B – PSC Blower & Aluminum Air Coil
C – ECM Blower & Aluminum Air Coil
Non-Standard Option
Details
SS – Standard Option
Air Coil/Insulation Option
5 – AlumiSeal
TM
/Extended Range
Sound Kit
A – None
B – Blanket
Future Option
N – None
Motorized Outside Air Da
mper
(Field Installed)
N – None
M – Motorized Damper
Water Coil Option
Thermostat Control
Rev.:
N
11
31-2
NB5SS
121314
15-16
C
17
Model Nomenclature
Model
NK – Envision Series
Console 50Hz
Cabinet Configuration
C – Chassis Only
F – Chassis with CabinetS – Chassis Slope Top
E – Chassis with Extended
Slope Top
Unit Capacity
02, 03, 04, 05
Piping Option
L – Left
R – Right
Voltage
6 – 220-240/50/1
Unit Control
1 – CCM
2 – Versatec Microprocessor
4 – FX10 Std. w/o Communication
5 – FX10 w/Open N2 Com Card
6 – FX10 w/Lonworks Com Card
7 – FX10 w/BacNet Com Card
NOTES: Chassis only available with left piping option.
FX10 option is only available with remote wall-mounted thermostat control.
C – Copper
N - CuproNickel
1 – Unit Mounted T-Stat
2 – Remote Wall-Mounted T-Stat
02 March 2014D
All Envision Series product is Safety listed under UL1995 thru ETL.
4
Page 5
General Installation Information
ENVISION CONSOLE - 50 HZ INSTALLATION MANUAL
Safety Considerations
WARNING: Before performing service or
maintenance operations on a system, turn off main
power switches to the indoor unit. If applicable,
turn off the accessory heater power switch.
Electrical shock could cause personal injury.
Installing and servicing heating and air conditioning
equipment can be hazardous due to system pressure and
electrical components. Only trained and qualified service
personnel should install, repair or service heating and air
conditioning equipment. Untrained personnel can perform
the basic maintenance functions of cleaning coils and
cleaning and replacing filters. All other operations should
be performed by trained service personnel. When working
on heating and air conditioning equipment, observe
precautions in the literature, tags and labels attached to the
unit and other safety precautions that may apply.
Follow all safety codes. Wear safety glasses and work
gloves. Use a quenching cloth for brazing operations and
have a fire extinguisher available.
Moving and Storage
Move units in the normal “up” orientation. Do not stack
units. When the equipment is received, all items should be
carefully checked against the bill of lading to be sure all
crates and cartons have been received. Examine units for
shipping damage, removing the units from the packaging
if necessary. Units in question should also be internally
inspected. If any damage is noted, the carrier should make
the proper notation on the delivery receipt, acknowledging
the damage.
Refrigerant Systems
To maintain sealed circuit integrity, do not install service
gauges unless unit operation appears abnormal. Compare
the change in temperature on the air side as well as the
water side to the Unit Operating Parameters tables. If the
unit’s performance is not within the ranges listed, and the
airflow and water flow are known to be correct, gauges
should then be installed and superheat and subcooling
numbers calculated. If superheat and subcooling are outside
recommended ranges, an adjustment to the refrigerant
charge may be necessary.
Water Piping
The proper water flow must be provided to each unit
whenever the unit operates. To assure proper flow, use
pressure/temperature ports to determine the flow rate.
These ports should be located at the supply and return
water connections on the unit. The proper flow rate cannot
be accurately set without measuring the water pressure
drop through the refrigerant-to-water heat exchanger.
All source water connections on commercial units are
fittings that accept a male pipe thread (MPT). Insert the
connectors by hand, then tighten the fitting with a wrench
to provide a leakproof joint. When connecting to an open
loop (groundwater) system, thread any copper MPT fitting
into the connector and tighten in the same manner as
described above.
• Choose level flooring surface (Correctable with shims.
Do not pitch towards drain.)
• Location of wall support and fasteners required to
secure chassis backplate.
• Easy access for both installation and service.
• Consider availability and ease of wiring, water piping and
condensate drain.
• No obstructions to block airflow in front of the unit.
Step 3: Mark Unit Position
• Ensure that floor is level. If shims are required, make
sure that the entire compressor compartment area is
uniformly shimmed and that the backplate mounting
height is increased by the thickness of the shims used.
Figure 1
• Position backplate in desired equipment location. To
further reduce the operating sound level of the unit,
1/8 in. thick rubber matting may be placed under the
chassis to eliminate vibration on hard flooring surfaces.
(Make sure back plate is level).
• Mark and cut floor or wall penetrations for electrical
wiring, water and condensate piping.
Optional Electrical Disconnect and Motorized
Outside Air Damper
• Mark and cut wall penetrations for field fabricated
outside air duct sleeve.
• Align mounting holes with backplate and attach with
screws supplied.
1=<A=:31/07<3B
0/19 >:/B3
=>B7=</:
4CA323:31B@71/:
27A1=<<3 1B =>B7=</ :
E/::>3<3B@/B7=<
4=@E/B3@1=<<31B7=<
4:==@>3<3B@/B7=<
4=@E/B3@1=<<31B7=<
E/B3@
7<
E/B3@
=CB
>B>:C5A
=>B7=</:
0/::D/:D3A
=>B7=</:
=>B7=</: 6=A3 A
1=<23<A/B 3
2@/7< :=1/B7=<
;=B=@7H32
2/; >3@
=>3<7<5
;=B=@7H32
2/; >3@
=>B7=</:
1=<A=:3
1/07<3 B
1=<A=:3
16/AA7A
13
Page 14
ENVISION CONSOLE - 50 HZ INSTALLATION MANUAL
Installation Steps cont.
Step 4: Provide Water and Condensate Drain
Connections
• A two-pipe reverse return piping configuration is
recommended as it equalizes the piping circuit lengths
and delivers even water flow to each unit. A direct return
piping configuration may be used, but it may be difficult
to achieve and maintain proper water flow to the units.
Pipe Locations
Figure 2
1=<A=:3
1/07<3B
E/B 3@1=<< 31B7 =<A
4CA323:31B@71/:
27A1=<<31B=>B7=</:
1=<A=:3
16/AA7A
• An air vent must be installed in the water
distribution system.
• The supply and return water piping should be run
through the wall or floor penetration and terminate with
a ball valve. The piping material used must comply with
all local codes.
• Refer to: System Cleaning and Flushing procedures.
"D /113AA=@G
%[[f [[/@3/
/>>=F ![[4@=;3253=4
16/AA7A %$[ [4@= ;4:= =@
B/@53B/@3/4=@
E/::>3<3B@/B7=<
B/@53B/@3/4=@
4:==@>3<3B@/B7=<
1/07<3B3FB3<2A
B=B67A>=7<B
%[[f [[/@3/
/>>=F ![[4@=;3253
=416/AA7A #[[4@=;
4@=<B3253=41/07<3B
3:31 B@71/:
8C<1B7=<0=F
1=<23<A/B 3
2@/7< :=1/B7=<
&Þ
#Þ
14
Page 15
Installation Steps cont.
ENVISION CONSOLE - 50 HZ INSTALLATION MANUAL
Step 5: Provide Line Voltage Wiring
• Check unit data plate located on control side of chassis
for ampacity and fuse size.
• Remove electrical knockouts from chassis backplate.
• Run line voltage wiring through knockout and secure
wiring to backplate or disconnect.
Step 6: Chassis Installation
• Level and secure backplate to wall.
• Position the chassis against back plate. Drive (2) screws
through holes in lip of backplate into top flange of chassis.
Step 7: Final Electrical Connection
• Install flexible electrical conduit between the backplate or
electrical disconnect and the unit mounted junction box.
• Make final wiring connections in disconnect and junction
box, taking care to replace all covers when done. Wiring
must conform to NEC and/or all local codes. Refer to
Electrical Data.
NOTE: It is necessary to make final wiring connections
prior to securing unit chassis to back plate on right-hand
piping models with electrical disconnect.
Step 8: Final Water Connection
• For ease of installation and sound attenuation, high
pressure (recommended) flexible hoses with a swivel
fitting should be provided. Apply Teflon® tape or sealant
compound to threaded hose fittings.
• Combination shut-off/balancing valves should be installed
on both the supply and return water lines of the unit.
• Flow control valves should be installed on the water
discharge line.
• It is recommended that P/T ports be installed on the
supply and return water lines.
Step 9: Set Unit Controls
• Locate the “continuous fan/cycle fan” switch within the
electrical compartment of the chassis and set to desired
position. (Remote wall thermostat units do not use this
optional switch.)
• Optional Control Settings- Remote Thermostat - Run
low voltage wiring from unit to the desired thermostat
location. Mount and wire thermostat according to
manufacturer’s recommendations.
Motorized Outside Air Damper - Locate the “damper on/
damper off” damper switch within the electrical compartment of the chassis and set to desired position.
Step 10: Secure the Cabinet Cover
• Position and lower cabinet over unit chassis. Apply
pressure to the front of the cabinet to ensure that the
back lip of the cabinet hooks over the tabs provided on
the backplate.
• Secure cabinet to chassis with mounting screws provided.
Step 11: Perform Final Unit Check
• Measure the pressure drop across the water coil and
monitor water or air temperatures in both heating
and cooling modes. The measured values should fall
within the acceptable ranges shown in the Startup Performance table.
15
Page 16
ENVISION CONSOLE - 50 HZ INSTALLATION MANUAL
Installation Steps cont.
Field Converting Console
Chassis is normally configured with controls on right end
and piping on left end (see Figure 3 top view). In this
position panel number 1 would be positioned against wall
or back plate. Unit may also be turned 180° against wall or
back plate. In this position controls will be on left end and
piping on right end panel number 2 would be positioned
against wall or back plate. Chassis must be enclosed with
an approved cabinet enclosure.
Figure 3
Top view
Side view
1
2
5. Replace grille/frame assembly into cabinet, and secure
by replacing mounting brackets.
