WaterFurnace 700A11 User Manual

700A11
Geothermal Heat Pump - 50Hz
• R-410A Refrigerant
• 009, 012, 015 kW Variable Speed
Installation Information
Water Piping Connections
Hot Water Generator Connections
Electrical
Startup Procedures
Troubleshooting
Preventive Maintenance
CUS
IM2705AN 01/15
Table of Contents
Model Nomenclature. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
General Installation Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Closed Loop Ground Source Systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Open Loop Ground Water Systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Hot Water Generator Connections. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Electrical Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .13
Electronic Thermostat Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Auxiliary Heat Ratings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15
Auxiliary Heat Electrical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15
Electrical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15
7 SERIES 700A11 INSTALLATION MANUAL
Blower Performance Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Dimensional Data. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .17
Physical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .21
The Aurora™ Advanced VS Control System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Operation Logic . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .31
Wiring Schematics. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
Unit Startup. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
Pressure Drop . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
Compressor and Thermistor Resistance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
Refrigerant Circuit Guideline . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
Heat of Extraction/Rejection. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
Operating Parameters. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
Reference Calculations and Legend. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
Preventive Maintenance and Replacement Procedures. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
Service Parts List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
7 SERIES 50Hz 700A11 INSTALLATION MANUAL
N
1 2-3 4 5-7 8 9 10
11 12 13 15
VK V 012 * 6 1 1 C T L 014J16N
17

Model Nomenclature

Model Type
N – 7 Series Water-to-Air
Compressor Type
VK – Variable Speed
Cabinet Configuration
V – Vertical H - Horizontal
Unit Capacity (kW)
009, 012, 015
Vintage
* - Factory Use Only
Voltage
6 – 220-240/50/1
Hot Water Generation
0 – No Hot Water Generation 1 – Hot Water Generation with Factory Installed Pump
Blower Options
1 – Variable Speed ECM 2 – High Static Variable Speed ECM (009 Only)
Future Option
N - None
Control Option
J – Aurora K – Aurora Variable Speed Control with Performance Monitoring
Filter Option
0 – 5.08cm MERV11 Filter 1 – AlpinePure 411 (Vertical Only)
Return Air Configuration
L – Left R – Right
Discharge Air Configuration
T – Top (Vertical) B – Bottom (Vertical) R – Rear (Vertical) S – Side (Horizontal) E – End (Horizontal)
Water Coil Option
C – Copper N – CuproNickel
Rev.: 17 July 2013D
TM
Variable Speed Control
4

