Water Furnace 500A11 5 Series, 500A11 Installation Manual

500A11
mation
s
nntion
s
en
ce
Geothermal Heat Pump
• R-410A Refrigerant
• 1, 1.5, 2, 2.5, 3, 3.5, 4, 5, 6 Ton Single Speed
• 2, 3, 4, 5, 6 Ton Dual Capacity
Installation Information
Water Piping Connections
Hot Water Generator Connections
Electrical
Startup Procedures
Troubleshooting
Preventive Maintenance
nnection
ures
CUS
IM2500AN 02/13
Table of Contents
Model Nomenclature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
General Installation Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Closed Loop Ground Source Systems. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Open Loop Ground Water Systems. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11
Hot Water Generator Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Electrical Connections. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Electronic Thermostat Installation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Auxiliary Heat Ratings. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Auxiliary Heat Electrical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Electrical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
5 SERIES 500A11 INSTALLATION MANUAL
Blower Performance Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Dimensional Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Physical Data. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
The Aurora™ Control System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .30
Reference Calculations and Legend . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
Wiring Schematics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .40
Unit Startup. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
Operating Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .50
Pressure Drop . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
Compressor and Thermistor Resistance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
Refrigerant Circuit Guideline . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
Heat of Extraction/Rejection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .54
Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
Preventive Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59
Replacement Procedures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59
Service Parts List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .60
5 SERIES 500A11 INSTALLATION MANUAL
Model Nomenclature
1N2D3V4-6
0497G819110111C12T13L14015A16N
Model Type
N = 5 Series Water-to-Air
Compressor Type
D = Dual Capacity S = Single Speed
Cabinet Configuration
V = Vertical H = Horizontal
Unit Capacity
012, 018, 022, 026, 030, 036, 038, 042, 048, 049, 060, 064, 070, 072
Vintage
G = Current
Voltage
1 = 208-230/60/1
Hot Water Generation
0 = No Hot Water Generation 1 = Hot Water Generation with factory installed pump (018-072)
Blower Options
0 = PSC 1 = Variable Speed ECM (018-072) 2 = High Static Variable Speed ECM (036-049) 3 = High Static PSC (022, 030, 036, 042, 048) 4 = 5-Speed ECM (022-072)
IntelliStart Options
N = None A = IntelliStart (022-072)
Controls Options
TM
A = Aurora
Base Control (ABC) B = Aurora Advanced Control (ABC and AXB) C = Aurora Performance Package (018-072)
2
D = Aurora Performance and Refrigeration Package (018-072)
Filter Option
0 = 2 in. MERV 11 Filter 1 = AlpinePure 411 (022-072)
1
Return Air Configuration
L = Left R = Right
Discharge Air Configuration
T = Top (vertical) S = Side (horizontal) E = End (horizontal) B = Bottom (vertical 022-072) R = Rear (vertical 042-072)
Water Coil Options
C = Copper N = Cupronickel
2
NOTES: All models include sound kits as standard equipment.
1
Available on vertical configurations only (not available on horizontal models).
2
Control option not available with PSC motor.
4
General Installation Information
5 SERIES 500A11 INSTALLATION MANUAL
Safety Considerations
WARNING: Before performing service or maintenance operations on a system, turn off main power switches to the indoor unit. If applicable, turn off the accessory heater power switch. Electrical shock could cause personal injury.
Installing and servicing heating and air conditioning equipment can be hazardous due to system pressure and electrical components. Only trained and qualified service personnel should install, repair or service heating and air conditioning equipment. Untrained personnel can perform the basic maintenance functions of cleaning coils and cleaning and replacing filters. All other operations should be performed by trained service personnel. When working on heating and air conditioning equipment, observe precautions in the literature, tags and labels attached to the unit and other safety precautions that may apply.
Follow all safety codes. Wear safety glasses and work gloves. Use a quenching cloth for brazing operations and have a fire extinguisher available.
Moving and Storage
Move units in the normal “up” orientation. Horizontal units may be moved and stored per the information on the packaging. Do not stack more than three units in total height. Vertical units may be stored one upon another to a maximum height of two units. Do not attempt to move units while stacked. When the equipment is received, all items should be carefully checked against the bill of lading to be sure all crates and cartons have been received. Examine units for shipping damage, removing the units from the packaging if necessary. Units in question should also be internally inspected. If any damage is noted, the carrier should make the proper notation on the delivery receipt, acknowledging the damage.
Filter Rack Conversion
A 2 in. MERV 11 filter is shipped with the heat pump. To field convert the filter rack to use 1 in. filters, simply insert the provided plastic push pins into the holes located in the filter rack. There are holes on the top and bottom of the rack, underneath the instruction labels, for field conversion to 1 in. filters.
Installing Vertical Units
Prior to setting the unit in place, remove and discard the compressor hold down shipping bolt located at the front of the compressor mounting bracket.
Vertical units are available in left or right air return configurations. Top and rear air discharge vertical units should be mounted level on a vibration absorbing pad slightly larger than the base to provide isolation between the unit and the floor. It is not necessary to anchor the unit to the floor (see below).