6. Replace cabinet by sliding it down over the top of
the chassis.
7. Remove tab on leg that extends into return air opening.
When the grille side of the cabinet is flat against chassis
there will be 4 holes that line up in the leg section.
Only use 1 hole for alignment for opposite side of grille.
(NOTE: The tab can be removed by twisting back and
forth until it breaks off.)
8. Remove plastic strip from tab and replace on rough
edge that the tab was removed from.
9. Replace screws in font kick panel to secure cabinet
to chassis.
10. Mount filter bracket in designated opening area.
(NOTE: The filter bracket will only fit in one direction if
cabinet is installed properly.)
Figure 4
Depends on Cabinet Size
3
2
1
1. Remove 4 screws from front kick panel on cabinet.
2. Remove cabinet from chassis by lifting and sliding
cabinet straight up.
3. Remove grille assembly from cabinet by removing 4
screws from brackets located on the bottom of the grille
and door assemblies.
4. Replace grille/door assemblies into cabinet
repositioning pieces 1, 2, and 3 into the locations directly
opposite the original positions. Secure by replacing
mounting brackets. (Note: Be sure that louvers on the
grille assembly are facing the proper direction when
replacing the grille section.)
4
5
16
Page 17
Water Quality
ENVISION CONSOLE - 50 HZ INSTALLATION MANUAL
In ground water situations where scaling could be heavy
or where biological growth such as iron bacteria will be
with extremely hard water, the owner should be informed
that the heat exchanger may require occasional flushing.
present, a closed loop system is recommended. The heat
exchanger coils in ground water systems may, over a period
of time, lose heat exchange capabilities due to a buildup
of mineral deposits inside. These can be cleaned, but only
by a qualified service mechanic, as special solutions and
pumping equipment are required. Hot water generator coils
Units with cupronickel heat exchangers are recommended
for open loop applications due to the increased resistance
to build-up and corrosion, along with reduced wear caused
by acid cleaning. Failure to adhere to the guidelines in the
water quality table could result in loss of warranty.
can likewise become scaled and possibly plugged. In areas
AmmoniaLess than 2 ppmLess than 2 ppmLess than 20 ppm
Ammonia ChlorideLess than 0.5 ppmLess than 0.5 ppmLess than 0.5 ppm
Ammonia NitrateLess than 0.5 ppmLess than 0.5 ppmLess than 0.5 ppm
Ammonia HydroxideLess than 0.5 ppmLess than 0.5 ppmLess than 0.5 ppm
Ammonia SulfateLess than 0.5 ppmLess than 0.5 ppmLess than 0.5 ppm
Total Dissolved Solids (TDS)Less than 1000 ppm1000 - 1500 ppm1000 - 1500 ppm
LSI Index+0.5 to -0.5+0.5 to -0.5+0.5 to -0.5
Iron, FE
Bacterial Iron Potential
Iron Oxide
Suspended Solids
Threshold Velocity
(Fresh Water)
Less than 0.5 ppm (rotten egg
smell appears at 0.5 ppm)
SulfatesLess than 125 ppmLess than 125 ppmLess than 200 ppm
ChlorineLess than 0.5 ppmLess than 0.5 ppmLess than 0.5 ppm
2
+ (Ferrous)
Less than 1 ppm, above this
level deposition will occur
Less than 10 ppm and filtered
for max. of 600 micron size
7 - 97 - 97 - 9
(Total Hardness)
less than 350 ppm
< 0.2 ppm< 0.2 ppm< 0.2 ppm
< 1.8 m/sec< 1.8 m/sec< 1.8 m/sec
(Total Hardness)
less than 350 ppm
10 - 50 ppmLess than 1 ppm
Less than 1 ppm, above this
level deposition will occur
Less than 10 ppm and filtered
for max. of 600 micron size
(Total Hardness)
less than 350 ppm
Less than 1 ppm, above this
level deposition will occur
Less than 10 ppm and filtered
for max. of 600 micron size
2/22/12
17
Page 18
ENVISION CONSOLE - 50 HZ INSTALLATION MANUAL
System Cleaning and Flushing
Cleaning and Flushing
Prior to start up of any heat pump, the water circulating
system must be cleaned and flushed of all dirt and debris.
If the system is equipped with water shutoff valves, the
supply and return runouts must be connected together at
each unit location (This will prevent the introduction of dirt
into the unit, see Figure 7). The system should be filled
at the water make-up connection with all air vents open.
After filling, vents should be closed.
The contractor should start the main circulator with the
pressure reducing valve makeup open. Vents should be
checked in sequence to bleed off any trapped air and to
verify circulation through all components of the system.
As water circulates through the system, the contractor should
check and repair any leaks found in the piping system. Drain(s)
at the lowest point(s) in the system should be opened for
initial flush and blowdown, making sure water fill valves are
set at the same rate. Check the pressure gauge at the pump
suction and manually adjust the make-up water valve to hold
the same positive pressure both before and after opening the
drain valves. Flushing should continue for at least two hours, or
longer if required, until drain water is clean and clear.
The supplemental heater and/or circulator pump, if used,
should be shut off. All drains and vents should be opened
to completely drain the system. Short-circuited supply and
return runouts should now be connected to the unit supply
and return connections.
Refill the system with clean water. Test the system water
for acidity and treat as required to leave the water slightly
alkaline (pH 7.5 to 8.5). The specified percentage of
antifreeze may also be added at this time. Use commercial
grade antifreeze designed for HVAC systems only.
Environol™ brand antifreeze is recommended.
Ground Source Loop System Checkout
Figure 7: Flushing with Water
Shutoff Valve Equipped Systems
Return Runout
Supply Runout
Mains
Rubber Hose
Runouts Initially
Connected Together
Once piping is completed between the unit pumping
system and ground loop, final purging and charging of
the loop is needed. A high pressure pump is needed to
achieve adequate flow velocity in the loop to purge air
and dirt particles from the loop itself. Antifreeze solution
is used in most areas to prevent freezing. Flush the
system adequately to remove as much air as possible;
then pressurize the loop to a static pressure of 275-345
kPa (summer) or 345-517 kPa (winter). This is normally
adequate for good system operation. Loop static pressure
may decrease soon after initial installation, due to pipe
expansion and loop temperature change. Running the
unit for at least 30 minutes after the system has been
completely purged of air will allow for the “break-in”
period. It may be necessary to adjust static loop pressure
(by adding water) after the unit has run for the first time.
Loop static pressure will also fluctuate with the seasons.
Pressures will be higher in the winter months than during
the cooling season. This fluctuation is normal and should
be considered when charging the system initially.
Once the system has been filled with clean water and
antifreeze (if used), precautions should be taken to protect
the system from dirty water conditions. Dirty water will
result in system-wide degradation of performance, and
solids may clog valves, strainers, flow regulators, etc.
Additionally, the heat exchanger may become clogged
which reduces compressor service life and can cause
premature unit failure.
In boiler/tower application, set the loop control panel
set points to desired temperatures. Supply power to all
motors and start the circulating pumps. After full flow has
been established through all components including the
heat rejector (regardless of season), air vented and loop
temperatures stabilized, each of the units will be ready for
check, test and start up and for air and water balancing.
Ensure the pump provides adequate flow through the unit
by checking pressure drop across the heat exchanger.
Usually 33-45 ml/s of flow per kW of cooling capacity is
recommended in earth loop applications.
18
Page 19
Open Loop Ground Water Systems
ENVISION CONSOLE - 50 HZ INSTALLATION MANUAL
Always maintain water pressure in the heat exchanger by
placing water control valves at the outlet of the unit to
prevent mineral precipitation. Use a closed, bladder-type
expansion tank to minimize mineral formation due to air
exposure. Ensure proper water flow through the unit by
checking pressure drop across the heat exchanger and
comparing it to the figures in unit capacity data tables
in the specification catalog. .09-.13 l/s of flow per kW of
cooling capacity is recommended in open loop applications.
Discharge water from the unit is not contaminated in any
manner and can be disposed of in various ways, depending
on local codes, i.e. recharge well, storm sewer, drain field,
adjacent stream or pond, etc. Most local codes forbid
the use of sanitary sewer for disposal. Consult your local
building and zoning departments to assure compliance in
your area.
NOTE: For open loop/groundwater systems or systems
that do not contain an antifreeze solution, set SW1-Switch
#2 to the “WELL” position
Selection table). Slow opening/closing solenoid valves
(type VM) are recommended to eliminate water hammer.
(Refer to the Dip Switch Field
19
Page 20
ENVISION CONSOLE - 50 HZ INSTALLATION MANUAL
Electrical Connections
General
Be sure the available power is the same voltage and phase
as that shown on the unit serial plate. Line and low voltage
wiring must be done in accordance with local codes or the
National Electric Code, whichever is applicable.
240 Volt Operation
All Envision Series 220/240 units are factory wired for 220
volt operation. For 240 volt operation, the red and blue
transformer wires must be switched.
Microprocessor Remote Thermostat Wiring
Figure 5
Requires common
connections or 24
VAC for activation
Field
Connections
24 VAC
COMMON
COMPRESSOR
REVERSING
VALVE
FAN
LOCKOUT
SIGNAL
SHUTDOWN
NIGHT
SETBACK
LOAD SHED
Connections
TB
R
C
Y
O
G
L
S
X2
X1
W2
Unit
Red
Black
Yellow
Orange
Green
Brown
Blue
Violet
Pink
20
Page 21
Electrical Data
ECM Blowers
ENVISION CONSOLE - 50 HZ INSTALLATION MANUAL
Model
02
03
04
05
HACR circuit breaker in USA only3/05/14
Rated
Voltage
220-240/50/1198/2646.44.117.02.66.77.710/15
220-240/50/1198/2647.64.918.72.67.58.810/15
220-240/50/1198/2649.25.923.02.68.510.015
220-240/50/1198/26410.56.724.02.69.311.015
Voltage
Min/Max
MCCRLALRA
Compressor
Blower
Motor
FLA
Total
Unit
FLA
Min
Circ
Amp
Max
Fuse/
HACR
PSC Blowers
Model
02
03
04
05
HACR circuit breaker in USA only3/05/14
Rated
Voltage
220-240/50/1198/2646.44.117.00.504.65.610/15
220-240/50/1198/2647.64.918.70.505.46.610/15
220-240/50/1198/2649.25.923.00.696.68.110/15
220-240/50/1198/26410.56.724.00.697.49.115
Voltage
Min/Max
MCCRLALRA
Compressor
Blower
Motor
FLA
Total
Unit
FLA
Min
Circ
Amp
Max
Fuse/
HACR
Blower Performance Data
PSC BlowersECM Blowers
Model
02
03
04
05
Factory settings are in Bold
Air fl ow values are with dry coil and standard fi lter.