General Installation Information

7 SERIES 50Hz 700A11 INSTALLATION MANUAL
Safety Considerations
WARNING: Before performing service or maintenance operations on a system, turn off main power switches to the indoor unit. If applicable, turn off the accessory heater power switch. Electrical shock could cause personal injury.
Installing and servicing heating and air conditioning equipment can be hazardous due to system pressure and electrical components. Only trained and qualified service personnel should install, repair or service heating and air conditioning equipment. Untrained personnel can perform the basic maintenance functions of cleaning coils and cleaning and replacing filters. All other operations should be performed by trained service personnel. When working on heating and air conditioning equipment, observe precautions in the literature, tags and labels attached to the unit and other safety precautions that may apply.
Follow all safety codes. Wear safety glasses and work gloves. Use a quenching cloth for brazing operations and have a fire extinguisher available.
Moving and Storage
Move units in the normal “up” orientation. Horizontal units may be moved and stored per the information on the packaging. Do not stack more than three units in total height. Vertical units may be stored one upon another to a maximum height of two units. Do not attempt to move units while stacked. When the equipment is received, all items should be carefully checked against the bill of lading to be sure all crates and cartons have been received. Examine units for shipping damage, removing the units from the packaging if necessary. Units in question should also be internally inspected. If any damage is noted, the carrier should make the proper notation on the delivery receipt, acknowledging the damage.
locate the unit above supply piping. Care should be taken
when units are located in unconditioned spaces to prevent damage from frozen water lines and excessive heat that could damage electrical components.
Filter Rack Conversion
A 50.8mm MERV 11 filter is shipped with the heat pump. To field convert the filter rack to use 25.4mm filters, simply insert the provided plastic push pins into the holes located in the filter rack. There are holes on the top and bottom of the rack, underneath the instruction labels, for field conversion to 25.4mm filters.
Installing Vertical Units
Prior to setting the unit in place, remove and discard the compressor hold down shipping bolt located at the front of the compressor mounting bracket.
Vertical units are available in left or right air return configurations. Top and rear air discharge vertical units should be mounted level on a vibration absorbing pad slightly larger than the base to provide isolation between the unit and the floor. It is not necessary to anchor the unit to the floor (see below).
Bottomflow units should be mounted level and sealed well to floor to prevent air leakage. Bottomflow units require the supply air opening to be cut at least 12.7mm larger than the unit’s air outlet. Protect the edges of combustible flooring with sheet metal over-wrap or other non­combustible material.
Figure 1: Vertical Unit Mounting
Unit Location
Locate the unit in an indoor area, minimum ambient of
7.2°C and maximum ambient of 37.8°C, that allows for easy removal of the filter and access panels. Attic installations are not approved and could result in loss of warranty. Installation is not recommended in areas with excessive dirt and debris as this may be drawn into the VS drive causing overheating of the VS drive. Location should have enough space for service personnel to perform maintenance or repair. Provide sufficient room to make water, electrical and duct connection(s). If the unit is located in a confined space, such as a closet, provisions must be made for return air to freely enter the space by means of a louvered door, etc. Any access panel screws that would be difficult to remove after the unit is installed should be removed prior to setting the unit. On horizontal units, allow adequate room below the unit for a condensate drain trap and do not
50.8mm Extruded Polystyrene
5
7 SERIES 50Hz 700A11 INSTALLATION MANUAL
General Installation Information cont.
Installing Horizontal Units
Remove and discard the compressor hold down shipping bolt located at the front of the compressor mounting bracket prior to setting the unit in place. Horizontal units are available with side or end discharge. Horizontal units are normally suspended from a ceiling by four or six 9.5mm diameter threaded rods. The rods are usually attached to the unit by hanger bracket kits furnished with each unit.
Lay out the threaded rods per the dimensions in Figure
3. Assemble the hangers to the unit as shown. Securely tighten the brackets to the unit using the weld nuts located on the underside of the bottom panel. When attaching the hanger rods to the bracket, a double nut is required since