Bottomflow units should be mounted level and sealed well to floor to prevent air leakage. Bottomflow units require the supply air opening to be cut at least 1/2 in. larger than the unit’s air outlet. Protect the edges of combustible flooring with sheet metal over-wrap or other non­combustible material.
Figure 1: Vertical Unit Mounting
Unit Location
Locate the unit in an indoor area that allows for easy removal of the filter and access panels. Location should have enough space for service personnel to perform maintenance or repair. Provide sufficient room to make water, electrical and duct connection(s). If the unit is located in a confined space, such as a closet, provisions must be made for return air to freely enter the space by means of a louvered door, etc. Any access panel screws that would be difficult to remove after the unit is installed should be removed prior to setting the unit. On horizontal units, allow adequate room below the unit for a condensate drain trap and do not locate the unit above supply piping. Care should be taken when units are
located in unconditioned spaces to prevent damage from frozen water lines and excessive heat that could damage electrical components.
2 in. Extruded Polystyrene
5
5 SERIES 500A11 INSTALLATION MANUAL
General Installation Information cont.
Installing Horizontal Units
Remove and discard the compressor hold down shipping bolt located at the front of the compressor mounting bracket prior to setting the unit in place. Horizontal units are available with side or end discharge. Horizontal units are normally suspended from a ceiling by four or six 3/8 in. diameter threaded rods. The rods are usually attached to the unit by hanger bracket kits furnished with each unit.
Lay out the threaded rods per the dimensions in Figure
3. Assemble the hangers to the unit as shown. Securely tighten the brackets to the unit using the weld nuts located on the underside of the bottom panel. When attaching the hanger rods to the bracket, a double nut is required since vibration could loosen a single nut. To allow filter access, one bracket on the filter side should be installed 180° from
Figure 2: Horizontal Unit Mounting
O
Threaded Rods
To Line
Power
To Thermostat
Hanging Brackets
(Included)
Hose
Kits
Flexible Duct Collar
Insulate supply plenum and use at least one 90 elbow to reduce noise
the position shown in Figure 3. The unit should be pitched approximately 1/4-inch towards the drain in both directions to facilitate the removal of condensate. Use only the bolts provided in the kit to attach hanger brackets. The use of longer bolts could damage internal parts.
Some residential applications require the installation of horizontal units on an attic floor. In this case, the unit should be set in a full size secondary drain pan on top of a vibration absorbing pad. The secondary drain pan prevents possible condensate overflow or water leakage damage to the ceiling. The secondary drain pan is usually placed on a plywood base isolated from the ceiling joists by additional layers of vibration absorbing material.
CAUTION: Do not use rods smaller than 3/8-inch diameter since they may not be strong enough to support the unit. The rods must be securely anchored to the ceiling.
Electrical
Disconnect
Line Voltage
Building Water Loop
Ball Valves
6
General Installation Information cont.
Figure 3: Hanger Location and Assembly
4
/
5 SERIES 500A11 INSTALLATION MANUAL
:STb@WUVb
0
2
Hanger Dimensions
Model
012
018
022-030
036
Single Speed
042-048
060-070
026
038
049
Dual Capacity
064
072
in.
cm. 113.5 63.8 54.4 n/a
in.
cm. 136.4 63.8 54.4 n/a
in.
cm. 161.0 63.0 53.6 n/a
in.
cm. 183.9 70.6 61.2 74.4
in.
cm. 196.6 70.6 61.2 74.4
in.
cm. 209.3 70.6 61.2 74.4
in.
cm. 161.0 63.0 53.6 n/a
in.
cm. 183.9 70.6 61.2 74.4
in.
cm. 196.6 70.6 61.2 74.4
in.
cm. 209.3 70.6 61.2 74.4
in.
cm. 209.3 70.6 61.2 74.4
Hanger Kit
Part Number
99S500A04
99S500A04
99S500A04
99S500A03
99S500A03
99S500A03
99S500A04
99S500A03
99S500A03
99S500A03
99S500A03
!
1
"
/W`1]WZ
Unit Hanger Dimensions
ABCD
44.7 25.1 21.4 n/a
53.7 25.1 21.4 n/a
63.4 24.8 21.1 n/a
72.4 27.8 24.1 29.3
77.4 27.8 24.1 29.3
82.4 27.8 24.1 29.3
63.4 24.8 21.1 n/a
72.4 27.8 24.1 29.3
77.4 27.8 24.1 29.3
82.4 27.8 24.1 29.3
82.4 27.8 24.1 29.3
!&BV`SORSR
@]RPg]bVS`a
2/8/12
6Sf<cba  Pg]bVS`a
0]ZbO\R :]QYEOaVS`
DWP`ObW]\ 7a]ZOb]`
EOaVS`
/W`1]WZ
"
!