For wet coil performance fi rst calculate the face velocity of the air
coil (Face Velocity [mps] = Airfl ow [lps] / Face Area [m
velocities of 1 mps, reduce the static capability by 7.5 pa, 1.5 mps by 19.9
pa, 2 mps by 29.9 pa and 2.5 mps by 39.8 pa.
Low SpeedHigh Speed
120140
120140
175200
175200
LPS
2
]). Then for
Model
02
03
04
05
Factory settings are in Bold
Air fl ow values are with dry coil and standard fi lter.
For wet coil performance fi rst calculate the face velocity of the air
coil (Face Velocity [mps] = Airfl ow [lps] / Face Area [m
velocities of 1 mps, reduce the static capability by 7.5 pa, 1.5 mps by 19.9
pa, 2 mps by 29.9 pa and 2.5 mps by 39.8 pa.
LPS
Low SpeedMedium SpeedHigh Speed
140150190
140150190
165210280
165210280
2
]). Then for
21
Page 22
ENVISION CONSOLE - 50 HZ INSTALLATION MANUAL
Wiring Schematics
CCM - ELECTRONIC THERMOSTAT220-240/50/1
PSC
Fan
Motor
Grn
HL
Wht
White (28)
Brn
Cap
Blue
Tan (33)
Whit e ( 28 )
Compressor
S
R
RedBlk
T2
CC
L2
C
Ground
Handi -Box
T1
Brown (26)
L1
Black (31 )
Red (32)
Lug
Unit
Power Supply
220/50/1
G
Red (30)
Electronic THERMOSTAT
A Heat
T2
Shu t d own
T5
Overide
B Cool
J1
Black (2 9)
Yellow (13)
T1
T3
T4
T6
IN
PUT
Fan Swi tch
High
Low
White (18)
Red (17)
Red (11)
Ther
mistor
24 V
AC
T3
T1
T2
T4
T6
T5
SHUT
DOWN
Black (2 5)
Mode Switch
4
6
1
Auto
Fan
3
Black
Black
Red
Black (1 2)
Red (11)
Orange
4
5
2
ST
Red
Red (15)
Red (16)
2
Black (2 7)
RB
5
Brown (26)
Red (19)
Yellow (10 )
T
Red (17)
Yell o w (1 3)
Orange (14)Orange ( 21)
Blue (T 6 )
24VAC
Shu t do w n
Yell o w (1 3)
Fan M ode Sw
Continuous
Cycled
RV
Whit e ( 20 )
Not Used
Whit e (18 )
Black
NOTE 1
Red
Trans f ormer
NOTE 2
FS
200V
Yellow Black/White
HP
LP
Violet (5)
Violet (4)
Blue/Wht (36)
24 V
Black/White (1)
Red (2)
Brown (3)
Violet (4)
Violet (5)
Black (6)
Black (7)
Blue (8)
Blue (9)
Yell o w (1 0)
Blk/ W h t (23)
24 V Acce ss or y
HP HP CC CG LO R CLP LPY
CC
Blk/Wh t (24 )
HP HP CC CG LO R CLP LPY
White (34)
Damper
Motor
D
TEST
PIN
COMPRESSOR
CONTROL MODULE
Damper Swi tch
ON
OFF
Blue/Wht (35)
DT
Blue
220V
PB
Red (19)
Black (1 2 )
Black (2 2)
Black (22)
31
RB
1
2
3
Green (00)
NOTE 3
Factory low voltage wiring
Factory line voltage wiring
Field low voltage wiring
Field line voltage wiring
Quick connect terminal
Wire nut
CC -Compressor Contactor
DT - Damper Terminal Block
FS -Freeze Sensing Device
HP -High Pressure Switch
LP -Low Pressure Switch
PB - Power Block
RB -Blower Relay
RV -Reversing Valve Coil
ST -Entering Air Temperature Sensor
Legend
Field wire lug
L1
Earth Ground
Relay Contacts -
N.O., N.C.
132
P
Polarized connector
22
HP
LP
T
Switch -High Pressure
Switch -Low Pressure
Relay coil
Capacitor
Thermistor
Temperature Switch
Notes:
1. Switch Red and Blue wires for 200 volt
operation
2. Terminal C of 24 V PB is used as “L”
output for Brown wire 3 for Lockout.
CC - Compressor Contactor
DT - Damper Terminal Block
FS - Freeze Sensing Device
HP - High Pressure Switch
LP - Low Pressure Switch
PB - Power Block
RB - Blower Relay
RV - Reversing Valve Coil
ST - Entering Air Temperature Sensor
Legend
23
HP
LP
T
Switch - High Pressure
Switch - Low Pressure
Relay coil
Capacitor
Thermistor
Temperature Switch
Notes:
1. Switch Red and Blue wires for 208 volt
operation
2. Terminal C of 24 V PB is used as “L”
output for Brown wire 3 for Lockout.
3. Optional field installed freeze sensing device.
4. Factory wired. Refer to blower table settings.
L1
Field wire lug
Earth Ground
Relay Contacts N.O., N.C.
132
P
Polarized connector
Page 24
ENVISION CONSOLE - 50 HZ INSTALLATION MANUAL
Wiring Schematics cont.
Schematic [A]
Black
PSC
Fan
Motor
Low
White (28)
Brn/Wht
Brn
Cap
LS2
White
T2T1
L2
Blue (40)
LS1
White
EH
L1
Tan ( 4 1 )
Fan Speed
Switch
Grn
Black(29)
High
HL
Red (30)
220-240/50/1VERSATEC CONTROL - REMOTE WALL THERMOSTAT
Compressor
C
S
Blu
Tan ( 3 6 )
T2T1
R
Red
Blk
CC
L1L2
Black (3 1 )
Red (32)
Handi - B ox
Ground
Lug
Unit
Power Supply
208-230/60/1 or
265-277/60/1
G
Red
Black (2 5 )
DAMPER M ODE
Damper
Motor
White (34)
D
Off
On
RB
42
Blue /Wh t (35 )
Blue/Wht (36)
Black(27)
Black (22 )
COM
DT
CC
Brown (43 )
Red(19)
5
4
Red (39)
Blue (38)
EH
E1
2
Black (3 7 )
CC
CCG
SW1
1
2
3
4
5
OnOff
Test / Nor m a l
Loop / Well
Inp u ts / N o r ma l
Ou tp u ts / N o rma l
Motorized Valve / No r ma l
CPU
Blue 26 5V
Blue 23 0V
13
RB
FAN
P1
NOTE 5
Black Com
Orange (21)
Red 208V
Transformer
24V
Yellow
FAN
Black/White
R
R
C
C
6
2
7
3
8
4
9
5
10
Green (00)
P2
Black (47)1
Black (4 6 )
Blue (45)
Blue (44 )
Brown(43)
Orange (42)
Orange (41)
Yellow
Yellow
HP
LP
CO
Gray (42 )
RV
FS
T
LSNSESLOGOYCR
Red
Bl ack
Green
Yellow
Orange
Pink
Bl ue
Violet
Brown
White
E1
Factory low voltage wiring
Factory line voltage wiring
Field low voltage wiring
Field line voltage wiring
DC voltage PCB traces
Internal junction
Quick conne ct terminal
Wire nut
L1
Field wire lug
Ground
T
Relay ContactsN.O., N.C.
Thermistor
Re lay coil
Black/
White
MV
NOTE 2
P
Black/
White
Legend
132
Legend
Switch - High pressure
Switch - Low pressure
Polarized connector
Condensate Overflow
24
CRY1OGLS
Terminal Board
AQ – Aqua sta t
CC – Compres s or Contactor
CO – Condensate Overflow
DT – Damper Terminal Block
E1 – Electric Heat Relay
EH – Electric Heat Contactor
ES – Emergency Shutdown
FS – Freeze Sensing Device
HP – High Pressure Switch
LP – Low Pressure Switch
LS – Loadshed
MV – Mo to rized V alve
NS – Night Setback
RB – Blower Power Relay
RV – Reversing Valve Coil
SW1 – DIP Switch #1
X2 X1 W1
NOTE 1
NOTE 3
AQ
Notes:
1 -Requires common connection or 24 VAC for
activation.
2 -When fiel d ins tal l ed 24 V A C motor i z ed
valve is used, connect to C and Y or SV terminals.
3 -Optional field installed aquastat for use with single heat
4 -Check installlation wiring information for
specific thermostat hookup instructions.
5 -Switch blue and red wires for 208V operation.
97P786-04 6/10/08
Page 25
Wiring Schematics cont.