Figure 2: Horizontal Unit Mounting
O
Threaded Rods
Electrical
Disconnect
To Line
Power
To Thermostat
Line Voltage
Building Water Loop
Hanging Brackets
(Included)
Ball Valves
Hose
Kits
Flexible Duct Collar
Insulate supply plenum and use at least one 90 elbow to reduce noise
vibration could loosen a single nut. To allow filter access, one bracket on the filter side should be installed 180° from the position shown in Figure 3. The unit should be pitched approximately 6.35mm towards the drain in both directions to facilitate the removal of condensate. Use only the bolts provided in the kit to attach hanger brackets. The use of longer bolts could damage internal parts.
Some residential applications require the installation of horizontal units on an attic floor. In this case, the unit should be set in a full size secondary drain pan on top of a vibration absorbing pad. The secondary drain pan prevents possible condensate overflow or water leakage damage to the ceiling. The secondary drain pan is usually placed on a plywood base isolated from the ceiling joists by additional layers of vibration absorbing material.
SPECIAL NOTE: The VS drive is limited to a maximum of
51.7°C ambient temperature. For this reason the 7 Series is not approved for attic installations. The compressor compartment temperature is also monitored by the Aurora. This ‘compressor ambient’ temperature is available on the AID Tool for reading. The control will de-rate the compressor when ambient air is above 51.7°C. Installing this product in an attic could result in loss of warranty.
CAUTION: Do not use rods smaller than 9.5mm diameter since they may not be strong enough to support the unit. The rods must be securely anchored to the ceiling.
Figure 3: Hanger Location and Assembly
4
0
2
/
!
"
/W`1]WZ
Hanger Dimensions
Unit Hanger Dimensions
ABCD
009
012
015
Model
Hanger Kit Part
Number
cm. 99S500A03 196.6 70.6 61.2 74.4
cm. 99S500A03 196.6 70.6 61.2 74.4
cm. 99S500A03 209.3 70.6 61.2 74.4
:STb@WUVb
!&BV`SORSR
@]RPg]bVS`a
1
0]ZbO\R :]QYEOaVS`
DWP`ObW]\ 7a]ZOb]`
EOaVS`
6Sf<cba  Pg]bVS`a
/W`1]WZ
"
!
Weight Distribution
Horizontal Weight Distribution
Front Back
1234
6/1/12
Model
009
012
015
Weights are listed in kg 7/18/13
Vertical
Shipping
Weight
159.7 175.5 61.2 37.7 39.0 37.7
163.8 179.6 65.8 38.1 38.1 37.7
174.6 188.2 54.4 54.4 20.4 59.0
Horizontal
Shipping
Weight
6
General Installation Information cont.
7 SERIES 50Hz 700A11 INSTALLATION MANUAL
Duct System
An air outlet collar is provided on vertical top and rear air discharge units and all horizontal units to facilitate a duct connection (vertical bottomflow units have no collar). A flexible connector is recommended for discharge and return air duct connections on metal duct systems. Uninsulated duct should be insulated with a minimum of 25.4mm duct insulation. Application of the unit to uninsulated ductwork in an unconditioned space is not recommended as the unit’s performance will be adversely affected.
If the unit is connected to existing ductwork, check the duct system to ensure that it has the capacity to accommodate the air required for the unit application. If the duct is too small, as in the replacement of heating only systems, larger ductwork should be installed. All existing ductwork should be checked for leaks and repaired if necessary.
The duct system should be sized according to the table below to handle the design airflow quietly and efficiently. To maximize sound attenuation of the unit blower, the supply and return plenums should include an internal duct liner of fiberglass or constructed of ductboard for the first few meters. On systems employing a sheet metal duct system, canvas connectors should be used between the unit and the ductwork. If air noise or excessive airflow is a problem, the blower speed can be changed.
Model Design Airflow L/s
NVK009
NVK012
NVK015
708
849.6
1038.4
seal is in the swivel connector prior to attempting any connection. The rubber seals are shipped attached to the waterline. To make the connection to a ground loop system, mate the brass connector (supplied in CK4LI connector kit) against the rubber gasket in the swivel connector and thread the female locking ring onto the pipe threads, while maintaining the brass connector in the desired direction. Tighten the connectors by hand, then gently snug the fitting with pliers to provide a leak-proof joint. When connecting to an open loop (ground water) system, thread any 25.4mm MPT fitting (SCH80 PVC or copper) into the swivel connector and tighten in the same manner as noted above. The open and closed loop piping system should include pressure/temperature taps for serviceability.
Never use flexible hoses smaller than 25.4mm inside diameter on the unit. Limit hose length to 3.1 meters per connection. Check carefully for water leaks.
