WaterFurnace NEW050 Installation Manual

504W11 Geothermal Hydronic Heat Pump
e
Installation Information
Water Piping Connections
Electrical Data
Startup Procedures
Preventive Maintenance
5 Series OptiHeat Installation Manual
5 S
IM2508WN 02/19
Table of Contents
Model Nomenclature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
General Installation Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Field Connected Water Piping. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
Hydronic Section . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
External Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Accessories and Options. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Electrical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Wiring Schematics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Unit Startup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .20
Aurora Base Control. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Reference Calculations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .30
Legend and Notes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .30
5 SERIES OPTIHEAT 504W11 INSTALLATION MANUAL
Water Pressure Drop . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Pressure Drop . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .32
Operating Limits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Physical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Flow Rates . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Heating & Cooling Operating Envelope . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
Thermistor and Compressor Resistance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
Operating Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .35
Antifreeze Correction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
Troubleshooting Guideline for Refrigerant Circuit. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .38
HR Data. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .39
HE Data. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
Heating and Cooling Cycle Analysis. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
Troubleshooting Form . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .42
Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
Preventive Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .44
Service Parts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .45
Revision Guide. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .47
5 SERIES OPTIHEAT 504W11 INSTALLATION MANUAL
N E W
NEW
050 * 1 0 R C
34-67 8 91011
Model
N – 5 Series Hy dronic
Heat Pump
Compressor Type
E – Vapor Injection
Cabinet Configuration
W – Water-to-Water
Unit Capacity
040, 050, 066
Vintag e
* - Factory Use Only
Voltag e
1 – 208-230/60/1
Hot Wate r Op tio n
0 – No H ot Wa ter G ene ra ti on
IntelliStart®
N – None
A – IntelliStart
Controls Option
B – Aurora
TM
Advanced Controls
D – AuroraTM Performanc e1 & Refrigeration
Future Option
0 – Standar d
Future Option
S – Standard
Future Option
S – Standard
Water Coil Option
C – Copper
Reversible Option
R – Reversible
H – Heating Only
Rev.: A 9/27/18 ADL
S
12
21
S 0 B N
y
H
um p
y
Inj
ig
o
W
y
n
o
er
n
13 14 15
16
Model Nomenclature
ries
dro
t P
sor T
or
onf
t
cit
ry Use Onl
ic
e
ctio
rati
n
t
NOTE: 1 – Flow meter for Performance Refrigeration option is shipped inside the unit and must be externally field installed.
Voltage
208-230/60/1
- Voltage available in this size
040 050 066
●●
●● - Voltage and soft start available in this size
NEW
All 5 Series product safety listed under UL1995 thru ETL and performance listed with AHRI in accordance with standard 13256-1. The 5 Series is also ENERGY STAR rated.
®
4
General Installation Information
5 SERIES OPTIHEAT 504W11 INSTALLATION MANUAL
Safety Considerations
Installing and servicing air conditioning and heating equipment can be hazardous due to system pressure and electrical components. Only trained and qualified service personnel should install, repair or service heating and air conditioning equipment. When working on heating and air conditioning equipment, observe precautions in the literature, tags and labels attached to the unit and other safety precautions that may apply.
Follow all safety codes. Wear safety glasses and work gloves. Use quenching cloth for brazing operations. Have fire extinguisher available for all brazing operations.
NOTE: Before installing, check voltage of unit(s) to ensure proper voltage.
WARNING: Before performing service or maintenance operations on the system, turn off main power switches to the unit. Electrical shock could cause serious personal injury.
WARNING: This heat pump is capable of producing hot water up to 150°F. All exposed piping surfaces shall be insulated to prevent serious personal injury that can occur from touching water piping.
Unit Location
Provide sufficient room to make water and electrical connections. If the unit is located in a confined space, provisions must be made for unit servicing. Locate the unit in an indoor area that allows easy removal of the access panels and has enough space for service personnel to perform maintenance or repair. These units are not approved for outdoor installation and, therefore, must be installed inside the structure being conditioned. Do not locate units in areas subject to freezing conditions.