Legend for Schematic [A]
Blower of f delay
Compressor on delay
Short c y c le delay
Minimum compressor on time
High pres s ure f ault rec ognit ion delay
Low pres s ure f ault rec ognit ion delay
Freez e s ens ing f ault rec ognit ion delay
Condens at e ov erf low f ault rec ognit ion delay
Low pres s ure f ault by pas s delay
Freez e s ens ing f ault by pas s delay
Mot oriz ed v alv e delay
Random s t art delay
Norm al C ont rol T im ing T able
30 sec onds
10 sec onds
5 minutes
60 sec onds (except f or f ault c ondit ion )
Less t han 1 sec ond
30 sec onds
30 sec onds
30 sec onds
2 minut es
2 minutes
90 sec onds
0 -25 sec onds
ENVISION CONSOLE - 50 HZ INSTALLATION MANUAL
220-240/50/1VERSATEC CONTROL - REMOTE WALL THERMOSTAT
Versatec Logic Board Physical Layout
FANFANCOM
CC Relay
6
1
7
2
P2
8
3
9
4
10
5
CCG
CC
Fan Relay
C
C
R
R
Blower of f delay
Compressor on delay
Short c y c le delay
Minimum compressor on time
High pres s ure f ault rec ognit ion delay
Low pres s ure f ault rec ognit ion delay
Freez e s ens ing f ault rec ognit ion delay
Condens at e ov erf low f ault rec ognit ion delay
Low pres s ure f ault by pas s delay
Freez e s ens ing f ault by pas s delay
Mot oriz ed v alv e delay
Random s t art delay
5 seconds
2 sec onds
15 sec onds
5 sec onds (except f or f ault c ondit ion )
Less t han 1 sec ond
30 sec onds
30 sec onds
30 seconds
0 seconds
0 sec onds
90 sec onds
0 sec onds
LED Display Mode Table
LEDNormal Display Mode
SW1 - #4 On, SW2 Off
Test Control Timing Table
Drain
Wat e r Flo w
High Press
Low Pres s
Air Flow
Status
DHW Limit
HWD
LED
Drain
Wat e r Flo w
High Pres s
Low Pres s
Air Flow
Status
DHW Limit
HWD
*Flashing Status light indicates microprocessor is functioning properly. Solid "on" indicates a
microproce ssor malfunction.
Drain pan over f low loc kout
FS ther m istor (loop < - 9° C, well < -1° C ) lock out
High press ure >15 0 kPa lockout
Low press ur e <1 0 kPa lockout
Not used
Microprocessor malfunction*
Not Used
SW 2 status (Off = down pos it ion, On = up pos it ion)
Diagnostic Modes
Current Fault Status
SW1-# 4 On, SW2 On
Drain pan over f low
FS ther m istor (loop <-9° C, well <
High pressure > 150 kPa
Low press ur e < 10 kPa
Not used
Not used
Not used
SW2 in the On position
-1°C)
Inputs
SW1-#4 O ff , SW2 Off
Y
G
O
ES
NS
LS
Not Used
Off pos it ion
Outputs
SW 1- # 4 Off, SW2 On
Compressor
Not Used
On posit io n
FAN
Microprocessor
P3
P1
RCYOGLOESNSLS
Logic Cont rol
17P529A01
SW1
Logic Board D I P Sw it c h Set t ings
SwitchOFFON
Test - Selected timings sped up to facilitate
SW1 - 1
troubleshooting
Loop - Closed loop freeze sensing setting (15°F)
SW1 - 2
Enables NS features
SW1 - 3
IO Display * - Enables Input/Output display on external
SW1 - 4
LED board*
SW1 - 5
Motorized Valve - 1.5 minute compressor on delay
OFF * - Normal or Input display mode activated
SW2
*Refer to LED Display Mode table for position of SW1-4 and SW2
Normal - Standard timings
Well - Open loop freeze sensing setting (30°F)
Normal - Standard thermostat operation
Normal * - Unit status display
Normal - Standard delay on call from
compressor used
ON * - Current fault or Output display
mode activated
Operational Logic T able
Mode
O
ES
NS
LS
Htg
Clg
FanGON
InputsFanCompRV
Y,O
Y
ON
ON
ON
ON
OFF
OFF
ON
OFF
25
Page 26
ENVISION CONSOLE - 50 HZ INSTALLATION MANUAL
Wiring Schematics cont.
FX10 - EH220-240/50/1
Compressor
S
C
Handi -B ox
Red
MEHS
Red (20)
Black
Yellow
Ground
PB1
L1
L2
HP
RB
Lug
RV
R
T2
L2
Yell ow (3 3)
Molex
20
19
18
17
16
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
BlkRed
T1
L1
Black
Plug
Black (1)
Yellow ( 16)
Black
(12)
Black (111)
Black (310)
Yellow (9)
Orange (7)
Black (6 )
Black (5 )
Blue (4)
Gray (3)
Black (2 )
Tan
Blue 240V
277V
NOTE 1
Red 208V
Blk
Power S upply
208-230/60/1 or
265-277/60/1
Blk/Wht
White
CC
Blk/Wht
Unit
G
Transf ormer
Yellow
Blk
Orange
EHC
NOTE 5
24VAC
24V COM
Alarm
Acc 1
Acc 2
Fan
Rev Valve
Comp
Setpoint Shift
AI Com
Room Sens or
Sensor Com
Tem p Oc c
TB
R
C
L
X1
X2
G
O
Y1
SS
AIC
RS
SC
TO
LC1
LC2
Black (111)
Black (310)
PB2
L2
L1
Molex
Plug
NOTE 2
Black (3 1)
Fan Spe e d
NOTE 3
Switch
NOTE 4
Grn
HL
Blk
Red
HighLow
FS
DA
Org/Wht (12)
Green (17)
Orange (19)
Red (120)
Yellow ( 21)
CP/FP
Gray (26 )
ES
OS
PSC
Fan
Motor
CO
Org/ Bck (11)
DF/AP
LP
Red (120)
Brown (1)
Brown (2)
T
Wht /B lu ( 6)
T
Blk/Red (9)
Blu/ W h t (10 )
Gry /Wht (14)
Black (6 )
Black (2 2)
Viol et (2 3)
Red (24)
Blue (27)Blue (32 )
Pink (28)
Blk /W ht (2 9)
Orange (30)
Brn
White (5)
Brn/Wht
11K
Cap
White
Blue
Blu
EHC
L1
Black(121)
Yellow (35)
A33
White
LS2
Black (5 15)
Blk/ W ht (3 6)
TAN
BLUE
Black (1 3 1)
CC
Black (3 4 )
D09
D08
D07
D06
D05
D04
D03
D02
D01
LS1
White
T2T1
L2
RB
Black
J8
5VDC
23
-
24
AI3
+
25
-
26
AI5
+
27
-
28
AI4
+
29
-
30
AI6
+
31
-
32
AI2
+
33
5VDC
34
-
35
AI1
+
36
37
38
J2
39
40
41
J10
42
43
44
45
46
47
48
J9
49
50
51
52
53
54
55
56
LED
5VDC
PWM2
PWM2 Com
PWM1
24VAC Com
DI12
DI11
DI10
DI9
DI8
DI7
DI 3/4/ 5/6/ Com
DI6
DI5
DI4
DI3
DI2
9VDC
DI1
A21A12
A23
Black
Black (6 )
Gree n ( 37)
24VAC
24VAC Com
GROUND
A14
A24
A34
A25 A22
A32
A31A35
A13
A11
A15
Johnson FX-10
J7
L1
Ground
Quick connect terminal
Wire nut
Field wire lug
Factory low voltage wiring
Factory line voltage wiring
Field low voltage wiring
Field line voltage wiring
Field Zone Sensor Wiring
Internal junctio n
Relay Contacts-
N.O., N.C.
Thermistor -Johnson Control
T
Re lay coil
Open Jumper
Closed Jumper
P
Legend
Switch -High pressure
Switch - Low pressure
Polar ized connect or
132
Condensate Overflow
26
CC - Compressor Contactor
CO - Condens at e Over f low
CP/FP - Compressor Proving/Fan Proving
DA - Discharge Air Temperature
DF/AP - Dirty Filter /Air Proving
EHC -Electric Heat Contactor
EHR -Electric Heat Relay
ES -Emergency Shutdow n
FS - Freeze Sens ing Device
HP -High Pressure Switch
LP -Low Pressure Switch
MEHS -Manual EH Switch
OS -Occupied Switch
RB -Blower P ower Replay
RV -Rev ers ing V alve Coil
TB -Terminal Block
Notes:
1 -Switch Blue and Red wires for 208V operation
2 -Disconnect for 15 degree freeze protection
3 - Acc 1 output is cycled with the compre ssor.
4 - Acc 2 output is cycled with the fan.
5 - R, C, Y1, O, and G inputs are for use with a wall mounted
thermostat.
is a more reliable replacement for
electro-mechanical control applications.
It features a small microprocessor
board that handles the lockout function
of the unit. A second microporcessor
handles the unit mounted thermostat for
maintaining accurate room temperature.
Versatec ControlThe Versatec Control is a
microprocessor based board that adds
the features of emergency shutdown
(ES), night setback (NS), water freeze
detection (FS), Load Shed (LS) and
condensate overfl ow (CO). The
Versatec Control also features Optional
Field servicing LED's for mode, Fault
and diagnostic indication.
Residential and commercial
applications requiring minimal but
reliable controls. Includes Random
Start, High and low pressure
switches and auto changeover
capability.
Residential and commercial
applications requiring more controls
features than CCM and Includes
Random Start, High and low
pressure switches, auto changeover
capability, emergency shutdown
(ES), night setback (NS), load shed
(LS), water freeze detection (FS),
and condensate overfl ow (CO).
Dial thermostat with Hi and
Low blower speeds, and
auto changeover or cont
blower selection switches.
Optional fi eld servicing LED
board for mode, fault and
diagnostic indication
NoneUnit Mounted Digital Dial
Thermostat
Remote Mounted Standard
Thermostat
NoneUnit Mounted Digital Dial
Thermostat
Remote Mounted Standard
Thermostat
FX10The FX10 microprocessor control is self
contained control featuring LP, LOC,
HP, LWT, and condensate overfl ow
fault modes can be displayed on BAS
system. Optional handheld Medium User
Interface (MUI) Control can be used for
additional setup or servicing. Program
customization is possible. This control is
suited for both single and dual capacity
compressors as well as PSC and ECM
blower motors.
FX10 w/ N2FX10 Control functions as both
unitary heat pump control and DDC
communication, therefore detail
operational and fault information is
available to BAS. Other features are
same as FX10 with addition of Johnson
Controls N2 compatibility.