Weight Distribution
Horizontal Weight Distribution
Front Back
1234
012
018
Vertical
Weight
185 185 70 45 45 25
[84] [84] [32] [20] [20] [11]
220 220 84 44 59 33
[100] [100] [38] [20] [27] [15]
313 320 122 64 86 48
[142] [145] [55] [29] [39] [22]
328 335 130 42 105 59
[149] [152] [59] [19] [47] [27]
373 388 147 94 94 52
[169] [176] [67] [43] [43] [24]
388 423 161 56 130 76
[176] [192] [73] [25] [59] [35]
428 438 136 114 123 66
[194] [199] [62] [52] [56] [30]
463 473 147 123 132 71
[210] [214] [67] [56] [60] [32]
488 498 154 129 139 75
[221] [226] [70] [59] [63] [34]
313 320 121 78 78 43
[142] [145] [55] [35] [35] [20]
378 388 147 94 94 52
[171] [176] [67] [43] [43] [24]
428 438 136 114 123 66
[194] [199] [62] [52] [56] [30]
473 483 150 126 135 72
[214] [219] [68] [57] [61] [33]
488 500 155 130 140 75
[221] [226] [70] [59] [64] [34]
Model
022
030
036
Single Speed
042
048
060
070
026
038
049
Dual Capacity
064
072
Weights are listed in lbs. [kg] 2/29/12
Horizontal
Weight
7
5 SERIES 500A11 INSTALLATION MANUAL
General Installation Information cont.
Duct System
An air outlet collar is provided on vertical top and rear air discharge units and all horizontal units to facilitate a duct connection (vertical bottomflow units have no collar). A flexible connector is recommended for discharge and return air duct connections on metal duct systems. Uninsulated duct should be insulated with a minimum of 1-inch duct insulation. Application of the unit to uninsulated ductwork in an unconditioned space is not recommended as the unit’s performance will be adversely affected.
If the unit is connected to existing ductwork, check the duct system to ensure that it has the capacity to accommodate the air required for the unit application. If the duct is too small, as in the replacement of heating only systems, larger ductwork should be installed. All existing ductwork should be checked for leaks and repaired if necessary.
The duct system should be sized to handle the design airflow quietly and efficiently. To maximize sound attenuation of the unit blower, the supply and return plenums should include an internal duct liner of fiberglass or constructed of ductboard for the first few feet. On systems employing a sheet metal duct system, canvas connectors should be used between the unit and the ductwork. If air noise or excessive airflow is a problem, the blower speed can be changed.
CAUTION: When attaching ductwork or accessories to the cabinet, make sure the fasteners do not come into contact with the air coil.
the swivel connector prior to attempting any connection. The rubber seals are shipped attached to the waterline. To make the connection to a ground loop system, mate the brass connector (supplied in CK4LI connector kit) against the rubber gasket in the swivel connector and thread the female locking ring onto the pipe threads, while maintaining the brass connector in the desired direction. Tighten the connectors by hand, then gently snug the fitting with pliers to provide a leak-proof joint. When connecting to an open loop (ground water) system, thread any 1-inch MPT fitting (SCH80 PVC or copper) into the swivel connector and tighten in the same manner as noted above. The open and closed loop piping system should include pressure/temperature taps for serviceability.
Never use flexible hoses smaller than 1-inch inside diameter on the unit. Limit hose length to 10 feet per connection. Check carefully for water leaks.
Figure 4: Swivel Connections
Stainless Steel Snap Ring
Gasket Material
Locking Ring
Gasket Support Sleeve
Water Piping
The proper water flow must be provided to each unit whenever the unit operates. To assure proper flow, use pressure/temperature ports to determine the flow rate. These ports should be located at the supply and return water connections on the unit. The proper flow rate cannot be accurately set without measuring the water pressure drop through the refrigerant-to-water heat exchanger.
All source water connections on residential units are swivel piping fittings (see Figure 4) that accept a 1-inch male pipe thread (MPT). The swivel connector has a rubber gasket seal similar to a rubber hose gasket, which when mated to the flush end of any 1-inch threaded pipe provides a leak-free seal without the need for thread sealing tape or compound. Check to ensure that the rubber seal is in
8
General Installation Information cont.