Figure 4: Swivel Connections
Stainless Steel Snap Ring
Gasket Material
Locking Ring
Gasket Support Sleeve
Water Piping
The proper water flow must be provided to each unit whenever the unit operates. To assure proper flow, use pressure/temperature ports to determine the flow rate. These ports should be located at the supply and return water connections on the unit. The proper flow rate cannot be accurately set without measuring the water pressure drop through the refrigerant-to-water heat exchanger.
All source water connections on residential units are swivel piping fittings (see Figure 4) that accept a 25.4mm male pipe thread (MPT). The swivel connector has a rubber gasket seal similar to a rubber hose gasket, which when mated to the flush end of any 25.4mm threaded pipe provides a leak-free seal without the need for thread sealing tape or compound. Check to ensure that the rubber
7
7 SERIES 50Hz 700A11 INSTALLATION MANUAL
General Installation Information cont.
Water Quality
In ground water situations where scaling could be heavy or where biological growth such as iron bacteria will be present, a closed loop system is recommended. The heat exchanger coils in ground water systems may, over a period of time, lose heat exchange capabilities due to a buildup of mineral deposits inside. These can be cleaned, but only by a qualified service mechanic, as special solutions and pumping equipment are required. Hot water generator coils
Material Copper 90/10 Cupronickel 316 Stainless Steel
pH Acidity/Alkalinity
Scaling
Corrosion
Iron Fouling
(Biological Growth)
Erosion
NOTES: Grains = ppm divided by 17
mg/L is equivalent to ppm
Calcium and
Magnesium Carbonate
Hydrogen Sulfide
Chlorine Less than 0.5 ppm Less than 0.5 ppm Less than 0.5 ppm
Chlorides Less than 20 ppm Less than 125 ppm Less than 300 ppm
Carbon Dioxide Less than 50 ppm 10 - 50 ppm 10 - 50 ppm
Ammonia Less than 2 ppm Less than 2 ppm Less than 20 ppm
Ammonia Chloride Less than 0.5 ppm Less than 0.5 ppm Less than 0.5 ppm
Ammonia Nitrate Less than 0.5 ppm Less than 0.5 ppm Less than 0.5 ppm
Ammonia Hydroxide Less than 0.5 ppm Less than 0.5 ppm Less than 0.5 ppm
Ammonia Sulfate Less than 0.5 ppm Less than 0.5 ppm Less than 0.5 ppm
Total Dissolved Solids (TDS) Less than 1000 ppm 1000 - 1500 ppm 1000 - 1500 ppm
LSI Index +0.5 to -0.5 +0.5 to -0.5 +0.5 to -0.5
Iron, FE
Bacterial Iron Potential
Iron Oxide
Suspended Solids
Threshold Velocity
(Fresh Water)
Less than 0.5 ppm (rotten egg
Sulfates Less than 125 ppm Less than 125 ppm Less than 200 ppm
2
+ (Ferrous)
smell appears at 0.5 ppm)
Less than 1 ppm, above this
level deposition will occur
Less than 10 ppm and filtered
for max. of 600 micron size
7 - 9 7 - 9 7 - 9
(Total Hardness)
less than 350 ppm
< 0.2 ppm < 0.2 ppm < 0.2 ppm
< 1.8 m/sec < 1.8 m/sec < 1.8 m/sec
can likewise become scaled and possibly plugged. In areas with extremely hard water, the owner should be informed that the heat exchanger may require occasional flushing.
Units with cupronickel heat exchangers are recommended for open loop applications due to the increased resistance to build-up and corrosion, along with reduced wear caused by acid cleaning. Failure to adhere to the guidelines in the water quality table could result in the loss of warranty.
(Total Hardness)
less than 350 ppm
10 - 50 ppm Less than 1 ppm
Less than 1 ppm, above this
level deposition will occur
Less than 10 ppm and filtered
for max. of 600 micron size
(Total Hardness)
less than 350 ppm
Less than 1 ppm, above this
level deposition will occur
Less than 10 ppm and filtered
for max. of 600 micron size
2/22/12
Low Water Coil Limit
Set the freeze sensing switch SW2-1 on the Aurora Base Control (ABC) printed circuit board for applications using a closed loop antifreeze solution to “LOOP” (-9.4°C). On applications using an open loop/ground water system (or closed loop no antifreeze), set this dip switch to “WELL” (-1.1°C), the factory default setting. (Refer to the DIP Switch Settings table in the Aurora Control section.)
Condensate Drain
On vertical units, the internal condensate drain assembly consists of a drain tube which is connected to the drain pan, a 19.1mm PVC female adapter and a flexible connecting hose. The female adapter may exit either the front or the side of the cabinet. The adapter should be glued to the field-installed PVC condensate piping. On vertical units, a condensate hose is inside all cabinets as a trapping loop; therefore, an external trap is not necessary.
On horizontal units, a PVC stub is provided for condensate drain piping connection. An external trap is required (see below). If a vent is necessary, an open stand pipe may be applied to a tee in the field-installed condensate piping.
Figure 5: Horizontal Drain Connection
PVC coupling
PVC tube stub
38.1 mm
Figure 6: Unit Pitch for Drain
8
Vent (if needed)
PVC tube stub
10.4 mm per meter
38.1 mm
12.7 mm Pitch
Drain