FX10 w/ LonWorksFX10 Control functions as both unitary
heat pump control and DDC communication, therefore detail operational and
fault information is available to BAS.
Other features are same as FX10 with
addition of LonWorks compatibility.
FX10 w/ BACnetFX10 Control functions as both unitary
heat pump control and DDC communication, therefore detail operational and
fault information is available to BAS.
Other features are same as FX10 with
addition of BACnet compatibility.
Commercial applications using
single and dual capacity compressors with either PSC or ECM blower
motors. Also suitable for multicompressor products. Cannot be
integrated with centralized building
automation systems. Software can
be customized for specifi c projects.
Same as FX10 with Johnson
Controls N2 BAS compatibility.
Same as FX10 with LonWorks BAS
compatibility.
Same as FX10 with BACnet BAS
compatibility.
Due to communication speed,
no more than 30 units should
be connected to a single trunk
of the network.
Optional Medium User
Interface (MUI) can be
used as a
fi eld service tool.
Optional Medium User
Interface (MUI) can be
used as a
fi eld service tool.
Optional Medium User
Interface (MUI) can be
used as a
fi eld service tool.
Optional Medium User Interface (MUI) can be mounted
or used as a
fi eld service tool.
StandaloneUnit Mounted Digital Dial
Johnson
Controls
N2 network
LonWorksUnit Mounted Digital Dial
BACnet - MS/
TP
(19,200 Baud
Rate)
Sensor
Remote Mounted Standard
Thermostat
Remote Mounted Sensor
Unit Mounted Digital Dial
Sensor
Remote Mounted Standard
Thermostat
Remote Mounted Sensor
Sensor
Remote Mounted Standard
Thermostat
Remote Mounted Sensor
Unit Mounted Digital Dial
Sensor
Remote Mounted Standard
Thermostat
Remote Mounted Sensor
Standard CCM Control Features
Compressor control module (CCM) controls are standard on
the Envision console heat pump. This control features unit
mounted thermostat and switches,
Features of the standard control are:
• Easy to understand color coded thermostat
adjustment markings.
• Large, rocker type mode and blower switches.
• Internally mounted blower switch to choose cycled or
constant blower operation.
• High pressure and low pressure safety controls to
protect the unit components.
• Lockout circuit to shut down unit operation upon
receipt of a fault indicator from the safety controls.
• A 24 volt control circuit allows for safe and
easy diagnosis.
27
Page 28
ENVISION CONSOLE - 50 HZ INSTALLATION MANUAL
Envision Controls cont.
The user selects either “Heat/Cool” or “Fan Only” on the
mode switch, then either “High” or “Low” at the blower
speed switch. The temperature can be controlled by
rotating the thermostat control knob.
Figure 6: Unit Mounted Control
The “Fan Only” setting provides constant blower operation.
In the “Heat” mode, a call for heat by the thermostat
closes the compressor contactor contacts, energizing the
compressor, which will run until the thermostat is satisfied.
In the “Cool” mode, a call for cooling by the
thermostat energizes the reversing valve and closes the
compressor contactor contacts, energizing the compressor,
which will run until the thermostat is satisfied.
Component Sequencing Delays
Components are sequenced and delayed for optimum
unit performance.
Short Cycle Protection
The control allows a minimum on or off time of 5 minutes
for short cycle protection.
Emergency Shutdown
A grounded signal to common or connecting 24 VAC to
the ES terminal places the controller into the emergency
shutdown mode. The compressor and blower operation are
suspended while in the emergency shutdown mode.
Condensate Overflow Protection
The board incorporates an impedance liquid sensor at
the top of the condensate drain pan. Upon a continuous
30-second sensing of the condensate, the cooling operation
of the unit is suspended.
Safety Controls
The microprocessor board receives separate signals from
a high pressure switch for safety, a low pressure switch
to prevent loss of refrigerant charge and a low suction
temperature thermistor for freeze detection. Upon a
continuous 30-second measurement of the fault (immediate
for high pressure), compressor operation is stopped.
The emergency electric heat operation in the “Heat/
Cool” If either the low or high pressure safety switches are
opened, the compressor and reversing valve are disabled
by the lockout relay. Unit operation will resume only after
the voltage to the unit is interrupted or the mode switch is
placed in the “Off” position.
Optional Versatec Microprocessor
Control Features
The Versatec microprocessor board provides control of
the entire unit as well as outputs for status modes, faults
and diagnostics. The control system is a microprocessorbased control board that is located in the unit control box.
This feature is available for either unit mounted controls
or optional remote wall mounted thermostat. A 9-pin low
voltage terminal strip provides all necessary terminals for
the wall mounted thermostat.
Startup
The unit will not operate until all the inputs and safety
controls are checked for normal operating conditions.
Fault Retry
All faults are retried twice before finally locking the unit out
to prevent nuisance service calls.
28
Page 29
ENVISION CONSOLE - 50 HZ INSTALLATION MANUAL
Envision Controls cont.
Control Tables for Optional Versatec Microprocessor
Logic Board DIP Switch Settings
SwitchOFFON
SW1 - 1
SW1 - 2
SW1 - 3
SW1 - 4
SW1 - 5
Test - Selected timings sped up to facilitate troubleshootingNormal - Standard timings
Commercial - Enables NS features when TA32U02 thermostat is usedNormal - Standard thermostat operation
IO Display* - Enables Input/Output display on external LED boardNormal* - Unit status display
Configures board for 2-speed compressor without blowerConfigures board for 2-speed compressor with blower
Normal Control Timing
Blower off delay
Compressor on delay
Short cycle delay
Miniumum compressor on time
High pressure fault recognition delay
low pressure fault recognition delay
Freeze detection fault recognition delay
Condensate overflow fault recognition delay
Low pressure fault bypass delay
Freeze detection fault bypass delay
Power on delay
Test Control Timing
Blower off delay
Compressor on delay
Short cycle delay
Miniumum compressor on time
High pressure fault recognition delay
low pressure fault recognition delay
Freeze detection fault recognition delay
Condensate overflow fault recognition delay
Low pressure fault bypass delay
Freeze detection fault bypass delay
Power on delay
Fault off time
30 seconds
10 seconds
5 minutes
2 minutes (except for fault condition)
Less than 1 second
30 seconds
30 seconds
30 seconds
2 minutes
2 minutes
5 minutes
5 seconds
2 seconds
15 seconds
5 seconds (except for fault condition)
Less than 1 second
30 seconds
30 seconds
30 seconds
0 seconds
0 seconds
15 seconds
5 minutes
Operational Logic
ModeInputsBlowerCompRV
Htg
Clg
Blower
YONONOFF
Y,OONONON
GONOFFOFF
Diagnostic Modes
LED
DrainDrain pan overflowYCompressor
Water FlowFS thermistor (loop <-9°C, well <-1°C)GBlower
High PressHigh pressure >4130 kPaOO
Low Press Low pressure <275 kPaESES
Air FlowNot usedNSNS
StatusNot usedLSLS
DHW LimitNot usedNot usedNot used
HWDSW2 in the On positionOff positionOn position
Current Fault Status
SW1 - #4 On, SW2 On
Inputs
SW1 - #4 Off, SW2 Off
Outputs
SW1 - #4 Off, SW2 On
29
Page 30
ENVISION CONSOLE - 50 HZ INSTALLATION MANUAL
Envision Controls cont.
Optional FX10 Control
Main FX 10 Board
The optional FX10 control provides unparalleled capability
in several areas including performance monitoring, zoning,
humidity, energy management, and service diagnosis, and
then communicates it all thru standard DDC protocols like
N2, Lon and BACnet (MS/TP @ 19,200 Baud rate).
The most unique feature is integrating the FX10 into the
Envision series as both the heat pump and DDC controller
providing both a cost advantage and providing features
not typically found on WLHP controls. This integration
allows heat pump monitoring sensors, status and service
diagnosis faults to be communicated thru the DDC direct
to the building automation system (BAS), giving building
supervisors detailed and accurate information on every
piece of equipment without removing an access panel.
FX10 Advanced Control Overview
The Johnson Controls FX10 board is specifically designed
for commercial heat pumps and provides control of the
entire unit as well as input ports for Open N2, LonTalk,
BACnet (MS/TP @ 19,200 Baud rate) communication
protocols as well as an input port for a user interface. The
user interface is an accessory item that can be used to aid
in diagnostics and unit setup. A 16-pin low voltage terminal
board provides terminals for common field connections. The
FX10 Control provides:
• Operational sequencing
• High and low-pressure switch monitoring
• General lockout
• Freeze detection
• Condensate overflow sensing
• Lockout mode control
• Emergency shutdown mode
• Random start and short cycle protection
Short Cycle Protection
Allows a minimum compressor “off” time of four minutes
and a minimum “on” time of two minutes.
Random Start
A delay of 1 to 120 seconds is generated after each powerup to prevent simultaneous startup of all units within a
building after the release from an unoccupied cycle or
power loss.
Emergency Shutdown
A field-applied dry contact can be used to place the control
into emergency shutdown mode. During this mode, all
outputs on the board are disabled.
Freeze Detection Limit
Field selectable for 15° or 30°F (-9° or -1°C)
Installation Options
• Standalone controlled by standard room thermostat
• Standalone with a Zone Temperature Sensor (must
have user interface to change set points beyond the
allowed +/- 5°F [2.7°C])
• Integrated into BAS by adding communication module
Accessory Outputs
Quantity 2. One cycled with blower, other with compressor.
User Interface
4 x 20 backlit LCD.
Optional Plug-in Communication Modules (compatible with standard BAS protocols)
• Open N2
• LonTalk
• BACnet (MS/TP @ 19,200 Baud rate)
Display
Requires DLI Card/Kit. Up to 2 displays, either 1 local and
1 remote, or 2 remote. (A 2-display configuration requires
identical displays.) Local display can be up to 3 meters
from the controller, power supply, and data communication.