5 SERIES 500A11 INSTALLATION MANUAL
Water Quality
In ground water situations where scaling could be heavy or where biological growth such as iron bacteria will be present, a closed loop system is recommended. The heat exchanger coils in ground water systems may, over a period of time, lose heat exchange capabilities due to a buildup of mineral deposits inside. These can be cleaned, but only by a qualified service mechanic, as special solutions and pumping equipment are required. Hot water generator coils
Material Copper 90/10 Cupronickel 316 Stainless Steel
pH Acidity/Alkalinity
Scaling
Corrosion
Iron Fouling
(Biological Growth)
Erosion
NOTES: Grains = ppm divided by 17
mg/L is equivalent to ppm
Calcium and
Magnesium Carbonate
Hydrogen Sulfide
Chlorine Less than 0.5 ppm Less than 0.5 ppm Less than 0.5 ppm
Chlorides Less than 20 ppm Less than 125 ppm Less than 300 ppm
Carbon Dioxide Less than 50 ppm 10 - 50 ppm 10 - 50 ppm
Ammonia Less than 2 ppm Less than 2 ppm Less than 20 ppm
Ammonia Chloride Less than 0.5 ppm Less than 0.5 ppm Less than 0.5 ppm
Ammonia Nitrate Less than 0.5 ppm Less than 0.5 ppm Less than 0.5 ppm
Ammonia Hydroxide Less than 0.5 ppm Less than 0.5 ppm Less than 0.5 ppm
Ammonia Sulfate Less than 0.5 ppm Less than 0.5 ppm Less than 0.5 ppm
Total Dissolved Solids (TDS) Less than 1000 ppm 1000 - 1500 ppm 1000 - 1500 ppm
LSI Index +0.5 to -0.5 +0.5 to -0.5 +0.5 to -0.5
Iron, FE
Bacterial Iron Potential
Iron Oxide
Suspended Solids
Threshold Velocity
(Fresh Water)
Less than 0.5 ppm (rotten egg
Sulfates Less than 125 ppm Less than 125 ppm Less than 200 ppm
2
+ (Ferrous)
smell appears at 0.5 ppm)
Less than 1 ppm, above this
level deposition will occur
Less than 10 ppm and filtered
for max. of 600 micron size
7 - 9 7 - 9 7 - 9
(Total Hardness)
less than 350 ppm
< 0.2 ppm < 0.2 ppm < 0.2 ppm
< 6 ft/sec < 6 ft/sec < 6 ft/sec
can likewise become scaled and possibly plugged. In areas with extremely hard water, the owner should be informed that the heat exchanger may require occasional flushing.
Units with cupronickel heat exchangers are recommended for open loop applications due to the increased resistance to build-up and corrosion, along with reduced wear caused by acid cleaning. Failure to adhere to the guidelines in the water quality table could result in the loss of warranty.
(Total Hardness)
less than 350 ppm
10 - 50 ppm Less than 1 ppm
Less than 1 ppm, above this
level deposition will occur
Less than 10 ppm and filtered
for max. of 600 micron size
(Total Hardness)
less than 350 ppm
Less than 1 ppm, above this
level deposition will occur
Less than 10 ppm and filtered
for max. of 600 micron size
2/22/12
Low Water Coil Limit
Set the freeze sensing switch SW2-1 on the Aurora Base Control (ABC) printed circuit board for applications using a closed loop antifreeze solution to “LOOP” (15°F). On applications using an open loop/ground water system (or closed loop no antifreeze), set this dip switch to “WELL” (30°F), the factory default setting. (Refer to the DIP Switch Settings table in the Aurora Control section.)
Condensate Drain
On vertical units, the internal condensate drain assembly consists of a drain tube which is connected to the drain pan, a 3/4-inch PVC female adapter and a flexible connecting hose. The female adapter may exit either the front or the side of the cabinet. The adapter should be glued to the field-installed PVC condensate piping. On vertical units, a condensate hose is inside all cabinets as a trapping loop; therefore, an external trap is not necessary.
On horizontal units, a PVC stub is provided for condensate drain piping connection. An external trap is required (see below). If a vent is necessary, an open stand pipe may be applied to a tee in the field-installed condensate piping.
Figure 5: Horizontal Drain Connection
PVC coupling
PVC tube stub
NOTE: Check dimensional data for actual PVC sizes.
1.5 in.
1.5 in.
Figure 6: Unit Pitch for Drain
9
Vent (if needed)
PVC tube stub 1/8 in. per foot
1/2'' Pitch
Drain
5 SERIES 500A11 INSTALLATION MANUAL
Closed Loop Ground Source Systems
NOTE: For closed loop systems with antifreeze protection,
set SW2-1 to the “LOOP” (15°F) position. (Refer to the DIP Switch Settings table in the Aurora Control section.)
Once piping is completed between the unit, pumps and the ground loop (see figure below), final purging and charging of the loop is required. A flush cart (or a 1.5 HP pump minimum) is needed to achieve adequate flow velocity in the loop to purge air and dirt particles from the loop itself. Antifreeze solution is used in most areas to prevent freezing. Flush the system adequately to remove as much air as possible then pressurize the loop to a static pressure of 40-50 psi (summer) or 50-75 psi (winter). This is normally adequate for good system operation. Loop static pressure will fluctuate with the seasons. Pressures will be higher in the winter months than during the cooling season. This fluctuation is normal and should be considered when initially charging the system.
After pressurization, be sure to turn the venting (burping) screw in the center of the pump two (2) turns open (water will drip out), wait until all air is purged from the pump, then tighten the plug. Ensure that the loop pumps provide adequate flow through the unit(s) by checking the pressure drop across the heat exchanger and comparing it to the unit capacity data in this catalog. 2.5 to 3 gpm of flow per ton of cooling capacity is recommended in earth loop applications.
