WaterFurnace Envision2 User Manual

Water Source/Geothermal Heat Pump
• R-410A Refrigerant
• Commercial 0.75-6 Ton
Installation Information
Water Piping Connections
Hot Water Connections
Electrical
Startup Procedures
Troubleshooting
Preventive Maintenance
Compact Installation Manual
2
Envision
IM1022ANA 05/14
Table of Contents
Model Nomenclature. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
General Installation Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Dimensional Data. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Installing Horizontal Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Hanger Bracket Locations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11
Duct System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Water Piping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Condensate Drain . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Water Quality . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
System Cleaning and Flushing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Open Loop Ground Water Systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
ENVISION2 COMPACT INSTALLATION MANUAL
Hot Water Generator Connections. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Freeze Detection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Electrical Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Electrical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Blower Performance Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Wiring Schematics. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Controls . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .29
Unit Startup. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .42
Operating Limits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .43
Operating Parameters. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .43
Pressure Drop . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .45
Reference Calculations and Legend. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .46
Refrigerant Circuit Guideline . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .46
Compressor and Thermistor Resistance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
Heat of Extraction/Rejection Data. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .48
Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .49
Preventive Maintenance and Replacement Parts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
Service Parts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
Revision Guide . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
ENVISION2 COMPACT INSTALLATION MANUAL
1-2 3 4-6 7 8 9
10 11 12 14
NB V 048 T L 0 0 0 C A N13A15N16117A18319020SS
21-22*23

Model Nomenclature

Model Type
NB – Envision
Cabinet Configuration
V – Vertical H - Horizontal
Unit Capacity (MBTUH)
Single Speed 009, 012, 015, 018, 024, 030 036, 042, 048, 060, 070 Dual-Capacity 026, 038, 049, 064, 072
Discharge Configuration
T – Top (Vertical) E – End (Horizontal) S – Side (Horizontal)
Return Air Configuration
L – Left R – Right
Voltage
0 – 208-230/60/1 2 – 265-277/60/1 (009-038) 3 – 208-230/60/3 (024-072) 4 – 460/60/3 (024-072) 5 – 575/60/3 (PSC Only 042-070)
Refrigeration Option
0 – None 2 – HWG Only w/o Pump (Vertical 018-072) G – Hot Gas Bypass (015-072) R – Hot Gas Reheat (015-072) B – Hot Gas Bypass w/Hot Gas Reheat (015-072)
Blower Options
0 – PSC Blower (Single Speed Only) 1 – Variable Speed ECM Blower (015-072) 2 – High Static Variable Speed ECM Blower (036, 038, 042, 048, 049) 3 – High Static PSC Blower (024-048) 4 – 5-Speed ECM Blower (015-072)
Water Coil Option
C – Copper D – Insulated Copper N – CuproNickel P – Insulated CuproNickel
Note: 1 - Phase Guard Only Available on 208-230/60/3, 460/60/3, and 575/60/3
2
Compact
Vintage
* - Factory Use Only
Non-Standard Options
SS – Standard
Drain Pan Option
0 – Composite, No Secondary Connection 1 – Composite, Secondary Connection 2 – Stainless Steel, No Secondary Connection 3 – Stainless Steel, Secondary Connection
Air Coil Option
3 – All-Aluminum, Uncoated 4 – All-Aluminum, AlumiSeal
Filter Option
A – MERV 4 B – MERV 13
Cabinet Option
0 – Unpainted Cabinet, Filter Rail 1 – Painted Cabinet, Filter Rail 2 – Unpainted Cabinet, 4-Sided Filter Rack 3 – Painted Cabinet, 4-Sided Filter Rack
Electrical Option
N – None A – IntelliStart E – IntelliStart and Disconnect P – Phase Guard, No Disconnect B – Phase Guard, Disconnect D – No Phase Guard, Disconnect
Control Option
A – Aurora E – Aurora UPC DDC Controller F – Aurora UPC DDC Controller with LON
Water Control Option
N – None R – Water Flow Regulator V – 2-Way Valve B – 2-Way Valve w/ Water Flow Regulator
Sound Kit Option
A – None B – Sound Kit
Rev.: 24 April 2014D
1
®
Only
TM
Base Control (ABC)
TM
4

General Installation Information

ENVISION2 COMPACT INSTALLATION MANUAL
Safety Considerations
WARNING: Before performing service or maintenance operations on a system, turn off main power switches to the indoor unit. If applicable, turn off the accessory heater power switch. Electrical shock could cause personal injury.
Installing and servicing heating and air conditioning equipment can be hazardous due to system pressure and electrical components. Only trained and qualified service personnel should install, repair or service heating and air conditioning equipment. Untrained personnel can perform the basic maintenance functions of cleaning coils and cleaning and replacing filters. All other operations should be performed by trained service personnel. When work­ing on heating and air conditioning equipment, observe precautions in the literature, tags and labels attached to the unit and other safety precautions that may apply.
Follow all safety codes. Wear safety glasses and work gloves. Use a quenching cloth for brazing operations and have a fire extinguisher available.
Moving and Storage
Move units in the normal “up” orientation. Horizontal units may be moved and stored per the information on the packaging. Do not stack more than three units in total height. Vertical units may be stored one upon another to a maximum height of two units. Do not attempt to move units while stacked. When the equipment is received, all items should be carefully checked against the bill of lading to be sure all crates and cartons have been received. Examine units for shipping damage, removing the units from the packaging if necessary. Units in question should also be internally inspected. If any damage is noted, the carrier should make the proper notation on the delivery receipt, acknowledging the damage.
Unit Location
Locate the unit in an indoor area that allows for easy removal of the filter and access panels. Location should have enough space for service personnel to perform maintenance or repair. Provide sufficient room to make water, electrical and duct connection(s). If the unit is located in a confined space, such as a closet, provisions must be made for return air to freely enter the space by means of a louvered door, etc. Any access panel screws that would be difficult to remove after the unit is installed should be removed prior to setting the unit. On horizontal units, allow adequate room below the unit for a condensate drain trap and do not locate the unit above supply piping. Care should be taken when units are
located in unconditioned spaces to prevent damage from frozen water lines and excessive heat that could damage electrical components.
Installing Vertical Units
Prior to setting the unit in place, remove and discard the compressor hold down shipping bolt located at the front of the compressor mounting bracket.
Vertical units are available in left or right air return configurations. Top flow vertical units should be mounted level on a vibration absorbing pad slightly larger than the base to provide isolation between the unit and the floor. It is not necessary to anchor the unit to the floor (see figure below).
Vertical Unit Mounting
2 in. PEX Foam
5
ENVISION2 COMPACT INSTALLATION MANUAL
Vertical Dimensional Data
Standard filter rails for
open return applications
Field installed duct flange
Deluxe filter rack for
ductable return applications
A
RN
S
Q
AIR COIL SIDE
P
B
AIR COIL SIDE
F
4 3
FRONT
1.4 in (3.5 cm)
M
M
G
Top View - Right Return Top View - Left Return
A
N
FRONT
1.4 in (3.5 cm)
Air coil
Q
P
B
2' (61 cm)
G
Alternate Service Access
4 3
F
Service Access Left Return
2' (61 cm)
ACCESS
PANEL
Isometric View - Left Return
(Right Return opposite side)
U
T
W
Air coil
Air coil
ACCESS
PANEL
C
1.6 in (4.1 cm) Condensate 3/4 in
PVC glue socket
1.6 in (4.1 cm)
5
H
2
E
1
D
6 8
1 in (25.4 mm)
1/2" (12.7 mm)
J
L
Power supply
knockout
Low voltage
knockout
L
K
Front View - Right Return
ACCESS
PANEL
Condensate
3/4 in PVC
glue socket
1.6 in (4.1 cm)
8 7
5 2
1
Front View - Left Return
1.6 in (4.1 cm)
H
E
D
V
C
6
ACCESS
J
8
L
PANEL
8 7
L
K
Right View - Right Return
Left View - Left Return
6
Vertical Dimensional Data cont.
ENVISION2 COMPACT INSTALLATION MANUAL
Overall Cabinet
Vertical
Models
009-012
015-018
024-030
036-038
042-049
060-072
009-012
015-018
024-030
036-038
042-049
060-072
Condensate is 3/4 in. PVC female glue socket and is switchable from side to front. *Discharge fl ange is fi eld installed and extends 1 in. (25.4 mm) from top of cabinet.
**Vertical units shipped with standard 2 in. (fi eld adjustable to 1 in.) open application fi lter rack extending 2.2 in. from unit and is not suitable for duct connection, for ductable return connection applications, order the deluxe 2 in. (fi eld adjustable to 1 in.) duct collar/fi lter rack which extends 3.25 in. from the unit and is suitable for duct connections.
cm. 57.2 56.4 76.7 6.6 19.3 N/A N/A 27.4 12.7 mm N/A 23.9 13.7 18.8
cm. 57.2 66.5 102.1 6.6 19.3 3.6 11.2 27.4 19.1 mm 22.2 mm 25.7 15.5 20.6
cm. 57.2 66.5 112.3 6.6 19.3 3.6 11.2 27.4 19.1 mm 22.2 mm 25.7 15.5 20.6
cm. 64.8 79.2 112.3 6.6 19.3 3.6 11.2 27.4 25.4 mm 22.2 mm 25.7 15.5 20.6
cm. 64.8 79.2 122.4 6.6 19.3 3.6 11.2 27.4 25.4 mm 22.2 mm 25.7 15.5 20.6
cm. 64.8 79.2 132.6 6.6 19.3 3.6 11.2 27.4 25.4 mm 22.2 mm 25.7 15.5 20.6
Vertical
Models
cm. 5.6 25.4 25.4 15.5 13.5 24.9 5.1 46.0 35.6 5.1
cm. 5.6 35.6 35.6 15.5 11.4 19.6 5.1 56.1 55.9 4.8
cm. 5.6 35.6 35.6 15.5 11.4 19.6 5.1 56.1 66.3 4.6
cm. 5.6 45.7 45.7 16.8 11.7 16.0 4.1 71.4 66.3 5.1
cm. 5.6 45.7 45.7 16.8 11.7 16.0 4.1 71.4 76.2 5.1
cm. 5.6 45.7 45.7 16.8 12.7 16.3 4.1 71.4 86.4 5.1
A B C D E F G H Loop Knockout
Width Depth Height* In Out HWG In HWG Out
in. 22.5 22.2 30.2 2.6 7.6 N/A N/A 10.8 1/2 in. N/A 9.4 5.4 7.4
in. 22.5 26.2 40.2 2.6 7.6 1.4 4.4 10.8 3/4 in. 0.875 10.1 6.1 8.1
in. 22.5 26.2 44.2 2.6 7.6 1.4 4.4 10.8 3/4 in. 0.875 10.1 6.1 8.1
in. 25.5 31.2 44.2 2.6 7.6 1.4 4.4 10.8 1 in. 0.875 10.1 6.1 8.1
in. 25.5 31.2 48.2 2.6 7.6 1.4 4.4 10.8 1 in. 0.875 10.1 6.1 8.1
in. 25.5 31.2 52.2 2.6 7.6 1.4 4.4 10.8 1 in. 0.875 10.1 6.1 8.1
MNPQR S T U VW
Filter Rack
Width
in. 2.2 10.0 10.0 6.1 5.3 9.8 2.0 18.1 14.0 2.0
in. 2.2 14.0 14.0 6.1 4.5 7.7 2.0 22.1 22.0 1.9
in. 2.2 14.0 14.0 6.1 4.5 7.7 2.0 22.1 26.1 1.8
in. 2.2 18.0 18.0 6.6 4.6 6.3 1.6 28.1 26.1 2.0
in. 2.2 18.0 18.0 6.6 4.6 6.3 1.6 28.1 30.0 2.0
in. 2.2 18.0 18.0 6.6 5.0 6.4 1.6 28.1 34.0 2.0
Supply
Width
12345 JKL
Discharge Connection
duct fl ange installed (±0.10 in)
Supply
Depth
Water Connections
Cond-
ensate
Water
FPT
HWG
Provisions
**Return Connection
using deluxe fi lter rack (±0.10 in)
Return
Depth
Electrical Knockouts
678
1/2 in.
cond
Low
Voltage
1/2 in.
Voltage
Return Height
cond
Low
1 in. cond
Power
Supply
3/16/12
3/16/12
Vertical Disconnect
When using disconnect, do not use dimension L from the standard vertical dimensional data. Use dimension LL from the vertical disconnect dimensional data.
Vertical Models LL
009-012
015-018 024-030 036-038 042-049 060-064 070-072
Dimensions in inches [cm] 3/16/12
17.8 [45.2]
14.3 [36.3]
15.3 [38.9]
14.3 [36.3]
14.3 [36.3]
14.3 [36.3] External
Disconnect Located on this
Side for a Right Return Disconnect Location
Alternative Power
Power
Location
Supply
LL
1.8 in.
[4.6 cm]
Vertical Shown in
Left Return Configuration
7
ENVISION2 COMPACT INSTALLATION MANUAL
Horizontal Dimensional Data
Right Return
Condensate "X" PVC size
End Discharge
Deluxe filter rack option shown
H
2.3 in. [5.8 cm]
FILTER RACK
AIR COIL SIDE
2.1 in. [5.3 cm]
Right Return
End Discharge
N
BLOWER
OUTLET
A
Standard filter rails
1 in. [2.5 cm] knockout
0.5 in. [1.3 cm] knockout
Side Discharge
P
M
C
L
Front
AP
CMP
Service Access
2' (61 cm)
1.7 in. [5.3 cm]
K
J
E
D
AP = Alternate Service Panel BP = Blower Service Panel CP = Control Access Panel CMP = Compressor Service Panel
CP AP
A
RR Front View
1.7
CP AP
LR Front View
Legend
1.7
1.7 in. [5.3 cm]
E
D
J
0.5 in. [1.3 cm] knockout
1 in. [2.5 cm]
K
knockout
Standard filter rails
Front
AP
CMP
2' (61 cm)
Service Access
Side Discharge
Deluxe filter rack option shown P
N
L
C
M
BLOWER
OUTLET
2.1 in. [5.3 cm]
Left Return
End Discharge
A
Left Return
Condensate
"X" PVC size
End Discharge
2.3 in. [5.8 cm]
AIR COIL SIDE
FILTER RACK
H
BP
Front
P
N
L
M
Air Coil
BLOWER
OUTLET
Right Return Side Discharge
C
Right Return Side View
J
K
T
R
1.5 in. [3.8 cm]
AP
CMP
S
Left Return Side Discharge
Q
B
Left Return Side View
1.5 in. [3.8 cm]
0.5 in. [1.3 cm]
K
AP
CMP
FILTER RACK CONNECTION FILTER RACK CONNECTION
B
J
SQ
R
Front
1 in. [2.5 cm]
knockout
0.5 in. [1.3 cm] knockout
T
Deluxe filter
rack option
(shown)
knockout
Front
C
N
BLOWER
OUTLET
P
BP
M
L
Air Coil
Front
8
Horizontal Dimensional Data cont.
ENVISION2 COMPACT INSTALLATION MANUAL
Horizontal
Models
Width Depth Height* In Out Condensate Water FPT Low Voltage Power Supply
009-012
015-018
024-030
036-038
042-049
060-064
070-072
Horizontal
009-012
015-018
024-030
036-038
042-049
060-064
070-072
Horizontal units shipped with standard 2 in. (fi eld adjustable to 1 in.) open application fi lter rack extending 2.2 in. from unit and is not suitable for duct connection, for ductable return connection applications, order the deluxe 2 in. (fi eld adjustable to 1 in.) fi lter rail/fi lter rack which extends 3.25 in. from the unit and is suitable for duct connections.
in. 22.5 35.0 17.2 1.8 6.8 0.8 1/2 in. 7.1 7.1
cm. 57.2 88.9 43.7 4.6 17.3 2.0 12.7 mm 18.0 18.0
in. 22.5 42.0 19.2 1.8 6.8 0.8 3/4 in. 9.1 7.1
cm. 57.2 106.7 48.8 4.6 17.3 2.0 19.05 mm 23.1 18.0
in. 22.5 45.0 19.2 1.8 6.8 0.8 3/4 in. 9.2 7.1
cm. 57.2 114.3 48.8 4.6 17.3 2.0 19.05 mm 23.4 18.0
in. 25.5 48.0 21.2 1.8 6.8 0.8 1 in. 9.2 9.1
cm. 64.8 121.9 53.8 4.6 17.3 2.0 25.4 mm 23.4 23.1
in. 25.5 53.0 21.2 1.8 6.8 0.8 1 in. 9.2 9.1
cm. 64.8 134.6 53.8 4.6 17.3 2.0 25.4 mm 23.4 23.1
in. 25.5 61.0 21.2 1.8 6.8 0.8 1 in. 9.2 9.1
cm. 64.8 154.9 53.8 4.6 17.3 2.0 25.4 mm 23.4 23.1
in. 25.5 68.0 21.2 1.8 6.8 0.8 1 in. 9.2 9.1
cm. 64.8 172.7 53.8 4.6 17.3 2.0 25.4 mm 23.4 23.1
Models
in. 5.9 7.2 9.5 6.0 16.4 14.5 2.0 1.4 3/4”
cm. 15.0 18.3 24.1 15.2 41.7 36.8 5.1 3.6 1.9
in. 6.7 10.5 9.4 4.9 27.4 16.6 2.0 1.4 3/4”
cm. 17.0 26.7 23.9 12.4 69.6 42.2 5.1 3.6 1.9
in. 6.7 10.5 9.4 4.9 30.4 16.6 2.0 1.5 3/4”
cm. 17.0 26.7 23.9 12.4 77.2 42.2 5.1 3.8 1.9
in. 4.9 13.6 13.2 4.6 35.4 18.6 2.3 1.4 3/4”
cm. 12.4 34.5 33.5 11.7 89.9 47.2 5.8 3.6 1.9
in. 4.9 13.6 13.2 4.6 40.4 18.6 2.3 1.4 3/4”
cm. 12.4 34.5 33.5 11.7 102.6 47.2 5.8 3.6 1.9
in. 4.9 13.6 13.2 4.6 45.4 18.6 2.3 1.4 3/4”
cm. 12.4 34.5 33.5 11.7 115.3 47.2 5.8 3.6 1.9
in. 4.9 13.6 13.2 4.6 45.4 18.6 2.3 1.4 3/4”
cm. 12.4 34.5 33.5 11.7 115.3 47.2 5.8 3.6 1.9
Overall Cabinet
A B C D E H Loop 1/2 in. cond 1 in. cond
Discharge Connection
duct fl ange installed (±0.10 in.)
LMNPQRS TX
Supply Width Supply Depth Return Depth Return Height
123 JK
Water Connections Electrical Knockouts
Return Connection
using deluxe fi lter rack option (±0.10 in.)
3/16/12
PVC Size
3/16/12
Horizontal Disconnect
When using disconnect, do not use dimension K from the standard horizontal dimensional data. Use dimension KK from the horizontal disconnect dimensional data.
Horizontal Models KK
009-012
015-018 024-030 036-038 042-049 060-064 070-072
Dimensions in inches [cm] 3/16/12
8.2 [20.8]
9.2 [23.4]
9.2 [23.4]
11.2 [28.4]
10.2 [25.9]
11.2 [28.4]
10.2 [25.9]
Disconnect Located
on this Side for a
Left Return
9
2.1 in.
[5.3 cm]
Disconnect Location
KK
Power Supply
Horizontal Shown in
Right Return Configuration
ENVISION2 COMPACT INSTALLATION MANUAL

Installing Horizontal Units

Installing Horizontal Units
Remove and discard the compressor hold down shipping bolt located at the front of the compressor mounting bracket prior to setting the unit in place. Horizontal units are available with side or end discharge.
NOTE: Horizontal units are normally suspended from a ceiling by four (009-060 models) or five (070-072 models) 3/8 in. diameter threaded rods. The rods are usually attached to the unit by hanger bracket kits furnished with each unit.
Lay out the threaded rods per the Hanger Bracket Dimensions table. Assemble the hangers to the unit as shown. Securely tighten the brackets to the unit using the weld nuts located on the underside of the bottom panel. When attaching the hanger rods to the bracket, a double nut is required since vibration could loosen a single nut. To allow filter access, install hanger brackets as illustrated in the Hanger Bracket Locations section. The unit should
be pitched approximately 1/4 in. towards the drain in both directions to facilitate the removal of condensate. Use only the bolts provided in the kit to attach hanger brackets. The use of longer bolts could damage internal parts.
Some applications require the installation of horizontal units on an attic floor. In this case, the unit should be set in a full size secondary drain pan on top of a vibration absorbing pad. The secondary drain pan prevents possible condensate overflow or water leakage damage to the ceiling. The secondary drain pan is usually placed on a plywood base isolated from the ceiling joists by additional layers of vibration absorbing material.
CAUTION: Do not use rods smaller than 3/8 in. diameter since they may not be strong enough to support the unit. The rods must be securely anchored to the ceiling.
10

Hanger Bracket Locations

ENVISION2 COMPACT INSTALLATION MANUAL
H
D
Compressor
Section
B
E
NOTE: Model sizes 070-072 will be shipped with six (6) hanger brackets. Only five (5) hanger brackets will be used on the unit. See the above illustration for the fifth hanger bracket location. All other models will use four (4) hanger brackets.
Hanger Bracket Dimensions
Model
009-012
015-018
024-030
036
042-048
Single Speed
060
070
026
038
049
064
Dual Capacity
072
Hanger Kit
Part Number
in.
99S500A04
cm. 90.7 63.8 54.4 n/a
in.
99S500A04
cm. 108.7 63.8 54.4 n/a
in.
99S500A04
cm. 116.3 63.8 54.4 n/a
in.
99S500A04
cm. 124.0 71.4 62.0 n/a
in.
99S500A04
cm. 136.7 71.4 62.0 n/a
in.
99S500A04
cm. 157.0 71.4 62.0 n/a
in.
99S500A03
cm. 174.8 71.4 62.0 74.4
in.
99S500A04
cm. 116.3 63.8 54.4 n/a
in.
99S500A03
cm. 124.0 71.4 62.0 n/a
in.
99S500A04
cm. 136.7 71.4 62.0 n/a
in.
99S500A04
cm. 157.0 71.4 62.0 n/a
in.
99S500A03
cm. 174.8 71.4 62.0 74.4
Right
F
C
Air Handler
Section
G
A
3/8”
Threaded Rod
(not supplied)
Bolt and Lockwasher
Unit Hanger Dimensions
ABCH
35.7 25.1 21.4 n/a
42.8 25.1 21.4 n/a
45.8 25.1 21.4 n/a
48.8 28.1 24.4 n/a
53.8 28.1 24.4 n/a
61.8 28.1 24.4 n/a
68.8 28.1 24.4 34.0
45.8 25.1 21.4 n/a
48.8 28.1 24.4 n/a
53.8 28.1 24.4 n/a
61.8 28.1 24.4 n/a
68.8 28.1 24.4 34.0
3/16/12
E
Compressor
Section
D
H
Vibration Isolator
Washer
Hex Nuts (not supplied)
Weight Distribution
009
012
015
018
024
030
036
042
048
060
070
026
038
049
064
072
Vertical Weight
[202] [206] [61] [54] [45] [39]
[202] [206] [61] [54] [45] [39]
Model
Single Speed
Dual Capacity
Weights are listed in lbs. [kg]. 3/16/12
Horizontal
Weight
171 176 32 67 32 45
[78] [80] [15] [30] [15] [20]
171 176 32 67 32 45
[78] [80] [15] [30] [15] [20]
210 220 65 40 70 35
[95] [100] [29] [18] [32] [16]
210 220 65 40 70 35 [95] [100] [29] [18] [32] [16] 280 295 75 70 75 20
[127] [134] [34] [31] [34] [13]
285 295 75 70 75 30
[129] [134] [34] [31] [34] [13]
300 305 85 80 85 40
[136] [138] [39] [36] [39] [18]
365 375 115 95 75 60
[166] [170] [52] [43] [34] [27]
370 380 120 100 80 65
[168] [172] [54] [45] [36] [29]
410 420 120 110 95 80
[186] [191] [54] [50] [43] [36]
445 455 135 120 100 85
280 295 75 70 75 50
[127] [134] [34] [31] [34] [13]
360 375 115 95 75 60
[163] [170] [52] [43] [34] [27]
370 380 120 100 80 65
[168] [172] [54] [45] [36] [29]
410 420 120 110 95 80
[186] [191] [54] [50] [43] [36]
445 455 135 120 100 85
Left
G
Air Handler
Section
F
Horizontal Weight Distribution
Front Back
DEFG
11
ENVISION2 COMPACT INSTALLATION MANUAL

Duct System

An air outlet collar is provided on vertical top flow units and all horizontal units to facilitate a duct connection. A flexible connector is recommended for discharge and return air duct connections on metal duct systems. Uninsulated duct should be insulated with a minimum of 1-inch duct insulation. Application of the unit to uninsulated ductwork in an unconditioned space is not recommended as the unit’s performance will be adversely affected.
If the unit is connected to existing ductwork, check the duct system to ensure that it has the capacity to accommodate the air required for the unit application. If the duct is too small, as in the replacement of heating only systems, larger ductwork should be installed. All existing ductwork should be checked for leaks and repaired if necessary.