Closed Loop Ground Source Systems

7 SERIES 50Hz 700A11 INSTALLATION MANUAL
NOTE: For closed loop systems with antifreeze protection, set SW2-1 to the “LOOP” (-9.4°C) position. (Refer to the DIP Switch Settings table in the Aurora Control section.)
Once piping is completed between the unit, pumps and the ground loop (see figure below), final purging and charging of the loop is required. A flush cart (or a 1.5 HP pump minimum) is needed to achieve adequate flow velocity in the loop to purge air and dirt particles from the loop itself. Antifreeze solution is used in most areas to prevent freezing. Flush the system adequately to remove as much air as possible then pressurize the loop to a static pressure of 276-345 kPa (summer) or 345-517 kPa (winter). This is normally adequate for good system operation. Loop static pressure will fluctuate with the seasons. Pressures will be higher in the winter months than during the cooling season. This fluctuation is normal and should be considered when initially charging the system.
After pressurization, be sure to turn the venting (burping) screw in the center of the pump two (2) turns open (water will drip out), wait until all air is purged from the pump, then tighten the plug. Variable speed pumps do not have a venting screw. Ensure that the loop pumps provide adequate flow through the unit(s) by checking the pressure drop across the heat exchanger and comparing it to the unit capacity data in this catalog. 0.14-0.19 L/s of flow per ton of cooling capacity is recommended in earth loop applications.
Figure 7: Closed Loop Ground Source Application
Multiple Units on One Flow Center
NOTE: This feature is only available in the Aurora Advanced
Control package (AXB board), NOT the Aurora Base Control (ABC).
When two units are connected to one loop pumping system, pump control is automatically achieved by connecting the SL terminals on connector P2 in both units with 2-wire thermostat wire. These terminals are polarity dependant (see Figure 8). The loop pump(s) may be powered from either unit, whichever is more convenient. If either unit calls, the loop pump(s) will automatically start. The use of two units on one flow center is generally limited to a total of 1.26 L/s capacity.
Variable Speed Pump Setup
When using a variable speed pump flow center (FCV1-GL, FCV2-GL, FCV1-GLNP, or FCV2-GLNP) the use of an AID Tool will be necessary to adjust minimum and maximum flow rates. The factory default is: minimum=50% and maximum=100% speed levels. See the 7 Series Variable Speed Pump Setup and Modulating Water Valve Setup instructions within the Unit Startup section which is located in the back of this manual. Always ensure that there is adequate flow for the heat pump. See Recommended Minimum/Maximum Flow Rates table.
NOTE: When sharing a flow center, the variable speed heat pump should be the primary unit. When two variable speed heat pumps share a flow center, the larger capacity heat pump should be the primary unit.
Disconnects
(If Applicable)
Unit Supply
Auxiliary Heat Supply
Low
Voltage to
Thermostat
P/T Plugs
Vibration Absorbing Pad
®
GeoLink
Polyethylene w/
®
Armaflex Insulation
Flexible Duct Collar
Auxiliary Heater Knockout
Unit Power
Hot Water Generator Connections
Drain
P/T
GeoLink
Flow
Center
Insulated piping or hose kit
NOTE: Additional information can be found in Flow Center installation manual and Flush Cart manual.
TO
LOOP
®
Recommended Minimum/Maximum Flow Rates
Model
and Size
NVK009
NVK012 NVK015
Closed Loop Open Loop
Min. Flow Rate Max. Flow Rate Min. Flow Rate Max. Flow Rate
L/s L/s L/s L/s
0.3 0.8 0.3 0.5
0.3 0.9 0.3 0.6
0.3 1.1 0.3 0.8 5/23/13
Figure 8: Primary/Secondary Hook-up
7 Series to
5 or 7 Series Units
7 Series Unit #1
with AXB Board
With pump wired to Unit 1
With pump wired to Unit 2
OUTIN C C
OUTIN C C
VSPUMPSLAVE
12
12
VSPUMPSLAVE
7 Series to
Envision Units
7 Series Unit #1
with AXB Board
With pump wired to Unit 1
Shut
Down
OUTIN C C
CC
VSPUMPSLAVE
12
With pump wired to Unit 2
SL1InSL1
Out
7 Series to
Electromechanical Units
7 Series Unit #1
with AXB Board
VSPUMPSLAVE
12
OUTIN C C
C
S
9
7 SERIES 50Hz 700A11 INSTALLATION MANUAL

Open Loop Ground Water Systems

Typical open loop piping is shown below. Always maintain water pressure in the heat exchanger by placing water control valves at the outlet of the unit to prevent mineral precipitation. Use a closed, bladder-type expansion tank to minimize mineral formation due to air exposure. Ensure proper water flow through the unit by checking pressure drop across the heat exchanger and comparing it to the figures in unit capacity data tables in the specification catalog. 0.095-0.13 L/s of flow per ton of cooling capacity is recommended in open loop applications.
Discharge water from the unit is not contaminated in any manner and can be disposed of in various ways, depending on local codes, i.e. recharge well, storm sewer, drain field, adjacent stream or pond, etc. Most local codes forbid the use of sanitary sewer for disposal. Consult your local building and zoning departments to assure compliance in your area. On VS systems, a modulating valve, as shown in figure 9a is the best choice to limit water consumption. The WWKVS well water kit with modulating valve is the recommended setup for open loop applications with variable speed products.
NOTE: For open loop/groundwater systems or systems that do not contain an antifreeze solution, set SW2-Switch #1 to the “WELL” (-1.1°C) position. (Refer to the DIP Switch Settings in the Aurora Control section.) Slow opening/ closing solenoid valves (type VM or V) or modulating valves are recommended to eliminate water hammer.
Figure 9a: Modulating Water Valve Connection Option
Typical 0-10VDC modulating water valve.
AXB BOARD
2 1
GND
24 VAC
0-10DC
1 2
3
VS PUMP C R
VALVE
ABC BOARD
Figure 9b: Open Loop Solenoid Valve Connection Option
Typical slow operating external 24V water solenoid valve (type V) wiring.
C R
C
W/Y
Acc Com
ACC NC
Acc NO
V Valve ABC Board
Modulating Water Valve Setup
When using a modulating water valve (23P529-01) the use of an AID Tool will be necessary to adjust minimum and maximum flow rates. The factory default is: minimum=50% and maximum=100% flow levels. See the 7 Series Variable Speed Pump Setup and Modulating Water Valve Setup instructions within the Unit Startup section which is located in the back of this manual. See Recommended Minimum and Maximum Flow Rates table. Always ensure that there is adequate flow for the heat pump. A modulating water valve is preferred on variable speed system to conserve water.
Figure 10: Open System - Groundwater Application
Unit Supply
Aux. Heat Supply
Flexible Duct Collar
Rubber Bladder Expansion Tank
Auxiliary
Disconnects
(IfApplicable)
Compressor Line Voltage
Low Voltage
to Thermostat
and Valve
P/T Plugs
Vibration
Absorbing Pad
Heater Knockout
Hot Water Generator
Connections
Drain
Strainer
Boiler Drains
For HX Flushing
Solenoid
Valve
valve while acid flushing)
Flow Control (on outlet of
Solenoid Valve)
Water Out
Shut Off Valves
Shut Off Valves
(to isolate solenoid
Valve
Water In
Figure 9c: Open Loop Solenoid Valve Connection Option
Typical slow operating external 24V water solenoid valve (type VM) wiring.
C R
VM Valve
Acc Com
ACC NC
Acc NO
ABC Board
NOTE: SW2-4 should be “ON” and SW2-5 should be “OFF” when using a slow opening (VM or V) water valve.
Figure 9d: Open Loop Solenoid Valve Connection Option
Typical quick operating external 24V water solenoid valve (type PPV100 or BPV100) wiring.
C
P1
R
SV
Solenoid
Acc Com Acc NC Acc NO
ABC Board
1 2
P2
3
Valve
NOTE: SW2-4 and SW2-5 should be “OFF” to cycle with the compressor.
10