WARNING: Do not store or install units in corrosive environments or in locations subject to temperature or humidity extremes (e.g. attics, garages, rooftops, etc.). Corrosive conditions and high temperature or humidity can significantly reduce performance, reliability, and service life.
Mounting Units
Prior to setting the unit in place, remove and discard the compressor hold down shipping bolt located at the front of each compressor mounting bracket. Units should be mounted level on a vibration absorbing pad slightly larger than the base to provide isolation between the unit and the floor. It is not necessary to anchor the unit to the floor. Allow access to the front, back, top and side access panels for servicing.
Application
Units are not intended for heating domestic (potable) water or swimming pools by direct coupling. If used for this type of application, a secondary heat exchanger must be used.
Moving and Storage
Move units in the normal “Up” orientation as indicated by the labels on the unit packaging. When the equipment is received, all items should be carefully checked against the bill of lading to ensure that all crates and cartons have been received in good condition. Examine units for shipping damage, removing unit packaging if necessary to properly inspect unit. Units in question should also be internally inspected. If any damage is observed, the carrier should make the proper notation on delivery receipt acknowledging the damage. Units are to be stored in a location that provides adequate protection from dirt, debris and moisture.
WARNING: To avoid equipment damage, do not leave the system filled in a building without heat during cold weather, unless adequate freeze protection levels of antifreeze are used. Heat exchangers do not fully drain and will freeze unless protected, causing permanent damage.
Vibration Pad Mounting
5
5 SERIES OPTIHEAT 504W11 INSTALLATION MANUAL
Field Connected Water Piping
General
Each unit is equipped with captive FPT water connections to eliminate ‘egg-shaping’ from use of a backup wrench. For making the water connections to the unit, a Teflon tape thread sealant is recommended to minimize internal fouling of the piping. Do not over tighten connections. All supply and return water piping should be insulated to prevent excess condensation from forming on the water lines.
NOTE: Units are factory run-tested using propylene glycol. Prior to connecting piping to unit, thoroughly flush heat exchangers.
The piping installation should provide service personnel with the ability to measure water temperatures and pressures. The water lines should be routed so as not to interfere with access to the unit. The use of a short length of high pressure hose with a swivel type fitting may simplify the connections and prevent vibration. Optional stainless steel hose kits are available as an accessory item.
Before final connection to the unit, the supply and return hose kits must be connected, and the system flushed to remove dirt, piping chips and other foreign material. Normally, a combination balancing and close-off (ball) valve is installed at the return, and a rated gate or ball valve is installed at the supply. The return valve can be adjusted to obtain the proper water flow. The valves allow the unit to be removed for servicing.
Water Quality
It is the responsibility of the system designer and installing contractor to ensure that acceptable water quality is present and that all applicable codes have been met in these installations. Failure to adhere to the guidelines in the water quality table could result in loss of warranty. In ground water situations where scaling could be heavy or where biological growth such as iron bacteria will be present, a closed loop system is recommended. The heat exchanger coils in ground water systems may, over a period of time, lose heat exchange capabilities due to a buildup of mineral deposits inside. These can be cleaned, but only by a qualified service mechanic, as special solutions and pumping equipment are required. Hot water generator coils can likewise become scaled and possibly plugged. In areas with extremely hard water, the owner should be informed that the heat exchanger may require occasional flushing.
Heat pumps with cupronickel heat exchangers are recommended for open loop applications due to the increased resistance to build-up and corrosion, along with reduced wear caused by acid cleaning.
The proper water flow must be delivered to each unit whenever the unit heats or cools. To assure proper flow, the use of pressure/temperature ports is recommended to determine the flow rate. These ports should be located adjacent to the supply and return connections on the unit. The proper flow rate cannot be accurately set without measuring the water pressure drop through the refrigerant­to-water heat exchanger (See Pressure Drop Table for water flow and pressure drop information). Normally about 3 GPM flow rate per ton of cooling capacity (2.25 GPM per ton minimum) is needed. Both source as well as load fluid piping must be at least as large as the unit connections on the heat pump (larger on long runs).