Figure 7: Closed Loop Ground Source Application
Disconnects
(If Applicable)
Unit Supply
Auxiliary Heat Supply
Low
Voltage to
Thermostat
P/T Plugs
Vibration Absorbing Pad
®
GeoLink
Polyethylene w/
®
Armaflex Insulation
Flexible Duct Collar
Auxiliary Heater Knockout
Unit Power
Hot Water Generator Connections
Drain
P/T
®
GeoLink
low
F enter
C
Insulated piping or hose kit
TO
LOOP
NOTE: Additional information can be found in Flow Center installation manual and Flush Cart manual.
Multiple Units on One Flow Center
NOTE: This feature is only available in the Aurora Advanced
Control package (AXB board), NOT the Aurora Base Control (ABC).
When two units are connected to one loop pumping system, pump control is automatically achieved by connecting the SL terminals on connector P2 in both units with 2-wire thermostat wire. These terminals are polarity dependant (see Figure 8b). The loop pump(s) may be powered from either unit, whichever is more convenient. If either unit calls, the loop pump(s) will automatically start. The use of two units on one flow center is generally limited to a total of 20 gpm capacity.
NOTE: To achieve this same feature when heat pumps have only the Aurora Base Control, follow Figure 8a. Installer will be required to supply fuses, two relays, and wiring.
Variable Speed Pump Setup
When using a variable speed pump flow center (FCV1-GL or FCV2-GL) the use of an AID Tool will be necessary to adjust minimum and maximum flow rates. The factory default is: minimum=75% and maximum=100% speed levels.
Figure 8a: Primary/Secondary Wiring with Aurora Base Control (no AXB Board)
Ext Pump
1/2 hp Total
208-230/60/1
Pump
G
Pump
Circuit
Breaker
PB1
1
1
1
2
2
Circuit
Breaker
Field Supplied Relay for Heat
5A
5A
Pump 2
Hot Water
Limit Switch
130°F
HWG Pump
Cabinet
HW Switch
Blue
Optional Internal
HWG Pump
Cap
Field Supplied
Fuses 5A
Purple
3
2
1
Field Supplied Relay for Heat
Pump 1
Figure 8b: Primary/Secondary Hook-up
5 Series to
Envision Units
5 Series Unit #1
with AXB Board
With pump wired to Unit 1
Shut
Down
Envision Unit #2
OUTIN C C
CC
VSSLOSLI
With pump wired to Unit 2
SL1InSL1
Out
Electromechanical Units
To Electromechanical Unit
With pump wired to Unit 1
With pump wired to Unit 2
5 Series to
5 Series Units
5 Series Unit #1
with AXB Board
OUTIN C C
OUTIN C C
5 Series Unit #2
with AXB Board
VSSLOSLI
VSSLOSLI
Compressor
Blue
CRS
Red
Black
Tan(6)
T1
T2
CC
L2
L1
5 Series to
5 Series Unit #1
with AXB Board
OUTIN C C
C
S
Heat Pump 1
Contactor Coil
Heat Pump 2
Contactor Coil
VSSLOSLI
10
Open Loop Ground Water Systems
5 SERIES 500A11 INSTALLATION MANUAL
Typical open loop piping is shown below. Always maintain water pressure in the heat exchanger by placing water control valves at the outlet of the unit to prevent mineral precipitation. Use a closed, bladder-type expansion tank to minimize mineral formation due to air exposure. Ensure proper water flow through the unit by checking pressure drop across the heat exchanger and comparing it to the figures in unit capacity data tables in the specification catalog. 1.5-2 gpm of flow per ton of cooling capacity is recommended in open loop applications.
Discharge water from the unit is not contaminated in any manner and can be disposed of in various ways, depending
Figure 9a: Open Loop Solenoid Valve Connection Option
Typical quick operating external 24V water solenoid valve (type PPV100 or BPV100) wiring.
C
P1
R
SV
Acc Com Acc NC Acc NO
1 2
P2
3
Solenoid
Valve
on local codes, i.e. recharge well, storm sewer, drain field, adjacent stream or pond, etc. Most local codes forbid the use of sanitary sewer for disposal. Consult your local building and zoning departments to assure compliance in your area.
NOTE: For open loop/groundwater systems or systems that do not contain an antifreeze solution, set SW2-Switch #1 to the “WELL” (30°F) position. (Refer to the DIP Switch Settings table in the Aurora Control section.) Slow opening/ closing solenoid valves (type VM) are recommended to eliminate water hammer.
Figure 9b: Open Loop Solenoid Valve Connection Option
Typical slow operating external 24V water solenoid valve (type VM) wiring and one (1) quick operating valve.
C R
VM Valve
Acc Com ACC NC
Acc NO
NOTE: SW2-4 and SW2-5 should be “OFF” to cycle with the compressor.