Hot Water Generator Connections

7 SERIES 50Hz 700A11 INSTALLATION MANUAL
To maximize the benefits of the hot water generator a minimum 189-liter water heater is recommended for higher demand applications, use an 302.8-liter water heater or two 189-liter water heaters connected in a series as shown below. Two tanks plumbed in a series is recommended to maximize the hot water generator capability. Electric water heaters are recommended. Make sure all local electrical and plumbing codes are met for installing a hot water generator. Residential units with hot water generators contain an internal circulator and fittings. A water softener is recommended with hard water (greater than 10 grains or 170 total hardness).
NOTES: 1) Using a preheat tank, as shown in Figure 12, will maximize hot water generator capabilities. 2) The hot water generator coil is constructed of vented double wall copper suitable for potable water.
Water Tank Preparation
To install a unit with a hot water generator, follow these installation guidelines.
1. Turn off the power to the water heater.
2. Attach a water hose to the water tank drain connection and run the other end of the hose to an open drain or outdoors.
3. Close the cold water inlet valve to the water heater tank.
4. Drain the tank by opening the valve on the bottom of the tank, then open the pressure relief valve or hot water faucet.
5. Flush the tank by opening the cold water inlet valve to the water heater to free the tank of sediments. Close when draining water is clear.
6. Disconnect the garden hose and remove the drain valve from the water heater.
7. Refer to Plumbing Installation and Hot Water Generator Startup.
Figure 11: Typical Hot Water Generator Installation
19.1mm x 19.1mm x 12.7mm tee
Venting Waste
Valve or Vent
Coupling
HWG
Water Out
HWG
Water In
Cold
Water In
P/T Relief
Drain Valve
Valve
Hot
Water Out
In
Figure 12: Hot Water Generator Installation In Preheat Tank
19.1mm x 19.1mm x
tee
Venting Waste Valve or Vent Coupling
Water In
12.7mm
HWG
HWG
Water Out
Cold
Water In
P/T Relief
Valve
Storage
Tank
Water Out
P/T Relief
In
Drain ValveDrain Valve
Electric Powered
Water Heater
Hot
Valve
NOTE: This configuration maximizes hot water generator capability.
CAUTION: Elements will burn out if energized dry.
11
7 SERIES 50Hz 700A11 INSTALLATION MANUAL
Hot Water Generator Connections cont.
Plumbing Installation
1. Inspect the dip tube in the water heater cold inlet for a check valve. If a check valve is present it must be removed or damage to the hot water generator circulator will occur.
2. Remove drain valve and fitting.
3. Thread the 19.1mm NPT x 88.9mm brass nipple into the water heater drain port.
4. Attach the center port of the 19.1mm FPT tee to the opposite end of the brass nipple.
5. Attach the 12.7mm copper to 19.1mm NPT adaptor to the side of the tee closest to the unit.
6. Install the drain valve on the tee opposite the adaptor.
7. Run interconnecting tubing from the tee to hot water generator water out.
8. Cut the cold water “IN” line going to the water heater.
9. Insert the reducing solder tee in line with cold water “IN” line as shown.
10.
Run interconnecting copper tubing between the unit hot water generator water “IN” and the tee ( The recommended maximum distance is 15.24 meters.
11.
To prevent air entrapment in the system, install a vent coupling at the highest point of the interconnecting lines.
12. Insulate all exposed surfaces of both connecting water lines with 9.5mm wall closed cell insulation.
NOTE: All plumbing and piping connections must comply with local plumbing codes.
Hot Water Generator Switch
The hot water generator switch is taped in the disabled position at the factory.
12.7mm
nominal).
Hot Water Generator Startup
1. Turn the hot water generator switch to the “ON” position. The hot water generator switch will allow the hot water generator pump to be enabled or disabled by the service technician or homeowner.
2. Close the drain valve to the water heater.
3. Open the cold water supply to the tank.
4. Open a hot water faucet in the building to bleed air from the system. Close when full.
5. Open the pressure relief valve to bleed any remaining air from the tank, then close.
6. If so equipped, turn the venting (burping) screw in the center of the pump two (2) turns open (water will drip out), wait until all air is purged from the pump, then tighten the plug. Use vent couplings to bleed air from the lines.
7. Carefully inspect all plumbing for water leaks and correct as required.
8. Before restoring electrical supply to the water heater, adjust the temperature setting on the tank.
• On tanks with both upper and lower elements,
the lower element should be turned down to the lowest setting, approximately 37.8°C. The upper element should be adjusted to 48.9°C to
54.4°C. Depending upon the specific needs of the customer, you may want to adjust the upper element differently.
• On tanks with a single element, lower the
thermostat setting to 48.9°C.
9. After the thermostat(s) is adjusted, replace the access cover and restore electrical supply to the water heater.
10. Make sure that any valves in the hot water generator water circulating circuit are open.
11. Use an AID Tool to enable HWG and select the desired water heating set point. Selectable set points are 37.8°C – 60°C in 5°C increments (default 54.4°C). From the Main Menu of the AID Tool select Setup, then AXB Setup.
12. Turn on the unit to first stage heating..
13. The hot water generator pump should be running. When the pump is first started, turn the venting (burping) screw (if equipped) in the center of the pump two (2) turns open until water dribbles out, then replace. Allow the pump to run for at least five minutes to ensure that water has filled the circulator properly. Be sure the switch for the hot water generator pump is “ON”.
14. Allow the unit to heat water for 15 to 20 minutes to be sure operation is normal.
CAUTION: Never operate the HWG circulating pump while dry. If the unit is placed in operation before the hot water generator piping is connected, be sure that the pump switch is set to the OFF position.
12