Never use flexible hoses of a smaller inside diameter than that of the water connection on the unit and limit hose length to 10 ft. per connection. Check carefully for water leaks.
CAUTION: Water piping exposed to outside temperature may be subject to freezing.
6
5 SERIES OPTIHEAT 504W11 INSTALLATION MANUAL
Field Connected Water Piping cont.
Material Copper 90/10 Cupronickel 316 Stainless Steel
pH Acidity/Alkalinity
Scaling
Corrosion
Iron Fouling
(Biological Growth)
Erosion
NOTES: Grains = ppm divided by 17
mg/L is equivalent to ppm
Calcium and
Magnesium Carbonate
Hydrogen Sulfide
Chlorine Less than 0.5 ppm Less than 0.5 ppm Less than 0.5 ppm
Chlorides Less than 20 ppm Less than 125 ppm Less than 300 ppm
Carbon Dioxide Less than 50 ppm 10 - 50 ppm 10 - 50 ppm
Ammonia Less than 2 ppm Less than 2 ppm Less than 20 ppm
Ammonia Chloride Less than 0.5 ppm Less than 0.5 ppm Less than 0.5 ppm
Ammonia Nitrate Less than 0.5 ppm Less than 0.5 ppm Less than 0.5 ppm
Ammonia Hydroxide Less than 0.5 ppm Less than 0.5 ppm Less than 0.5 ppm
Ammonia Sulfate Less than 0.5 ppm Less than 0.5 ppm Less than 0.5 ppm
Total Dissolved Solids (TDS) Less than 1000 ppm 1000 - 1500 ppm 1000 - 1500 ppm
LSI Index +0.5 to -0.5 +0.5 to -0.5 +0.5 to -0.5
Iron, FE
Bacterial Iron Potential
Iron Oxide
Suspended Solids
Threshold Velocity
(Fresh Water)
Less than 0.5 ppm (rotten egg
Sulfates Less than 125 ppm Less than 125 ppm Less than 200 ppm
2
+ (Ferrous)
smell appears at 0.5 ppm)
Less than 1 ppm, above this
level deposition will occur
Less than 10 ppm and filtered
for max. of 600 mic
7 - 9 7 - 9 7 - 9
(Total Hardness)
less than 350 ppm
< 0.2 ppm < 0.2 ppm < 0.2 ppm
ron size
< 6 ft/sec < 6 ft/sec < 6 ft/sec
(Total Hardness)
less than 350 ppm
10 - 50 ppm Less than 1 ppm
Less than 1 ppm, above this
level deposition will occur
Less than 10 ppm and filtered
for max. of 600 micron size
(Total Hardness)
less than 350 ppm
Less than 1 ppm, above this
level deposition will occur
Less than 10 ppm and filtered
for max. of 600 micron size
2/22/12
Water Treatment
Do not use untreated or improperly treated water. Equipment damage may occur. The use of improperly treated or untreated water in this equipment may result in scaling, erosion, corrosion, algae or slime. Purchase of a pre­mix antifreeze could significantly improve system reliability if the water quality is controlled and there are additives in the mixture to inhibit corrosion. There are many examples of such fluids on the market today such as Environol™ 1000 (pre-mix ethanol), and others. The services of a qualified water treatment specialist should be engaged to determine what treatment, if any, is required. The product warranty specifically excludes liability for corrosion, erosion or deterioration of equipment.
The heat exchangers and water lines in the units are copper or cupronickel tube. There may be other materials in the buildings piping system that the designer may need to take into consideration when deciding the parameters of the water quality. If antifreeze or water treatment solution is to be used, the designer should confirm it does not have a detrimental effect on the materials in the system
.
Contaminated Water
In applications where the water quality cannot be held to prescribed limits, the use of a secondary or intermediate heat exchanger is recommended to separate the unit fro the contaminated water. The table above outlines the water quality guidelines for unit heat exchangers. If these conditions are exceeded, a secondary heat exchanger is required. Failure to supply a secondary heat exchanger where needed will result in a warranty exclusion for primary heat exchanger corrosion or failure.