Water Piping

The proper water flow must be provided to each unit whenever the unit operates. To assure proper flow, use pressure/temperature ports to determine the flow rate. These ports should be located at the supply and return water connections on the unit. The proper flow rate cannot be accurately set without measuring the water pressure drop through the refrigerant-to-water heat exchanger.
The duct system should be sized to handle the design airflow quietly and efficiently. To maximize sound attenuation of the unit blower, the supply and return plenums should include an internal duct liner of fiberglass or constructed of ductboard for the first few feet. On systems employing a sheet metal duct system, canvas connectors should be used between the unit and the ductwork. If air noise or excessive airflow is a problem, the blower speed can be changed.
All source water connections on commercial units are fittings that accept a male pipe thread (MPT). Insert the connectors by hand, then tighten the fitting with a wrench to provide a leakproof joint. When connecting to an open loop (groundwater) system, thread any copper MPT fitting into the connector and tighten in the same manner as described above.

Condensate Drain

On vertical units, the internal condensate drain assembly consists of a drain tube which is connected to the drain pan, a 3/4 in. PVC female adapter and a flexible connecting hose. The female adapter may exit either the front or the side of the cabinet. The adapter should be glued to the field-installed PVC condensate piping. On vertical units, a condensate hose is inside all cabinets as a trapping loop; therefore, an external trap is not necessary.
Vent (if needed)
PVC tube stub 1/8 in. per foot
PVC tube stub
PVC coupling
1.5 in.
1.5 in.
On horizontal units, a PVC stub or stainless steel tube is provided for condensate drain piping connection. An external trap is required (see below). If a vent is necessary, an open stand pipe may be applied to a tee in the field­installed condensate piping.
Unit Pitch for DrainHorizontal Drain Connection (Composite Drain Pan)
1/2'' Pitch
Drain
12

Water Quality

ENVISION2 COMPACT INSTALLATION MANUAL
In ground water situations where scaling could be heavy or where biological growth such as iron bacteria will be present, a closed loop system is recommended. The heat exchanger coils in ground water systems may, over a period
with extremely hard water, the owner should be informed that the heat exchanger may require occasional flushing. Failure to adhere to the guidelines in the water quality table
could result in loss of warranty. of time, lose heat exchange capabilities due to a buildup of mineral deposits inside. These can be cleaned, but only by a qualified service mechanic, as special solutions and pumping equipment are required. Hot water generator coils can likewise become scaled and possibly plugged. In areas
Material Copper 90/10 Cupronickel 316 Stainless Steel
pH Acidity/Alkalinity
Scaling
Corrosion
Iron Fouling
(Biological Growth)
Erosion
NOTES: Grains = ppm divided by 17
mg/L is equivalent to ppm
Calcium and
Magnesium Carbonate
Hydrogen Sulfide
Chlorine Less than 0.5 ppm Less than 0.5 ppm Less than 0.5 ppm
Chlorides Less than 20 ppm Less than 125 ppm Less than 300 ppm
Carbon Dioxide Less than 50 ppm 10 - 50 ppm 10 - 50 ppm
Ammonia Less than 2 ppm Less than 2 ppm Less than 20 ppm
Ammonia Chloride Less than 0.5 ppm Less than 0.5 ppm Less than 0.5 ppm
Ammonia Nitrate Less than 0.5 ppm Less than 0.5 ppm Less than 0.5 ppm
Ammonia Hydroxide Less than 0.5 ppm Less than 0.5 ppm Less than 0.5 ppm
Ammonia Sulfate Less than 0.5 ppm Less than 0.5 ppm Less than 0.5 ppm
Total Dissolved Solids (TDS) Less than 1000 ppm 1000 - 1500 ppm 1000 - 1500 ppm
LSI Index +0.5 to -0.5 +0.5 to -0.5 +0.5 to -0.5
Iron, FE
Bacterial Iron Potential
Iron Oxide
Suspended Solids
Threshold Velocity
(Fresh Water)
Less than 0.5 ppm (rotten egg
Sulfates Less than 125 ppm Less than 125 ppm Less than 200 ppm
2
+ (Ferrous)
smell appears at 0.5 ppm)
Less than 1 ppm, above this
level deposition will occur
Less than 10 ppm and filtered
for max. of 600 mic
7 - 9 7 - 9 7 - 9
(Total Hardness)
less than 350 ppm
< 0.2 ppm < 0.2 ppm < 0.2 ppm
< 6 ft/sec < 6 ft/sec < 6 ft/sec
Units with cupronickel heat exchangers are recommended
for open loop applications due to the increased resistance
to build-up and corrosion, along with reduced wear caused
by acid cleaning.
ron size
(Total Hardness)
less than 350 ppm
10 - 50 ppm Less than 1 ppm
Less than 1 ppm, above this
level deposition will occur
Less than 10 ppm and filtered
for max. of 600 micron size
(Total Hardness)
less than 350 ppm
Less than 1 ppm, above this
level deposition will occur
Less than 10 ppm and filtered
for max. of 600 micron size
2/22/12

System Cleaning and Flushing

Cleaning and Flushing
Prior to start up of any heat pump, the water circulating system must be cleaned and flushed of all dirt and debris.
If the system is equipped with water shutoff valves, the supply and return runouts must be connected together at each unit location (This will prevent the introduction of dirt into the unit, see Flushing with Water Shutoff Valve Equipped Systems illustration). The system should be filled at the water make-up connection with all air vents open. After filling, vents should be closed.
The contractor should start the main circulator with the pressure reducing valve makeup open. Vents should be checked in sequence to bleed off any trapped air and to verify circulation through all components of the system.
As water circulates through the system, the contractor should check and repair any leaks found in the piping system. Drain(s) at the lowest point(s) in the system should
Flushing with Water Shutoff Valve Equipped Systems
Return Runout
Supply Runout
Mains
Rubber Hose
Runouts Initially Connected Together
13
ENVISION2 COMPACT INSTALLATION MANUAL
System Cleaning and Flushing cont.
be opened for initial flush and blowdown, making sure water fill valves are set at the same rate. Check the pressure gauge at the pump suction and manually adjust the make­up water valve to hold the same positive pressure both before and after opening the drain valves. Flushing should continue for at least two hours, or longer if required, until drain water is clean and clear.
The supplemental heater and/or circulator pump, if used, should be shut off. All drains and vents should be opened to completely drain the system. Short-circuited supply and return runouts should now be connected to the unit supply and return connections.
Refill the system with clean water. Test the system water for acidity and treat as required to leave the water slightly alkaline (pH 7.5 to 8.5). The specified percentage of antifreeze may also be added at this time. Use commercial grade antifreeze designed for HVAC systems only. Environol™ brand antifreeze is recommended.
Once the system has been filled with clean water and antifreeze (if used), precautions should be taken to protect the system from dirty water conditions. Dirty water will result in system-wide degradation of performance, and solids may clog valves, strainers, flow regulators, etc. Additionally, the heat exchanger may become clogged which reduces compressor service life and can cause premature unit failure.
In boiler/tower application, set the loop control panel set points to desired temperatures. Supply power to all motors and start the circulating pumps. After full flow has
been established through all components including the heat rejector (regardless of season), air vented and loop temperatures stabilized, each of the units will be ready for check, test and start up and for air and water balancing.

Ground Source Loop System Checkout

Once piping is completed between the unit pumping system and ground loop, final purging and charging of the loop is needed. A high pressure pump is needed to achieve adequate flow velocity in the loop to purge air and dirt particles from the loop itself. Antifreeze solution is used in most areas to prevent freezing. Flush the system adequately to remove as much air as possible; then pressurize the loop to a static pressure of 40-50 PSI (summer) or 50-75 PSI (winter). This is normally adequate for good system operation. Loop static pressure may decrease soon after initial installation, due to pipe expansion and loop temperature change. Running the unit for at least 30 minutes after the system has been completely purged of air will allow for the “break-in” period. It may be necessary to adjust static loop pressure (by adding water) after the unit has run for the first time. Loop static pressure will also fluctuate with the seasons. Pressures will be higher in the winter months than during the cooling season. This fluctuation is normal and should be considered when charging the system initially.
Ensure the pump provides adequate flow through the unit by checking pressure drop across the heat exchanger. Usually 2.25-3.0 gpm of flow per ton of cooling capacity is recommended in earth loop applications.

Open Loop Ground Water Systems

Typical open loop piping is shown below. Always maintain water pressure in the heat exchanger by placing water control valves at the outlet of the unit to prevent mineral precipitation. Use a closed, bladder-type expansion tank to minimize mineral formation due to air exposure. Insure proper water flow through the unit by checking pressure drop across the heat exchanger and comparing it to the figures in unit capacity data tables in the specification catalog. 1.5-2 gpm of flow per ton of cooling capacity is recommended in open loop applications. Due to only minor differences in flow rate from low to high, only one solenoid valve should be used. The valve should be sized for full flow.
Discharge water from the unit is not contaminated in any manner and can be disposed of in various ways, depending on local codes, i.e. recharge well, storm sewer, drain field, adjacent stream or pond, etc. Most local codes forbid the use of sanitary sewer for disposal. Consult your local building and zoning departments to assure compliance in your area.
Open System - Groundwater Application
14
Unit Supply
Disconnects
(IfApplicable)
Compressor Line Voltage
Aux. Heat Supply
Low Voltage
to Thermostat
and Valve
P/T Plugs
Vibration
Absorbing Pad
Flexible Duct Collar
Hot Water Generator
Connections
Drain
Strainer
Rubber Bladder Expansion Tank
Solenoid
Valve
valve while acid flushing)
Boiler Drains
For HX Flushing
Flow Control
(on outlet of
Solenoid Valve)
Water Out
Shut Off Valves
Shut Off Valves
(to isolate solenoid
Valve
Water In

Hot Water Generator Connections

ENVISION2 COMPACT INSTALLATION MANUAL
The heat reclaiming hot water generator coil is of vented double-wall copper construction and is suitable for potable water.
To maximize the benefits of the hot water generator a minimum 50-gallon water heater is recommended. For higher demand applications, use an 80-gallon water heater or two 50-gallon water heaters connected in a series as shown below. Electric water heaters are recommended. Make sure all local electrical and plumbing codes are met for installing a hot water generator. A water softener is recommended with hard water (greater than 10 grains or 170 total hardness).
Water Tank Preparation
To install a unit with a hot water generator, follow these installation guidelines.
1. Turn off the power to the water heater.
2. Attach a water hose to the water tank drain connection and run the other end of the hose to an open drain or outdoors.
3. Close the cold water inlet valve to the water heater tank.
4. Drain the tank by opening the valve on the bottom of the tank, then open the pressure relief valve or hot water faucet.
5. Flush the tank by opening the cold water inlet valve to the water heater to free the tank of sediments. Close when draining water is clear.
6. Disconnect the garden hose and remove the drain valve from the water heater.
7. Refer to Plumbing Installation and Hot Water Generator Startup.
Typical Hot Water Generator Installation
3/4 in. x 3/4 in. x 1/2 in. Tee
Ball Valve
Vent
HWG
Water Out
Field Installed
HWG Pump
HWG
Water In
Cold
Water In
Drain Valve
P/T Relief
Valve
Water Out
In
Hot
Hot Water Generator Installation In Preheat Tank
Cold
3/4 in. x 3/4 in. x 1/2 in. Tee
Ball Valve
Vent
Water Out
Field Installed
HWG
Water In
HWG
HWG Pump
Water In
P/T Relief
Valve
In
Drain Valve
NOTE: This configuration maximizes hot water generator capability.
Hot
Water Out
P/T Relief
Valve
Plumbing Installation
1. Inspect the dip tube in the water heater cold inlet
for a check valve. If a check valve is present it must be removed or damage to the hot water generator circulator will occur.
2. Remove drain valve and fitting.
3. Thread the 3/4-inch NPT x 3-1/2-inch brass nipple into
the water heater drain port.
4. Attach the center port of the 3/4-inch FPT tee to the
opposite end of the brass nipple.
5. Attach the 1/2-inch copper to 3/4-inch NPT adaptor to
the side of the tee closest to the unit.
6. Install the drain valve on the tee opposite the adaptor.
7. Run interconnecting tubing from the tee to HWG
water out.
CAUTION: Elements will burn out if energized dry.
8. Cut the cold water “IN” line going to the water heater.
9. Insert the reducing solder tee in line with cold water “IN” line as shown.
10. Run interconnecting copper tubing between the unit DHW water “IN” and the tee (1/2-inch nominal). The recommended maximum distance is 50 feet.
11.
To prevent air entrapment in the system, install a vent coupling at the highest point of the interconnecting lines.
12. Insulate all exposed surfaces of both connecting water lines with 3/8-inch wall closed cell insulation.
NOTE: All plumbing and piping connections must comply with local plumbing codes.
15
ENVISION2 COMPACT INSTALLATION MANUAL
Hot Water Generator Connections cont.
Hot Water Generator Startup
1. Make sure the power is off to the heat pump. Connect the wire from the hot water generator pump to T1 on the contactor.
2. Close the drain valve to the water heater.
3. Open the cold water supply to the tank.
4. Open a hot water faucet in the building to bleed air from the system. Close when full.
5. Open the pressure relief valve to bleed any remaining air from the tank, then close.
6. If so equipped, turn the venting (burping) screw in the center of the pump two (2) turns open (water will drip out), wait until all air is purged from the pump, then tighten the plug. Use vent couplings to bleed air from the lines.
7. Carefully inspect all plumbing for water leaks and correct as required.
8. Before restoring electrical supply to the water heater, adjust the temperature setting on the tank.
• On tanks with both upper and lower elements, the lower element should be turned down to the lowest setting, approximately 100°F. The upper element should be adjusted to 120°F to 130°F. Depending upon the specific needs of the customer, you may want to adjust the upper element differently.
• On tanks with a single element, lower the thermostat setting to 120°F.
9. After the thermostat(s) is adjusted, replace the access cover and restore electrical supply to the water heater.
10. Make sure that any valves in the hot water generator circuit are open.
11. Turn on the unit to heating.
12. The HWG pump should be running. When the pump is first started, turn the venting (burping) screw (if equipped) in the center of the pump two (2) turns open until water dribbles out, then replace. Allow the pump to run for at least five minutes to ensure that water has filled the circulator properly.
13. The temperature difference between the water entering and leaving the hot water generator should be 5°F to 15°F. The water flow should be approximately 0.4 gpm per ton of nominal cooling.
14. Allow the unit to heat water for 15 to 20 minutes to be sure operation is normal.
CAUTION: Never operate the HWG circulating pump while dry. If the unit is placed in operation before the hot water generator piping is connected, be sure that the pump wires are disconnected from the contactor.
16

Freeze Detection

For Aurora Base Control, set SW2-1, FP1, on the printed circuit board for applications using a closed loop antifreeze solution to 15°F [-9.4°C]. On applications using an open loop/ground water system (or closed loop no antifreeze), set this dip switch to 30°F [-1.1°C], the factory default setting. (Refer to the Dip Switch Field Selection table).

Electrical Connections

ENVISION2 COMPACT INSTALLATION MANUAL
General
Be sure the available power is the same voltage and phase as that shown on the unit serial plate. Line and low voltage wiring must be done in accordance with local codes or the National Electric Code, whichever is applicable.
Power Connection
Connect the incoming line voltage wires to L1 and L2 of the contactor for single-phase unit. Consult the Electrical Data tables for correct fuse sizes.
Aurora Base Control Box
208 Volt Operation
All 208/230 units are factory wired for 230 volt operation. For 208 volt operation, the red and blue transformer wires must be switched on terminal strip PS.
CAUTION: When installing a unit with a variable speed ECM blower motor in 460/60/3 voltage, a neutral wire is required to allow proper unit operation.
17
ENVISION2 COMPACT INSTALLATION MANUAL