Figure 10: Open System - Groundwater Application
Unit Supply
Aux. Heat Supply
Flexible Duct Collar
Rubber Bladder Expansion Tank
Auxiliary
Disconnects
(IfApplicable)
Compressor Line Voltage
Low Voltage
to Thermostat
and Valve
P/T Plugs
Vibration
Absorbing Pad
Heater Knockout
Hot Water Generator
Connections
Drain
Strainer
Boiler Drains
For HX Flushing
Solenoid
Valve
valve while acid flushing)
Flow Control (on outlet of
Solenoid Valve)
Water Out
Shut Off Valves
Shut Off Valves
(to isolate solenoid
Valve
Water In
NOTE: SW2-4 should be “ON” and SW2-5 should be “OFF” when using a slow opening (VM) water valve.
Figure 9c: Modulating Water Valve Connection Option
Typical 0-10VDC modulating water valve.
AXB BOARD
2 1
GND
24 VAC
0-10DC
1 2
3
VS PUMP C R
ABC BOARD
11
5 SERIES 500A11 INSTALLATION MANUAL
Hot Water Generator Connections
To maximize the benefits of the hot water generator a minimum 50-gallon water heater is recommended For higher demand applications, use an 80-gallon water heater or two 50-gallon water heaters connected in a series as shown below. Two tanks plumbed in a series is recommended to maximize the hot water generator capability. Electric water heaters are recommended. Make sure all local electrical and plumbing codes are met for installing a hot water generator. Residential units with hot water generators contain an internal circulator and fittings. A water softener is recommended with hard water (greater than 10 grains or 170 total hardness).
NOTES: 1) Using a preheat tank, as shown in Figure 12, will maximize hot water generator capabilities. 2) The hot water generator coil is constructed of vented double wall copper suitable for potable water.
Water Tank Preparation
To install a unit with a hot water generator, follow these installation guidelines.
1. Turn off the power to the water heater.
2. Attach a water hose to the water tank drain connection and run the other end of the hose to an open drain or outdoors.
3. Close the cold water inlet valve to the water heater tank.
4. Drain the tank by opening the valve on the bottom of the tank, then open the pressure relief valve or hot water faucet.
5. Flush the tank by opening the cold water inlet valve to the water heater to free the tank of sediments. Close when draining water is clear.
6. Disconnect the garden hose and remove the drain valve from the water heater.
7. Refer to Plumbing Installation and Hot Water Generator Startup.
Figure 11: Typical Hot Water Generator Installation
3/4” x 3/4” x 1/2” tee
Venting Waste
Valve or Vent
Coupling
HWG
Water In
HWG
Water Out
Cold
Water In
P/T Relief
Drain Valve
Valve
Hot
Water Out
In
Figure 12: Hot Water Generator Installation In Preheat Tank
Venting Waste Valve or Vent Coupling
Water In
3/4" x 3/4" x 1/2" tee
HWG
HWG
Water Out
Cold
Water In
P/T Relief
Valve
Storage
Tank
Water Out
P/T Relief
In
Drain ValveDrain Valve
Electric Powered
Water Heater
Hot
Valve
NOTE: This configuration maximizes hot water generator capability.
CAUTION: Elements will burn out if energized dry.
12
Hot Water Generator Connections cont.
5 SERIES 500A11 INSTALLATION MANUAL
Plumbing Installation
1. Inspect the dip tube in the water heater cold inlet for a check valve. If a check valve is present it must be removed or damage to the hot water generator circulator will occur.
2. Remove drain valve and fitting.
3. Thread the 3/4-inch NPT x 3-1/2-inch brass nipple into the water heater drain port.
4. Attach the center port of the 3/4-inch FPT tee to the opposite end of the brass nipple.
5. Attach the 1/2-inch copper to 3/4-inch NPT adaptor to the side of the tee closest to the unit.
6. Install the drain valve on the tee opposite the adaptor.
7. Run interconnecting tubing from the tee to hot water generator water out.
8. Cut the cold water “IN” line going to the water heater.
9. Insert the reducing solder tee in line with cold water “IN” line as shown.
10.
Run interconnecting copper tubing between the unit hot water generator water “IN” and the tee (1/2-inch nominal). The recommended maximum distance is 50 feet.
11.
To prevent air entrapment in the system, install a vent coupling at the highest point of the interconnecting lines.
12. Insulate all exposed surfaces of both connecting water lines with 3/8-inch wall closed cell insulation.
NOTE: All plumbing and piping connections must comply with local plumbing codes.
Hot Water Generator Switch
The hot water generator switch is taped in the disabled position at the factory.
Hot Water Generator Startup
1. Turn the hot water generator switch to the “ON” position. The hot water generator switch will allow the hot water generator pump to be enabled or disabled by the service technician or homeowner.
2. Close the drain valve to the water heater.
3. Open the cold water supply to the tank.
4. Open a hot water faucet in the building to bleed air from the system. Close when full.
5. Open the pressure relief valve to bleed any remaining air from the tank, then close.
6. If so equipped, turn the venting (burping) screw in the center of the pump two (2) turns open (water will drip out), wait until all air is purged from the pump, then tighten the plug. Use vent couplings to bleed air from the lines.