WARNING: Must have intermediate heat exchanger when used in pool and spa applications.
7
5 SERIES OPTIHEAT 504W11 INSTALLATION MANUAL
Field Connected Water Piping cont.
Figure 1a: Open Loop Solenoid Valve Connection Option
Open Loop Well Water Systems
Always maintain water pressure in the heat exchanger by placing water control valves at the outlet of the unit. Use a closed bladder type expansion tank to minimize mineral deposits. Ensure proper water flow through the unit by checking pressure drop across the heat exchanger and comparing it to the figures in the pressure drop table. Normally, about 2 GPM flow rate per ton of cooling capacity is needed in open loop systems, (1.5 GPM per ton minimum if entering source temperature is above 50°F [10°C].
Some water control valves draw their power directly from the unit’s 24V transformer and can overload and possibly burn out the transformer. Check total VA draw of the water valve(s) and ensure it is under 40 VA.
Typical quick operating external 24V water solenoid valve (type PPV100 or BPV100) wiring.
SV
Solenoid
Valve
C R
Acc Com Acc NC Acc NO
ABC Board
P1
1 2
P2
3
Discharge water from a heat pump can be disposed of in various ways depending on local building codes (i.e. recharge well, storm sewer, drain field, adjacent stream or pond, etc.). Most local codes restrict the use of sanitary sewer for disposal. Consult your local building and zoning departments to ensure compliance in your area.
Typical Open Loop Installation
NOTE: SW2-4 and SW2-5 should be “OFF” to cycle with the compressor.
Figure 1b: Open Loop Solenoid Valve Connection Option
Typical slow operating external 24V water solenoid valve (type V100FPT) wiring.
Orange(29)
C R
Black/
C
W/Y
White(31)
Blue(30)
Acc Com
ACC NC
Acc NO
V Valve ABC Board
NOTE: SW2-4 should be “ON” and SW2-5 should be “OFF” when using a slow opening (V100FPT) water valve.
Rubber Bladder
Expansion Tank
Line Voltage Disconnect
Load Liquid
Connections
(to isolate solenoid
Shut-off Valve
valve while acid
flushing)
Flow Regulator Valve
Solenoid
Valve
Boiler Drains for HX Flushing
P/T Plugs
Vibration Absorbing Mesh or Air Pad
8
Water Out
Water In
Shut-off Valve
NOTE: Valves and boiler drains must be installed so the heat exchanger can be acid flushed.
5 SERIES OPTIHEAT 504W11 INSTALLATION MANUAL
VS
GN D
24 VA C
0-10DC
1 2
3
R
C
ABC BOAR D
AXB BOARD
MODULATING VALVE
1
2
Red
White
Green
NO TE: 13
Field Connected Water Piping cont.
Modulating Water Valve Setup
When using a modulating water valve kit (4MWVK or 5MWVK) the use of an AID Tool will be necessary to adjust minimum and maximum flow rates. The factory default is minimum = 70% and maximum = 100% flow levels. Since the
OptiHeat is a single speed unit, the minimum and maximum must be set at the same level. See the Variable Speed Pump
Setup and Modulating Water Valve Setup instructions within the Unit Startup section which is located in the back of this manual. Refer to the Flow Rate section of this manual to
ensure that there is adequate flow for the heat pump.
Modulating Water Valve Connection Option
Typical 0-10VDC modulating water valve.
Earth Coupled Systems with Flow Center
NOTE: For closed loop systems with antifreeze protection,
set SW2-1 to the “LOOP” (15°F) position. (Refer to the DIP Switch Settings table in the Aurora Control section.)
Once piping is completed between the unit, pumps and the ground loop (see figure below), final purging and charging of the loop is required. A flush cart (or a 1.5 HP pump minimum) is needed to achieve adequate flow velocity in the loop to purge air and dirt particles from the loop itself. Antifreeze solution is used in most areas to prevent freezing. Flush the system adequately to remove as much air as possible then pressurize the loop to a static pressure of 40-50 psi (summer) or 50-75 psi (winter). This is normally adequate for good system operation. Loop static pressure will fluctuate with the seasons. Pressures will be higher in the winter months than during the cooling season. This fluctuation is normal and should be considered when initially charging the system.