Electrical Data

PSC Motor
Model
009
012
015
018
024
024*
030
030*
036
036*
Single Speed
042
042*
048
048*
060
070
HACR circuit breaker in USA only *With optional High-static PSC motor **With optional IntelliStart
Rated
Voltage
208-230/60/1 187/253 6.4 4.1 21.0 n/a 0.6 4.7 5.7 10/15
265/60/1 238/292 6.7 4.3 22.0 n/a 0.6 4.9 6.0 10/15
208-230/60/1 187/253 7.7 4.9 25.0 n/a 0.6 5.5 6.7 10/15
265/60/1 238/292 7.0 4.5 22.0 n/a 0.6 5.1 6.2 10/15
208-230/60/1 187/253 9.7 6.2 29.0 n/a 1.1 7.3 8.9 15
265/60/1 238/292 7.8 5.0 28.0 n/a 1.0 6.0 7.3 10/15
208-230/60/1 187/253 13.1 8.4 33.5 13.4 1.1 9.5 11.6 20
265/60/1 238/292 8.7 5.6 28.0 n/a 1.0 6.6 8.0 10/15
208-230/60/1 187/253 21.0 13.5 58.3 23.3 1.2 14.7 18.1 25
265/60/1 238/292 14.0 9.0 54.0 n/a 1.1 10.1 12.4 20
208-230/60/3 187/253 11.0 7.1 55.4 33.2 1.2 8.3 10.1 15
460/60/3 414/506 5.5 3.5 28.0 16.8 0.6 4.1 5.0 10/15
208-230/60/1 187/253 21.0 13.5 58.3 23.3 1.5 15.0 18.4 30
265/60/1 238/292 14.0 9.0 54.0 n/a 1.5 10.5 12.8 20
208-230/60/3 187/253 11.0 7.1 55.4 33.2 1.5 8.6 10.4 15
460/60/3 414/506 5.5 3.5 28.0 16.8 1.0 4.5 5.4 10/15
208-230/60/1 187/253 20.0 12.8 58.0 23.2 1.5 14.3 17.5 30
265/60/1 238/292 15.0 9.6 54.0 n/a 1.5 11.1 13.5 20
208-230/60/3 187/253 12.0 7.7 55.4 33.2 1.5 9.2 11.1 15
460/60/3 414/506 5.6 3.6 28.0 16.8 1.0 4.6 5.5 10/15
208-230/60/1 187/253 20.0 12.8 58.0 23.2 2.8 15.6 18.8 30
265/60/1 238/292 15.0 9.6 54.0 n/a 2.0 11.6 14.0 20
208-230/60/3 187/253 12.0 7.7 55.4 33.2 2.2 9.9 11.8 15
460/60/3 414/506 5.6 3.6 28.0 16.8 1.1 4.7 5.6 10/15
208-230/60/1 187/253 22.0 14.1 73.0 29.2 2.8 16.9 20.4 30
265/60/1 238/292 17.5 11.2 60.0 n/a 2.0 13.2 16.0 25
208-230/60/3 187/253 13.9 8.9 58.0 34.8 2.8 11.7 13.9 20
460/60/3 414/506 6.5 4.2 28.0 16.8 1.4 5.6 6.7 10/15
208-230/60/1 187/253 22.0 14.1 73.0 29.2 3.5 17.6 21.1 35
265/60/1 238/292 17.5 11.2 60.0 n/a 3.5 14.7 17.5 25
208-230/60/3 187/253 13.9 8.9 58.0 34.8 1.8 10.7 12.9 20
460/60/3 414/506 6.5 4.2 28.0 16.8 1.8 5.6 6.7 10/15 208-230/60/1 187/253 26.0 16.7 79.0 31.6 3.5 20.2 24.4 40 208-230/60/3 187/253 16.3 10.4 73.0 43.8 3.5 13.9 16.5 25
460/60/3 414/506 9.0 5.8 38.0 22.8 1.8 7.6 9.0 10/15
575/60/3 517/633 5.9 3.8 36.5 n/a 1.4 5.2 6.1 10/15 208-230/60/1 187/253 26.0 16.7 79.0 31.6 4.6 21.3 25.5 40 208-230/60/3 187/253 16.3 10.4 73.0 43.8 4.6 15.0 17.6 25
460/60/3 414/506 9.0 5.8 38.0 22.8 2.3 8.1 9.5 15
575/60/3 517/633 5.9 3.8 36.5 n/a 1.9 5.7 6.6 10/15 208-230/60/1 187/253 31.0 19.9 109.0 43.6 3.5 23.4 28.4 45 208-230/60/3 187/253 21.2 13.6 83.1 49.9 3.5 17.1 20.5 30
460/60/3 414/506 9.5 6.1 41.0 24.6 1.8 7.9 9.4 15
575/60/3 517/633 6.5 4.2 33.0 n/a 1.4 5.6 6.7 10/15 208-230/60/1 187/253 31.0 19.9 109.0 43.6 4.6 24.5 29.5 45 208-230/60/3 187/253 21.2 13.6 83.1 49.9 4.6 18.2 21.6 35
460/60/3 414/506 9.5 6.1 41.0 24.6 2.3 8.4 9.9 15
575/60/3 517/633 6.5 4.2 33.0 n/a 1.9 6.1 7.2 10/15 208-230/60/1 187/253 41.2 26.4 134.0 53.6 5.9 32.3 38.9 60 208-230/60/3 187/253 24.9 16.0 110.0 66.0 5.9 21.9 25.9 40
460/60/3 414/506 12.1 7.8 52.0 31.2 3.0 10.8 12.8 20
575/60/3 517/633 8.9 5.7 38.9 n/a 1.9 7.6 9.0 10/15 208-230/60/1 187/253 44.2 28.3 178.0 71.2 5.9 34.2 41.3 70 208-230/60/3 187/253 30.0 19.2 136.0 81.6 5.9 25.1 29.9 45
460/60/3 414/506 13.6 8.7 66.1 39.7 3.0 11.7 13.9 20
575/60/3 517/633 10.7 6.9 55.3 n/a 1.9 8.8 10.5 15
Voltage
Min/Max
MCC RLA LRA LRA**
Compressor
Blower
Motor
FLA
Total
Unit FLA
Min
Circ
Amp
Max Fuse/
HACR
Breaker
8/06/13
18
Electrical Data cont.
5-Speed ECM Motor
Model
015
018
024
030
036
Single Speed
042
048
060
070
026
038
049
Dual Capacity
064
072
HACR circuit breaker in USA only **With optional IntelliStart
Rated
Voltage
208-230/60/1 187/253 9.7 6.2 29.0 n/a 4.1 10.3 11.9 15
265/60/1 238/292 7.8 5.0 28.0 n/a 3.6 8.6 9.9 10/15
208-230/60/1 187/253 13.1 8.4 33.5 13.4 4.1 12.5 14.6 20
265/60/1 238/292 8.7 5.6 28.0 n/a 3.6 9.2 10.6 15
208-230/60/1 187/253 21.0 13.5 58.3 23.3 4.1 17.6 21.0 30
265/60/1 238/292 14.0 9.0 54.0 n/a 3.6 12.6 14.9 20
208-230/60/3 187/253 11.0 7.1 55.4 33.2 4.1 11.2 13.0 20
460/60/3 414/506 5.5 3.5 28.0 16.8 2.1 5.6 6.5 10/15
208-230/60/1 187/253 20.0 12.8 58.0 23.2 4.1 16.9 20.1 30
265/60/1 238/292 15.0 9.6 54.0 n/a 3.6 13.2 15.6 25
208-230/60/3 187/253 12.0 7.7 55.4 33.2 4.1 11.8 13.7 20
460/60/3 414/506 5.6 3.6 28.0 16.8 2.1 5.7 6.6 10/15
208-230/60/1 187/253 22.0 14.1 73.0 29.2 4.1 18.2 21.7 35
265/60/1 238/292 17.5 11.2 60.0 n/a 3.6 14.8 17.6 25
208-230/60/3 187/253 13.9 8.9 58.0 34.8 4.1 13.0 15.2 20
460/60/3 414/506 6.5 4.2 28.0 16.8 2.1 6.3 7.4 10/15
208-230/60/1 187/253 26.0 16.7 79.0 31.6 7.6 24.3 28.5 45
208-230/60/3 187/253 16.3 10.4 73.0 43.8 7.6 18.0 20.6 30
460/60/3 414/506 9.0 5.8 38.0 22.8 4.0 9.8 11.2 15
208-230/60/1 187/253 31.0 19.9 109.0 43.6 7.6 27.5 32.5 50
208-230/60/3 187/253 21.2 13.6 83.1 49.9 7.6 21.2 24.6 35
460/60/3 414/506 9.5 6.1 41.0 24.6 4.0 10.1 11.6 15
208-230/60/1 187/253 41.2 26.4 134.0 53.6 7.6 34.0 40.6 60
208-230/60/3 187/253 24.9 16.0 110.0 66.0 7.6 23.6 27.6 40
460/60/3 414/506 12.1 7.8 52.0 31.2 4.0 11.8 13.8 20
208-230/60/1 187/253 44.2 28.3 178.0 71.2 7.6 35.9 43.0 70
208-230/60/3 187/253 30.0 19.2 136.0 81.6 7.6 26.8 31.6 50
460/60/3 414/506 13.6 8.7 66.1 39.7 4.0 12.7 14.9 20
208-230/60/1 187/253 18.2 11.7 58.3 23.3 4.1 15.8 18.7 30
265/60/1 238/292 14.2 9.1 54.0 n/a 3.6 12.7 15.0 20
208-230/60/3 187/253 10.1 6.5 55.4 33.2 4.1 10.6 12.2 15
460/60/3 414/506 5.4 3.5 28.0 16.8 2.1 5.6 6.4 10/15
208-230/60/1 187/253 23.8 15.3 83.0 33.2 4.1 19.4 23.2 35
265/60/1 238/292 20.3 13.0 72.0 n/a 3.6 16.6 19.9 30
208-230/60/3 187/253 18.1 11.6 73.0 43.8 4.1 15.7 18.6 30
460/60/3 414/506 8.9 5.7 38.0 22.8 2.1 7.8 9.2 10/15
208-230/60/1 187/253 33.0 21.1 104.0 41.6 7.6 28.7 34.0 50
208-230/60/3 187/253 21.9 14.0 83.1 49.9 7.6 21.6 25.1 35
460/60/3 414/506 10.0 6.4 41.0 24.6 4.0 10.4 12.0 15
208-230/60/1 187/253 42.3 27.1 152.9 61.2 7.6 34.7 41.5 60
208-230/60/3 187/253 25.8 16.5 110.0 66.0 7.6 24.1 28.2 40
460/60/3 414/506 11.3 7.2 52.0 31.2 4.0 11.2 13.0 20
208-230/60/1 187/253 46.3 29.7 179.2 71.7 7.6 37.3 44.7 70
208-230/60/3 187/253 27.4 17.6 136.0 81.6 7.6 25.2 29.6 45
460/60/3 414/506 13.2 8.5 66.1 39.7 4.0 12.5 14.6 20
Voltage
Min/Max
ENVISION2 COMPACT INSTALLATION MANUAL
Compressor
MCC RLA LRA LRA**
Blower
Motor
FLA
Total
Unit FLA
Min Circ
Amp
Max Fuse/
HACR
Breaker
5/21/13
19
ENVISION2 COMPACT INSTALLATION MANUAL
Electrical Data cont.
Variable Speed ECM Motor
Model
015
018
024
030
036
036*
Single Speed
042
042*
048
048*
060
070
026
038
038*
049
Dual Capacity
049*
064
072
HACR circuit breaker in USA only *With optional 1 HP variable speed ECM motor **With optional IntelliStart
Rated
Voltage
208-230/60/1 187/253 9.7 6.2 29.0 n/a 4.0 10.2 11.8 15
265/60/1 238/292 7.8 5.0 28.0 n/a 4.1 9.1 10.4 15
208-230/60/1 187/253 13.1 8.4 33.5 13.4 4.0 12.4 14.5 20
265/60/1 238/292 8.7 5.6 28.0 n/a 4.1 9.7 11.1 15
208-230/60/1 187/253 21.0 13.5 58.3 23.3 4.0 17.5 20.9 30
265/60/1 238/292 14.0 9.0 54.0 n/a 4.1 13.1 15.4 20
208-230/60/3 187/253 11.0 7.1 55.4 33.2 4.0 11.1 12.9 20
460/60/3 414/506 5.5 3.5 28.0 16.8 4.1 7.6 8.5 10/15
208-230/60/1 187/253 20.0 12.8 58.0 23.2 4.0 16.8 20.0 30
265/60/1 238/292 15.0 9.6 54.0 n/a 4.1 13.7 16.1 25
208-230/60/3 187/253 12.0 7.7 55.4 33.2 4.0 11.7 13.6 20
460/60/3 414/506 5.6 3.6 28.0 16.8 4.1 7.7 8.6 10/15
208-230/60/1 187/253 22.0 14.1 73.0 29.2 4.0 18.1 21.6 35
265/60/1 238/292 17.5 11.2 60.0 n/a 4.1 15.3 18.1 25
208-230/60/3 187/253 13.9 8.9 58.0 34.8 4.0 12.9 15.1 20
460/60/3 414/506 6.5 4.2 28.0 16.8 4.1 8.3 9.4 10/15
208-230/60/1 187/253 22.0 14.1 73.0 29.2 7.0 21.1 24.6 35
265/60/1 238/292 17.5 11.2 60.0 n/a 6.9 18.1 20.9 30
208-230/60/3 187/253 13.9 8.9 58.0 34.8 7.0 15.9 18.1 25
460/60/3 414/506 6.5 4.2 28.0 16.8 6.9 11.1 12.2 15
208-230/60/1 187/253 26.0 16.7 79.0 31.6 4.0 20.7 24.9 40
208-230/60/3 187/253 16.3 10.4 73.0 43.8 4.0 14.4 17.0 25
460/60/3 414/506 9.0 5.8 38.0 22.8 4.1 9.9 11.3 15
208-230/60/1 187/253 26.0 16.6 79.0 31.6 7.0 23.6 27.8 40
208-230/60/3 187/253 16.3 10.4 73.0 43.8 7.0 17.4 20.0 30
460/60/3 414/506 9.0 5.8 38.0 22.8 6.9 12.7 14.1 15
208-230/60/1 187/253 31.0 19.9 109.0 43.6 4.0 23.9 28.9 45
208-230/60/3 187/253 21.2 13.6 83.1 49.9 4.0 17.6 21.0 30
460/60/3 414/506 9.5 6.1 41.0 24.6 4.1 10.2 11.7 15
208-230/60/1 187/253 31.0 19.9 109.0 43.6 7.0 26.9 31.9 50
208-230/60/3 187/253 21.2 13.6 83.1 49.9 7.0 20.6 24.0 35
460/60/3 414/506 9.5 6.1 41.0 24.6 6.9 13.0 14.5 20
208-230/60/1 187/253 41.2 26.4 134.0 53.6 7.0 33.4 40.0 60
208-230/60/3 187/253 24.9 16.0 110.0 66.0 7.0 23.0 27.0 40
460/60/3 414/506 12.1 7.8 52.0 31.2 6.9 14.7 16.7 20
208-230/60/1 187/253 44.2 28.3 178.0 71.2 7.0 35.3 42.4 70
208-230/60/3 187/253 30.0 19.2 136.0 81.6 7.0 26.2 31.0 50
460/60/3 414/506 13.6 8.7 66.1 39.7 6.9 15.6 17.8 25
208-230/60/1 187/253 18.2 11.7 58.3 23.3 4.0 15.7 18.6 30
265/60/1 238/292 14.2 9.1 54.0 n/a 4.1 13.2 15.5 20
208-230/60/3 187/253 10.1 6.5 55.4 33.2 4.0 10.5 12.1 15
460/60/3 414/506 5.4 3.5 28.0 16.8 4.1 7.6 8.4 10/15
208-230/60/1 187/253 23.8 15.3 83.0 33.2 4.0 19.3 23.1 35
265/60/1 238/292 20.3 13.0 72.0 n/a 4.1 17.1 20.4 30
208-230/60/3 187/253 18.1 11.6 73.0 43.8 4.0 15.6 18.5 30
460/60/3 414/506 8.9 5.7 38.0 22.8 4.1 9.8 11.2 15
208-230/60/1 187/253 23.8 15.3 83.0 33.2 7.0 22.3 26.1 40
265/60/1 238/292 20.3 13.0 72.0 n/a 7.0 20.0 23.3 35
208-230/60/3 187/253 18.1 11.6 73.0 43.8 7.0 18.6 21.5 30
460/60/3 414/506 8.9 5.7 38.0 22.8 6.9 12.6 14.0 15
208-230/60/1 187/253 33.0 21.1 104.0 41.6 4.0 25.1 30.4 50
208-230/60/3 187/253 21.9 14.0 83.1 49.9 4.0 18.0 21.5 35
460/60/3 414/506 10.0 6.4 41.0 24.6 4.1 10.5 12.1 15
208-230/60/1 187/253 33.0 21.1 104.0 41.6 7.0 28.1 33.4 50
208-230/60/3 187/253 21.9 14.0 83.1 49.9 7.0 21.0 24.5 35
460/60/3 414/506 10.0 6.4 41.0 24.6 6.9 13.3 14.9 20
208-230/60/1 187/253 42.3 27.1 152.9 61.2 7.0 34.1 40.9 60
208-230/60/3 187/253 25.8 16.5 110.0 66.0 7.0 23.5 27.6 40
460/60/3 414/506 11.3 7.2 52.0 31.2 6.9 14.1 15.9 20
208-230/60/1 187/253 46.3 29.7 179.2 71.7 7.0 36.7 44.1 70
208-230/60/3 187/253 27.4 17.6 136.0 81.6 7.0 24.6 29.0 45
460/60/3 414/506 13.2 8.5 66.1 39.7 6.9 15.4 17.5 25
Voltage
Min/Max
MCC RLA LRA LRA**
Compressor
Blower
Motor
FLA
Total
Unit FLA
Min
Circ
Amp
Max Fuse/
HACR
Breaker
5/21/13
CAUTION: When installing a unit with a variable speed ECM blower motor in 460/60/3 voltage, a neutral wire is required to allow proper unit operation.
20
ENVISION2 COMPACT INSTALLATION MANUAL

Blower Performance Data

Standard PSC Motor
Blower
Blower
Model
009
012
015
018
024
030
036
042
048
060
070
Spd
H
MH
ML* 395370360340330310290280270250240-----
L 325310300280270250240230220210200-----
H
MH* 440410400380370350330310300280270-----
ML 395370360340330310290280270250240-----
L 325310300280270250240230220210200----­H
M 735730725715705700690675660630600485----
L
H
M
L 620615610605600590580565550520490----­H
M
L 845830815795775750725702.5680650625505---­H
M
L 910 905 900 895 885 875 865 850 835 810 780 710 560 - - ­H
M
L 1130 1115 1100 1090 1075 1035 995 965 930 895 860 795 730 - - ­H
M
L 1220 1215 1210 1295 1200 1180 1160 1130 1100 1060 1020 930 ---­H
M
L 1220 1215 1210 1295 1200 1180 1160 1130 1100 1060 1020 930 ---­H
M
L 2075 2050 2020 1995 1965 1940 1915 1885 1850 1820 1785 1720 1610 1505 1335 1175
H
M 2265 2235 2205 2175 2145 2110 2070 2035 2000 1960 1915 1825 1730 1605 1440 1260
L 2075 2050 2020 1995 1965 1940 1915 1885 1850 1820 1785 1720 1610 1505 1335 1175
Motor
Size
HP
6 x 8 1/10
6 x 8 1/10
9 x 7 1/6
9 x 7 1/6
9 x 7 1/5
9 x 7 1/3
10 x 10 1/2
10 x 10 1/2
10 x 10 1/2
11 x 10 1
11 x 10 1
0 0.05 0.10 0.15 0.20 0.25 0.30 0.35 0.40 0.45 0.50 0.60 0.70 0.80 0.90 1.00
480450440420410380360340330310300-----
440410400380370350330310300280270-----
480450440420410380360340330310300-----
845835825815800790775755735710680565----
620615610605600590580565550520490----­845835825815800790775755735710680565---­735730725715705700690675660630600485----
1085 1055 1030 1005 980 950 925 895 870 830 795 735 555 - - -
915 895 875 855 835 815 795 765 735 705 675 590 520 - - -
1290 1270 1245 1220 1190 1160 1125 1090 1055 1020 985 880 760 - - ­1100 1090 1075 1060 1045 1020 995 970 940 910 875 785 625 - - -
1665 1640 1610 1580 1550 1515 1480 1450 1415 1315 1215 1090 980 - - ­1465 1445 1425 1400 1375 1350 1325 1260 1190 1140 1090 990 890 - - -
2010 1975 1940 1905 1870 1825 1780 1735 1690 1640 1590 1470 1210 - - ­1670 1650 1630 1610 1590 1560 1530 1495 1460 1425 1390 1190 1080 - - -
2010 1975 1940 1905 1870 1825 1780 1735 1690 1640 1590 1470 1210 - - ­1670 1650 1630 1610 1590 1560 1530 1495 1460 1425 1390 1190 1080 - - -
2430 2400 2365 2330 2290 2255 2215 2180 2140 2095 2045 1945 1835 1715 1510 1330
2265 2235 2205 2175 2145 2110 2070 2035 2000 1960 1915 1825 1730 1605 1440 1260
2430 2400 2365 2330 2290 2255 2215 2180 2140 2095 2045 1945 1835 1715 1510 1330
Optional High Static PSC Motor
Blower
Blower
Model
Factory settings are in Bold
Air fl ow values are with dry coil and 1 in. MERV 4. For wet coil performance fi rst calculate the face velocity of the air coil (Face Velocity [fpm] = Airfl ow [cfm] / Face Area [sq ft]). Then for velocities of 200 fpm reduce the static capability by 0.03 in. wg, 300 fpm by 0.08 in. wg, 400 fpm by 0.12in. wg. and 500 fpm by 0.16 in. wg. * Denotes setting for 265 V operation.
024
030
036
042
048
Spd
H
M
L 910 905 900 895 885 875 865 850 835 810 780 710 560 - - ­H
M
L 880 880 880 880 875 870 860 840 820 800 775 730 480 - - ­H
M
L 1230 1230 1225 1215 1200 1165 1130 1095 1060 1035 1005 935 795 675 - ­H
M
L 1860 1835 1805 1780 1750 1715 1675 1635 1590 1540 1490 1260 1115 980 - ­H
M
L 1860 1835 1805 1780 1750 1715 1675 1635 1590 1540 1490 1260 1115 980 - -
Motor
Size
HP
9 x 7 1/3
9 x 7 1/2
10 x 10 1/2
10 x 10 3/4
10 x 10 3/4
0 0.05 0.10 0.15 0.20 0.25 0.30 0.35 0.40 0.45 0.50 0.60 0.70 0.80 0.90 1.00
1290 1270 1245 1220 1190 1160 1125 1090 1055 1020 985 880 760 - - -
1100 1090 1075 1060 1045 1020 995 970 940 910 875 785 625 - - -
1365 1340 1325 1305 1280 1250 1215 1180 1140 1100 1055 960 850 - - -
1040 1040 1035 1030 1020 1005 990 970 945 915 885 810 735 - - -
1930 1905 1875 1840 1805 1765 1725 1680 1635 1530 1425 1270 1150 1025 - -
1635 1620 1600 1580 1555 1530 1505 1465 1425 1335 1240 1135 1035 775 - -
2115 2075 2035 1980 1920 1900 1880 1840 1795 1730 1660 1390 1225 1070 - -
2005 1980 1950 1910 1865 1815 1765 1725 1685 1585 1485 1315 1140 1025 - -
2115 2075 2035 1980 1920 1900 1880 1840 1795 1730 1660 1390 1225 1070 - -
2005 1980 1950 1910 1865 1815 1765 1725 1685 1585 1485 1315 1140 1025 - -
Airfl ow (cfm) at External Static Pressure (in. wg)
Airfl ow (cfm) at External Static Pressure (in. wg)
3/16/12
3/16/12
Setting Blower Speed - PSC
CAUTION: Disconnect all power before performing this operation.
21
E
R
I
W
D
E
E
P
S
R
E
W
O
L
B
HIGH
PSC BLOWER MOTOR BODY
LOWMEDIUM
ENVISION2 COMPACT INSTALLATION MANUAL
Blower Performance Data cont.
5-Speed ECM - Single Speed
Motor
Motor
T’Stat
Blower
Model
Factory settings are in Bold
Air fl ow values are with dry coil and standard 1 in. fi lter
Spd
Tap
Cnct.
High 5
Med High 4 W 809 787 765 754 743 725 707 688 669 654 639 606 536 - - -
Med 3 727 715 703 682 661 638 616 601 587 561 536 485----
015
Med Low 2 Y1 699 675 652 631 611 594 577 551 525 490 455 -----
Low 1 G 656 604 552 530 508 493 479 436 394 350 - -----
High 5
Med High 4 W 809 787 765 754 743 725 707 688 669 654 639 606 536 - - -
018
Med 3 727 715 703 682 661 638 616 601 587 561 536 485----
Med Low 2 Y1 699 675 652 631 611 594 577 551 525 490 455 -----
Low 1 G 656 604 552 530 508 493 479 436 394 350 - -----
High 5 W
Med High 4 Y1 935 915 895 880 875 855 840 825 815 800 785 755 720 580 - -
024
Med 3 865 855 845 825 810 795 780 765 750 735 720 675 610 570 - -
Med Low 2 G 810 790 770 755 740 725 710 695 680 660 640 560 530 - - -
Low 1 695 645 595 575 550 520 495 455 420 400 - -----
High 5
Med High 4 W 1146 1134 1122 1111 1099 1085 1071 1062 1052 1042 1031 966 ----
030
Med 3 Y1 102310121001985969959949937925913901-----
Med Low 2 978 962 946 934 922 907 891 882 872 858 843 -----
Low 1 G 795777759748737718698686673650626-----
High 5 W
Med High 4 Y1 1413 1388 1363 1342 1321 1303 1285 1263 1240 1226 1212 1173 1016 946 - -
036
Med 3 1355 1325 1294 1276 1258 1235 1212 1188 1164 1144 1123 982 909 883 - -
Med Low 2 1336 1299 1261 1242 1222 1202 1181 1157 1132 1111 1090 937 874 830 - -
Low 1 G 1243 1182 1121 1061 1000 964 928 856 784 744 703 647 592 - - -
High 5
Med High 4 W 1799 1783 1767 1744 1720 1693 1666 1649 1631 1617 1603 1560 1530 1492 - -
042
Med 3 1694 1680 1666 1642 1617 1592 1567 1552 1537 1519 1500 1453 1421 1372 - -
Med Low 2 Y1 1575 1560 1540 1520 1502 1487 1471 1448 1424 1409 1393 1351 1308 1266 - -
Low 1 G 1454 1406 1358 1333 1308 1285 1261 1239 1217 1198 1179 1072 1002 988 - -
High 5
Med High 4 W 1799 1783 1767 1744 1720 1693 1666 1649 1631 1617 1603 1560 1530 1492 - -
048
Med 3 Y1 1694 1680 1666 1642 1617 1592 1567 1552 1537 1519 1500 1453 1421 1372 - -
Med Low 2 1575 1560 1540 1520 1502 1487 1471 1448 1424 1409 1393 1351 1308 1266 - -
Low 1 G 1454 1406 1358 1333 1308 1285 1261 1239 1217 1198 1179 1072 1002 988 - -
High 5 W
Med High 4 Y1 2081 2065 2048 2032 2015 1998 1980 1963 1946 1928 1910 1880 1849 1806 1767 1728
060
Med 3 1951 1931 1910 1889 1868 1850 1831 1812 1793 1774 1755 1722 1688 1654 1612 1562
Med Low 2 1812 1790 1767 1748 1728 1708 1688 1671 1654 1640 1626 1584 1547 1510 1472 1417
Low 1 G 1668 1651 1633 1612 1591 1566 1540 1525 1510 1491 1472 1433 1400 1351 1299 1208
High 5 W
Med High 4 Y1 2271 2248 2225 2205 2184 2166 2147 2129 2110 2094 2078 2039 2011 1977 1930 1846
070
Med 3 2133 2115 2096 2072 2047 2030 2013 1996 1979 1965 1950 1909 1873 1837 1793 1748
Med Low 2 2008 1985 1962 1939 1915 1898 1880 1862 1843 1828 1812 1774 1742 1703 1669 1635
Low 1 G 1806 1784 1761 1742 1722 1696 1669 1656 1642 1625 1607 1564 1527 1490 1443 1404
Motor
Size
HP
9 x 7 1/2
9 x 7 1/2
9 x 7 1/2
9 x 7 1/2
11 x 10 1/2
11 x 10 1
11 x 10 1
11 x 10 1
11 x 10 1
0 0.05 0.10 0.15 0.20 0.25 0.30 0.35 0.40 0.45 0.50 0.60 0.70 0.80 0.90 1.00
916 898 881 866 851 679 813 804 795 774 754
916 898 881 866 851 679 813 804 795 774 754 731 695 643 - -
1015 1003 990 975 955 945 935 920 905 890 880 850 825 745 - -
1407 1381 1354 1327 1300 1267 1233 1201 1168 1131 1094 1009 ----
1530 1503 1476 1453 1429 1413 1397 1376 1355 1342 1329 1276 1231 1173 - -
1934 1910 1886 1871 1855 1827 1799 1780 1760 1747 1734 1700 1659 1617 - -
1934 1910 1886 1871 1855 1827 1799 1780 1760 1747 1734 1700 1659 1617 - -
2230 2212 2193 2173 2152 2139 2125 2109 2092 2076 2059 2026 1992 1951 1892 1806
2472 2454 2435 2414 2393 2371 2349 2328 2306 2289 2271 2236 2189 2121 2033 1936
Airfl ow (cfm) at External Static Pressure (in. wg)
731 695 643 - -
11/20/12
About 5-Speed ECM Constant Torque Motors
The 5-speed ECM is a ‘Constant Torque’ ECM motor and delivers air fl ow similar to a PSC but operates as effi ciently as a variable speed ECM motor. Because it is an ECM motor, the 5-speed ECM can ramp slowly up or down like the variable speed ECM motor. There are 5 possible speed taps available on the 5-speed ECM motor with #1 being the lowest airfl ow and #5 being the highest airfl ow. These speed selections are preset at the time of manufacture and are easily changed in the fi eld if necessary.
If more than one tap are energized at the same time, built in logic gives precedence to the highest tap number and allows air fl ow to change with G, Y1, Y2 and W signals. Each of those 5 speeds has a specifi c ‘Torque’ value programmed into the motor for each speed selection. As static pressure increases,
airfl ow decreases resulting in less torque on the rotor. The motor responds only to changes in torque and adjusts its speed accordingly.
The 5-speed ECM motor is powered by line voltage but the motor speed is energized by 24VAC.
5-Speed ECM Benefi ts:
- High effi ciency
- Soft start
- 5 speeds with up to 4 speeds on-line
- Built in logic allows air fl ow to change with G, Y1, Y2 and W signals
- Super effi cient low airfl ow continuous blower setting (G)
22
ENVISION2 COMPACT INSTALLATION MANUAL
L
5
Blower Performance Data cont.
5-Speed ECM - Dual Capacity
Motor
Motor
T’stat
Blower
Model
Speed
Med High 4
026
Med Low 2
Med High 4
038
Med Low 2 1336 1299 1261 1242 1222 1202 1181 1157 1132 1111 1090 937 874 830 - -
Med High 4 1799 1783 1767 1744 1720 1693 1666 1649 1631 1617 1603 1560 1530 1492 - -
049
Med Low 2
Med High 4
064
Med Low 2
Med High 4
072
Med Low 2
Factory speed settings are in Bold
Air fl ow values are with dry coil and standard fi lter For wet coil performance fi rst calculate the face velocity of the air coil (Face Velocity [fpm] = Airfl ow [cfm] / Face Area [sq ft]). Then for velocities of 200 fpm reduce the static capability by 0.03 in. wg, 300 fpm by 0.08 in. wg, 400 fpm by 0.12in. wg., and 500 fpm by 0.16 in. wg. Highest setting is for auxiliary heat (W) and lowest setting is for constant blower (G). The “Y1” and “Y2” settings must be between the “G” and “W” settings.
Tap
High 5
Med 3 917 906 895 884 872 854 836 824 812 792 772 754 719 - - -
Low 1
High 5
Med 3
Low 1
High 5
Med 3
Low 1
High 5
Med 3 1951 1931 1910 1889 1868 1850 1831 1812 1793 1774 1755 1722 1688 1654 1612 1562
Low 1
High 5
Med 3 2133 2115 2096 2072 2047 2030 2013 1996 1979 1965 1950 1909 1873 1837 1793 1748
Low 1
Cnct.
W
Y2 1020 1006 991 980 968 950 932 922 911 894 876 849 812 - - -
Y1 836 824 812 794 776 765 754 735 715 703 691 653 631 - - ­G 735 721 707 687 666 653 640 622 603 589 574 533 - - - ­W
Y2 1413 1388 1363 1342 1321 1303 1285 1263 1240 1226 1212 1173 1016 946 - -
Y1 1355 1325 1294 1276 1258 1235 1212 1188 1164 1144 1123 982 909 883 - -
G 1243 1182 1121 1061 1000 964 928 856 784 744 703 647 592 - ­W
Y2 1694 1680 1666 1642 1617 1592 1567 1552 1537 1519 1500 1453 1421 1372 - -
Y1 1575 1560 1540 1520 1502 1487 1471 1448 1424 1409 1393 1351 1308 1266 - ­G 1454 1406 1358 1333 1308 1285 1261 1239 1217 1198 1179 1072 1002 988 - ­W
Y2 2092 2073 2054 2035 2015 1995 1975 1958 1940 1922 1904 1880 1843 1806 1767 1728
Y1 1812 1796 1780 1761 1741 1718 1695 1682 1668 1651 1633 1591 1555 1518 1480 1433 G 1682 1661 1640 1616 1591 1573 1555 1533 1510 1495 1480 1441 1400 1351 1316 1263 W
Y2 2271 2248 2225 2205 2184 2166 2147 2129 2110 2094 2078 2039 2011 1977 1930 1846
Y1 2008 1985 1962 1939 1915 1898 1880 1862 1843 1828 1812 1774 1742 1703 1669 1635 G 1806 1784 1761 1742 1722 1696 1669 1656 1642 1625 1607 1564 1527 1490 1443 1404
Motor
Size
HP
9 x 7 1/2
11 x 10 1/2
11 x 10 1
11 x 10 1
11 x 10 1
0 0.05 0.10 0.15 0.20 0.25 0.30 0. 35 0. 40 0.45 0.50 0.60 0.70 0.80 0. 90 1.00
1120 1109 1097 1082 1066 1055 1044 1028 1011 1001 991 932 839 - - -
1530 1503 1476 1453 1429 1413 1397 1376 1355 1342 1329 1276 1231 1173 - -
1934 1910 1886 1871 1855 1827 1799 1780 1760 1747 1734 1700 1659 1617 - -
2245 2360 2214 2315 2173 2290 2136 2275 2103 2250 2070 2032 1998 1957 1910 1825
2472 2360 2435 2315 2393 2290 2349 2275 2306 2250 2271 2236 2189 2121 2033 1936
Airfl ow (cfm) at External Static Pressure (in. wg)
3/16/12
Setting Blower Speed - 5-Speed ECM
5-speed ECM blower motors have fi ve (5) speeds of which three (3) are selectable on single speed and four (4) are selectable on dual capacity.
CAUTION: Disconnect all power before performing this operation.
-Speed ECM Motor Connections - Single Speed 5-Speed ECM Motor Connections - Dual Capacity
High Voltage
C - Black L - Orange
G - Green
G - Blue Y1 - Red
Connections
3/16 in.
C
GN
L
12
345
Low Voltage
Connections 1/4 in.
N - Brown
AUX - Gray
C - Black L - Orange
G - Green
G - Blue Y1 - Red
High Voltage Connections
3/16 in.
C
GN
345
12
Low Voltage
Connections 1/4 in.
N - Brown
AUX - Gray Y2 - Tan
23
ENVISION2 COMPACT INSTALLATION MANUAL
Blower Performance Data cont.
Variable Speed ECM Motor
Single Speed
Max
Model
015
018
024
030
036
036
w/1hp*
042
042
w/1hp*
048
048
w/1hp*
060
070
Blower
ESP
0.50 9 x 7 1/2
0.50 9 x 7 1/2
0.50 9 x 7 1/2
0.50 9 x 7 1/2
0.50 11 x 10 1/2
0.75 11 x 10 1
0.50 11 x 10 1/2
0.75 11 x 10 1
0.50 11 x 10 1/2
0.75 11 x 10 1
0.75 11 x 10 1
0.75 11 x 10 1
Dual Capacity
Max
Model
026
038
038
w/1hp*
049
049
w/1hp*
064
072
Factory settings are at recommended L-M-H DIP switch locations M-H settings MUST be located within boldface cfm range Lowest and Highest DIP switch settings are assumed to be L and H respectively cfm is controlled within ±5% up to the maximum ESP Max ESP includes allowance for wet coil and 1 in. MERV 4
Blower
ESP
0.50 9 x 7 1/2
0.50 11 x 10 1/2
0.75 11 x 10 1
0.50 11 x 10 1/2
0.75 11 x 10 1
0.75 11 x 10 1
0.75 11 x 10 1
Size
Size
Motor
hp
Motor
hp
123456789101112
300 400
300 400
400 500
400 500 600
650 750 850 1000
800 1000
650 800 900 1050
800 900 1000
650 800 900 1050 1150
800 900 1000 1200
800 950 1100 1300
800 950 1100 1300
123456789101112
400 500 600
650 750 850 1000
800 1000
L
650 800 900 1050 1150
800 900 1000 1200
L
800 950 1100 1300
800 950 1100 1300
500 600 700
L
500 600 700 800
L
L
L
L
1100 1300 1500 1600
L
L
L
L
L
MH
L
L
L
L
L
1100 1300 1500 1600
MH
L
MH
MH
600 700 800 900
MH
1200 1400 1600 1700 1850
MH
L
Airfl ow DIP Switch Settings
1000 1100 1200
700 800 900 1000 1100
MH
1100 1200 1300 1400 1500
MH
1800
1150 1250 1350 1450 1550
MH
2000 2200 2300 2400
1250 1350 1450 1550
MH
1400 1600 1700 1850
MH
1500 1750 1950 2100 2300
MH
1500 1750 1950 2100 2300
MH
Air Flow DIP Switch Settings
700 800 900 1000
MH
1100 1200 1300 1400 1500
MH
1800
1250 1350 1450 1550
MH
1400 1600 1700 1850
MH
1500 1750 1950 2100 2300
MH
1500 1750 1950 2100 2300
MH
2000 2200 2300 2400
1100 1200
2000 2200 2300 2400
1200
3/16/12
3/16/12
24
Blower Performance Data cont.
ENVISION2 COMPACT INSTALLATION MANUAL
Setting Blower Speed - Variable Speed ECM
The ABC board’s Yellow Confi g LED will fl ash the current variable speed ECM blower speed selections for low, med, and high continuously with a short pause in between. The speeds can also be confi rmed with the AID Tool under the Setup/ECM Setup screen. The variable speed ECM blower motor speeds can be fi eld adjusted with or without using an AID Tool.
Variable Speed ECM Setup without an AID Tool
The blower speeds for Low (G only), Med (Y1), and High (Y2/Aux) can be adjusted directly at the Aurora ABC board which utilizes the push button (SW1) on the ABC board. This procedure is outlined in the Variable Speed ECM Confi guration Mode portion of the Aurora ‘Base’ Control System section.
Variable Speed ECM Setup with an AID Tool
A much easier method utilizes the AID Tool to change the airfl ow using the procedure below. First navigate to the Setup screen and then select ECM Setup. This screen displays the current variable speed ECM settings. It allows the technician to enter the setup screens to change the variable speed ECM settings. Change the highlighted item using the and buttons and then press the button to select the item.
Variable Speed ECM Setup with an AID Tool cont.
ECM SPEED INFO
Selecting YES will enter variable speed ECM speed
LOW SPEED: 3 MED SPEED: 5 HIGH SPEED: 7
WANT TO CHANGE?
YES
OPTION ◄►NOENTER
setup, while selecting NO will return to the previous screen.
Variable Speed ECM Speed Setup - These screens allow the technician to select the low, medium, and high blower speed for the variable speed ECM blower motor. Change the highlighted item using the and buttons. Press the button to select the speed.
ECM SPEED INFO
1 2 <– LOW 3 4 5 6 7 8 9 10 11 12
OPTION ◄► ENTER
ECM SPEED INFO
1 2 LOW 3 4 5 <– MED 6 7 8 9 10 11 12
OPTION ◄► ENTER
ECM SPEED INFO
1 2 LOW 3 4 5 MED 6 7 8 9 10 11 12 <– HIGH
OPTION ◄► ENTER
After the high speed setting is selected the AID Tool will automatically transfer back to the ECM Setup screen.
25
ENVISION2 COMPACT INSTALLATION MANUAL
s
ff
OffOnOff
/
Y
A
Y1
T
r
Resisto