Remote display can be up to 300 meters from the
controller. Remote display must be independently powered
with data communication done via 3 pole shielded cable.
Control Timing and Fault Recognition Delays
Lead compressor “ON” delay ..........................................90 seconds
(not applicable for single compressor models)
Minimum compressor “ON” time ...................................... 2 minutes
(except for fault condition)
Short cycle delay ..................................................................... 5 minutes
Random start delay ....................................................... 0-120 seconds
High pressure fault ................................................................. <1 second
The FX10 is a microprocessor based control that not
only monitors and controls the heat pump but also can
communicate any of this information back to the building
automation system (BAS). This means that not only does
the control monitor the heat pump at the unit you can also
monitor and control many the features over the BAS. This
clearly puts the FX10 in a class of its own.
The control will enumerate all fault conditions (HP, LP, CO,
LOC, and Freeze Detection) over a BAS as well as display
them on a medium user interface (MUI). HP, LP, CO and
Freeze Detection faults can all be reset over a BAS. A
Loss Of Charge fault can not be reset or bypassed until
the problem has been corrected. A MUI is invaluable as a
service tool for the building service team.
The unit can be commanded to run by a typical heat pump
thermostat or run based on heating and cooling set points
supplied by a BAS. The control board is wired with quick
connect harnesses for easy field change out of a bad
control board. All ECM variable blower speed settings can
be changed over a BAS or with a MUI. The control has an
input programmed to enable field installed emergency
heat in the event that the compressor is locked out. This
input can also be commanded on from a BAS as needed.
An alarm history can be viewed through the MUI and will
be held in memory until the unit is power cycled. Relative
humidity can be read by a 0-5VDC humidity sensor that is
displayed over the network. If you are using an ECM blower
motor the control can enable dehumidification mode based
on a set point in the control. The dehumidification set
point itself can also be changed over a BAS or with a MUI.
Dehumidification mode can also be enabled by the BAS.
Because the FX10 is not factory configured to read CO
levels, contact the factory for application assistance.
2
The FX10 control has unused analog and digital inputs
for field installed items such as air temperature, water
temperature, CO
unused binary and PWM outputs that can be commanded
over the BAS for field use. An optional Medium User
Interface (MUI) for control setup and advanced diagnostics
is available with some mounting kits, MUIK1 - Panel mount
version and the MUIK2-Wall mount version.
2
or current status switches. The control has
Zone Sensors
There are two options for zone sensors that can be used
with the FX10 control. Both sensors use a Johnson controls
A99 positive temperature coefficient type sensor. The
TAXXJ02 has a set point adjustment now which will give
the end user a +/- 5°F [2.7°C] adjustment from the set point
as well as a push button that can be used for temporary
occupancy. The control leaves the factory set to operate
with a TAXXJ02 sensor and can be changed to read the
TAXXA01 sensor through a building automation system or
with a user interface.
Standard Features
• Anti Short Cycle
• High Pressure Protection
• Low Pressure Protection
• Freeze Detection
• Loss Of Charge Detection
• Random Start
• Display for diagnostics
• Reset Lockout at disconnect or through BAS
• 2 Accessory outputs
• Optional BAS add-on controls
DDC Operation and Connection
Other optional network protocol boards that can be added
to the FX10 are:
• Johnson Control N2
• LonWorks
• BACnet
- MS/TP @ 19,200 Baud rate
- Limit devices to 30 on a single trunk line.
Control and Safety Feature Details
Emergency Shutdown
The emergency shutdown mode can be activated by a
command from a facility management system or a closed
contact on BI-2. The default state for the emergency
shutdown data point is off. When the emergency shutdown
mode is activated, all outputs will be turned off immediately
and will remain off until the emergency shutdown mode is
de-activated. The first time the compressor starts after the
emergency shutdown mode has been de-activated, there
will be a random start delay present.
31
Page 32
ENVISION CONSOLE - 50 HZ INSTALLATION MANUAL
Envision Controls cont.
Lockout Mode
Lockout mode can be activated by any of the following fault
signals: refrigerant system high pressure, refrigerant system
low pressure, freeze detection, and condensate overflow.
When any valid fault signal remains continuously active for
the length of its recognition delay, the controller will go
into fault retry mode, which will turn off the compressor.
After the Compressor short cycle delay, the compressor
will attempt to operate once again. If three consecutive
faults occur in 60 minutes during a single heating or cooling
demand, the unit will go into lockout mode, turning off the
compressor, enabling the alarm output, and setting the
blower back to low speed operation until the controller
is reset. If the control faults due to the low pressure input
(BI-3) being open during the pre-compressor startup check,
the control will go into lockout mode immediately, disabling
the compressor from starting and enabling the alarm output
(BO-6). The lockout condition can be reset by powering
down the controller, by a command from the BAS, or by the
holding the ESC and Return keys on the MUI for 5 seconds.
Freeze Detection Limit (AI-5)
The freeze detection limit sensor will monitor the liquid
refrigerant temperature entering the water coil in the
heating mode. If the temperature drops below the freeze
detection limit trip point for the recognition delay period,
the condition will be recognized as a fault. The freeze
detection limit trip point will be factory set for 30°F (-1°C)
and will be field selectable for 15°F (-9°C) by removing
a jumper wire on BI-5. The freeze detection limit fault
condition will be bypassed 2 minutes at normal compressor
startup, to allow the refrigeration circuit to stabilize. If the
freeze detection limit sensor becomes unreliable at any time
compressor operation will immediately be suspended until
the problem is corrected. This should be displayed as an
alarm on the BAS and the MUI. This alarm will be reported a
“Water Low Temp Limit” fault.
will be disabled. The compressor will not restart until the
compressor short cycle time delay has been satisfied.
Condensate Overflow
The condensate overflow sensing circuit will monitor
the condensate level as a resistance input to AI-3. If the
condensate water level rises resulting in the input resistance
rising above the set point for the recognition delay period,
the condition will be recognized as a fault. The condensate
will be subjected to a (30) second lockout delay which
requires that the fault be sensed for a continuous (30)
seconds before suspending unit operation.
Alarm Output (BO-6)
The alarm output will be enabled when the control is in the
lockout mode and will be disabled when the lockout is reset.
Test Mode
Raising the zone temperature input (AI-1) reading to
180–220°F [82-104°C] or by holding the ESC and down
arrow keys on the MUI for 5 seconds will put the control
into test mode. In test mode the random start delay and
the compressor fixed on delay time will both be shortened
to 5 seconds and the reversing valve will be allowed to
cycle with out shutting down the compressor. If an MUI is
connected to the control LED 8 will flash and the words
“Test Mode Enabled” will be shown on the LCD display
when the control is in test mode. Test mode will be disabled
after a power cycle, 30 minute timeout, or by holding the
ESC and Up arrow keys on the MUI.
Sequence of Operation
Power Fail Restart
When the controller is first powered up, the outputs will be
disabled for a random start delay. The delay is provided
to prevent simultaneous starting of multiple heat pumps.
Once the timer expires, the controller will operate normally.
High Pressure (BI-11)
The high-pressure switch shall be a normally closed (NC)
switch that monitors the systems refrigerant pressure. If the
input senses the high-pressure switch is open it must disable
the compressor output immediately and count the fault. The
compressor minimum on time does not apply if the highpressure switch opens. The compressor will not restart until
the compressor short cycle time delay has been satisfied.
Low Pressure (BI-3)
The low-pressure switch shall be a normally closed (NC)
switch that monitors the systems refrigerant pressure. The
input shall be checked 15 seconds before compressor start
up to be sure the pressure switch is closed and then ignored
for the first 2 minutes after the compressor output (BO-2) is
enabled. If the switch is open continuously for (30) seconds
during compressor operation the compressor output (BO-2)
Random Start Delay
This delay will be used after every power failure, as well as
the first time the compressor is started after the control
exits the unoccupied mode or the emergency shutdown
mode. The delay should not be less than 1 second and not
longer than 120 seconds. If the control is in test mode the
random start delay will be shortened to 5 seconds.
Compressor Fixed On Delay Time
The Compressor Fixed On Delay Time will ensure that the
compressor output (B02) is not enabled for (90) seconds
after the control receives a call to start the compressor.
This delay is adjustable from 30 – 300 seconds over a BAS
or a MUI. If the control is in test mode the Compressor
Fixed On Delay Timer will be shortened to 5 seconds.
32
Page 33
Envision Controls cont.
ENVISION CONSOLE - 50 HZ INSTALLATION MANUAL
Compressor Minimum On Delay
The compressor minimum on delay will ensure that the
compressor output is enabled for a minimum of (2)
minute each time the compressor output is enabled. This
will apply in every instance except in the event the high
pressure switch is tripped or emergency shutdown then the
compressor output will be disable immediately.
Compressor Short Cycle Delay Time
The compressor short cycle time delay will ensure
that the compressor output will not be enabled for a
minimum of (5) minutes after it is disabled. This allows
for the system refrigerant pressures to equalize after the
compressor is disabled.
Heating Cycle
On a call for heating, the blower enable output and
accessory output 2 will turn on immediately after the
random start delay timer has been satisfied. If the
compressor short cycle time delay has been satisfied,
the compressor will turn on after the blower enable and
accessory output 2 are on and the fixed compressor start
delay timers have been satisfied.
Set Point Control Mode
In set point control mode the reversing valve output
will be disabled. As the temperature drops below the
heating set point and begins to operate in the heating
proportional band, the low capacity compressor output
(BO-2) will be enabled. A PI loop in the programming
of the control will determine when the full capacity
compressor output (BO-4) is to be enabled. The
compressor must be operating in low capacity for
a minimum of 30 seconds before the full capacity
compressor output can be enabled. During low capacity
compressor operation the ECM2 blower will operate in
medium speed and will operate in high speed when the
compressor is operating at full capacity.
Thermostat Control Mode
In thermostat mode the compressor will be cycled
based on Y1 and Y2 calls from a room thermostat.