After pressurization, be sure to turn the venting (burping) screw in the center of the pump two (2) turns open (water will drip out), wait until all air is purged from the pump, then tighten the plug. Ensure that the flow center provides adequate flow through the unit by checking pressure drop across the heat exchanger and by comparing it to the figures shown in the Pressure Drop tables. Usually 3 GPM/ton or minimum 2.25 GPM/ton of cooling capacity is needed in closed loop earth-coupled applications.
Typical Closed Loop Earth Coupled Installation
Earth Coupled Loop
Piping with Insulation
Line Voltage Disconnect
Unit Connector Kits
with Insulation
P/T Plugs
Load Liquid
Connections
Vibration Absorbing Mesh or Air Pad
9
5 SERIES OPTIHEAT 504W11 INSTALLATION MANUAL
Field Connected Water Piping cont.
Multiple Units on One Flow Center
NOTE: This feature is only available in the Aurora Advanced
Control package (AXB board), NOT the Aurora Base Control (ABC).
When two units are connected to one loop pumping system, pump control is automatically achieved by connecting the SL terminals on connector P2 in both units with 2-wire thermostat wire. These terminals are polarity dependant (see Figure 2). The loop pump(s) may be powered from either unit, whichever is more convenient. If either unit calls, the loop pump(s) will automatically start. The use of two units on one flow center is generally limited to a total of 20 gpm capacity. It is recommended that water solenoid valves be installed on heat pumps that share a flow center. This is to allow water flow through only the heat pump that has a demand. Circulating fluid through a heat exchanger of a system that is not operating could be detrimental to the long term reliability of the compressor.
Figure 2: Primary/Secondary Hook-up
5 Series to
Electromechanical Units
5 Series Unit #1 with AXB Board
C
To Electromechanical Unit
S
OUTIN C C
VSSLOSLI
With pump wired to Unit 1
With pump wired to Unit 2
5 Series to
5 Series Units
5 Series Unit #1
with AXB Board
OUTIN C C
OUTIN C C
5 Series Unit #2 with AXB Board
VSSLOSLI
VSSLOSLI
5 Series to
Envision Units
5 Series Unit #1
with AXB Board
With pump wired to Unit 1
Shut
CC
Down
Envision Unit #2
OUTIN C C
VSSLOSLI
With pump wired to Unit 2
SL1InSL1
Out
Variable Speed Pump Setup
When using a variable speed pump flow center (FCV1-GL, FCV2-GL, FCV1-GLNP or FCV2-GLNP) the use of an AID Tool will be necessary to adjust minimum and maximum flow rates. The factory default is minimum = 75% and maximum 100% flow levels. Since the OptiHeat is a single speed unit, the minimum and maximum must be set at the same level. See the Variable Speed Pump Setup and Modulating Water Valve Setup instructions within the Unit Startup section which is located in the back of this manual. Refer to the Flow Rate section of this manual to ensure that there is adequate flow for the heat pump.
10
Hydronic Section
5 SERIES OPTIHEAT 504W11 INSTALLATION MANUAL
General guidelines are shown below for component selection and design/installation criteria for the piping system. Local codes supersede any recommendations in this manual.
Shut Off/Flow Regulation Valves
Use full port ball valves or gate valves for component isolation. If valves are going to be used frequently, ball valves are recommended. Globe valves are designed for flow regulation. Always install globe valves in the correct direction (fluid should enter through the lower body chamber).
Check valves
Swing check valves must be installed in the horizontal position with the bonnet of the valve upright. Spring check valves can be mounted in any position. A flow check valve is required to prevent thermo-siphoning (or gravity flow) when the circulator pump is off or when there are two circulators on the same system.
Storage (Buffer) Tank
A buffer tank is required for all hydronic heating systems
using OptiHeat heat pumps. The tank should be sized to provide 2 gallons of storage capacity for every one thousand Btuh’s of nominal heat pump capacity.