Electrical Connections

7 SERIES 50Hz 700A11 INSTALLATION MANUAL
General
Be sure the available power is the same voltage and phase as that shown on the unit serial plate. Line and low voltage wiring must be done in accordance with local codes or the National Electric Code, whichever is applicable. The compressor has no internal overload. The circuit breaker in the control box is the overload protection for the drive and the compressor. Bypassing the circuit breaker could result in damage to the compressor and voiding the warranty.
Unit Power Connection
Connect the incoming line voltage wires to L1 and L2 of the contactor as shown in Figure 13c for single-phase unit. Consult the Unit Electrical Data in this manual for correct fuse sizes.
Open lower front access panel. Remove ground fastener from bottom of control box (Figure 13b). Swing open control box (Figure 13a). Insert power wires through knockouts on lower left side of cabinet. Route wires through left side of control box and connect to contactor and ground (Figure 13c). Close control box and replace grounding fastener before unit startup.
CAUTION: Frequent cycling of power to the drive can damage the drive! Wait at least 5 minutes between cycles (connecting and disconnecting power to the drive).
Accessory Relay
A set of “dry” contacts has been provided to control accessory devices, such as water solenoid valves on open loop installations, electronic air cleaners, humidifiers, etc. This relay contact should be used only with 24 volt signals and not line voltage power. The relay has both normally open and normally closed contacts and can operate with either the blower or the compressor. Use DIP switch SW2-4 and 5 to cycle the relay with blower, compressor, or control a slow opening water valve. The relay contacts are available on terminals #2 and #3 of P2.
A second configurable accessory relay is provided on the AXB board. When powering high VA draw components such as electronic air cleaners or VM type open loop water valves, R should be taken ‘pre-fuse’ from the ‘R’ quick connect on the ABC board and not the ‘post-fuse’ ‘R’ terminal on the thermostat connection. If not, blown ABC fuses might result.
220 Volt Operation
All 220-240 units are factory wired for 240 volt operation. For 220 volt operation, the red and blue transformer wires must be switched on terminal strip PS.
Figure 13a:
Wire access (control box open)
Wire Insert
Location
Figure 13b:
Wire access (control box closed)
Ground Fastener
must be installed for
proper unit ground
Figure 13c:
Line Voltage 220-240/50/1 control box
CB
PB1
L2
L1
Compressor
Drive
Overload
L1
L2
13
7 SERIES 50Hz 700A11 INSTALLATION MANUAL
Electrical Connections cont.
Pump Power Wiring
See Figure 14 for electrical connections from control box to pumps.
FC1/FC2 style flow centers with fixed speed pumps connect to PB1 in the control box. If using a variable speed pump it should be connected to L1 and L2 on the AXB.
Figure 14: Pump Wiring 220-240/50/1
CB
PB1
L1
L2
External Loop Pump(s)
(ex. UP26-99)
220-240/50/1
1/2 hp Max
Wire Nuts
(Optional)
External Variable
Speed Loop Pump
(ex. Magna Geo)
220-240/50/1