7. Carefully inspect all plumbing for water leaks and correct as required.
8. Before restoring electrical supply to the water heater, adjust the temperature setting on the tank.
• On tanks with both upper and lower elements,
the lower element should be turned down to the lowest setting, approximately 100°F. The upper element should be adjusted to 120°F to 130°F. Depending upon the specific needs of the customer, you may want to adjust the upper element differently.
• On tanks with a single element, lower the
thermostat setting to 120°F.
9. After the thermostat(s) is adjusted, replace the access cover and restore electrical supply to the water heater.
10. Make sure that any valves in the hot water generator water circulating circuit are open.
11. Turn on the unit to first stage heating.
12. Use an AID Tool to enable HWG and select the desired water heating set point. Selectable set points are 100°F – 140°F in 5°F increments (default 130°F). From the Main Menu of the AID Tool select Setup, then AXB Setup.
13. The hot water generator pump should be running. When the pump is first started, turn the venting (burping) screw (if equipped) in the center of the pump two (2) turns open until water dribbles out, then replace. Allow the pump to run for at least five minutes to ensure that water has filled the circulator properly. Be sure the switch for the hot water generator pump switch is “ON”.
14. The temperature difference between the water entering and leaving the hot water generator should be 5°F to 15°F. The water flow should be approximately 0.4 gpm per ton of nominal cooling.
15. Allow the unit to heat water for 15 to 20 minutes to be sure operation is normal.
CAUTION: Never operate the HWG circulating pump while dry. If the unit is placed in operation before the hot water generator piping is connected, be sure that the pump switch is set to the OFF position.
13
5 SERIES 500A11 INSTALLATION MANUAL
Electrical Connections
General
Be sure the available power is the same voltage and phase as that shown on the unit serial plate. Line and low voltage wiring must be done in accordance with local codes or the National Electric Code, whichever is applicable.
Unit Power Connection
Connect the incoming line voltage wires to L1 and L2 of the contactor as shown in Figure 13C for single-phase unit. Consult the Unit Electrical Data in this manual for correct fuse sizes.
Open lower front access panel. Remove ground fastener from bottom of control box (Figure 13B). Swing open control box (Figure 13A). Insert power wires through knockouts on lower left side of cabinet. Route wires through left side of control box and connect to contactor and ground (Figure 13C). Close control box and replace grounding fastener before unit start-up.
Accessory Relay
A set of “dry” contacts has been provided to control accessory devices, such as water solenoid valves on open loop installations, electronic air cleaners, humidifiers, etc. This relay contact should be used only with 24 volt signals and not line voltage power. The relay has both normally open and normally closed contacts and can operate with either the fan or the compressor. Use DIP switch SW2-4 and 5 to cycle the relay with blower, compressor, or control a slow opening water valve. The relay contacts are available on terminals #2 and #3 of P2.
A second configurable accessory relay is provided on the AXB board, if installed. When powering high VA draw components such as electronic air cleaners or VM type open loop water valves, R should be taken ‘pre-fuse’ from the ‘R’ quick connect on the ABC board and not the ‘post­fuse’ ‘R’ terminal on the thermostat connection. If not, blown ABC fuses might result.
208 Volt Operation
All 208/230 units are factory wired for 230 volt operation. For 208 volt operation, the red and blue transformer wires must be switched on terminal strip PB2.
Figure 13A:
Wire access (control box open)
Wire Insert
Location
Figure 13B:
Wire access (control box closed)
Ground Fastener
must be installed for
proper unit ground
Figure 13C:
Line Voltage 208-230/60/1 control box
1
PB1
2
L2 L1
T1T2
1 2 3
PS
14
Electrical Connections cont.
5 SERIES 500A11 INSTALLATION MANUAL
Pump Power Wiring
See Figure 14 for electrical connections from control box to pumps.
FC1/FC2 style flow centers with fixed speed pumps connect to PB1 in the control box. If using a variable speed pump it should be connected to L1 and L2 on the AXB.
Figure 14: Pump Wiring 208-230/60/1
Optional External
Variable Speed Loop
Pump (ex. Magna Geo)
208-230/60/1
PB1
External Loop Pump(s) 208-230/60/1
1/2 hp Max
CB
Electronic Thermostat Installation
Position the thermostat subbase against the wall so that it is level and the thermostat wires protrude through the middle of the subbase. Mark the position of the subbase mounting holes and drill holes with a 3/16-inch bit. Install supplied anchors and secure base to the wall. Thermostat wire must be 8-conductor (4 or 5 counductor for communicating thermostats), 20-AWG (minimum) wire. Strip the wires back 1/4-inch (longer strip lengths may cause shorts) and insert the thermostat wires into the connector as shown. Tighten the screws to ensure secure connections. The thermostat has the same type connectors, requiring the same wiring. See instructions enclosed in the thermostat for detailed installation and operation information. The W1 terminal on TPCM32U03 and TPCM32U04 communicating thermostats may be hard wired to provide aux/emergency heat in the event communication is lost between the thermostat and the ABC microprocessor.