Wiring Schematics

Aurora Control 460/60/3 Variable Speed ECM
Compressor
T1
T3
Black (54) Blue (55) Red (56)
RA-B+
K4
Black (7) White (8) Red (9)
P7
Note 3
CC
Violet (14)
K2
Phase Guard Monitor (PGM)
L1 L2 L3
Dual
Capacity
Units Only
UltraTech
CS
Black (15)
RCP
Blue(16)
Blue(18)
CC2HICC2LOCC2
P5
G
K3
urora Base Control
(ABC)
LED4LED5
RS485 EXP
C
RA-B+C
Brown
Black (54)
Blue (55)
Red (56)
CC
24V
REVREV FP1 FP1 FP2 FP2 LPS LPS HPSHPS
P12
K1
CO
N/A
C
P6
Note 2
Isolation
Valve
213
Red (51)
Green
(50)
White
(52)
Y-OU T
Note 4
PGM
C
Yellow (91)
Y
Black/White (92)
Red (53)
Note 2
T2
YellowRed Black
T2T3
T1
CC
L2L3
L1
Blue
Black
460V
ransforme
24V
RS485 NET
Black/White
P9
P8
JW2
RS485 NET
Yellow
DH W Y2 Y1 G O/B C R LO R F FG CC CCG
P2
ES LS
ALM
K5
ALG ACC COM ACC NO ACC NC
LO R C
O/B G Y1
Y2
W
DH
P1
R
K6
F1
C
Orange
RV
RV
Orange (01)
Orange (02)
SW1
EH2CEH1
Unit Power Supply 460/60/3 w/Neutral
G
HPLP
Black (09)
Black (10)
Fault
R
30°F
RV – B/O Acc – Dip 1 Acc – Dip 2
Config
Green (93) Gray (94)
Black (95)
Yellow (96)
Red (97)
P4
Off
Note 1
Ground Neutral
Disconnect
L1 L1
L2 L2
L3 L3
Orange
R
Variable Speed
Blower Motor
G
PWM
16
Notes
Brown
P112 3 4 51
ECM
C1
C2
CFM
1 312 15 10
P12
Green
C
Black/White
R
Yellow
F
Violet (42)
Blue (24)
PWM CFM
Yellow (25)
C
Green/Yellow (28)
P13
On
1 2 3 4 5
1 – Optional, factory installed unit mounted disconnect.
6 7
2 – Optional, factory installed internal isolation valve.
8
SW2
3 – Optional, factory installed phase guard 4 – Optional, factory installed phase guard. The yellow transformer wire shall be connected directly to the CPU board, if this option is not installed.
PB3
N
L1
L2
L3

r

FD
T
Blue (07)
Yellow
Status
G
Blue (08)
FP1 – 15°F FP2 – 15°F/30°F
CC – Dual/Single
L – Pulse/Continuous
Reheat/Normal
CCG
Yellow
P3
Accessory Relay
Operation
Cycle with Blower Cycle with Compressor Water Valve Slow Open Outdoor Air Damper
Event
Random Start Delay Compressor On Delay Compressor Minimum On Time Compressor Short Cycle Delay Blower Off Delay Fault Recognition Delay – High Pressure Start-Up Bypass – Low Pressure Fault Recognition Delay – Low Pressure Start-Up Bypass – Low Water/Air Coil Limit Fault Recognition Delay – Low Water/Air Coil Limit Fault Recognition Delay – Condensate Overflow Thermostat Call Recognition Time Auxiliary Heat Staging Delay Emergency Heat Staging Delay Water Valve Slow Open Delay Reheat Delay
Gray (61)
SW2-4
On Off
Off On
RH
Gray (60)
SW2-5
On
Aurora Timing Events
Normal Mode
5 to 80 seconds 1 second
5 seconds < 1 second 2 minutes 5 seconds 4 minutes 15 seconds
30 seconds 2 seconds
Less than 1 second
2 minutes
30 seconds 30 seconds
2 minutes 30 seconds 30 seconds
2 seconds 2 seconds
5 minutes
2 minutes 90 seconds 90 seconds 30 seconds 30 seconds
Green
Test Mode
Less than 1 second
30 seconds
30 seconds 30 seconds 30 seconds
20 seconds
7.5 seconds
1
econd on and 1 second o
Slow Flash
100 milliseconds on and 100 milliseconds off
Fast Flash
100 milliseconds on and 400 milliseconds off with a 2 second pause before repeating
Flash Code
Random Start Delay
Status LED (LED1, Green) Configuration LED (LED2, Yellow) Fault LED (LED3, Red)
Status LED (LED1, Green)
Normal Mode Control is Non-Functional Test Mode Lockout Active Dehumidification Mode Reserved Reserved Load Shed ESD Reserved
ON
OFF Slow Flash Fast Flash
Flash Code 2 Flash Code 3 Flash Code 4 Flash Code 5 Flash Code 6 Flash Code 7
Aurora LED Flash Codes
Fast Flash Fast Flash Fast Flash
Configuration LED (LED2, Yellow)
No Software Overide Flash ECM Setting DIP Switch Overide Slow Flash ECM Configure Mode Fast Flash Reset Configure Mode Off
Brown (23)
Condensate
26
Fault LED (LED3, Red)
Normal Mode Input Fault Lockout High Pressure Lockout Low Pressure Lockout Low Air Coil Limit Lockout - FP2 Low Water Coil Limit Lockout - FP1 Reserved Condensate Overflow Lockout Over/Under Voltage Shutdown Reserved Reserved Air/Water Coil Limit Sensor Error
OFF Flash Code 1 Flash Code 2 Flash Code 3 Flash Code 4 Flash Code 5 Flash Code 6 Flash Code 7 Flash Code 8 Flash Code 9
Flash Code 10 Flash Code 11
Factory Low Voltage Wiring Factory Line Voltage Wiring Field Low Voltage Wiring Field Line Voltage Wiring Optional Block DC Voltage PCB Traces Field Zone Sensor Wiring Internal Junction Quick Connect Terminal
Field Wiring Lug
L1
Ground Relay Contacts – N.O., N.C.
Capacitor
Fuse
CC – Compressor Contactor CO – Condensate Overflow Sensor ES – Emergency Shutdown HP – High Pressure Switch LP – Low Pressure Switch FD – Freeze Detection Sensor F1 – Fuse
Legend
T
G
Y
R
SW1 – Push button SW2 – DIP package 8 position RB – Blower Relay RV – Reversing Valve Coil PGM – Phase Guard Monitor RH – Reheat Valve Coil
97P818-08 3/19/12
Thermistor
Relay Coil
Switch - Condensate Overflow Switch - High pressure
Switch - Low pressure
123
Polarized connector
Light Emitting Diode - Green
Light Emitting Diode - Yellow
Light Emitting Diode - Red
ENVISION2 COMPACT INSTALLATION MANUAL
Wiring Schematics cont.
Aurora Base Control 460/60/3 5-Speed ECM with Reheat
T1
Phase Guard Monitor (PGM)
L1 L2 L3
Note 2
Isolation
Valve
213
Red (51)
Green
(50)
White
Note 4
Red (9) White (8)
Black (7)
Note 5
PGM
Y-OUT
Y
C
Black/White (92)
Yellow (91)
(52)
Gray
(61)
Red (53)
Note 2
RH Gray (60)
P2
ES LS ALM ALG ACC COM ACC NO ACC NC
LO R C O/B G Y1 Y2 W DH
P1
R
Red
Yellow
CC2
EH1
K5-Alarm
T3
T2
Yellow
T2T3
CC
L2L3
L1
Blue
Blue
460V
460V
Transformer
24V
CCFC
Relay
K6-Acc Relay
RS485 NET
C
Green
Slow Flash Fast Flash Flash Code
Status LED (LED1, Green) Configuration LED (LED2, Yellow) Fault LED (LED3, Red)
Status LED (LED1, Green)
Normal Mode Control is Non-Functional Test Mode Lockout Active Dehumidification Mode Reserved Reserved Load Shed ESD Reserved
Black
T1
Green (93)
Black (95)
Yellow (96)
Red (97)
Black
Black
Black/White
Dual
Capacity
Units Only
UltraTech
CC
CS
Violet (14)
Black (15)
RCP
Blue(16)
Blue(18)
JW2
P9
Com2
LED5
G
RS485 NET
R-+
P8
1 second on and 1 second off 100 milliseconds on and 100 milliseconds off 100 milliseconds on and 400 milliseconds off with a 2 second pause before repeating
Random Start Delay
CC2HICC2LOCC2
R F FG CC CCG
K4-Fan Relay
K2-CC Relay
Aurora Base Control
Com1 LED5
G
P7
Fast Flash Fast Flash Fast Flash
Configuration LED (LED2, Yellow)
No Software Overide Flash ECM Setting
ON
DIP Switch Overide Slow Flash
OFF
ECM Configure Mode Fast Flash
Slow Flash
Reset Configure Mode Off
Fast Flash Flash Code 2 Flash Code 3 Flash Code 4 Flash Code 5 Flash Code 6 Flash Code 7
P5
G
K3-CC2 Relay
(ABC)
RS485 EXP
C
R-+C
Aurora LED Flash Codes
REVREV FP1 FP1 FP2 FP2 LPS LPSHPS HPS
K1-RV Relay
Test Mode
P6
Brown (23)
Condensate
Note 1
Ground Neutral
Disconnect
L1 L1
L2 L2
L3 L3
470
Resistor
RV
470
FD
RV
T
Orange (02)
Orange (01)
Yellow
Yellow
Status
SW1
LED3
G
EH2CEH1CCO
P3
Normal Mode Input Fault Lockout High Pressure Lockout Low Pressure Lockout Low Air Coil Limit Lockout - FP2 Low Water Coil Limit Lockout - FP1 Reserved Condensate Overflow Lockout Over/Under Voltage Shutdown Reserved Reserved Air/Water Coil Limit Sensor Error
HPLP
Blue (07)
Blue (08)
Black (09)
Black (10)
P4
Fault LED1
R
FP1 – 15°F/30°F FP2 – 15°F/30°F
RV – B/O Acc – Dip 4 Acc – Dip 5
CC – Dual/Single
L Output Type
Future Use
Config
LED2
Y
CCGY1
Fault LED (LED3, Red)
Brown
C
R
F1-3A
F
PWM CFM
C
P13
Off
SW2
Flash Code 1 Flash Code 2 Flash Code 3 Flash Code 4 Flash Code 5 Flash Code 6 Flash Code 7 Flash Code 8
Flash Code 9 Flash Code 10 Flash Code 11
On 1 2 3 4 5 6 7 8
Orange
Gray Tan Red Blue Black
OFF
Unit Power Supply
460/60/3
G
Black/White Yellow
Green
NG
X13 Fan
L
Motor
123
C45
Note 5
Accessory Relay
Operation
Cycle with Blower Cycle with Compressor Water Valve Slow Open Outdoor Air Damper
Event
Random Start Delay Compressor On Delay Compressor Minimum On Time Compressor Short Cycle Delay Blower Off Delay Fault Recognition Delay – High Pressure Start-Up Bypass – Low Pressure Fault Recognition Delay – Low Pressure Start-Up Bypass – Low Water/Air Coil Limit Fault Recognition Delay – Low Water/Air Coil Limit Fault Recognition Delay – Condensate Overflow Thermostat Call Recognition Time Auxiliary Heat Staging Delay Emergency Heat Staging Delay Water Valve Slow Open Delay Reheat Delay
SW2-5
SW2-4
On
On
Off
Off
Off
On Off On
Aurora Timing Events
Normal Mode
5 to 80 seconds 1 second
5 seconds < 1 second 2 minutes 5 seconds 4 minutes 15 seconds
30 seconds 2 seconds
Less than 1 second
2 minutes
30 seconds 30 seconds
2 minutes 30 seconds 30 seconds
2 seconds 2 seconds
5 minutes
2 minutes 90 seconds 90 seconds 30 seconds 30 seconds
Notes:
1 – Optional, factory installed unit mounted disconnect. 2 – Optional, factory installed internal isolation valve. 3 – Optional, factory installed phase guard 4 – Optional, factory installed phase guard. The yellow transformer wire shall be connected directly to the CPU board, if this option is not installed. 5 – Wire is provided with the unit but only connected to the X13 motor on dual capacity units.
Legend
Factory Low Voltage Wiring Factory Line Voltage Wiring Field Low Voltage Wiring Field Line Voltage Wiring Optional Block DC Voltage PCB Traces Field Zone Sensor Wiring Internal Junction Quick Connect Terminal
Field Wiring Lug
L1
Ground Relay Contacts – N.O., N.C.
Capacitor
Fuse
CC – Compressor Contactor CO – Condensate Overflow Sensor ES – Emergency Shutdown HP – High Pressure Switch LP – Low Pressure Switch FD – Freeze Detection Sensor F1 – Fuse
Thermistor
T
Relay Coil
Switch - Condensate Overflow Switch - High pressure
Switch - Low pressure
123
Polarized connector
Light Emitting Diode - Green
G
Light Emitting Diode - Yellow
Y
Light Emitting Diode - Red
R
SW1 – Push button SW2 – DIP package 8 position RB – Blower Relay RV – Reversing Valve Coil PGM – Phase Guard Monitor RH – Reheat Valve Coil
97P819-16 10/30/12
Test Mode
Less than 1 second
30 seconds
30 seconds 30 seconds 30 seconds
20 seconds
7.5 seconds
27
ENVISION2 COMPACT INSTALLATION MANUAL
A
A
N
/
CN/
C
S
ignal
Wiring Schematics cont.
Aurora Control and UPC
To ABC - P8
12345678
LON Network
Connections
Devices Must
Be Wired in Daisy Chain
Configuration
12
Service
LED1
LED2
Tx
LED3
Rx
LED4
Net
12
Optional LON
Add-On Module
LON OC
ECHELON
BACnet or N2
Network
Connections
Devices Must Be Wired in Daisy Chain Configuration
NET+
COM
NET-
NET+
NET-
COM
NET+ NET­COM
NET+ NET­N/C N/C
Signal
Orange
Red
White
Black
LED1
LED2
LON
ADAPTER
PORT
LED6
LED7
2W
4W
GND
GND
RNET+
LN+
LN-
RNET-
+12
+12V
/S
RNET LOCAL ACCESS
Blue
Green
Brown Yellow
POWER
GND
24 VAC
LED3
TX
RX
POWER
FORMAT BATT
Communication
Options
NOTE 1
TX
RX
LED4
LED5
RUN
ERR
12345678 ON
TEN’S
0
149
238
7
6
5 0
149
238
7
6
5
ONE’S
MAC Address Setting
GND
RNET+
RNET-
+12V
GND
RNET+
RNET-
+12V
12
ZS Sensor 2
Addr: 1
ZS Sensor 3
Addr: 2
ZS Sensor 1
Addr: 0
GND
RNET+
RNET-
+12V
ZS Sensor Information
Zone Sensors can be wired in daisy chain as show or in a star or hybrid configuration. Maximum of 5 sensors per UPC. Maximum allowable load 210mA. See the UPC install manual for possible sensor combinations.
DIP
Switch
Value
1 2 4
8
1234
Each ZS sensor must have a unique address, but the addresses do not need to be sequential. Use the DIP switches on the back of the ZS sensor to
ON
set an address from 0 to 4. (0 is the factory default.) Each DIP switch has the value shown in the figure to the left. Turn on as many DIP switches as you need so that their total value equals the address.
28
Notes
1. Use DIP Switches 5 – 8 to change communication protocol and DIP switches 1 – 2 to change BACnet baud rate
Legend
Factory Low Voltage Wiring Field Low Voltage Wiring
RJ45 Connector
12345678