Electronic Thermostat Installation

Position the thermostat subbase against the wall so that it is level and the thermostat wires protrude through the middle of the subbase. Mark the position of the subbase mounting holes and drill holes with a 0.1875mm bit. Install supplied anchors and secure base to the wall. Thermostat wire must be 4-conductor, 20-AWG (minimum) wire. Strip the wires back 6.35mm (longer strip lengths may cause shorts) and insert the thermostat wires into the connector as shown. Tighten the screws to ensure secure connections. The thermostat has the same type connectors, requiring the same wiring. See instructions enclosed in the thermostat for detailed installation and operation information. The W1 terminal on TPCM32U04 communicating thermostats may be hard wired to provide aux/emergency heat in the event communication is lost between the thermostat and the ABC microprocessor.
Figure 15: Thermostat Wiring (Communicating Style Signals)
P7
C
ABC Controller
R – +
P1
W
C 24VAC (Common) R 24VAC (Hot)
B- Communication A+ Communication
W1 (Optional)
TPCM32U04
Monochrome Thermostats
Thermostat Connection
Controller
ABC
P7
C R – +
C 24VAC (Common) R 24VAC (Hot)
DX- Communication DX+ Communication
TPCC32U01
Color Touchscreen
Thermostat
Connection
NOTE: If using the IntelliZone2 zoning system, then disregard the diagrams above. The IntelliZone2 system will connect directly to the AXB control board instead. See the IntelliZone2 installation manual for more details.
Thermostat
14

Auxiliary Heat Ratings

7 SERIES 50Hz 700A11 INSTALLATION MANUAL
Model
EAL(H)10
EAL(H)15
EAL(H)20
Air flow level for auxiliary heat (Aux) must be above the minimum air flow in this table Order the “H” part number when installed on horizontal and vertical rear discharge units
kW
208V 230V 009 012 015
7.2 9.6 2 519
10.8 14.4 3 590
14.4 19.2 4 708
Stages Min L/s

Auxiliary Heat Electrical Data

Model
EAL(H)10
EAL(H)15
EAL(H)20
All heaters rated single phase 60 cycle and include unit fan load All fuses type “D” time delay (or HACR circuit breaker in USA)
Supply Circuit
Single 34.7 40 53.3 60 60 60 60 60 60 60
Single 52.0 60 75 85 80 90 80 90 70 100
L1/L2 34.7 40 53.3 60 60 60 60 60 60 60
L3/L4 17.3 20 21.7 25 25 25 25 25 20 30
Single 69.3 80 96.7 110 100 110 100 110 100 100
L1/L2 34.7 40 53.3 60 60 60 60 60 60 60
L3/L4 34.7 40 43.3 50 45 50 45 50 40 50
Heater Amps Min Circuit Amp Max Fuse (USA) Max Fuse (CAN) Max CKT BRK
208 V 240 V 208 V 240 V 208 V 240 V 208 V 240 V 208 V 240 V
Model Compatibility
7/17/13
6/1/12

Electrical Data

Model
009
*009
012
015
*With optional 1 hp Variable Speed ECM Motor Rated Voltage of 220-240/50/1 HACR circuit breaker in USA only All fuses Class RK-5
Rated
Voltage
220-240/50/1 198/264 10.2 18.0 22.0 30.0 0.4 5.4 4.0 31.8 37.3 40
220-240/50/1 198/264 10.2 18.0 22.0 30.0 0.4 5.4 7.0 34.8 40.3 45
220-240/50/1 198/264 12.0 23.5 28.0 35.0 0.4 5.4 7.0 40.8 47.8 50
220-240/50/1 198/264 12.0 30.0 33.0 40.0 0.4 5.4 7.0 45.8 54.1 60
Voltage
Min/Max
Compressor Drive
LRA CMCC LRA
Internal Breaker
HWG
Pump
FLA
Ext Loop
FLA
Blower
Motor
FLA
Total Unit
FLA
Minimum
Circuit
Amp
Max Fuse
HACR
Breaker
5/08/13
15
Loading...
+ 33 hidden pages