When the control receives a Y1 command (BI-7) from
the thermostat the low capacity compressor output
(BO2) will be enabled and the ECM2 blower will
operate in medium speed. When the control receives
a Y2 command (BI-8) from the thermostat the full
capacity compressor output will be enabled and the
ECM2 blower will operate in high speed. During the
heating cycle the reversing valve will be commanded
into the off position.
Cooling Cycle
On a call for cooling, the blower enable output and
accessory output 2 will turn on immediately after the
random start delay timer has been satisfied. If the
compressor short cycle time delay has been satisfied,
the compressor will turn on after the blower enable and
accessory output 2 are on and the fixed compressor start
delay timers have been satisfied.
Set Point Control Mode
In set point control mode the reversing valve output
will be enabled. As the temperature falls below the
cooling set point and begins to operate in the cooling
proportional band, the low capacity compressor output
(BO-2) will be enabled. A PI loop in the programming
of the control will determine when the full capacity
compressor output (BO-4) is to be enabled. The
compressor must be operating in low capacity for
a minimum of 30 seconds before the full capacity
compressor output can be enabled. During low capacity
compressor operation the ECM2 blower will operate in
medium speed and will operate in high speed when the
compressor is operating at full capacity.
Thermostat Control Mode
In thermostat mode the compressor will be cycled based
on Y1 and Y2 calls from a room thermostat. When the
control receives a Y1 command (BI-7) from the thermostat
the low capacity compressor output (BO2) will be
enabled and the ECM2 blower will operate in medium
speed. When the control receives a Y2 command (BI-8)
from the thermostat the full capacity compressor output
will be enabled and the ECM2 blower will operate in high
speed. During the cooling cycle the reversing valve will be
commanded into the “ON” position.
Emergency Heat/Network Enabled Output (BO5)
This output is set from the factory to enable/disable
emergency heat. If a problem occurs with the unit resulting
in the compressor being locked out in heating mode, the
control will automatically enable this output to turn on field
installed electric heat. This output is interlocked with the
blower proving input BI-6 (Blower proving sensors must
be field supplied and installed). BI-6 must be connected to
PB2 position 3 (see unit schematic) in the field if no blower
proving sensor is desired. There is a configurable parameter
available through a BAS network that must be enabled if
this output is to be commanded over the BAS network.
33
Page 34
ENVISION CONSOLE - 50 HZ INSTALLATION MANUAL
Envision Controls cont.
MUI Alarm History Reporting
If a fault occurs the fault will be recorded in history for
display on the medium user interface in the History Menu.
Each fault type will be displayed in the history menu with
a number between 0 and 3. A reading of 3+ will mean that
fault has occurred more than three times in the past. The
history menu can be cleared with a power cycle only. Alarm
date and time are not included in the history.
Inputs and Outputs Configuration
Field Selectable Options
Freeze Detection Limit Set Point (BI-5)
The freeze detection limit set point input allows you to
adjust the freeze detection limit set point (AI-5). When the
jumper is installed on BI-5 (Wire #24) the freeze detection
limit set point is factory set for 30°F [-1°C]. When the
jumper on BI-5 (Wire #24) is removed the freeze detection
set point will be 15°F [-9°C].
Accessory Outputs (BO-7 and BO-8)
Accessory Output 1 will be energized 90 seconds prior to
the compressor output being energized. Accessory Output
2 will be energized with the blower output (BO-1). When
the corresponding compressor output is turned off the
accessory output will be deactivated immediately. These
outputs are selectable for normally open or normally closed
operation through the Medium User interface or through the
Building Automation System.
Control Accessories
Zone Sensors
• TAXXJ02 Room Command Module
• TAXXA01 LCD Room Command Module
• A99 Sensor
MUI (LCD User interface) for diagnostics
and commissioning.
• MUIK3 - Panel Mount, Portable
• MUIK4 - Wall Mount
SINGLE and DUAL STAGE WATER-TO-AIR
Input NameInput Output NameOutput
Zone Temp 1AI 1 Fan EnableBO1
Relative Humidity InputAI 2 Comp – Low CapacityBO2
Condensate LevelAI 3 Reversing Valve BO3
Universal Temp InputAI 4 Comp – Full CapacityBO4
Water Coil Low Temperature LimitAI 5 Network Output/EH OutputBO5
Warm/Cool Adjust and Temp OccAI 6 AlarmBO6
Alarm LED - Indicates a Lock-Out or a bad Freeze Sensor
Power LED - Shows FX processor is operational
LED 1 - Flashing shows Compressor 1 running
Left ArrowDown Arrow
LED 3 - On shows Fan running
LED 4 - On shows Reversing Valve in cool
LED 8 - Flashing shows unit in ‘Test’ Mode
LED 2 - Flashing shows Full Capacity Compressor running
MUI Menu Navigation for Single Compressor - Envision Water-to-Air
Escape (ESC)
Button
Return Button
Info
Water Source
Heat Pump
PROFXENV-XX
_/_/__
Welcome
Info Status Temps Outputs Settings Maint Ala rms Alm-History
Status
Run Mode Auto
Eff Occup’y Occ
Y1 Input OFF
Y2 Input OFF
G Input OFF
O Input Heat/Cool
Occ Input Occ
Temp Occ Inp OFF
Condensate NML
Emg Input Run
Lo Press ON
Hi Press ON
Rndm Tmr 0
BI-4 Input OFF
Temps
Zone Temp 25.1 ºC
Dis Air Temp 10.6 ºC
Eff Clg Setpt 21.1°C
Eff Htg Setpt 18.9°C
Water Coil 25.4°C
Low WC Limit -1.1°C
Humidity 56.7 %RH
WarmCool AI 14.6
WarmCoolAd j 0.2
OutputsSettings
nvoFanStatus ON
CmpCmd Status OFF
Cmp Capacity OFF
Rev Valve Heat
X1 Output OFF
X2 Output OFF
PWMOut 98%
BO5 OFF
BO9 OFF
AO2 Output 0%
Unit of Measure C
Occ Clg Setpt 23.3 ºC
Occ Htg Setpt 21.1 ºC
Unocc Clg 28.9 ºC
Unocc Htg 15.6 ºC
DeHumSetpt 0%
SensorSelect TAXXJ02
35
Page 36
ENVISION CONSOLE - 50 HZ INSTALLATION MANUAL
Envision Controls cont.
MUI Menu Navigation for Single Compressor - Envision Water-to-Air
Alarms
ALARM SUMMARY
^/High Pressure
Maintenance
MinClgSetpt 15.5 ºC
MaxHtgSetpt 32.2 ºC
W Coil LoLim1 -1.1 ºC
W Coil LoLim2 9.4 ºC
TmpOccTime 120 min
Rev Vl v Default Heating
BO5 Mode Network
CompStrtDly 90 sec
SpaceT Offset -18 ºF
DehumEnaDis Dis
Acc1 Action On Comp
Acc2 A ction On Fan
Alm-History
Alarm #Events
Condensate 0
Hi Pressure 0
Low Pressure 0
Low Temp 0
Bad Sensor 0
Press right arrow key
one time from
Maintenance Menu
NOTE: This FX10 application implements an alarm histor y which is reset
only by cycling power. This history shows on the Alm-History page. Any
alarm showing 4+ events has occurred more than 4 times.
Alarm lock-outs
Return keys simultaneousl y for a minimum of 15 seconds, or by
commanding the nviAlarmReset over the BAS network.
Test mode
for a minimum of 15 seconds and releasing. Test mode ti mes out after 30
minutes, and may also be ended by pressing ‘ ESC’ and Up Arrow
simultaneously and releasing. Test Mode bypasses the On Delay (90 sec)
and Random Start timers for quicker troubleshooting. It also allows cyc ling
the reversing valve without compressor shutdown.
ECM
SW1 OFF
SW2 OFF
SW3 ON
SW4 OFF
SW5 OFF
SW6 OFF
SW7 ON
SW8 OFF
SW9 OFF
SW10 ON
SW11 OFF
SW12 OFF
No more than three
speeds should be “ON”
at one time
are reset by cyc ling power, by pressi ng the “ESC” and
is enabled by holding the ‘Esc’ and Down Arrow simultaneously
36
Page 37
Unit Startup
ENVISION CONSOLE - 50 HZ INSTALLATION MANUAL
Electrical Disconnect
Field installed on the optional chassis back plate, the
console disconnect provides a permanent electrical
connection to the main electrical supply branch. Wiring
between the disconnect and the unit chassis is field
supplied and allows the electrical power source to the
chassis to be interrupted for unit servicing.
Non-Fused
Constructed of heavy gauge galvanized steel, the
rocker style disconnect switch provides reliable
electrical control. Wiring pigtails, using 12-gauge wires,
are factory installed to simplify field wiring.
Fused
Similar in construction to the non-fused electrical
disconnect. The fused disconnect is available in
five models with equipment rated fuses to provide
additional circuit protection. The fuses are panel
mounted to allow easy inspection and removal without
removing the cover on the disconnect.
CFD-10 - 10 amp rated fuse
CFD-12 - 12 amp rated fuse
CFD-15 - 15 amp rated fuse
CFD-20 - 20 amp rated fuse
CFD-25 - 25 amp rated fuse
Motorized Outside Air Damper
A field installed motorized outside air damper is available
to allow the introduction of fresh air into the conditioned
space through an outside vent. The damper motor is
powered by 24 volts with a spring-close design in the
event of a power failure. The damper blade and housing are
constructed of aluminum for corrosion resistance and the
blade includes a neoprene gasket to prevent air infiltration
during off cycles. The damper assembly is installed on the
optional chassis back plate and a two-wire low voltage
connection simplifies wiring. A concealed, chassis mounted
rocker switch allows the damper to be disabled
Hydronic Loop Controller for
Boiler/Tower Installations
The hydronic loop controller is a microprocessor based
control panel for control of water loop heat rejector
(tower), heat supplier (boiler), and/or water well pumps
and circulation pumps. Includes audible and visual alarms,
temperature indication, and add-on options of low switches,
remote alarm sensor wells and pump alternator.