Controls - Aurora Base Control

S
ENVISION2 COMPACT INSTALLATION MANUAL
Aurora ‘Base’ Control
Field Selectable Options via Hardware
DIP Switch (SW1) – Test/Configuration Button (See SW1
Operation Table)
Test Mode
The control is placed in the test mode by holding the push button switch SW1 for 2 - 5 seconds. In test mode most of the control timings will be shortened by a factor of sixteen (16). LED3 (green) will flash at 1 second on and 1 second off. Additionally, when entering test mode LED1 (red) will
NOTE: Refer to the Aurora Base Control Application and Troubleshooting Guide and the Instruction Guide: Aurora Interface and Diagnostics (AID) Tool for additional information.
flash the last lockout one time. Test mode will automatically time out after 30 minutes. Test mode can be exited by pressing and holding the SW1 button for 2 to 5 seconds or by cycling the power. NOTE: Test mode will automatically be exited after 30 minutes.
Control Features
oftware ABC Standard Version 2.0
Single or Dual Capacity Compressors
Either single or dual capacity compressors can be operated.
Variable Speed ECM Blower Motor Option
A Variable Speed ECM blower motor can be driven directly using the onboard PWM output. Four blower speeds are available based upon the G, Y1, Y2, and W input signals to the board. The blower speeds can be changed either by the ECM manual configurations mode method or by using the Aurora AID Tool directly. All four blower speeds can be set to the same speed if desired.
5-Speed ECM Blower Motor Option
A 5-Speed ECM blower motor will be driven directly using the thermostat connections. Any of the G, Y1, or Y2/W signals can drive any of the 5 available pre-programmed blower speeds on the motor. All 5 Series "G" vintage units will be wired this way at the factory.
Other Control Features
• Random start at power up
• Anti-short cycle protection
• High and low pressure cutouts
• Loss of charge
• Water coil freeze detection
• Air coil freeze detection
• Over/under voltage protection
• Condensate overflow sensor
• Load shed
• Dehumidification (where applicable)
• Emergency shutdown
• Hot gas reheat operation (where applicable)
• Diagnostic LED
• Test mode push button switch
• Two auxiliary electric heat outputs
• Alarm output
• Accessory output with N.O. and N.C.
• Modbus communication (master)
• Modbus communication (slave)
ECM Configuration Mode
The control is placed in the ECM configuration mode by holding the pushbutton switch SW1 for 5 to 10 seconds, the high, low, and “G” ECM speeds can be selected by following the LED display lights. LED2 (yellow) will fast flash when entering the ECM configuration. When setting “G” speed LED3 (green) will be continuously lit, for low speed LED1 (red) will be continuously lit, and for high speed both LED3 (green) and LED1 (red) will be continuously lit. During the ECM configuration mode LED2 (yellow) will flash each of the 12 possible blower speeds 3 times. When the desired speed is flashed press SW1, LED2 will fast flash until SW1 is released. “G” speed has now been selected. Next select low speed, and high speed blower selections following the same process above. After third selection has been made, the control will exit the ECM configuration mode. Aux fan speed will remain at default or current setting and requires the AID Tool for adjustment.
Reset Configuration Mode
The control is placed in reset configuration mode by holding the push button switch SW1 for 50 to 60 seconds. This will reset all configuration settings and the EEPROM back to the factory default settings. LED3 (green) will turn off when entering reset configuration mode. Once LED3 (green) turns off, release SW1 and the control will reset.
DIP Switch (SW2)
SW2-1 FP1 Selection – Low water coil temperature limit
setting for freeze detection. On = 30°F; Off = 15°F.
SW2-2 FP2 Selection – On = 30°F; Off = N/A SW2-3 RV – O/B - thermostat type. Heat pump
thermostats with “O” output in cooling or “B” output in Heating can be selected. On = O; Off = B.
SW2-4 Access Relay Operation (P2) and 2-5
Access Relay Operation SW2-4 SW2-5
Cycle with Blower ON ON
Cycle with Compressor OFF OFF
Water Valve Slow Opening ON OFF
Cycle with Comm. T-stat Hum Cmd OFF ON
29
ENVISION2 COMPACT INSTALLATION MANUAL
A
Controls - Aurora Base Control cont.
Cycle with Blower - The accessory relay will cycle with the blower output.
Cycle with Compressor - The accessory relay will cycle with the compressor output.
Water Valve Slow Opening - The accessory relay will cycle and delay both the blower and compressor output for 90 seconds.
SW2-6 CC Operation – selection of single or dual capacity
compressor. On = Single Stage; Off = Dual Capacity
SW2-7 Lockout and Alarm Outputs (P2) – selection of a
continuous or pulsed output for both the LO and ALM Outputs. On = Continuous; Off = Pulsed
SW2-8 Future Use
Alarm Jumper Clip Selection
From the factory, ALM is connected to 24 VAC via JW2. By cutting JW2, ALM becomes a dry contact connected to ALG.
ECM Blower Speeds
The blower speeds can be changed either by using the ECM manual configurations mode method or by using the Aurora AID Tool directly (see Instruction Guide: Aurora Interface and Diagnostics (AID) Tool topic).
Field Selectable Options via Software
(Selectable via the Aurora AID Tool)
ECM Blower Speeds
An ECM blower motor can be driven directly using the onboard PWM output. Four blower speeds are available, based upon the “G”, Y1 (low), Y2 (high), and Aux input signals to the board. The blower speeds can be changed either by the ECM manual configurations mode method (see ECM Configuration Mode topic) or by using the Aurora AID Tool directly. All four blower speeds can be set to the same speed if desired. Aux blower speed will remain at default or current setting and requires the AID Tool for adjustment.
Lockout – when locked out, the blower will operate continuously in “G” speed, and PSC blower motor output will remain on. The Alarm output (ALM) and Lockout output (L) will be turned on. The fault type identification display LED1 (Red) shall flash the fault code. To reset lockout conditions with SW2-8 On, thermostat inputs “Y1”, “Y2”, and “W” must be removed for at least 3 seconds. To reset lockout conditions with SW2-8 Off, thermostat inputs “Y1”, “Y2”, “W”, and “DH” must be removed for at least 3 seconds. Lockout may also be reset by turning power off for at least 30 seconds or by enabling the emergency shutdown input for at least 3 seconds.
Lockout With Emergency Heat - if the control is locked out in the heating mode, and a Y2 or W input is received, the control will operate in the emergency heat mode while the compressor is locked out. The first emergency heat output will be energized 10 seconds after the W input is received, and the blower will shift to high speed. If the control remains locked out, and the W input is present, additional stage of emergency heat will stage on after 2 minutes. When the W input is removed, all of the emergency heat outputs will turn off, and the ECM blower will shift to “G” speed and PSC blower motor output will remain on.
High Pressure – fault is recognized when the Normally Closed High Pressure Switch, P4-9/10 opens, no matter how momentarily. The High Pressure Switch is electrically in series with the Compressor Contactor and serves as a hard­wired limit switch if an overpressure condition should occur.
Low Pressure - fault is recognized when the Normally Closed Low Pressure Switch, P4-7/8 is continuously open for 30 seconds. Closure of the LPS any time during the 30 second recognition time restarts the 30 second continuous open requirement. A continuously open LPS shall not be recognized during the 2 minute startup bypass time.
Loss of Charge – fault is recognized when the Normally Closed Low Pressure Switch, P4-7/8 is open prior to the compressor starting.
Safety Features
The following safety features are provided to protect the compressor, heat exchangers, wiring and other components from damage caused by operation outside of design conditions.
Fuse – a 3 amp automotive type plug-in fuse provides protection against short circuit or overload conditions.
nti-Short Cycle Protection – 4 minute anti-short cycle
protection for the compressor.
Random Start – 5 to 80 second random start upon power up.
Fault Retry – in the fault condition, the control will stage off
the outputs and then “try again” to satisfy the thermostat Y input call. Once the thermostat input calls are satisfied, the control will continue on as if no fault occurred. If 3 consecutive faults occur without satisfying the thermostat Y input call, then the control will go to Lockout mode.
Condensate Overflow - fault is recognized when the impedance between this line and 24 VAC common or chassis ground drops below 100K ohms for 30 seconds continuously.
Freeze Detection (Coax) - set points shall be either 30°F or 15°F. When the thermistor temperature drops below the selected set point, the control shall begin counting down the 30 seconds delay. If the thermistor value rises above the selected set point, then the count should reset. The resistance value must remain below the selected set point for the entire length of the appropriate delay to be recognized as a fault. This fault will be ignored for the initial 2 minutes of the compressor run time.
Freeze Detection (Air Coil) - uses the FP2 input to protect against ice formation on the air coil. The FP2 input will operate exactly like FP1 except that the set point is 30 degrees and is not field adjustable.
30
S
Controls - Aurora Base Control cont.
ENVISION2 COMPACT INSTALLATION MANUAL
Over/Under Voltage Shutdown - An over/under voltage condition exists when the control voltage is outside the range of 18 VAC to 30 VAC. If the over/under voltage shutdown lasts for 15 minutes, the lockout and alarm relay will be energized. Over/under voltage shutdown is self­resetting in that if the voltage comes back within range of 18 VAC to 30 VAC for at least 0.5 seconds, then normal operation is restored.
Operation Description
Power Up - The unit will not operate until all the inputs and safety controls are checked for normal conditions. The unit has a 5 to 80 second random start delay at power up. Then the compressor has a 4 minute anti-short cycle delay after the random start delay.
tandby In standby mode, Y1, Y2, W, DH, and G are not active. Input O may be active. The blower and compressor will be off.
Heating Operation
Heating, 1st Stage (Y1) - The blower is started on “G” speed immediately and the compressor is energized 10 seconds after the Y1 input is received. The ECM blower motor is switched to low speed 15 seconds after the Y1 input.
Heating, 2nd Stage (Y1, Y2) - The compressor will be staged to full capacity 20 seconds after Y2 input is received. The ECM blower will shift to high speed 15 seconds after the Y2 input is received.
Heating, 3rd Stage (Y1, Y2, W) - The hot water pump is de­energized and the first stage of electric heat is energized 10 seconds after the W command is received. If the demand continues the second stage of electric heat will be energized after 5 minutes.
Emergency Heat (W) - The blower will be started on “G” speed, 10 seconds later the first stage of electric heat will be turned on. 5 seconds after the first stage of electric heat is energized the blower will shift to Aux speed. If the emergency heat demand is not satisfied after 2 minutes the second electric heat stage will be energized.
Blower (G) - The blower will start immediately upon receiving a thermostat G command. If there are no other commands from the thermostat the ECM will run on “G” speed until the G command is removed. Regardless of blower input (G) from the thermostat, the blower will remain on for 30 seconds at the end of each heating cycle.
Cooling Operation
In all cooling operations, the reversing valve directly tracks the O input. Thus, anytime the O input is present, the reversing valve will be energized.
Cooling, 1st Stage (Y1, O) - The blower is started on “G” speed immediately and the compressor is energized 10 seconds after the Y1 input is received. The ECM blower motor is switched to low speed 15 seconds after the Y1 input.
Cooling, 2nd Stage (Y1, Y2, O) - The compressor will be staged to full capacity 20 seconds after Y2 input is received. The ECM blower will shift to high speed 15 seconds after the Y2 input is received.
Blower (G) - The blower will start immediately upon receiving a thermostat G command. If there are no other commands from the thermostat the ECM will run on “G” speed until the G command is removed. Regardless of blower input (G) from the thermostat, the blower will remain on for 30 seconds at the end of each heating, cooling, and emergency heat cycle.
Dehumidification (Y1, O, DH or Y1, Y2, O, DH) - When a DH command is received from the thermostat during a compressor call for cooling the ECM blower speed will be reduced by 15% to increase dehumidification.
Emergency Shutdown - Four (4) seconds after a valid ES input, P2-7 is present, all control outputs will be turned off and remain off until the emergency shutdown input is no longer present. The first time that the compressor is started after the control exits the emergency shutdown mode, there will be an anti-short cycle delay followed by a random start delay. Input must be tied to common to activate.
Continuous Blower Operation - The blower output will be energized any time the control has a G input present, unless the control has an emergency shutdown input present. The blower output will be turned off when G input is removed.
Load Shed - The LS input disables all outputs with the exception of the blower output. When the LS input has been cleared, the anti-short cycle timer and random start timer will be initiated. Input must be tied to common to activate.
31
ENVISION2 COMPACT INSTALLATION MANUAL
1
2
Controls - Aurora Base Control cont.
Aurora ‘Base’ Control LED Displays
These three LEDs display the status, configuration, and fault codes for the control. These can also be read in plain English via the Aurora AID Tool.
Status LED (LED3, Green)
Description of Operation Fault LED, Green
Normal Mode ON Control is Non-functional OFF Test Mode Slow Flash Lockout Active Fast Flash Dehumidification Mode Flash Code 2 (Future Use) Flash Code 3 (Future Use) Flash Code 4 Load Shed Flash Code 5 ESD Flash Code 6 (Future Use) Flash Code 7
Configuration LED (LED2, Yellow)
Description of Operation Configuration LED, Yellow
No Software Overwritten Flashing ECM Setting DIP Switch was Overwritten Slow Flash ECM Configuration Mode Fast Flash
Fault LED (LED1, Red)
Red Fault LED
LED Flash
Code*
Lockout
Normal - No Faults OFF – Fault - Input 1 No Auto Fault - High Pressure 2 Yes Hard or Soft Fault - Low Pressure 3 Yes Hard or Soft Fault - Freeze Detection FP2 4 Yes Hard or Soft Fault - Freeze Detection FP1 5 Yes Hard or Soft Fault - Condensate Overflow 7 Yes Hard or Soft
ABC Basic Faults
Fault - Over/Under Voltage 8 No Auto Fault - FP1 & FP2 Sensor Error 11 Yes Hard or Soft
NOTE: All codes >11 use long flash for tens digit and short flash for the ones digit. 20, 30, 40, 50, etc. are skipped.
Reset/
Remove
Aurora Interface and Diagnostics (AID) Tool
The Aurora Interface and Diagnostics (AID) Tool is a device that is a member of the Aurora network. The AID Tool is used to troubleshoot equipment which uses the Aurora control via Modbus RTU communication. The AID Tool provides diagnostics, fault management, ECM setup, and system configuration capabilities to the Aurora family of controls. An AID Tool is recommended, although not required, for ECM airflow settings. The AID Tool simply plugs into the exterior of the cabinet in the AID Tool port.
ABC Control Board Layout
5.0 in.
On
o
F/30
FP1 – 15
o
F/30oF
FP2 – 15
RV – B/O ACC – Dip ACC – Dip
Reheat/Normal
Control
C
G
O/B
Field ConnectionsField Connections
C
G
O/B
Off
LED 2
o
1
F
2
YR
3
Config
4 5 6 7 8
SW2
Com1
Com2
W
Y1
Y2
DH
W
Y1
Y2
DH
LED 5
LED 4
3A-Fuse
P6
P7
G
P8
G
RR
EH1
P3
Factory
Exp
RS485
RS 485
RS485 NET
EH2 EH1
N/A
CO
(+) (-)
(+) (-)
C C
R C
R C
CC C
6.25 in.
C
CFM
PWM
HP HP LP
LP FP2 FP2 FP1 FP1 REV REV
CC2
G
LO
CC2
HI
CCG
CC
FG
F R
F
CC
G
Y1
P4
Factory
P5
Factory
JW2 - Alarm
P2
LS
ES
ECM PWM
P13
ALM
SW1 Test
RV – K1
CC – K2
CC Hi – K3
Fan – K4
Alarm – K5
Acc – K6
ALG
ACC c
ACC no
LED 3
Status
ACC nc
LED 1
Fault
CC – Dual/Single
G
L – Pulse/Continuous
AuroraTM Base
Factory Use
P11
P9
Factory Fan Connection
R
LO
P1
R
LO
5.75 in.
5.5 in.
32

Controls - UPC DDC Control (optional)

