200°F (93°C) 688 = 215°F (102°C) 6013= 225°F (107°C) 719 = 230°F (110°C) 6023= 250°F (121°C) 715 = 265°F (129°C)
603
3
= 275°F (135°C) 6043= 300°F (149°C) 6053= 325°F (163°C) 6063= 350°F (177°C) 707 = 360°F (182°C) 6073= 375°F (191°C) 6083= 400°F (204°C) 6993= 425°F (218°C) 689 = 444°F (229°C) 704 = 465°F (240°C) 6983= 450°F (232°C) 6123= 475°F (246°C) 6133= 500°F (260°C) 614 = 525°F (274°C) 615 = 550°F (288°C) 616 = 575°F (302°C)
617 = 600°F (316°C) 618 = 625°F (329°C) 693 = 650°F (343°C) 620 = 675°F (357°C) 621 = 700°F (371°C) 622 = 725°F (385°C) 623 = 750°F (399°C) 624 = 775°F (413°C) 625 = 800°F (427°C) 627 = 850°F (454°C) 628 = 875°F (468°C) 696 = 900°F (482°C) 630 = 925°F (496°C) 631 = 950°F (510°C) 632 = 975°F (524°C) 633 = 1000°F (538°C)
ANSI Type K
716 = 122°F (50°C) 711 = 125°F (52°C) 125 = 257°F (125°C) 619 = 300°F (149°C) 667 = 460°F (238°C) 671 = 550°F (288°C) 695 = 572°F (300°C) 690 = 600°F (315°C) 674 = 700°F (700°C) 677 = 788°F (420°C) 629 = 800°F (427°C) 691 = 875°F (468°C) 634 = 1050°F (565°C) 635 = 1100°F (593°C) 636 = 1150°F (621°C)
673 = 1198°F (648°C) 637 = 1200°F (649°C) 638 = 1250°F (677°C) 639 = 1300°F (704°C) 640 = 1350°F (732°C) 687 = 1382°F (750°C) 717 = 750°F (399°C) 641 = 1400°F (760°C) 642 = 1450°F (788°C) 643 = 1500°F (816°C) 644 = 1550°F (843°C) 645 = 1600°F (871°C) 646 = 1650°F (899°C) 647 = 1700°F (927°C) 648 = 1750°F (954°C)
649 = 1800°F (982°C) 650 = 1850°F (1010°C) 651 = 1900°F (1038°C) 652 = 1950°F (1066°C) 692 = 2000°F (1093°C) 654 = 2050°F (1121°C) 655 = 2100°F (1149°C) 656 = 2150°F (1177°C) 657 = 2200°F (1204°C) 658 = 2250°F (1232°C) 659 = 2300°F (1260°C) 660 = 2350°F (1288°C) 661
4
= 2400°F (1316°C) 6624= 2450°F (1343°C) 6634= 2500°F (1371°C)
ANSI Type T
708 = -4°F (-20°C) 705 = -328 to 662°F (-200 to 350°C) 680 = 140°F (60°C) 714 = 175°F (79°C)
694 = 275°F (135°C) 712 = 347°F (175°C) 713 = 392°F (200°C) 710 = 482°F (250°C)
Line Voltage/Power
1 = 120V~ 2 = 208/240V~
Control Operation
2 = Limit Control—Manual reset on power loss and overtemperature 3 = Limit Control—Auto reset on power loss/manual reset on overtemperature 4 = Temperature Control—on-off
Watlow Series 142 User’s Manual 7
automatic power reset — A feature in latching limit controllers that does not recognize power outage as a limit condition. When power is restored, the output is re-ener­gized automatically, as long as the temperature is within limits.
electrical noise immunity — Ability of a temperature control to operate normally in the presence of electrical noise interference.
fixed set point — Temperature set point is preset at the factory. It cannot be readjusted in the field.
latched output — Limit control output latches in de­energized condition when overtemperature condition occurs and cannot be reset unless temperature drops below set point.
limit or limit controller — A highly reliable, discrete safety device (redundant to the primary controller) that monitors and limits the temperature of the process or a point in the process. When temperature exceeds or falls below the limit set point, the limit controller interrupts power through the load circuit. A limit controller can pro­tect equipment and people when it is correctly installed with its own power supply, power lines, switch and sensor.
manual reset — A feature on a limit controller that requires human intervention to return the limit to normal operation after a limit condition has occurred.
safety limit — An automatic limit intended for use in applications where an over-temperature fault may cause a fire.