Pressure Relief Valve
Most codes require the use of a pressure relief valve if a closed loop heat source can be isolated by valves. Even if local code does not require this device, WaterFurnace recommends its installation. If the pressure relief valve in the buffer tank is not already rated at 30 psi (207 kPa) maximum pressure, one must be installed. The pressure relief valve should be tested at start up for operation. Note that the waste pipe must be at least the same diameter as the valve outlet (never reduce), and valves may not be added to this pipe. The bottom of the pipe must terminate at least 6” (15 cm) above the floor. If the piping is connected to a drain, there must be an air gap.
Backflow Prevention Check Valves
Most codes require backflow prevention check valves. Note that a single check valve is not equal to a backflow prevention check valve. Even if local code does not require this device, WaterFurnace recommends its installation. This is particularly important if the system will use antifreeze.
0 psi (0 kPa), potentially causing pumps(s) failure. A valve should be installed on each side of the pressure reducing valve for servicing. Both valves should have tags reading
“Do not shut this valve under normal operation – service
valve only.”
Expansion Tanks
Expansion tanks are required on hydronic systems to help absorb the pressure swings as the temperature in the system fluctuates.
Elbows/Tees
Long radius elbows or two 45° elbows will lower pressure drop. Standard tees have a greater restriction on the “T” portion than tees designed with angled outlet ports.
Antifreeze
Antifreeze is required if any of the piping system is located
in areas subject to freezing.
Dielectric Unions
Dielectric unions are recommended whenever connecting two dissimilar metals together to prevent electro-galvanic corrosion.
When using the various types of hydronic heat distribution
systems, the temperature limits of the geothermal system must be a major consideration. In new construction, the distribution system can easily be designed with the temperature limits in mind. In retrofits, care must be taken to address the operating temperature limits of the existing distribution system. The maximum storage tank temperature for the OptiHeat is 150°F (65°C). Typical in floor radiant systems require much lower temperatures, typically 100°-115°F, which is ideal for the OptiHeat.
On load pumps open the screw 2 turns only in the end of the
pump motor (if Grundfos air to be discharged and to ensure the motor housing has been flooded.
®
pumps are used) to allow trapped
Pressure Reducing Valves or Feed Water Valves
This valve lowers the pressure from the make-up water line
to the system. Most are adjustable and directional. A “fast fill” valve is required for initial filling of the system. Some have screens, which must be cleaned after the initial filling. If there is a restriction in the screen, the system could go to
11
5 SERIES OPTIHEAT 504W11 INSTALLATION MANUAL
Hydronic Section cont.
If using a Geothermal Storage tank there will be two red wires exiting out of the top of the tank. These red wries extend internally down to the thermistor/tank thermostat section of the tank. Remove the bottom tank cover to expose the red wires as well as the yellow tank thermistor wires.
HydroZone
If using HydroZone control, connect the two red wires to the two yellow wires using wire nuts. Next, connect the two red wires from the top of the Geothermal Storage tank to “TS” and “GND” on the HydroZone. The “OAT” and “GND” terminals on the HydroZone are used for an outdoor air sensor.
HydroStat
If using HydroStat control, connect the two red wires to the yellow wires using wire nuts. Next, connect the two red wires from the top of the Geothermal Storage tank to “TS” and “GND” on the HydroStat. The “OAT” and “GND” terminals on the HydroStat are used to connect the controller to the ELWT (Entering Load Water Temperature) well point sensor. This sensor is located on the load side entering water line inside the unit.
For other field installed controllers, these two red wires will need wired to the appropriate sensor input terminals. Another option for connection is to connect the thermostat on the Geothermal Storage tank directly to “R” and “Y1” on the ABC board.
Adequate rate of flow (GPM) is very important to system performance and long term reliability. Follow the guidelines for recommended flow in the recommendations table.