ENVISION2 COMPACT INSTALLATION MANUAL
Aurora UPC Controller ZS Series Sensors
The Aurora Unitary Protocol Converter (UPC) is designed to add-on to any Aurora based heat pump control. The Aurora Unitary Protocol Convertor (UPC) is designed to allow water source heat pumps to be integrated into Building Automation Systems (BAS) with ease. The Aurora UPC is an integrated solution and communicates directly with the Aurora Heat Pump Controls and allows access/control of a variety of internal Aurora heat pump operations such as sensors, relay operation, faults and other information. In turn, the UPC then converts internal Aurora Modbus protocol to BACnet MS/TP, LON, or N2 protocols and communicates to the BAS system. This provides the great benefit of complete control integration and a myriad of information available to the BAS from the heat pump control. Plus it also allows individual unit configuration such as ECM fan speeds or freeze protection setting directly over the BAS without the need for access to the actual heat pump. The Aurora UPC is programmed using the powerful Eikon object oriented.
The Aurora UPC is implemented with the Aurora Base Controller (ABC) heat pump control into our latest water source heat pumps. This will allow for a BAS to integrate
and communicate to the heat pump thru a choice of 3 different communication protocols. The Aurora UPC has the ability to communicate BACnet MS/TP, N2 open, or LonWorks (requires LON Plugin card). This flexibility is possible due to the onboard dipswitches which allow for the desired protocol and baud rate to be selected in the field. All zone temperatures and zone sensors are connected to the UPC on an RNet bus, simplifying hook up at the unit. RNet sensors can include a combination of zone temperature and humidity, CO2, and VOC sensors. The UPC includes built-in support for a custom configurable keypad/display unit - BACview6 (4-line by 40 character per line display) or BACview5 (2-line by 16 character per line display). Up to 2 Keypad/display units can be mounted remotely for configuration and troubleshooting.
There are an extensive number of points that the UPC has available over the network for integration into the BAS. Control programmers need to carefully determine which points they want to add into the BAS database. A list of the BACnet points, N2 points, and LON SNVTs are available along with their individual point descriptions by contacting the Commercial Solutions Group at 1-877-677-4420.
33
ENVISION2 COMPACT INSTALLATION MANUAL
Controls - UPC DDC Control (optional) cont.
N2
BAS
BACnet
LonWorks
Aurora UPC Features
• Rugged enclosure made of GE C2950 Cycoloy plastic
• Built-in surge transient protection circuitry
• Operating range of -20° to 140°F; 10 to 95% relative hu­midity, non-condensing
• Onboard CR123A battery has a life of 10 years with 720 hours of cumulative power outage
• Multi-Protocol field selectable communication port that supports:
• EIA-485 BACnet MS/TP @ 9600, 19.2k, 38.4k, 76.8k baud
• Metasys N2 Open
• LonWorks TP/FT-10 (Requires optional LON plug-in
communication card)
• Status of all unit operating conditions and fault lockouts
• Visual LED’s for status of power, network communication, processor operation, and errors
• Provides gateway into Aurora heat pump controls for unsurpassed control flexibility
• Network point for commanding unit into load shed
• Network point for commanding unit into
emergency shutdown
• Network points to assist in fan speed selection
• Network points for freeze protection settings
• Heating and cooling control from a remotely located zone sensor
• Rnet communication port which allows for multiple Rnet zone sensors (5) to be connected for space temperature averaging if desired.
• Local laptop or BACview connection for field service
• FCC, UL and CE listed. BTL Certification is pending
Modbus
Rnet
Aurora UPC Optional Features
• BACview handheld display, needed for field configuration of fan speeds, set points, etc.
• AID Tool for Aurora ABC configuration and troubleshooting.
• Aurora Advanced Control adds the Aurora AXB expansion board and provides added I/O and standard features
• Optional Sensor Kits (requires Aurora Advanced Control with AXB - Future Availability on Select Models/Configurations)
• Refrigeration Monitoring – provides Suction and
discharge pressure, Suction, liquid line temps and superheat and subcooling.
• Performance Monitoring – provides entering and
leaving loop water temperatures, loop flow rate as well as heat of extraction or rejection rate into the loop.
• Energy Monitoring – provides real-time power
measurement (Watt) of compressor, fan, auxiliary heat and zone pump.
• Graphics packages available in the future
34
ENVISION2 COMPACT INSTALLATION MANUAL
Controls - UPC DDC Control (optional) cont.
Port 1a is used to
communicate to the
Building Automation
System (BAS). This
port’s settings are
configured through
the onboard dip
switches.
Port 2 is used to com-
municate to the Au­rora Base Controller
(ABC).
Port 1b is used for the
LonWorks plugin.
24Vac
Dip switches for configuring the communication port protocol and baud rate for the BAS port.
Rnet port is used
for communicating
zone sensors.
BACview or local
laptop connection.
Aurora Touch Interface
Utilizing a touch-screen interface, the UPC provides a technician the ability to configure and diagnose equipment at the unit or from any room sensor for added accessibility and simpler troubleshooting. The technician will have full access to equipment status, parameter values, temperature, and humidity sensing as well as access to alarm and trend history. With website-like navigation, the Auora Touch Interface is easy to use and provides important insight into the system so your building can operate as efficiently as possible.
Mac address is set by 2 rotary dials.
35
ENVISION2 COMPACT INSTALLATION MANUAL
Controls - UPC DDC Control (optional) cont.
1. Leaving Air Temperature (LAT) Sensor – This 10 kOhm NTC sensor is factory installed on all UPC equipped heat pumps. It typically is attached to wiring inside the blower cabinet on the suction side of the blower. This sensor is attached on ABC FP2 pins available as LAT AU-30.
1. Compressor Proving Sensors – This optional factory installed current sensor is connected to confirm compressor operation via the power wires. The sensor is attached at ABC Y1 and available at point BV-65.
1. Valve End Switch – This optional input is setup for a field installed flow valve end switch. This end switch input is attached at ABC Y2 and available at point BV-67.
1. Fan Proving Sensors – This optional factory installed current sensor is connected to confirm fan operation via the power wires. The sensor is attached at ABC G and available at point BV-33.
1. Occupancy Sensor - This standard feature includes a field installed and wired room sensor with occupancy sensor typically found in DDC systems. The RNet room sensors can be found thru your commercial representative. The occupancy Sensors are attached at ABC 0 and can be found at point BV-49.
1. Dirty Filter Switch –
This optional field installed switch is connected to confirm dirty filter operation. The dirty filter switch can be found thru your commercial representative. The sensor is attached at ABC W and available at point BV-63.
2. Fault, Configuration, and Status Codes – The codes can be visible to the BAS if desired
Aurora Base Fault Codes (ABC Only)
Fault LED (LED1, Red)
Red Fault LED
Normal - No Faults OFF – Fault - Input 1 No Auto Fault - High Pressure 2 Yes Hard or Soft Fault - Low Pressure 3 Yes Hard or Soft Fault - Freeze Detection FP2 4 Yes Hard or Soft Fault - Freeze Detection FP1 5 Yes Hard or Soft Fault - Condensate Overflow 7 Yes Hard or Soft
ABC Basic Faults
Fault - Over/Under Voltage 8 No Auto Fault - FP1 & FP2 Sensor Error 11 Yes Hard or Soft
NOTE: All codes >11 use long flash for tens digit and short flash for the ones digit. 20, 30, 40, 50, etc. are skipped.
LED Flash
Code*
Lockout
Reset/
Remove
Aurora Advanced Fault Codes (ABC + AXB Expansion Board)
Fault LED (LED1, Red)
Red Fault LED
Normal - No Faults Off ­Fault-Input 1 No Auto Tstat input error. Autoreset upon condition removal. Fault-High Pressure 2 Yes Hard or Soft HP switch has tripped (>600 psi) Fault-Low Pressure 3 Yes Hard or Soft Low Pressure Switch has tripped (<40 psi for 30 continuous sec.) Fault-Freeze Detection FP2 4 Yes Hard or Soft Freeze protection sensor has tripped (<15 or 30 degF for 30 continuous sec.) Fault-Freeze Detection FP1 5 Yes Hard or Soft Freeze protection sensor has tripped (<15 or 30 degF for 30 continuous sec.) Fault-Condensate Overflow 7 Yes Hard or Soft Condensate switch has shown continuity for 30 continuous sec.
ABC Basic Faults
Fault-Over/Under Voltage 8 No Auto Instantaneous voltage is out of range. **Controls shut down until resolved. Fault-FP1 & 2 Snsr Error 11 Yes Hard or Soft If FP1 or 2 Sensor Error Fault-Compressor Monitor 10 Yes Hard or Soft Open Crkt, Run, Start or welded cont Non-CriticAXBSnsrErr 13 No Auto Any Other Sensor Error CriticAXBSnsrErr 14 Yes Hard or Soft Sensor Error for EEV or HW Alert-HotWtr 15 No Auto HW over limit or logic lockout. HW pump deactivated. Fault-VarSpdPump 16 No Auto Alert is read from PWM feedback. Not Used 17 No Auto IZ2 Com Fault. Autoreset upon condition removal. Non-CritComErr 18 No Auto Any non-critical com error Fault-CritComErr 19 No Auto Any critical com error. Auto reset upon condition removal Alarm - Low Loop Pressure 21 No Auto Loop pressure is below 3 psi for more than 3 minutes Alarm - Home Automation 1 23 No Auto Closed contact input is present on Dig 2 input - Text is configurable
ABC & AXB Advanced Faults
Alarm - Home Automation 2 24 No Auto Closed contact input is present on Dig 3 input - Text is configurable
NOTES: *All codes >11 use long flash for tens digit and short flash for the ones digit. 20, 30, 40, 50 etc. are skipped! Alert’ is a noncritical sensor or function that has failed. Normal operation of the heat pump is maintained but service is desired at some point.
LED Flash
Code *
Lockout
Reset/
Remove
Fault Condition Summary
36
ENVISION2 COMPACT INSTALLATION MANUAL
Controls - UPC DDC Control (optional) cont.
Aurora Base or Advanced Control Configuration and Status Codes
Status LED (LED3, Green)
Description of Operation Fault LED, Green
Normal Mode ON Control is Non-functional OFF Test Mode Slow Flash Lockout Active Fast Flash Dehumidification Mode Flash Code 2 Load Shed Flash Code 5 Emergency Shutdown Flash Code 6 On Peak Mode Flash Code 7 (Future Use) Flash Code 8 (Future Use) Flach Code 9
Configuration LED (LED2, Yellow)
Description of Operation Configuration LED, Yellow
No Software Overwritten ECM Setting DIP Switch Overwritten Slow Flash ECM Configuration Mode Fast Flash Reset Configuration Mode OFF
9. Alarm Relay – The Alarm relay (ALM) is factory connected to 24 VAC via jumper JW2. By cutting JW2, ABC ALM becomes a dry contact connected to ABC ALG. The Relay is field switchable between Factory setting as an Alarm output or available for other uses.
10. Accessory Relay1 –
A configurable, accessory relay on the ABC is provided that can be cycled with the compressor, blower, or the Dehumidifier (DH) input. A third (factory) setting cycles the relay with the compressor but delays the compressor and blower output for 90 sec. Source pump or slow opening solenoid valves in well systems or variable speed primary pumping systems would be a prime use of this feature.
Access Relay Operation SW2-4 SW2-5
Cycle with Blower ON ON
Cycle with Compressor OFF OFF
Water Valve Slow Opening ON OFF
Cycle with Comm. T-stat Hum Cmd OFF ON
11.
Electric Heat EH1 – A digital 24VDC output is provided
for electric heat powering. UPC’s Default programming has EH1 set for AUX/ELEC Heat operation and will be controlled using the UPC’s internal P.I.D. logic. However it can be changed by the BAS to be network controlled.
12. Electric Heat EH2 – A digital VDC output is provided for field options converted from the original EH2 output. Default UPC program has the EH2 output set for Network Control but can be changed by the BAS to be controlled by the UPC’s internal P.I.D. logic.
37
ENVISION2 COMPACT INSTALLATION MANUAL
2
3
Controls - UPC DDC Control (optional) cont.
Aurora Advanced Control Configuration and Options (Future Availability on Select Models/Configurations)
1. Accessory Relay2 – A second, configurable, accessory relay on the AXB is provided that can be cycled with the compressor 1 or 2 , blower, or the Dehumidifier (DH) input. This is to complement the Accessory 1 Relay on the ABC board.
Position DIP 4 DIP 5 Description
1 ON ON Cycles with Fan or ECM (or G)
2 OFF ON
3 ON OFF
4 OFF OFF Cycles with DH input from ABC board
. Analog Out – A standard 0-10VDC analog output is
provided. This output can be used to drive modulat­ing dampers etc.
. Variable Speed Pump or Modulating Water Valve
- This input and output are provided to drive and
monitor a variable speed pump. The VS pump output is a PWM signal to drive the variable speed pump. The minimum and maximum level are set using the AID Tool. 75% and 100% are the default settings respec­tively. The VS data input allows a separate PWM signal to return from the pump giving fault and performance information. Fault received from the variable speed pump will be displayed as E16. Modulating Water Valve - This Variable speed PWM output is provided to optionally drive a modulating water valve. Through ad­vanced design a 0-10VDC valve can be driven directly from the VS pump output. The minimum and maxi­mum level are set in the same way as the VS pump using the AID Tool. 75% and 100% are the default set­tings respectively.
4. Loop Pump Slaving - This input and output are pro­vided so that two units can be slaved together with a common flow center. When either unit has a call for loop pump, both unit’s loop pump relays and variable speed pumps are energized. The flow center then can simply be wired to either unit. The output from one unit should be routed to the input of the other. If daisy chained up to 16 heat pumps can be wired and slaved together in this fashion.
Cycles with CC1 first stage of compressor
or compressor spd 1-12
Cycles with CC2 second stage of
compressor or compressor spd 7-12
38
ENVISION2 COMPACT INSTALLATION MANUAL
2
Controls - UPC DDC Control (optional) cont.
Aurora Advanced Control Optional Sensor Kits (Future Availability on Select Models/Configurations)
1. Energy Monitoring (Standard Sensor Kit on ‘Advanced’ models) - The Energy Monitoring Kit
includes two current transducers (blower and electric heat) added to the existing two compressor sensors so that the complete power usage of the heat pump can be measured. The BACview Tool provides configuration detail for the type of blower motor and a line voltage calibration procedure to improve the accuracy. This real time power usage information can be displayed on the AID Tool and is available thru network points when using BACnet or N2 Open.
Compressor Current 1
Compressor Current 2
• Fan Current
Aux Heat Current
• Pump Selection
• Voltage
• Compressor Watts
• Fan Watts
Aux Heat Watts
Pump Watts (VS Only)
. Refrigerant Monitoring (optional sensor kit) - The
optional Refrigerant Monitoring Kit includes two pressure transducers, and three temperature sensors, heating liquid line, suction temperature and existing cooling liquid line (FP1). These sensors allow the measurement of discharge and suction pressures, suction and liquid line temperatures as well as superheat and subcooling. This information can be displayed on the BACview Tool, or the network when using BACnet and N2.
Htg Liquid Line
Clg Liquid Line
• Discharge pressure
• Suction Pressure
Discharge Saturated Temp
Suction Saturated Temperature
• Superheat
• SubCooling
3. Performance Monitoring (optional sensor kit) - The optional Performance Monitoring Kit includes: three temperature sensors, entering and leaving water, leaving air temperature and a water flow rate sensor. With this kit, heat of extraction and rejection will be calculated. This requires configuration using the BACview
Leaving Air Temperature (supply)
Alt Leaving Air Temperature (Supply)
Entering Water Temperature
Leaving Water Temperature
Water Flow Meter
Entering Air Temperature (from zone sensor)
Brine Selection (water/antifreeze)
Heat of Extraction/Rejection
Tool for selection of water or antifreeze.
39
ENVISION2 COMPACT INSTALLATION MANUAL
Controls - UPC DDC Control (optional) cont.
ZS Series RNet Sensor Overview
The ZS Series line of intelligent zone sensors provides the function and flexibility you need to manage the conditions important to the comfort and productivity of the zone occupants. The ZS sensors are available in a variety of zone sensing combinations to address your application needs. These combinations include temperature, relative humidity, and indoor air quality (carbon dioxide or VOCs (Volatile Organic Compounds)). They are built to be flexible allowing for easy customization of what the user/ technician sees. Designed to work with the Aurora UPC controllers the ZS sensor line includes the ZS Base, ZS Plus, ZS Pro and ZS Pro-F.
The UPC uses a proprietary communication called Rnet to receive the space temperature from the zone sensor.
ZS Base
ZS Plus ZS Pro
This is done using (2) 18 AWG twisted pair unshielded cables for a total of 4 wires connected to the Rnet port. The sensor gets its power from the UPC controller and connecting multiple sensors to one UPC will allow for space temperature averaging. The UPC can support one ZS Pro or ZS Pro F with up to four ZS standard sensors wired to the Rnet port on the UPC for a total of 5 zone sensors. The sensors use a precise 10k ohm thermistor with less than 0.18°F drift over a ten year span, this allows for less maintenance or re-calibration after installation. The sensors also have a hidden communication port for connecting a BACview or local laptop that provides access to the equipment for commissioning and maintenance. The table below shows the features of each of the four sensors that are currently available.
ZS Pro-F
Features ZS Base ZS Plus ZS Pro ZS Pro-F
2
Temp, CO
Neutral Color
Addressable/supports daisy chaining
Hidden communication port
Mounts on a standard 2” by 4” electrical box
Occupancy Status indicator LED
Push button occupancy override
Setpoint adjust
Large, easy to read LCD
Alarm indicator
°F to °C conversion button
Options Part Number Part Number Part Number Part Number
Temperature Only ZSU ZSUPL ZSUP ZSUPF
Temp with CO
Temp with Humidity ZSU-H ZSUPL-H ZSUP-H ZSUPF-H
Temp with Humidity, CO
Temp, Humidity, VOC ZSU-HV ZSUPL-HV ZSUP-HV ZSUPF-HV
Temp with VOC ZSU-V ZSUPL-V ZSUP-V ZSUPF-V
, Humidity, and VOC Options
2
2
√√√√
√√√√
√√√√
√√√√
√√√√
√√√
√√√
√√√
√√
√√
ZSU-C ZSUPL-C ZSUP-C ZSUPF-C
ZSU-HC ZSUPL-HC ZSUP-HC ZSUPF-HC
40
ENVISION2 COMPACT INSTALLATION MANUAL
Controls - UPC DDC Control (optional) cont.
RNet Sensor Physical and Electrical Data
Sensing Element Range Accuracy
Temperature (on non-Humidity models) -4° to 122° F (-20° C to 50° C) ±0.35° F (0.2° C)
Temperature (on Humidity models) 50° F to 104° F (10° C to 40° C) ±0.5° F (0.3° C)
Humidity 10% to 90% ±1.8% typical
CO2
VOC 0 to 2,000 PPM ±100 PPM
Power Requirements Sensor Type Power Required
Temperature Only All Models 12 Vdc @ 8 mA
Temperature with Humidity All Models
Temp with VOC, or Temp/VOC/Humidity All Models 12 Vdc @ 60 mA
Temp with CO2 , or Temp/ CO2/Humidity All Models
Power Supply
Communication
Local Access Port
Environmental Operating Range
Mounting Dimensions
400 to 1250 PPM
1250 to 2000 PPM
A controller supplies the Rnet sensor network with 12 Vdc @ 210 mA. Additional
power may be required for your application. See sensor ZS Installation Guide
115 kbps Rnet connection between sensor(s) and controller
15 sensors max per Rnet network; 5 sensors max per control program
For connecting a laptop computer to the local equipment for maintenance and commissioning
32° to 122° F (0° - 50° C), 10% to 90% relative humidity, non-condensing
Standard 4”x 2” electrical box using provided 6/32” x 1/2” mounting screws
±30PPM or +/-3% of reading (greater of two)
±5% of reading plus 30 PPM
12 Vdc @ 15 mA (idle) to 190 mA
(CO2 measurement cycle)
12 Vdc @ 15 mA (idle) to 190 mA
(CO2 measurement cycle)
41
ENVISION2 COMPACT INSTALLATION MANUAL

Unit Startup

Before Powering Unit, Check The Following:
NOTE: Remove and discard the compressor shipping bolts. The bolts can then be discarded.
• High voltage is correct and matches nameplate.
• Fuses, breakers and wire size correct.
• Low voltage wiring complete.
• Piping completed and water system cleaned and flushed.
• Air is purged from closed loop system.
• Isolation valves are open, water control valves or loop pumps wired.
• Condensate line open and correctly pitched.
• Transformer switched to 208V if applicable.
• Dip switches are set correctly.
• Blower rotates freely – foam shipping support has been removed.
• Blower speed correct.
• Air filter/cleaner is clean and in position.
• Service/access panels are in place.
• Return air temperature is between 50-80°F heating and 60-95°F cooling.
• Check air coil cleanliness to insure optimum performance. Clean as needed according to maintenance guidelines. To obtain maximum performance the air coil should be cleaned before startup. A 10-percent solution of dishwasher detergent and water is recommended for both sides of coil, a thorough water rinse should follow.
Startup Steps
NOTE: Complete the Equipment Start-Up/Commissioning Check Sheet during this procedure. Refer to thermostat
operating instructions and complete the startup procedure.
1. Initiate a control signal to energize the blower motor. Check blower operation.
2. Initiate a control signal to place the unit in the cooling mode. Cooling setpoint must be set below room temperature.
3. Cooling will energize after a time delay. Check for correct rotation of scroll compressors in 3 phase applications. Incorrect rotation will cause low refrigerant pressures and possibly unusual noise. Switch any two power leads at the line voltage supply.
4. Be sure that the compressor and water control valve or loop pump(s) are activated.
5. Verify that the water flow rate is correct by measuring the pressure drop through the heat exchanger using the P/T plugs and comparing to the pressure drop table.
6. Check the temperature of both the supply and discharge water (Refer to Operating Parameters tables).
7. Check for an air temperature drop of 15°F to 25°F across the air coil, depending on the blower speed and entering water temperature.
8. Decrease the cooling set point several degrees and verify high-speed blower operation (variable speed ECM only).
9. Adjust the cooling setpoint above the room temperature and verify that the compressor and water valve or loop pumps deactivate.
10. Initiate a control signal to place the unit in the heating mode. Heating set point must be set above room temperature.
11. Heating will energize after a time delay.
12. Check the temperature of both the supply and discharge water (Refer to Unit Operating Parameters tables).
13. Check for an air temperature rise of 20°F to 35°F across the air coil, depending on the blower speed and entering water temperature.
14. If auxiliary electric heaters are installed, increase the heating setpoint until the electric heat banks are sequenced on. All stages of the auxiliary heater should be sequenced on when the thermostat is in the Emergency Heat mode. Check amperage of each element.
15. Adjust the heating setpoint below room temperature and verify that the compressor and water valve or loop pumps deactivate.
16. During all testing, check for excessive vibration, noise or water leaks. Correct or repair as required.
17. Set system to desired normal operating mode and set temperature to maintain desired comfort level.
18. Instruct the owner/operator in the proper operation of the thermostat and system maintenance.
NOTE: Be certain to fill out and forward all warranty registration papers.
42

Operating Limits

ENVISION2 COMPACT INSTALLATION MANUAL
Operating Limits
Air Limits
Min. Ambient Air 45 7.2 45 7.2 Rated Ambient Air 80 26.7 70 21.1 Max. Ambient Air 100 37.8 85 29.4 Min. Entering Air 50 10.0 40 4.4 Rated Entering Air db/wb 80.6/66.2 27/19 68 20.0 Max. Entering Air db/wb 110/83 43/28.3 80 26.7
Water Limits
Min. Entering Water 30 -1.1 20 -6.7 Normal Entering Water 50-110 10-43.3 30-70 -1.1 Max. Entering Water 120 48.9 90 32.2
Cooling Heating
(°F) (°C) (°F) (°C)

Operating Parameters

Single Speed Models
Entering Water
Temp °F
30
50
70
90
110
Water Flow
gpm/ton
1.5 115 - 125 150 - 170 20 - 35 10 - 17 17 - 22 17 - 23
3.0 105 - 120 130 - 145 20 - 35 10 - 17 8 - 10 17 - 23
1.5 130 - 140 215 - 235 12 - 20 8 - 14 16 - 22 17 - 23
3.0 128 - 138 190 - 210 12 - 20 8 - 14 8 - 12 17 - 23
1.5 138 - 148 280 - 310 10 - 16 10 - 16 15 - 21 17 - 23
3.0 136 - 146 250 - 280 10 - 16 8 - 14 7 - 13 17 - 23
1.5 145 - 155 350 - 380 9 - 14 10 - 16 14 - 20 17 - 23
3.0 143 - 153 320 - 350 9 - 14 8 - 14 6 - 10 17 - 23
1.5 145 - 155 420 - 450 9 - 14 10 - 16 14 - 20 17 - 23
3.0 143 - 153 405 - 435 9 - 14 8 - 14 6 - 10 17 - 23
Suction Pressure
psig
Discharge Pres-
sure psig
NOTE: Minimum/maximum limits are only for start-up conditions, and
are meant for bringing the space up to occupancy temperature. Units are not designed to operate at the minimum/maximum conditions on a regular basis. The operating limits are dependant upon three primary factors: 1) water temperature, 2) return air temperature, and 3) ambient temperature. When any of the factors are at the minimum or maximum levels, the other two factors must be at the normal level for proper and reliable unit operation.
Cooling -- No Hot Water Generation
Superheat Subcooling
Water Temp Rise °FAir Temp Drop
°F DB
Entering Water
Temp °F
30
50
70
90
110
NOTE: Cooling performance based on entering air temperatures of 80º F DB, 67º F WB.
Heating performance based on entering air temperature of 70º F DB.
Water Flow
gpm/ton
1.5 73 - 85 270 - 305 8 - 14 3 - 10 6 - 10 15 - 21
3.0 77 - 90 280 - 315 8 - 14 3 - 10 4 - 8 17 - 23
1.5 97 - 110 290 - 325 10 - 16 3 - 10 9 - 13 22 - 28
3.0 102 - 115 300 - 335 10 - 16 3 - 10 7 - 11 24 - 30
1.5 130 - 145 320 - 355 13 - 19 3 - 10 10 - 14 30 - 36
3.0 135 - 150 325 - 360 13 - 19 3 - 10 8 - 12 32 - 38
1.5 150 - 160 350 - 390 13 - 19 3 - 10 10 - 14 30 - 36
3.0 155 - 165 365 - 405 13 - 19 3 - 10 8 - 12 32 - 38
1.5
3.0
Suction Pressure
psig
Discharge Pres-
sure psig
Heating - No Hot Water Generation
Superheat Subcooling
Water Temp Drop °FAir Temp Rise
°F DB
2/15/12
43
ENVISION2 COMPACT INSTALLATION MANUAL
Operating Parameters cont.
Dual Capacity Models
First Stage Operation
Entering Water
Temp °F
30
50
70
90
110
Water Flow
gpm/ton
1.5 105 - 120 140 - 155 20 - 35 9 - 17 17 - 21 17 - 23
3.0 100 - 115 115 - 130 20 - 35 9 - 17 8 - 12 17 - 23
1.5 125 - 140 205 - 225 12 - 20 8 - 14 17 - 21 17 - 23
3.0 120 - 135 180 - 200 12 - 20 8 - 14 8 - 12 17 - 23
1.5 135 - 145 280 - 290 10 - 16 8 - 14 16 - 20 17 - 23
3.0 133 - 143 250 - 260 10 - 16 8 - 14 9 - 13 17 - 23
1.5 142 - 152 345 - 355 8 - 12 8 - 14 14 - 20 17 - 23
3.0 140 - 150 330 - 340 8 - 12 8 - 14 8 - 12 17 - 23
1.5 152 - 158 405 - 435 8 - 12 8 - 14 14 - 20 17 - 23
3.0 148 - 153 390 - 420 8 - 12 8 - 14 8 - 12 17 - 23
Suction Pressure
psig
Discharge Pres-
sure psig
Cooling -- No Hot Water Generation
Superheat Subcooling
Water Temp Rise °FAir Temp Drop
°F DB
Entering Water
Temp °F
30
50
70
90
110
NOTE: Cooling performance based on entering air temperatures of 80º F DB, 67º F WB.
Heating performance based on entering air temperature of 70º F DB.
Water Flow
gpm/ton
1.5 76 - 84 270 - 285 8 - 12 3 - 10 5 - 9 12 - 16
3.0 80 - 88 275 - 290 8 - 12 3 - 10 3 - 7 14 - 18
1.5 100 - 115 280 - 310 10 - 14 3 - 10 7 - 11 18 - 22
3.0 105 - 120 290 - 315 10 - 14 3 - 10 5 - 9 20 - 24
1.5 135 - 150 310 - 325 12 - 16 3 - 10 8 - 12 24 - 28
3.0 140 - 155 315 - 330 12 - 16 3 - 10 6 - 10 22 - 30
1.5 155 - 165 330 - 370 12 - 16 3 - 10 8 - 12 24 - 28
3.0 160 - 170 340 - 380 12 - 16 3 - 10 6 - 10 22 - 30
1.5
3.0
Suction Pressure
psig
Discharge Pres-
sure psig
Heating -- No Hot Water Generation
Superheat Subcooling
Second Stage Operation
Entering Water
Temp °F
30
50
70
90
110
Water Flow gpm/
ton
1.5 115 - 125 150 - 170 20 - 35 10 - 17 17 - 22 17 - 23
3.0 105 - 120 130 - 145 20 - 35 10 - 17 8 - 10 17 - 23
1.5 130 - 140 215 - 235 12 - 20 8 - 14 16 - 22 17 - 23
3.0 128 - 138 190 - 210 12 - 20 8 - 14 8 - 12 17 - 23
1.5 138 - 148 280 - 310 10 - 16 10 - 16 15 - 21 17 - 23
3.0 136 - 146 250 - 280 10 - 16 8 - 14 7 - 13 17 - 23
1.5 145 - 155 350 - 380 9 - 14 10 - 16 14 - 20 17 - 23
3.0 143 - 153 320 - 350 9 - 14 8 - 14 6 - 10 17 - 23
1.5 145 - 155 420 - 450 9 - 14 10 - 16 14 - 20 17 - 23
3.0 143 - 153 405 - 435 9 - 14 8 - 14 6 - 10 17 - 23
Suction Pressure
psig
Discharge Pres-
sure psig
Cooling -- No Hot Water Generation
Superheat Subcooling
Water Temp Drop °FAir Temp Rise
°F DB
2/15/12
Water Temp Rise °FAir Temp Drop
°F DB
Entering Water
Temp °F
30
50
70
90
110
NOTE: Cooling performance based on entering air temperatures of 80º F DB, 67º F WB.
Heating performance based on entering air temperature of 70º F DB.
Water Flow gpm/
ton
1.5 73 - 85 270 - 305 8 - 14 3 - 10 6 - 10 15 - 21
3.0 77 - 90 280 - 315 8 - 14 3 - 10 4 - 8 17 - 23
1.5 97 - 110 290 - 325 10 - 16 3 - 10 9 - 13 22 - 28
3.0 102 - 115 300 - 335 10 - 16 3 - 10 7 - 11 24 - 30
1.5 130 - 145 320 - 355 13 - 19 3 - 10 10 - 14 30 - 36
3.0 135 - 150 325 - 360 13 - 19 3 - 10 8 - 12 32 - 38
1.5 150 - 160 350 - 390 13 - 19 3 - 10 10 - 14 30 - 36
3.0 155 - 165 365 - 405 13 - 19 3 - 10 8 - 12 32 - 38
1.5
3.0
Suction Pressure
psig
Discharge Pres-
sure psig
Heating -- No Hot Water Generation
Superheat Subcooling
44
Water Temp Drop °FAir Temp Rise
°F DB
2/15/12