37
Page 38
ENVISION CONSOLE - 50 HZ INSTALLATION MANUAL
Unit Startup cont.
Before Powering Unit, Check The Following:
• High voltage is correct and matches nameplate.
• Fuses, breakers and wire size correct.
• Low voltage wiring complete.
• Piping completed and water system cleaned and flushed.
• Air is purged from closed loop system.
• Isolation valves are open, water control valves or loop pumps wired.
• Condensate line open and correctly pitched.
• Transformer switched to 220V if applicable.
• Dip switches are set correctly, if applicable.
• Blower rotates freely
• Air filter is clean and in position.
• Service/access panels are in place.
• Return air temperature is between 10-27°C heating and 15-35°C cooling.
• Check air coil cleanliness to ensure optimum performance. Clean as needed according to maintenance guidelines. To
obtain maximum performance the air coil should be cleaned before startup. A 10-percent solution of dishwasher
detergent and water is recommended for both sides of coil, a thorough water rinse should follow.
Startup Steps
NOTE: Complete the Equipment Start-Up/Commissioning Check Sheet during this procedure. Refer to thermostat
operating instructions and complete the startup procedure.
1. Initiate a control signal to energize the blower motor. Check blower operation.
2. Initiate a control signal to place the unit in the cooling mode. Cooling setpoint must be set below room temperature.
3. Be sure that the compressor and water control valve or loop pump(s) are activated.
4. Verify that the water flow rate is correct by measuring the pressure drop through the heat exchanger using the P/T
plugs and comparing to unit capacity data in specification catalog.
5. Check the temperature of both the supply and discharge water (Refer to Unit Operating Parameters tables).
6. Check for an air temperature drop of 8.3°C to 13.9°C across the air coil, depending on the blower speed and entering
water temperature.
7. Adjust the cooling setpoint above the room temperature and verify that the compressor and water valve or loop
pumps deactivate.
8. Initiate a control signal to place the unit in the heating mode. Heating set point must be set above room temperature.
9. Check the temperature of both the supply and discharge water (Refer to Unit Operating Parameters tables).
10. Check for an air temperature rise of 11.1°C to 19.4°C across the air coil, depending on the blower speed and entering
water temperature.
11. Adjust the heating setpoint below room temperature and verify that the compressor and water valve or loop pump
deactivate.
12. During all testing, check for excessive vibration, noise or water leaks. Correct or repair as required.
13. Set system to desired normal operating mode and set temperature to maintain desired comfort level.
14. Instruct the owner/operator in the proper operation of the thermostat and system maintenance.
Note: Be certain to fill out and forward all warranty registration papers.
38
Page 39
Operating Parameters
Single Speed Models
ENVISION CONSOLE - 50 HZ INSTALLATION MANUAL
Entering
Water Temp
°C
10
21
32
Entering
Water Temp
°C
10
21
32
NOTE: Cooling performance based on entering air temperatures of 27°C DB, 19°C WB. Heating performance based on entering air
temperature of 21°C DB.
Water Flow
l/s/kW
0.1876 - 9931413 - 15513 - 66 - 810 - 1210 - 12
2.9827 - 9651276 - 14134 - 83 - 64 - 610 - 12
0.1958 - 10621931 - 20684 - 64 - 710 - 1210 - 12
2.9945 - 10481724 - 18625 - 74 - 64 - 610 - 12
0.1986 - 10892482 - 26204 - 65 - 710 - 129 - 11
2.9972 - 10762275 - 24135 - 74 - 74 - 69 - 11
Water Flow
l/s/kW
0.1503 - 5451924 - 20964 - 71 - 34 - 610 - 13
2.9545 - 5861965 - 21374 - 81 - 32 - 311 - 14
0.1710 - 7522124 - 22964 - 72 - 44 - 611 - 14
2.9758 - 8002172 - 23445 - 72 - 42 - 412 - 16
0.1965 - 10072275 - 25176 - 84 - 66 - 814 - 18
2.91007 - 10552344 - 25866 - 84 - 64 - 616 - 19
Suction Pressure
kPa
Suction Pressure
kPa
Discharge
Pressure kPa
Discharge
Pressure kPa
SuperheatSubcooling
SuperheatSubcooling
Cooling
Water Temp
Rise °C
Heating
Water Temp
Drop °C
Air Temp Drop
°C DB
8/17/10
Air Temp Rise
°C DB
8/17/10
Operating Limits
Operating Limits
Air Limits
Min. Ambient Air457.2457.2
Rated Ambient Air8026.77021.1
Max. Ambient Air10037.88529.4
Min. Entering Air5010.0404.4
Rated Entering Air db/wb 80.6/66.227/196820.0
Max. Entering Air db/wb110/8343/28.38026.7
Water Limits
Min. Entering Water30-1.120-6.7
Normal Entering Water50-11010-43.330-70-1.1
Max. Entering Water12048.99032.2
CoolingHeating
(°F)(°C)(°F)(°C)
NOTE: Minimum/maximum limits are only for start-up conditions, and
are meant for bringing the space up to occupancy temperature. Units
are not designed to operate at the minimum/maximum conditions on
a regular basis. The operating limits are dependant upon three primary
factors: 1) water temperature, 2) return air temperature, and 3) ambient
temperature. When any of the factors are at the minimum or maximum
levels, the other two factors must be at the normal level for proper and
reliable unit operation.
39
Page 40
ENVISION CONSOLE - 50 HZ INSTALLATION MANUAL
Pressure Drop
Modell/s
0.086.96.25.54.84.1
02
03
04
05
0.1115.915.213.813.112.4
0.1626.225.524.122.821.4
0.096.25.54.84.13.5
0.1511.710.39.79.07.6
0.2220.718.617.216.615.2
0.1311.711.010.39.79.0
0.1922.822.120.720.019.3
0.2528.327.626.925.524.8
0.1311.711.010.39.79.0
0.2225.524.824.122.822.1
0.2839.337.936.535.233.8
Pressure Drop (kPa)
0°C10°C20°C30°C40°C
8/17/10
40
Page 41
DEALER:
PHONE #: DATE:
PROBLEM:
MODEL #:
ENVISION CONSOLE - 50 HZ INSTALLATION MANUAL
SERIAL #:
COOLING CYCLE ANALYSIS
Unit Amp Draw:
°C
AIR
COIL
°C
Line Voltage:
EXPANSION
VALVE
°F
LIQUID LINE
SOURCE
kPakPa
BRINE IN
Loop:Open
COAX
BRINE OUT
Startup/Troubleshooting Form
kPa
°C
Closed
REVERSING
VALVE
kPa =SAT C
°C°C
SAT °C=
SUCTION
COMPRESSOR
DISCHARGE
°
C
Superheat
Subcooling
°
Heat of Extraction/Rejection = l/s x 4.2 (4.1 for water/antifreeze) x ∆T
Note: DO NOT hook up pressure gauges unless there appears to be a performance problem.
HEATING CYCLE ANALYSIS
Unit Amp Draw:
°F
AIR
COIL
°F
Line Voltage:
°
LIQUID LINE
EXPANSION
VALVE
F
SOURCE
kPakPa
BRINE IN
Loop:Open
COAX
°C°C
BRINE OUT
Closed
kPa
°C
REVERSING
VALVE
SAT °C=
SUCTION
COMPRESSOR
DISCHARGE
°
C
kPa =SAT C
Superheat
Subcooling
°
41
Page 42
ENVISION CONSOLE - 50 HZ INSTALLATION MANUAL
Preventive Maintenance
Water Coil Maintenance
1. Keep all air out of the water. An open loop system should
be checked to ensure that the well head is not allowing
air to infiltrate the water line. Lines should always be
airtight.
2. Keep the system under pressure at all times. It is
recommended in open loop systems that the water
control valve be placed in the discharge line to prevent
loss of pressure during off cycles. Closed loop systems
must have positive static pressure.
NOTE: On open loop systems, if the installation is in an area
with a known high mineral content (125 PPM or greater) in
the water, it is best to establish with the owner a periodic
maintenance schedule so the coil can be checked regularly.
Should periodic coil cleaning be necessary, use standard
coil cleaning procedures which are compatible with either
the cupronickel or copper water lines. Generally, the more
water flowing through the unit the less chance for scaling.
Other Maintenance
Filters
Filters must be clean to obtain maximum performance.
They should be inspected monthly under normal operating
conditions and be replaced when necessary. Units should
never be operated without a filter.
Condensate Drain
In areas where airborne bacteria produce a slime in the
drain pan, it may be necessary to treat chemically to
minimize the problem. The condensate drain can pick up lint
and dirt, especially with dirty filters. Inspect twice a year to
avoid the possibility of overflow.
Blower Motors
Blower motors are equipped with sealed ball bearings and
require no periodic oiling.
Air Coil
The air coil must be cleaned to obtain maximum
performance. Check once a year under normal operating
conditions and, if dirty, brush or vacuum (with a brush
attachment) clean. Care must be taken not to damage the
aluminum fins while cleaning.
CAUTION: Fin edges are sharp.
Replacement Procedures
Obtaining Parts
When ordering service or replacement parts, refer to the
model number and serial number of the unit as stamped
on the serial plate attached to the unit. If replacement
parts are required, mention the date of installation of the
unit and the date of failure, along with an explanation of
the malfunctions and a description of the replacement
parts required.
In-Warranty Material Return
Material may not be returned except by permission of authorized warranty personnel. Contact your local distributor
for warranty return authorization and assistance.
42
Page 43
ENVISION CONSOLE - 50 HZ INSTALLATION MANUAL
Revision Guide
Pages:Description:Date:By:
AllUpdated With Aluminum Air Coils21 May 2014DS
43Added Revision Guide21 May 2014DS
43
Page 44
Manufactured by
WaterFurnace International, Inc.
9000 Conservation Way
Fort Wayne, IN 46809
www.waterfurnace.com