WaterFurnace Geothermal Storage Tank Thermostat and Thermistor
Thermostat
HydroZone
or HydroStat
30 psi
RELIEF VALVE
Back Flow Preventer /
Pressure Relief Valve
Dielectric
Unions
Dielectric
Unions
NOTES: * A 30 psi pressure relief valve (Part No: SRV30) should be used in
hydronic applications. ** Vent valve or P/T port at highest point in return line prior to ball valve.
Pressure
Gauge
GEO
STORAGE
TANK
1-1/2 in. FPT
Dip Tube
Ball Valve
Expansion
Tank
Air
Vent
Air
Separator
Ball Valve
LOAD PUMP
HYDRONIC
LOAD
Source OUT
P/T PortsP/T Ports
Source IN
NEW Series
12
5 SERIES OPTIHEAT 504W11 INSTALLATION MANUAL
External Control
An external controller is necessary for operation. For water storage tank set point control the HydroStat HSC, HZC, and HZ0
were designed specifically for our Geo-Storage Tanks. A field supplied aquastat may also be used as the external control to the heat pump. If zoning is required, the Hydrologic Zone Panels and Control system can provide up to eight zones of closed loop hydronic heating and cooling.
HydroStat (HSC) features:
• Communicating Controller
• Pump Sampling
2 1/2” x 2 1/2” LCD display and five push buttons serve as the human interface
Controls and regulates water tank temperature
Fahrenheit or Celsius
Symphony Compatibility - without HydroStat the tank temperature won’t be displayed on Symphony.
• Single Stage
HydroZone (HZC) features:
2 1/2” x 2 1/2” LCD display and five push buttons serve as the human interface
Controls and regulates water tank temperature
Fahrenheit or Celsius
• Outdoor reset
Warm weather shutdown
• Single Stage
HydroZone (HZO) features:
HZC mounted on 7.5” x 7.5” x 3.25” electrical box
HydroZone relay board
2 1/2” x 2 1/2” LCD display and five push buttons serve as the human interface
Controls and regulates water tank temperature
Fahrenheit or Celsius
• Outdoor reset
Warm weather shutdown
Staging (up to 4 stages)
Lead/Lag (when staging)
HydroLogic features:
Operates radiant floor heating
Operates hydronic fan coil heating and cooling
4 zones expandable to 8 zones
Communicating 2 wire controls
Controls 2 stages of compressors with rotation
Controls backup heat source
Intelligent heat/cool switchover
Fahrenheit or Celsius
• Outdoor reset
Indoor temperature feedback
Warm weather shutdown
13
5 SERIES OPTIHEAT 504W11 INSTALLATION MANUAL
Accessories and Options
IntelliStart (Model 040 only)
IntelliStart is a single phase compressor soft starter which reduces the normal start current (LRA) by 60-70%. It should be used in applications that require low starting amps, reduced compressor start-up noise, off-grid, and improved start-up behavior. IntelliStart is available as a factory installed option or a field installed kit. IntelliStart is available on 208-230/60/1 voltage.
Water Connection Kits (Field Installed)
Water connection kits are available to facilitate loop side and load side water connections.
• MA4FPT - Forged brass 1" MPT x 1" FPT square street elbow with P/T plug for NEW040 water side connections
• MA5FPT - Forged brass 1.25" MPT x 1.25" FPT square street elbow with P/T plug for NEW050-NEW066 water side connections
• WFI-HKM-100-24-MO - 1 inch x 24 inch stainless steel braided hose kit
• WFI-HKM-125-24-MO - 1
1
4 inch x 24 inch stainless steel
braided hose kit
Earth Loop Pump Kit (Field Installed)
A specially designed one or two-pump module provides all liquid flow, fill and connection requirements for independent single unit systems (230/60/1 only). The one-pump module (FC1-FPT or FC1-GL) is capable of 25 feet of head at 12.0 GPM, while the two-pump module (FC2-FPT or FC1-GL) is capable of 50 feet of head at 12.0 GPM.