Pressure Drop

Single Speed
Model gpm
1.5 1.9 1.8 1.7 1.6 1.5
009
012
015
018
024
030
036
042
048
060
070
2.0 3.5 3.4 3.2 3.1 3.0 2.0 9.7 0.04
3.0 6.9 6.5 6.3 6.0 5.7 3.0 9.9 0.09
4.0 12.0 11.4 11.0 10.8 10.5 4.0 10.1 0.16
1.5 0.3 0.3 0.3 0.3 0.3
2.5 1.0 1.0 1.0 1.0 1.0 2.5 9.8 0.06
3.5 1.7 1.7 1.7 1.6 1.6 3.5 10.0 0.12
4.5 2.5 2.4 2.4 2.4 2.3 4.5 10.2 0.19
2.0 0.6 0.6 0.6 0.6 0.6
3.0 1.6 1.6 1.6 1.6 1.6 3.0 9.9 0.09
4.0 2.6 2.6 2.6 2.6 2.5 4.0 10.1 0.16
5.0 3.7 3.7 3.6 3.6 3.5 5.0 10.4 0.23
3.0 1.6 1.6 1.5 1.5 1.4
4.0 2.9 2.9 2.8 2.8 2.7 4.0 10.1 0.16
5.0 4.2 4.2 4.1 4.0 3.9 5.0 10.4 0.23
6.0 6.0 5.8 5.7 5.6 5.5 6.0 10.6 0.32
3.0 1.1 1.1 0.9 0.8 0.6
4.5 2.1 2.0 1.8 1.7 1.5 4.5 10.2 0.19
6.0 4.1 4.0 3.8 3.7 3.5 6.0 10.6 0.32
8.0 4.5 4.4 4.1 3.9 3.7 8.0 11.0 0.53
4.0 1.5 1.4 1.3 1.2 1.1
6.0 3.0 2.8 2.7 2.5 2.3 6.0 10.6 0.32
8.0 5.1 4.8 4.5 4.2 3.9 8.0 11.0 0.53
10.0 7.7 7.2 6.8 6.3 5.8 10.0 11.5 0.76
5.0 1.0 1.0 0.9 0.8 0.8
7.0 2.1 1.9 1.8 1.7 1.6 7.0 16.6 0.23
9.0 3.6 3.3 3.0 2.8 2.6 9.0 17.2 0.41
12.0 6.3 5.9 5.5 5.1 4.8 12.0 17.9 0.61
5.0 0.8 0.7 0.7 0.7 0.6
8.0 2.1 2.1 1.9 1.8 1.7 8.0 16.6 0.23
11.0 4.2 4.1 3.8 3.5 3.3 11.0 17.2 0.41
14.0 7.6 6.7 6.3 5.8 5.4 14.0 17.9 0.61
6.0 1.1 1.0 1.0 0.9 0.8
9.0 2.3 2.1 2.0 1.9 1.7 9.0 16.8 0.29
12.0 3.9 3.7 3.4 3.2 3.0 12.0 17.4 0.47
16.0 6.7 6.3 5.9 5.5 5.1 16.0 18.3 0.76
9.0 2.4 2.2 2.1 2.0 1.8
12.0 3.9 3.6 3.4 3.2 2.9 12.0 17.4 0.47
15.0 5.7 5.3 5.0 4.7 4.3 15.0 18.1 0.69
20.0 9.5 8.9 8.3 7.8 7.2 20.0 19.2 1.09
12.0 3.0 2.8 2.6 2.4 2.2
15.0 4.4 4.0 3.8 3.5 3.3 15.0 18.1 0.69
18.0 6.0 5.5 5.1 4.8 4.4 18.0 18.7 0.92
24.0 9.7 9.1 8.5 7.9 7.3 24.0 20.1 1.43
Dual Capacity
Model gpm
4.0 1.4 1.3 1.2 1.1 1.0
026
038
049
064
072
6.0 2.8 2.6 2.4 2.3 2.1 6.0 10.6 0.32
8.0 4.7 4.4 4.1 3.8 3.5 8.0 11.0 0.53
10.0 7.0 6.6 6.2 5.8 5.3 10.0 11.5 0.76
5.0 1.2 1.2 1.1 1.0 1.0
7.0 2.2 2.1 1.9 1.8 1.7 7.0 10.8 0.42
9.0 3.4 3.2 3.0 2.8 2.6 9.0 11.2 0.64
11.0 4.9 4.6 4.3 4 3.7 12.0 11.9 1.02
6.0 1.2 1.2 1.1 1.0 1.0
9.0 2.4 2.2 2.1 2.0 1.8 9.0 16.8 0.29
12.0 3.9 3.6 3.4 3.2 2.9 12.0 17.4 0.47
15.0 5.7 5.3 5 4.7 4.3 15.0 18.1 0.69
8.0 1.8 1.7 1.6 1.4 1.3
12.0 3.8 3.5 3.3 3.0 2.8 12.0 17.4 0.47
16.0 6.5 6.0 5.6 5.2 4.8 16.0 18.3 0.76
20.0 9.7 9.1 8.5 8.0 7.4 20.0 19.2 1.09
12.0 3.2 3.0 2.8 2.6 2.4
15.0 4.5 4.2 4.0 3.7 3.4 15.0 18.1 0.69
18.0 6.0 5.7 5.3 4.9 4.6 18.0 18.7 0.92
21.0 7.8 7.3 6.8 6.4 5.9 24.0 20.1 1.43
30°F 50°F 70°F 90°F 110°F
30°F 50°F 70°F 90°F 110°F
Pressure Drop (psi)
3/16/12 3/16/12
Pressure Drop (psi)
3/16/12 3/16/12
ENVISION2 COMPACT INSTALLATION MANUAL
Valve gpm Cv
1.5 9.6 0.02
1/2 in.
1.5 9.6 0.02
1/2 in.
2.0 9.7 0.04
3/4 in.
3.0 9.9 0.09
3/4 in.
3.0 9.9 0.09
3/4 in.
4.0 10.1 0.16
3/4 in.
5.0 15.9 0.10
1 in.
5.0 15.9 0.10
1 in.
6.0 16.1 0.14
1 in.
9.0 16.8 0.29
1 in.
12.0 17.4 0.47
1 in.
Valve gpm Cv
4.0 10.1 0.16
3/4 in.
5.0 10.4 0.23
3/4 in.
6.0 16.1 0.14
1 in.
9.0 16.8 0.29
1 in.
12.0 17.4 0.47
1 in.
Pressure
Drop (psi)
Pressure
Drop (psi)
45
ENVISION2 COMPACT INSTALLATION MANUAL

Reference Calculations

Heating Calculations:
LWT = EWT -
LAT = EAT +
TH = HC + HWC
HE
gpm x 500
HC
cfm x 1.08
Cooling Calculations:
LWT = EWT +
LAT(DB) = EAT(DB) -
LC = TC - SC
SC
S/T =
TC
gpm x 500

Legend

ABBREVIATIONS AND DEFINITIONS:
cfm = airflow, cubic feet/minute EWT = entering water temperature, Fahrenheit gpm = water flow in gallons/minute WPD = water pressure drop, PSI and feet of water EAT = entering air temperature, Fahrenheit (dry bulb/wet bulb) HC = air heating capacity, MBtu/h TC = total cooling capacity, MBtu/h SC = sensible cooling capacity, MBtu/h KW = total power unit input, kilowatts HR = total heat of rejection, MBtu/h
HR
SC
cfm x 1.08
HE = total heat of extraction, MBtu/h HWC = hot water generator capacity, MBtu/h EER = Energy Efficient Ratio = BTU output/Watt input COP = Coefficient of Performance = BTU output/BTU input LWT = leaving water temperature, °F LAT = leaving air temperature, °F TH = total heating capacity, MBtu/h LC = latent cooling capacity, MBtu/h S/T = sensible to total cooling ratio

Refrigerant Circuit Guideline

Symptom
Under Charged System (Possible Leak) Low Low Low High Low Low Low Over Charged System High High High Normal High Normal/Low Normal Low Air Flow Heating High High High High/Normal Low High Low Low Air Flow Cooling Low Low Low Low/Normal High High Low Low Water Flow Heating Low/Normal Low/Normal Low Low High Low High Low Water Flow Cooling High High High High Low Low High High Air Flow Heating Low Low Low Low High Low Low High Air Flow Cooling Low High Normal High Low Low Normal High Water Flow Heating Normal Low Normal High Normal Normal Low High Water Flow Cooling Low Low Low Low High Normal Low Low Indoor Air Temperature Heating Low Low Low Normal High Normal Normal/High Low Indoor Air Temperature Cooling Low Low Low Normal/Low High Low Low High Indoor Air Temperature Heating High High High Normal/High Normal/Low Low Normal High Indoor Air Temperature Cooling High High High High Low Low High Restricted TXV (Check Service Advisory) High Low Normal/Low High High Low Low Insufficient Compressor (Possible Bad Valves) Low High Low High Normal/High Low Low TXV - Bulb Loss of Charge Low Low Low High High Low Low Scaled Coaxial Heat Exchanger Heating Low Low Low Normal/Low High Low Low Scaled Coaxial Heat Exchanger Cooling High High High Normal/Low Low Low Low Restricted Filter Drier Check temperature difference (delta T) across filter drier.
Head
Pressure
Suction
Pressure
Compressor
Amp Draw
46
Superheat Subcooling
Air Temp.
Differential
Water Temp.
Differential
7/ 6/ 1 0

Compressor Resistance

ENVISION2 COMPACT INSTALLATION MANUAL
Model
009 3.65 - 4.19 3.75 - 4.31 3.73 - 4.27 4.45 - 5.13 n/a n/a n/a
012 3.35 - 3.85 2.80 - 3.22 3.73 - 4.27 4.45 - 5.13 n/a n/a n/a 015 2.74 - 3.16 2.60 - 3.00 3.03 - 3.49 2.39 - 2.75 n/a n/a n/a 018 2.24 - 2.58 2.84 - 3.26 3.03 - 3.49 2.39 - 2.75 n/a n/a n/a
024 1.21 - 1.39 1.53 - 1.75 1.38 - 1.58 2.02 - 2.32 2.00 - 2.30 8.00 - 9.20 n/a
030 1.21 - 1.39 1.53 - 1.75 1.38 - 1.58 2.02 - 2.32 2.00 - 2.30 8.00 - 9.20 n/a
036 0.95 - 1.09 1.81 - 2.09 1.24 - 1.42 2.42 - 2.78 1.77 - 2.04 7.57 - 8.71 n/a
042 0.83 - 0.95 1.54 - 1.78 n/a 1.42 - 1.64 5.46 - 6.28 8.26 - 9.50
Single Speed
048 0.51 - 0.59 1.13 - 1.31 n/a 0.96 - 1.10 3.88 - 4.46 5.88 - 6.76 060 0.42 - 0.48 0.73 - 0.85 n/a 0.63 - 0.73 2.98 - 3.42 4.96 - 5.70
070 0.33 - 0.39 0.90 - 1.04 n/a 0.56 - 0.64 2.34 - 2.70 3.48 - 4.00 026 1.21 - 1.39 1.52 - 1.75 1.38 - 1.58 2.02 - 2.32 2.00 - 2.30 8.00 - 9.20 n/a
038 0.82 - 0.94 1.41 - 1.63 1.13 - 1.31 1.07 - 1.23 1.42 - 1.64 5.46 - 6.28 n/a
049 0.48- 0.56 1.73 - 1.99 n/a 0.96 - 1.10 3.88 - 4.46 n/a
064 0.36 - 0.42 1.52 - 1.74 n/a 0.63 - 0.73 2.98 - 3.42 n/a
Dual Capacity
072 0.32 - 0.36 1.72 - 1.98 n/a 0.56 - 0.64 2.34 - 2.70 n/a
208-230/60/1 265/60/1
Run Start Run Start
208-230/60/3 460/60/3 575/60/3

Thermistor Resistance

Thermistor
Temperature (°F)
5 75757-70117
14 57392-53234 23 43865-40771 32 33809-31487
41 26269-24513 50 20570-19230 59 16226-15196 68 12889-12093 77 10310-9688 86 8300-7812 95 6723-6337
104 5480-5172
113 4490-4246
122 3700-3504
131 3067-2907
140 2554-2424 149 2149-2019
Microprocessor
Resistance (Ohms)
7/ 6/ 1 0
3/16/12
47
ENVISION2 COMPACT INSTALLATION MANUAL

Heat of Extraction/Rejection Data

Single Speed
Model gpm
009
012
015
018
024
030
036
042
048
060
070
1.5 6.5 8.6 11.3 13.0 12.4 12.1
2.0 5.1 6.7 8.9 11.6 13.3 13.0 12.4 12.1 11.9
3.0 5.0 7.1 9.3 11.8 12.9 13.1 12.4 11.6 11.1
1.5 7.4 9.6 12.5 16.9 16.5 15.8
2.5 5.9 7.7 10.1 12.7 17.3 16.9 16.4 15.9 16.0
3.5 6.1 8.1 10.6 12.9 17.4 16.9 16.4 16.0 16.1
2.0 9.7 12.4 15.7 19.3 18.3 17.6
3.0 7.9 10.1 13.0 16.4 18.0 19.4 18.3 17.6 17.3
4.0 8.0 10.5 13.5 16.5 17.1 19.5 18.4 17.6 16.7
3.0 11.4 13.9 19.1 23.0 21.6 20.5
4.0 10.1 12.2 14.8 19.5 21.1 23.3 21.7 20.5 20.1
5.0 10.4 13.1 15.8 19.8 21.2 23.6 21.9 20.7 20.1
3.0 17.4 22.8 28.5 32.6 31.8 29.4
4.5 13.8 18.1 23.5 29.0 29.8 32.6 31.8 29.8 28.5
6.0 13.4 18.8 24.3 29.4 30.0 32.6 31.9 30.1 28.7
4.0 20.0 26.0 31.0 35.1 35.4 33.1
6.0 14.6 20.8 27.1 32.3 32.6 35.0 35.3 33.0 29.3
8.0 14.9 21.3 27.6 32.8 32.9 35.3 35.5 33.2 29.4
5.0 23.8 31.3 37.6 41.5 42.7 40.8
7.0 17.7 24.9 32.6 39.2 34.9 41.4 42.6 40.7 38.0
9.0 18.1 25.5 33.2 39.8 35.3 41.8 42.9 40.9 38.2
5.0 27.2 33.7 40.0 50.2 51.2 48.8
8.0 21.0 28.5 35.5 42.4 46.9 50.4 51.5 49.1 45.9
11.0 21.4 29.3 36.6 43.9 47.2 50.7 51.8 49.3 45.9
6.0 35.1 43.9 51.2 60.6 60.5 57.0
9.0 26.8 36.7 46.3 54.3 56.2 60.8 60.9 57.4 53.8
12.0 27.3 37.7 47.7 56.2 56.5 61.1 61.1 57.5 53.8
9.0 44.1 56.3 65.1 83.1 81.3 76.5
12.0 31.5 45.5 57.5 69.1 80.2 82.9 81.6 76.3 71.9
15.0 32.6 46.4 59.9 70.0 80.8 83.2 81.2 76.5 72.0
12.0 52.4 66.9 78.1 91.1 89.5 83.0
15.0 37.9 53.7 69.8 82.9 83.4 91.2 89.4 82.7 76.8
18.0 38.1 54.3 70.9 84.8 83.8 91.9 90.3 83.6 77.6
Heat of Extraction (HE) - MBtu/h Heat of Rejection (HR) - MBtu/h
30°F 50°F 70°F 90°F 30°F 50°F 70°F 90°F 110°F
3/16/12
Dual Capacity
Model gpm
Part Load
026
Full Load
Part Load
038
Full Load
Part Load
049
Full Load
Part Load
064
Full Load
Part Load
072
Full Load
Heat of Extraction (HE) - MBtu/h Heat of Rejection (HR) - MBtu/h
30°F 50°F 70°F 90°F 30°F 50°F 70°F 90°F 110°F
3.0 14.0 18.8 22.8 26.7 26.6 24.3
5.0 10.2 14.8 19.8 24.0 24.7 26.8 26.7 24.2 22.2
7.0 10.3 15.1 20.1 24.4 25.0 27.0 26.7 24.3 22.2
4.0 18.6 24.3 29.6 34.8 34.9 33.4
6.0 14.0 19.7 25.7 31.1 33.6 34.9 35.0 33.3 31.1
8.0 14.3 20.1 26.1 31.7 33.9 35.1 35.1 33.4 31.1
4.0 17.6 22.8 27.5 35.3 34.5 32.4
6.0 12.6 18.3 24.0 29.2 32.5 35.6 34.7 32.5 30.3
8.0 13.6 19.3 24.6 29.2 33.0 36.1 35.2 32.9 30.7
5.0 25.1 31.4 35.9 48.3 48.5 45.8
7.0 18.8 26.2 33.1 38.4 45.2 48.8 49.2 46.7 43.6
9.0 19.2 26.9 34.1 39.7 45.5 49.1 49.6 47.0 43.8
5.0 23.2 28.6 32.7 47.4 48.5 46.2
8.0 18.4 25.6 31.7 36.5 42.9 47.5 48.3 45.6 42.2
11.0 19.1 26.6 33.4 38.9 42.4 47.5 48.7 46.5 43.3
6.0 33.5 40.8 46.2 63.4 63.2 59.0
9.0 26.1 34.8 43.0 49.3 59.1 63.5 63.9 60.1 55.0
12.0 26.7 35.8 44.4 51.1 59.3 63.7 64.3 60.3 55.3
6.0 32.6 41.0 48.0 60.6 59.4 55.5
10.0 22.8 32.9 42.7 51.8 56.5 60.5 59.5 55.8 52.2
14.0 23.9 34.1 43.6 51.9 56.3 60.5 59.6 56.1 52.5
8.0 43.9 56.4 69.0 81.0 82.9 76.5
12.0 34.5 47.0 58.9 70.2 73.7 81.5 83.4 76.7 71.4
16.0 34.9 47.9 60.7 73.1 74.1 82.0 83.8 77.2 71.5
10.0 36.8 47.0 55.3 68.4 67.9 63.2
13.0 25.5 37.1 49.1 59.7 62.4 68.3 67.9 63.5 58.8
16.0 27.1 38.6 50.0 59.8 61.9 68.3 68.2 63.8 59.1
12.0 50.2 65.1 78.2 89.6 88.1 84.6
15.0 38.7 53.7 67.8 79.4 80.9 90.0 91.0 84.9 77.8
18.0 39.1 54.7 70.0 82.7 81.5 90.6 91.5 85.3 78.1 3/16/12
48

Troubleshooting

ENVISION2 COMPACT INSTALLATION MANUAL
Should a major problem develop, refer to the following information for possible causes and corrective steps.
If compressor won’t run:
1.
The fuse may be open or the circuit breaker is tripped. Check electrical circuits and motor windings for shorts or grounds. Investigate for possible overloading. Replace fuse or reset circuit breakers after fault is corrected.
2. Supply voltage may be too low. Check it with a volt meter.
3. Control system may be faulty. Check control for correct wiring of thermostat or aquastat and check the 24 volt transformer for proper voltage.
4. Wires may be loose or broken. Replace or tighten.
5. The low pressure switch may have tripped due to one or more of the following:
a) Heating
1) Plugged heat exchanger on source side
2) Water flow source side - (Low)
3) Water too cold source side
4) Low refrigerant
b) Cooling
1) Plugged heat exchanger on load side
2) Water flow load side - (Low)
3) Water too cold load side
4) Low refrigerant
6. The high pressure switch may have tripped due to one or more of the following:
a) Heating
1) Plugged heat exchanger on load side
2) Low water flow load side
3) Water too warm load side
b) Cooling
1) Plugged heat exchanger on source side
2) Low water flow on source side
3) Water too warm source side
7. The compressor overload protection may be open.
8.
The internal winding of the compressor motor may be grounded to the compressor shell. If so, replace the compressor.
9. The compressor winding may be open or shorted. Disconnect power. Check continuity with ohm meter. If the winding is open, replace the compressor.
If sufficient cooling or heating is not obtained:
1. Check control for improper location or setting.
2. Check for restriction in water flow.
3. Check refrigerant subcooling and superheat for proper refrigerant charge and expansion valve operation.
4. The reversing valve may be defective and creating a bypass of refrigerant. If the unit will not heat, check the reversing valve coil.
If the unit operation is noisy:
1. Check compressor for loosened mounting bolts. Make sure compressor is floating free on its isolator mounts. Check for tubing contact with the compressor or other surfaces. Readjust it by bending slightly.
2. Check screws on all panels.
3. Check for chattering or humming in the contactor or relays due to low voltage or a defective holding coil. Replace the component.
4. Check for proper installation of vibration absorbing material under the unit.
5. Check for abnormally high discharge pressures.
6. Compressor rotation incorrect
Aurora Control System
NOTE: Refer to the Aurora Base Control Application and
Troubleshooting Guide and the Instruction Guide: Aurora Interface and Diagnostics (AID) Tool for additional information.
To check the unit control board for proper operation:
1. Disconnect thermostat wires at the control board.
2. Jumper the desired test input (Y1, Y2, W, O or G) to the R
terminal to simulate a thermostat signal.
3. If control functions properly:
• Check for thermostat and field control wiring (use the diagnostic inputs mode).
4. If control responds improperly:
• Ensure that component being controlled is functioning (compressor, blower, reversing valve, etc.).
• Ensure that wiring from control to the component is functioning (refer to the LED Definition table below and use the diagnostic outputs mode).
• If steps above check properly, replace unit control.
Refrigerant Systems
To maintain sealed circuit integrity, do not install service gauges unless unit operation appears abnormal. Compare the change in temperature on the air side as well as the water side to the Operating Parameters tables. If the unit’s performance is not within the ranges listed, and the airflow and water flow are known to be correct, gauges should then be installed and superheat and subcooling numbers calculated. If superheat and subcooling are outside recommended ranges, an adjustment to the refrigerant charge may be necessary.
NOTE: Refrigerant tests must be made with hot water generator turned “OFF”. Verify that air and water flow rates are at proper levels before servicing the refrigerant circuit.
49
ENVISION2 COMPACT INSTALLATION MANUAL
p
p
q
q
(
)