Glossary
Declaration of Conformity Series 142
Watlow Controls 1241 Bundy Blvd., PO Box 5580 Winona, Minnesota 55987 USA
Declares that the following product: English Designation: Series 142 Model Number(s): 142A-(2 or 3) (600-999)-(1 or 2) (2,3, or 4) 00 Classification: Temperature Limit Control, Class II, Pollution Degree II Rated Voltage: 100 to 240VÅ (ac) Rated Frequency: 50/60 Hz Rated Power
Consumption: 4VA Meets the essential requirements of the following European Union Directive(s) using the relevant section(s) of the normalized standards and related documents shown:
89/336/EEC Electromagnetic Compatibility Directive
EN 50082-1: 1995 EMC Generic immunity standard, Part 1: Residential,
commercial and light industry
EN 61000-3-2: 1995 Limits for harmonic current EN 61000-3-3: 1995 Limitations of voltage fluctuations and flicker EN 61000-4-2: 1995 Electrostatic discharge EN 61000-4-4: 1995 Electrical fast transients EN 61000-4-5: 1995 Surge immunity EN 61000-4-11: 1994 Voltage dips, short interruptions and voltage variations
immunity ENV 50140: 1994 Radiated immunity ENV 50141: 1994 Conducted immunity ENV 50204: 1995 Cellular phone
EN 50081-1: 1994 EMC Generic emission standard, Part 1: Residential,
commercial and light industry
EN 55011: 1991 Limits and methods of measurement of radio disturbance
characteristics of industrial, scientific and medical radio-
frequency equipment (Class B)
73/23/EEC Low-Voltage Directive
EN 60730-1: 1993 Automatic electric controls for household and similar
use, Part 1: General requirements EN 60730-2-9: 1995 Automatic electric controls for household and similar
use, Part 2: Particular requirements Section 2.9,
Temperature sensing controls Note: Pre-insulated connectors must be used for compliance with EN 60730.
Déclare que le produit suivant : Français Désignation : Série 142 Numéro(s) de modèle(s) : 142A-(2 ou 3)(600-999)-(1 ou 2) (2, 3 ou 4) 00 Classification : Contrôle de limite de température, classe II, degré de
pollution II Tension nominale : 100 à 240 VÅ(c.a.) Fréquence nominale : 50/60 Hz Consommation d’alimentation nominale : 4 VA Conforme aux exigences de la (ou des) directive(s) suivante(s) de l’Union Européenne figurant aux sections correspondantes des normes et documents associés ci-dessous :
89/336/EEC Directive de compatibilité électromagnétique
EN 50082-2 : 1995 Norme générique d’insensibilité électromagnétique,
Partie 1 : Environnement résidentiel, commercial et industries légères
EN 61000-3-2 : 1995 Limites d’émission de courant harmonique EN 61000-3-3 : 1995 Limites de fluctuation de tension EN 61000-4-2 : 1995 Décharge électrostatique EN 61000-4-4 : 1995 Courants électriques transitoires rapides EN 61000-4-5 : 1995 Insensibilité aux surtensions EN 61000-4-11 :1994 Insensibilité aux chutes subites, aux courtes interruptions
et aux variations de tension ENV 50140 : 1994 Insensibilité à l’énergie rayonnée ENV 50141 : 1994 Insensibilité à l’énergie par conduction ENV 50204 : 1995 Téléphone cellulaire
EN 50081-1 : 1994 Norme générique sur les émissions
électromagnétiques, Partie 1 : Environnement
résidentiel, commercial et industries légères
EN 55011 : 1991 Limites et méthodes de mesure des caractéristiques
d’interférences du matériel radiofréquence industriel,
scientifique et médical (Classe B)
73/23/EEC Directive liée aux basses tensions
EN 60730-1 : 1993 Commandes électriques automatiques à usage
domestique et similaire, Partie 1 : Exigences générales EN 60730-2-9 : 1995 Commandes électriques automatiques à usage
domestique et similaire, Partie 2 : Exigences
particulières, Section 2.9, commandes thermosensibles Remarque : Des connecteurs pré-isolés doivent être utilisés pour respecter la conformité à la norme EN 60730.