Load-side Pump Kit (Field Installed)
Four (4) load pump kits are available to provide all liquid flow requirements for independent single unit systems (230/60/1 only). WaterFurnace part number 24S516-
10 (Grundfos UPS15-42RU) is a composite body pump. EWPK2 (Grundfos UP26-99SF) is stainless steel body
pump. WaterFurnace part number EWPK1 and EWPK3 come with a cast iron body pump (Grundfos UP26-99F) that can be used for hydronic heating applications.
Calculate the system pressure drop then refer to the pump curves in figure 8 to select the proper pump. All four (4) of the WaterFurnace pump kits can be used for hydronic heating applications as long as they meet the flow requirements. If the flow requirements are outside the pump curve, an alternate pump will need to be obtained to maintain the necessary flow.
• 24S516-10 - UPS15-42RU composite PPS, sweat connection
• EWPK1 - UP26-99F cast iron volute, 1 inch FPT flange connection
• EWPK2 - UP26-99SF Stainless Steel volute, 1 inch FPT flange connection
• EWPK3 - UP26-99F cast iron volute, 1­flange connection
3
4 inch union
1
4 inch FPT
Figure 8: UPS15-42RU and UP26-99F Pump Curve
UPS15-42RU, and UP26-99F Single Pump Curve
Pump Curve - Single Pump
35
30
25
20
15
Feet of Head
10
5
0
0 5 10 15 20 25 30 35
26-99F Two Pump Curve
Pump Curve - Two Pumps
70
60
50
40
30
Feet of Head
20
10
0
0 5 10 15 20 25 30 35
GPM
GPM
UP26-99F (2 pumps)
UP26-99F UPS15-42RU
NOTE: Never use piping smaller than 1 inch. Limit length of pipe to 50 feet or less.
Type L Copper Pressure Loss
Ft of Hd per 100 ft
GPM 3/4 1 1-1/4 1-1/2 2
2 3 4 5 6 7 8
9 10 12 14 16 18 20 22 25 30 35 40 45 50
1.5
3.2
5.5 1.4
8.5 2.1
Type L Copper Tube
2.9 1.1
3.9 1.4
5.0 1.8
6.1 2.3 0.9
7.5 2.8 1.1
3.9 1.6
5.2 2.1
6.6 2.7
8.2 3.4
10.0 4.1 1.1
5.0 1.3
6.3 1.6
2.2
2.9
3.8
4.7
5.7
NOTE: Standard piping practice limits pressure drop to 4 feet of hd per 100 feet in 2 inch and larger pipe.
14
Accessories and Options cont.
5 SERIES OPTIHEAT 504W11 INSTALLATION MANUAL
Geo Storage Tank Dimensions
PRIMARY ANODE
3/4˝ HOT OUTLET
w/14˝ SECONDARY ANODE
HEIGHT
Optional “To Geo”
Connection Shipped with
1-1/2˝ Pipe Plug
Taped to Bottom of Packaging
From Geo
1˝ x 3˝ Nipple
39˝ - 80 Gallon
42˝ - 119 Gallon
Approx. 1˝
VALV E
35-3/4˝
DRAIN VALVE
T & P
°
3
0
3
DIAMETER
0
°
To Geo 59˝ Dip Tube w/1˝ x 3˝ Nipple
COLD INLET
3/4˝
52˝ DIP TUBE
Red Wire attached to Thermistor or Thermostat for Top Exit
Element Location
Lower Sensor Thermistor to be used by Hydrozone or HydroStat Controllers
Optional “From Geo” Connection Shipped with 1-1/2˝ Pipe Plug Installed
5-1/4˝
Lower Thermostat to be used with Aurora Base Control Board
MODEL
NUMBER
GEO-STORAGE-80*
GEO-STORAGE-120**
* 040 Only ** 050 & 066 Only
GALLON
CAPACITY
80 4500 1 16 63-1/4 24 204
119 4500 1 16 63-1/4 28 311
ELEMENT
WATTAGE
(240 VOLT)
NUMBER
OF
ELEMENTS
R
VALUE
DIMENSIONS IN INCHES APPROX.
HEIGHT DIAMETER
15
SHIPPING
WEIGHT (lbs.)
Loading...
+ 33 hidden pages