Startup and Troubleshooting Form

Company Name: _________________________________ Technician Name: ________________________________ Model No: ______________________________________ Owner’s Name: __________________________________ Installation Address: ______________________________
Company Phone No:______________________________ Date: __________________________________________ Serial No:_______________________________________ Open or Closed Loop: _____________________________ Installation Date: _________________________________
Check One
Start up/Check-out for new installation
1. FLOW RATE IN GPM (COAXIAL HEAT EXCHANGER) Water In Pressure: a.______ PSI
Water Out Pressure: b.______ PSI Pressure Drop = a - b c.______ PSI Convert Pressure Drop to Flow Rate
(refer to Pressure Drop table) d.______ GPM
2. TEMPERATURE RISE OR DROP ACROSS COAXIAL HEAT EXCHANGER
Water In Temperature: e.______ °F e.______ °F Water Out Temperature: f. ______ °F f. ______ °F Temperature Difference: g.______ °F g.______ °F
3. TEMPERATURE RISE OR DROP ACROSS AIR COIL
Air In Temperature: h.______ °F h.______ °F Air Out Temperature: i. ______ °F i. ______ °F Temperature Difference: j. ______ °F j. ______ °F
Troubleshooting Problem:___________________________________
COOLING HEATING
COOLING HEATING
4. HEAT OF REJECTION (HR) / HEAT OF EXTRACTION (HE) CALCULATION HR or HE = Flow Rate x Temperature Difference x Brine Factor*
d. (above) x g. (above) x 485 for Methanol or Environol, 500 for water* Heat of Extraction (Heating Mode) = btu/hr Heat of Rejection (Cooling Mode) = btu/hr Compare results to Capacity Data Tables
Note: Steps 5 through 8 need only be completed if a problem is suspected
5. WATTS Volts: m._____
Total Amps (Comp. + Fan): n. _____ AMPS n. ______ AMPS Watts = m. x n. x 0.85 o. _____ WATTS o. ______ WATTS
6. CAPACITY Cooling Capacity = HR. - (o. x 3.413) Heating Capacity= HE. + (o. x 3.413)
7. EFFICIENCY Cooling EER = p. / o. Heating COP = p. / (o. x 3.413)
8. SUPERHEAT Suction Pressure: r. ______ PSI r. ______ PSI
Suction Saturation Temperature: s. ______ °F s. ______ °F Suction Line Temperature: t. ______ °F t. ______ °F Superheat = t. - s. u. _____ °F u. ______ °F
Head Pressure: v. ______ PSI v. ______ PSI High Pressure Saturation Temp.: w. _____ °F w. _____ °F Liquid Line Temperature*: x. ______ °F x. ______ °F Subcooling = w. - x. y. ______ °F y. ______ °F
* Note: Liquid line is between the coaxial heat exchanger and the expansion valve in the cooling mode; between the air coil and the expansion valve in the heating mode.
S.H.) / SUBCOOLING (S.C.
COOLING HEATING
VOLTS m.______ VOLTS
. _____ btu/hr . _____ btu/hr
. _____ EER . _____ COP
COOLING HEATING
50
ENVISION2 COMPACT INSTALLATION MANUAL
Startup/7roubleshooting Form
Dealer: Phone #: Date: Problem: Model #: Serial #:
COOLING CYCLE ANALYSIS
Unit Amp Draw:
°F
AIR
COIL
°F
BRINE IN
COAX
LOAD
°F
PSI
BRINE OUT
Line Voltage:
EXPANSION
°F
PSI
VALVE
LIQUID LINE
Controls Info: ABC Version: AXB Version: IZ2 Version: T-Stat Version: Installed Sensors:
Loop: Open
COAX
SOURCE
°F
°F
PSI
BRINE IN
BRINE OUT
PSI
°F
Closed
REVERSING
VALVE
Hot Water
-
Generator
°F °F
PSI
°F
SUCTION
COMPRESSOR
DISCHARGE
$
F
PSI = SAT F
SAT °F=
$
Superheat
Subcooling
Water to Water Application
+HDWRI([WUDFWLRQ5HMHFWLRQ JSP[IRUZDWHUDQWLIUHH]H[¨7
1RWH'2127 hook up pressure gauges unless there appears to be a performance problem.
HEA7,1*&<&/( ANALYSIS
Unit Amp Draw:
°F
AIR
COIL
°F
BRINE IN
COAX
LOAD
°F
PSI
BRINE OUT
Line Voltage:
LIQUID LINE
°F
PSI
EXPANSION
VALVE
$
F
PSI
BRINE IN
COAX
SOURCE
°F
BRINE OUT
Loop: Open
Closed
°F
PSI
REVERSING
Hot Water
-
Generator
°F
VALVE
°F
PSI
°F
SUCTION
COMPRESSOR
DISCHARGE
$
F
PSI = SAT F
SAT °F=
$
Superheat
Subcooling
51
ENVISION2 COMPACT INSTALLATION MANUAL

Preventive Maintenance

Water Coil Maintenance
1. Keep all air out of the water. An open loop system should be checked to ensure that the well head is not allowing air to infiltrate the water line. Lines should always be airtight.
2. Keep the system under pressure at all times. It is recommended in open loop systems that the water control valve be placed in the discharge line to prevent loss of pressure during off cycles. Closed loop systems must have positive static pressure.
NOTE: On open loop systems, if the installation is in an area with a known high mineral content (125 PPM or greater) in the water, it is best to establish with the owner a periodic maintenance schedule so the coil can be checked regularly. Should periodic coil cleaning be necessary, use standard coil cleaning procedures which are compatible with either the cupronickel or copper water lines. Generally, the more water flowing through the unit the less chance for scaling.
Other Maintenance
Filters
Filters must be clean to obtain maximum performance. They should be inspected monthly under normal operating conditions and be replaced when necessary. Units should never be operated without a filter.
Condensate Drain
In areas where airborne bacteria produce a slime in the drain pan, it may be necessary to treat chemically to minimize the problem. The condensate drain can pick up lint and dirt, especially with dirty filters. Inspect twice a year to avoid the possibility of overflow.
Blower Motors
Blower motors are equipped with sealed ball bearings and require no periodic oiling.
Hot Water Generator Coil
See Water Coil Maintenance section above.
Air Coil
The air coil must be cleaned to obtain maximum performance. Check once a year under normal operating conditions and, if dirty, brush or vacuum (with a brush attachment) clean. Care must be taken not to damage the aluminum fins while cleaning.
CAUTION: Fin edges are sharp.

Replacement Parts

Obtaining Parts
When ordering service or replacement parts, refer to the model number and serial number of the unit as stamped on the serial plate attached to the unit. If replacement parts are required, mention the date of installation of the unit and the date of failure, along with an explanation of the malfunctions and a description of the replacement parts required.
In-Warranty Material Return
Material may not be returned except by permission of authorized warranty personnel. Contact your local distributor for warranty return authorization and assistance.
52

Service Parts

ENVISION2 COMPACT INSTALLATION MANUAL
Part Description
Compressor 208-230/60/1 34P590-01 34P591-01 34P592-01 34P593-01 34P624-01 34P582-01 34P583-01 34P578-01 34P579-01 34P580-01 34P646-01 265/60/1 34P590-02 34P591-02 34P592-02 34P593-02 34P624-02 34P582-02 34P583-02 Not Available 230/60/3 Not Available 34P624-03 34P582-03 34P583-03 34P578-03 34P579-03 34P580-03 34P646-03 460/60/3 Not Available 34P624-04 34P582-04 34P583-04 34P578-04 34P579-04 34P580-04 34P646-04 575/60/3 Not Available Not Available 34P578-05 34P579-05 34P580-05 34P646-05 Run Capacitor 208-230/60/1 16P002D17 16P002D18 16P002D19 16P002D19 16P002D19 16P002D20 16P002D21 16P002D25 16P002D24
Compressor
Sound Jacket 92P504A01 92P504A05 92P504A03 Power Harness 11P521A01 11P781-01 Solenoid Harness Not Available
VS ECM Motor 208-230/60/1 Not Available 14S551-01 14S552-01 14S553-01
VS ECM Motor 265/60/1 Not Available 14S551-02 14S552-02 Not Available
VS ECM Motor 230/60/3 Not Available 14S551-01 14S552-01 14S553-01
VS ECM Motor 460/60/3 Not Available 14S551-02 14S552-02 14S553-02
Blower
VS ECM Blower Housing Not Available 53P512B01 53P515B01
VS ECM Harness Not Available 11P607B02
VS ECM Motor &
VS ECM Power Harness Not Available 11P585B02
High Static VS ECM Motor 208-230/60/1
High Static VS ECM Motor 265/60/1
High Static VS ECM Motor 230/60/ 3
Motor & Blower
High Static VS ECM Motor
High Static VS ECM
460/60/ 3 5-Spd ECM Motor
208-230/60/1
5-Spd ECM Motor 265/60/1 Not Available 14P536-02 14P537-02
5-Spd ECM Motor 230/60/3 Not Available 14P536-01 14P537-01
5-Spd ECM Motor 460/60/3 Not Available 14P536-03 14P537-03
5-Speed ECM
Motor & Blower
5-Spd ECM Blower Housing Not Available 53P512B01 53P515B01
PSC Motor 208-230/60/1 14P506-02 14P507B01 14P508B01 14P509B01 14P510B01 14P511B01 14P514B01 PSC Motor 265/60/1 14P506-02 14P507B02 14P508B02 14P509B02 14P510B02 Not Available PSC Motor 230/60/3 Not Available 14P508B01 14P509B01 14P510B01 14P511B01 14P514B01 PSC Motor 460/60/3 Not Available 14P508B03 14P509B03 14P510B03 14P511B02 14P514B02
Blower
PSC Motor 575/60/3 Not Available 14P511B03 14P514B03
PSC Motor &
PSC Blower & Housing 53P502B01 53P512B01 53P517-02 53P515B01 Air Coil 61P719-41 61P704-41 61P721-41 61P705-41 61P711-41 61P706-41 61P715-41 61P725-41 Coax 62P586-01 62P572-01 62P585-01 62P566-01 62P588-01 62P574-01 62P574-01 62P543-04 62P543-04 62P557-01 TXV 33P605-08 33P608-13 33P608-02 33P608-02 33P619-02 33P619-03 33P619-04 33P619-05 Reversing Valve 33P502-05 33P506-04 33P503-05 33P526-05
Components
Refrigeration
Filter Drier 36P500B01 36P500B02
Hot Water Generator Not Available 62P516-05 62P516-03
HWG
Contactor 13P004A03 Transformer 208-230/60/1 15P501B01 Transformer 265/60/1 15P507B01 Not Available Transformer 230/60/3 Not Available 15P501B01 Transformer 460/60/3 Not Available 15P505B01
Controls
Transformer 575/60/3 Not Available Not available 15P506B01 3 Pole Power Block Not Available 12P503-06 2 Pole Screw Term. Block 12P500A01 Freeze Protection Thermistor 12P505B01 12P505B03 HWL Thermistor Not Available 12P505B02 High Pressure Switch 35P506B02
Safeties
Sensors &
Low Pressure Switch 35P506B01
NOTE: Part numbers subject to change. 4/11/14
009 012 015 018 024 030 036 042 048 060 070
Not Available 14S553-01 14S553-01 14S553-01 Not Available
Not Available 14S553-02 Not Available
Not Available 14S553-01 14S553-01 14S553-01 Not Available
Not Available 14S553-02 14S553-02 14S553-02 Not Available
Not Available 14P536-01 14P537-01
Single Speed Vertical Units
53
ENVISION2 COMPACT INSTALLATION MANUAL
Service Parts cont.
Part Description
Compressor 208-230/60/1 34P590-01 34P591-01 34P592-01 34P593-01 34P624-01 34P582-01 34P583-01 34P578-01 34P579-01 34P580-01 34P646-01 265/60/1 34P590-02 34P591-02 34P592-02 34P593-02 34P624-02 34P582-02 34P583-02 Not Available 230/60/3 Not Available 34P624-03 34P582-03 34P583-03 34P578-03 34P579-03 34P580-03 34P646-03 460/60/3 Not Available 34P624-04 34P582-04 34P583-04 34P578-04 34P579-04 34P580-04 34P646-04 575/60/3 Not Available Not Available 34P578-05 34P579-05 34P580-05 34P646-05 Run Capacitor 208-230/60/1 16P002D17 16P002D18 16P002D19 16P002D19 16P002D19 16P002D20 16P002D21 16P002D25 16P002D24
Compressor
Sound Jacket 92P504A01 92P504A05 92P504A03 Power Harness 11P521A01 11P781-01 Solenoid Harness Not Available VS ECM Motor 208-230/60/1 Not Available 14S551-01 14S552-01 14S553-01 VS ECM Motor 265/60/1 Not Available 14S551-02 14S552-02 Not Available VS ECM Motor 230/60/3 Not Available 14S551-01 14S552-01 14S553-01 VS ECM Motor 460/60/3 Not Available 14S551-02 14S552-02 14S553-02
Blower
VS ECM Blower Housing Not Available 53P512B01 53P515B01 VS ECM Harness Not Available 11P607B02
VS ECM Motor &
VS ECM Power Harness Not Available 11P585B02 High Static VS ECM Motor
208-230/60/1 High Static VS ECM Motor
265/60/1 High Static VS ECM Motor
230/60/ 3
Motor & Blower
High Static VS ECM Motor
High Static VS ECM
460/60/ 3 5-Spd ECM Motor
208-230/60/1
5-Spd ECM Motor 265/60/1 Not Available 14P536-02 14P537-02
5-Spd ECM Motor 230/60/3 Not Available 14P536-01 14P537-01
5-Spd ECM Motor 460/60/3 Not Available 14P536-03 14P537-03
5-Speed ECM
Motor & Blower
5-Spd ECM Blower Housing Not Available 53P512B01 53P515B01
PSC Motor 208-230/60/1 14P506-02 14P507B01 14P508B01 14P509B01 14P510B01 14P511B01 14P514B01 PSC Motor 265/60/1 14P506-02 14P507B02 14P508B02 14P509B02 14P510B02 Not Available PSC Motor 230/60/3 Not Available 14P508B01 14P509B01 14P510B01 14P511B01 14P514B01 PSC Motor 460/60/3 Not Available 14P508B03 14P509B03 14P510B03 14P511B02 14P514B02
Blower
PSC Motor 575/60/3 Not Available 14P511B03 14P514B03
PSC Motor &
PSC Blower & Housing 53P502B01 53P512B01 53P517-02 53P515B01 Air Coil 61P719-41 61P704-41 61P720-41 61P729-41 61P730-41 61P709-41 61P710-41 61P731-41 Coax 62P586-01 62P572-01 62P585-01 62P566-01 62P573-01 62P574-01 62P543-04 62P555-01 TXV 33P605-08 33P608-13 33P608-02 33P608-02 33P619-02 33P619-03 33P619-04 33P619-05 Reversing Valve 33P502-05 33P506-04 33P503-05 33P526-05
Components
Refrigeration
Filter Drier 36P500B01 36P500B01 36P500B02
Hot Water Generator Not Available
HWG
Contactor 13P004A03 Transformer 208-230/60/1 15P501B01 Transformer 265/60/1 15P507B01 Not Available Transformer 230/60/3 Not Available 15P501B01 Transformer 460/60/3 Not Available 15P505B01
Controls
Transformer 575/60/3 Not Available Not available 15P506B01 3 Pole Power Block Not Available 12P503-06 2 Pole Screw Term. Block 12P500A01 Freeze Protection Thermistor 12P505B01 12P505B03 HWL Thermistor Not Available 12P505B02 High Pressure Switch 35P506B02
Safeties
Sensors &
Low Pressure Switch 35P506B01
NOTE: Part numbers subject to change. 04/11/14
009 012 015 018 024 030 036 042 048 060 070
Not Available 14S553-01 14S553-01 14S553-01 Not Available
Not Available 14S553-02 Not Available
Not Available 14S553-01 14S553-01 14S553-01 Not Available
Not Available 14S553-02 14S553-02 14S553-02 Not Available
Not Available 14P536-01 14P537-01
Single Speed Horizontal Units
54
Service Parts cont.
ENVISION2 COMPACT INSTALLATION MANUAL
Part Description
Compressor 208-230/60/1 34P640-01 34P641-01 34P642-01 34P643-01 34P644-01 34P640-01 34P641-01 34P642-01 34P643-01 34P644-01 265/60/1 34P640-02 34P641-02 Not Available 34P640-02 34P641-02 Not Available 230/60/3 34P640-03 34P573-03 34P642-03 34P643-03 34P644-03 34P640-03 34P573-03 34P642-03 34P643-03 34P644-03 460/60/3 34P640-04 34P573-04 34P642-04 34P575-04 34P644-04 34P640-04 34P573-04 34P642-04 34P575-04 34P644-04 575/60/3 Not Available 34P642-05 34P575-05 34P644-05 Not available 34P642-05 34P575-05 34P644-05 Run Capacitor 208-230/60/1 16P002D19 16P002D20 16P002D18 16P002D39 16P002D19 16P002D20 16P002D18 16P002D39
Compressor
Sound Jacket 92P504A16 92P504A03 92P504A16 92P504A03 Power Harness 11P781-01 11P781-01 Solenoid Harness 11P782-01 11P782-01 VS ECM Motor 208-230/60/1 14S551-01 14S552-01 14S553-01 14S551-01 14S552-01 14S553-01 VS ECM Motor 265/60/1 14S551-02 14S552-02 Not Available 14S551-02 14S552-02 Not Available VS ECM Motor 230/60/3 14S551-01 14S552-01 14S553-01 14S551-01 14S552-01 14S553-01 VS ECM Motor 460/60/3 14S551-02 14S552-02 14S553-02 14S551-02 14S552-02 14S553-02
Blower
VS ECM Blower Housing 53P512B01 53P515B01 53P512B01 53P515B01 VS ECM Harness 11P607B02 11P607B02
VS ECM Motor &
VS ECM Power Harness 11P585B02 11P585B02 High Static VS ECM Motor
208-230/60/1 High Static VS ECM Motor
265/60/1 High Static VS ECM Motor
230/60/ 3
Motor & Blower
High Static VS ECM Motor
High Static VS ECM
460/60/ 3 5-Spd ECM Motor 208-
230/60/ 1
5-Spd ECM Motor 265/60/1 14P536-02 14P537-02 14P536-02 14P537-02
5-Spd ECM Motor 230/60/3 14P536-01 14P537-01 14P536-01 14P537-01
5-Spd ECM Motor 460/60/3 14P536-03 14P537-03 14P536-03 14P537-03
5-Speed ECM
Motor & Blower
5-Spd ECM Blower Housing 53P512B01 53P515B01 53P512B01 53P515B01
PSC Motor 208-230/60/1 Not Available Not Available PSC Motor 265/60/1 Not Available Not Available PSC Motor 230/60/3 Not Available Not Available PSC Motor 460/60/3 Not Available Not Available
Blower
PSC Motor 575/60/3 Not Available Not Available
PSC Motor &
PSC Blower & Housing Not Available Not Available Air Coil 61P705-41 61P706-41 61P715-41 61P725-41 61P729-41 61P709-41 61P710-41 61P717-41 Coax 62P566-01 62P574-01 62P543-04 62P543-04 62P557-01 62P566-01 62P574-01 62P543-04 62P555-01 TXV 33P619-01 33P619-02 33P619-03 33P619-04 33P619-05 33P619-01 33P619-02 33P619-03 33P619-04 33P619-05 Reversing Valve 33P506-04 33P503-05 33P526-04 33P506-04 33P503-05 33P526-04
Components
Refrigeration
Filter Drier 36P500B01 36P500B02 36P500B01 36P500B02
Hot Water Generator 62P516-05 62P516-03 Not Available
HWG
Contactor 13P004A03 13P004A03 Transformer 208-230/60/1 15P501B01 15P501B01 Transformer 265/60/1 Not Available Not Available Transformer 230/60/3 15P501B01 15P501B01 Transformer 460/60/3 15P505B01 15P505B01
Controls
Transformer 575/60/3 Not Available Not Available 3 Pole Power Block 12P503-06 12P503-06 2 Pole Screw Term. Block 12P500A01 12P500A01 Freeze Protection Thermistor 12P505B03 12P505B03 HWL Thermistor 12P505B02 12P505B02 High Pressure Switch 35P506B02 35P506B02
Safeties
Sensors &
Low Pressure Switch 35P506B01 35P506B01
NOTE: Part numbers subject to change. 04/11/14
026 038 049 064 072 026 038 049 064 072
Not Available 14S553-01 14S553-01 Not Available Not Available 14S553-01 14S553-01 Not Available
Not Available 14S553-02 Not Available Not Available 14S553-02 Not Available
Not Available 14S553-01 14S553-01 Not Available Not Available 14S553-01 14S553-01 Not Available
Not Available 14S553-02 14S553-02 Not Available Not Available 14S553-02 14S553-02 Not Available
14P536-01 14P537-01 14P536-01 14P537-01
Dual Capacity Vertical Units Dual Capacity Horizontal Units
55
ENVISION2 COMPACT INSTALLATION MANUAL
Notes
56
ENVISION2 COMPACT INSTALLATION MANUAL
Revision Guide
Pages: Description: Date: By:
All Updated with All-Aluminum Air Coils 19 May 2014 DS
33-41 Added Aurora UPC DDC Controls 19 May 2014 DS
18-20 Updated Compressor LRA with IntelliStart 02 Aug 2013 DS
All Updated Nomenclature to Reflect New Variable Speed ECM Motor 08 Jan 2013 DS
All Added IntelliStart Availability for 3-Phase Units 08 Jan 2013 DS
27 Replaced Wiring Diagram with Reheat Version 08 Jan 2013 DS
31-34 Updated Aurora Controls Description 08 Jan 2013 DS
51-53 Updated Service Parts Lists 08 Jan 2013 DS
55 Added Revision Guide 08 Jan 2013 DS
57
Manufactured by WaterFurnace International, Inc. 9000 Conservation Way Fort Wayne, IN 46809 www.waterfurnace.com
Product: Envision2 Compact Type: Water Source/Geothermal Heat Pump Size: Commercial 0.75-6 Ton
IM1022ANA 05/14
©2014 WaterFurnace International, Inc., 9000 Conservation Way, Fort Wayne, IN 46809-9794. WaterFurnace has a policy of continual product research and development and
reserves the right to change design and specifi cations without notice.
Document: Installation Manual
Loading...