(1633)
Erklärt, daß das folgende Produkt: Deutsch Beschreibung: Serie 142 Modellnummer(n): 142A - (2 oder 3) (600-999) - (1 oder 2) (2, 3 oder 4) 00 Klassifikation: Temperaturregelsystem, Installationskategorie II,
Emissionsgrad II Nennspannung: 100 bis 240VÅ (V Wechselstrom) Nennfrequenz: 50/60 Hz Nominaler Stromverbrauch: 4VA Erfüllt die wichtigsten Normen der folgenden Anweisung(en) der Europäischen Union unter Verwendung des wichtigsten Abschnitts bzw. der wichtigsten Abschnitte der normalisierten Spezifikationen und der untenstehenden einschlägigen Dokumente:
89/336/EEC Elektromagnetische Übereinstimmungsanweisung
EN 50082-1: 1995 EMC-Rahmennorm für Störsicherheit, Teil 1:
Wohngegenden, Handelsverkehr und Leichtindustrie
EN 61000-3-2: 1995 Grenzen der Oberwellenstromemissionen EN 61000-3-3: 1995 Grenzen der Spannungsschwankungen EN 61000-4-2: 1995 Elektrostatische Entladung EN 61000-4-4: 1995 Elektrische schnelle Stöße EN 61000-4-5: 1995 Spannungsstoßimmunität EN 61000-4-11: 1994 Immunität gegen Spannungsgefälle, kurze
Unterbrechungen und Spannungsabweichungen ENV 50140: 1994 Strahlungsimmunität ENV 50141: 1994 Störimmunität ENV 50204: 1995 Mobiltelefon
EN 50081-1: 1994 EMC-Rahmennorm für Emissionen, Teil 1:
Wohngegenden, Handelsverkehr und Leichtindustrie
EN 55011: 1991 Beschränkungen und Methoden der Messung von
Funkstörungsmerkmalen industrieller, wissenschaftlicher
und medizinischer Hochfrequenzgeräte (Klasse B)
73/23/EEC Niederspannungsrichtlinie zu entsprechen
EN 60730-1: 1993 Automatische elektrische Regelsysteme für den
Haushalt und ähnlichen Einsatz, Teil 1: Allgemeine
Richtlinien EN 60730-2-9: 1995 Automatische elektrische Regelsysteme für den
Haushalt und ähnlichen Einsatz, Teil 2: Spezifische
Richtlinien Abschnitt 2.9, Temperaturregelsysteme Hinweis: Gemäß EN 60730 müssen vorisolierte Steckverbinder verewendet werden.
Declara que el producto siguiente: Español Designación: Serie 142 Números de modelo: 142A-(2 ó 3)(600-999)-(1 ó 2)(2, 3 ó 4) 00 Clasificación: Control de límite de temperatura, Clase II, grado de
contaminación ambiental II Tensión nominal: 100 a 240 VÅ (CA) Frecuencia nominal: 50/60 Hz
Consumo nominal de energía: 4 VA
Cumple con los requisitos esenciales de las siguientes Directivas de la Unión Europea, usando las secciones pertinentes de las reglas normalizadas y los documentos relacionados que se muestran:
89/336/EEC - Directiva de Compatibilidad Electromagnética
EN 50082-1: 1995 Norma de inmunidad genérica del EMC, Parte 1:
Ambiente residencial, comercial e industria ligera
EN 61000-3-2 1995 Límites para emisiones de corriente armónica EN 61000-3-3 1995 Limitaciones de fluctuaciones del voltaje EN 61000-3-2: 1995 Grenzen der Oberwellenstromemissionen EN 61000-3-3: 1995 Grenzen der Spannungsschwankungen EN 61000-4-2: 1995 Descarga electrostática EN 61000-4-4: 1995 Perturbaciones transitorias eléctricas rápidas EN 61000-4-5: 1995 Sobretensión EN 61000-4-11: 1994 Caídas de tensión, interrupciones breves y variaciones de
tensión ENV 50140: 1994 Inmunidad radiada ENV 50141: 1994 Inmunidad conducida ENV 50204: 1995 Teléfono portátil
EN 50081-1: 1994 Norma de emisión genérica del EMC, Parte 1:
Ambiente residencial, comercial e industria ligera
EN 55011: 1991 Límites y métodos para medición de características de
perturbaciones de radio correspondientes a equipos de
radiofrecuencia industriales, científicos y médicos (Clase B)
73/23/EEC Directiva de Baja Tensión
EN 60730-1: 1993 Controles eléctricos automáticos para
electrodomésticos y aparatos de uso similar, Parte 1:
Requerimientos generales EN 60730-2-9: 1995 Controles eléctricos automáticos para
electrodomésticos y aparatos de uso similar, Parte 2:
Requerimientos particulares Sección 2.9, Controles
para detección de temperatura Nota: Se requiere el uso de conectores aislados para cumplir con la norma EN
60730.
Signature of Authorized Representative
Erwin D. Lowell
Name of Authorized Representative
General Manager
Title of Authorized Representative
Winona, Minnesota USA
Place of Issue
July 2, 1997
Date of Issue
8 User’s Manual Watlow Series 142