NOTE: Aurora Base Control (ABC) DIP switch SW2-7 is required to be in the “OFF” position for the control to operate with FaultFlash or ComforTalk thermostats. SW2-7 in the “ON” position configures the control to operate with typical thermostats (continuous lockout signal). There must be a wire connecting Y2 on the Aurora controller to 2nd stage compressor on the thermostat for proper operation. SW2-7 DIP switch position is not relevant with communicating thermostats.
Figure 15a: Thermostat Wiring (Y1 Style Signals)
R
C Y1 Y2
W
O
G
L
Microprocessor Controller
24VAC (Hot) 24VAC (Common)
Compressor (1st Stage)
Compressor (2nd Stage) Aux. Heat Reversing Valve Blower Relay
System Monitor
Thermostat Connection
Figure 15b: Thermostat Wiring (Communicating Style Signals)
P7
Microprocessor Controller
C R – +
P1
W
C 24VAC (Common) R 24VAC (Hot)
B- Communication A+ Communication
W1 (Optional)
TPCM32U03/TPCM32U04 Monochrome Thermostats
Thermostat Connection
P7
Microprocessor
Controller
C R
– +
C 24VAC (Common) R 24VAC (Hot)
DX- Communication DX+ Communication
TPCC32U01
Color Touchscreen
Thermostat
Connection
Thermostat
15
5 SERIES 500A11 INSTALLATION MANUAL
Auxiliary Heat Ratings
Model
EAS(H)4 2.9 3.8 1 9,700 12,900 250
EAM(H)5 3.6 4.8 1 12,300 16,300 450
EAM(H)8 5.7 7.6 2 19,400 25,900 550
EAM(H)10 7.2 9.6 2 24,600 32,700 650
EAL(H)10 7.2 9.6 2 24,600 32,700 1100
EAL(H)15 10.8 14.4 3 36,900 49,100 1250
EAL(H)20 14.4 19.2 4 49,200 65,500 1500
Order the “H” part number when installed on horizontal and vertical rear discharge units Air flow level for auxiliary heat (Aux) must be above the minimum cfm in this table
kW
208V 230V 208V 230V 012 018 022 026 - 030 036 - 042 048 - 072
Stages
Btu/h
Min cfm
Auxiliary Heat Electrical Data
Model
EAS(H)4
EAM(H)5
EAM(H)8
EAM(H)10
EAL(H)10
EAL(H)15
EAL(H)20
All heaters rated single phase 60 cycle and include unit blower load All fuses type “D” time delay (or HACR circuit breaker in USA) Supply wire size to be determined by local codes
Supply Circuit
Single 13.7 15.8 17.9 20.5 20 20 20 20 20 20
Single 17.3 20.0 26.7 30.0 30 30 30 30 30 30
Single 27.5 31.7 39.3 44.6 40 45 40 45 40 45
Single 34.7 40.0 48.3 55.0 50 60 50 60 50 60
Single 34.7 40.0 53.3 60.0 60 60 60 60 60 60
Single 52.0 60.0 75.0 85.0 80 90 80 90 70 100
L1/L2 34.7 40.0 53.3 60.0 60 60 60 60 60 60
L3/L4 17.3 20.0 21.7 25.0 25 25 25 25 20 30
Single 69.3 80.0 96.7 110.0 100 110 100 110 100 100
L1/L2 34.7 40.0 53.3 60.0 60 60 60 60 60 60
L3/L4 34.7 40.0 43.3 50.0 45 50 45 50 40 50
Heater Amps Min Circuit Amp Fuse (USA) Fuse (CAN) CKT BRK
208 V 240 V 208 V 240 V 208 V 240 V 208 V 240 V 208 V 240 V
Model Size Compatibility
•••
•••
••
••
5/8/12
2/11/12
16
Electrical Data
Single Speed Unit with Variable Speed ECM Motor
Model Rated Voltage
018
208-230/60/1 197/253 10.4 6.7 33.5 n/a 0.4 5.4 4.0 16.5 18.1 20
022
030
036
036*
042
042*
048
048*
060
070
* With optional 1 hp ECM motor ** With optional IntelliStart Rated voltage of 208/230/60/1 All fuses Class RK-5 HACR circuit breaker in USA only
208-230/60/1 197/253 14.0 9.0 48.0 17.0 0.4 5.4 4.0 18.8 21.0 30 208-230/60/1 197/253 20.0 12.8 58.3 21.0 0.4 5.4 4.0 22.6 25.8 35 208-230/60/1 197/253 22.0 14.1 73.0 26.0 0.4 5.4 4.0 23.9 27.4 40 208-230/60/1 197/253 22.0 14.1 73.0 26.0 0.4 5.4 7.0 26.9 30.4 40 208-230/60/1 197/253 26.0 16.6 79.0 28.0 0.4 5.4 4.0 26.4 30.6 45 208-230/60/1 197/253 26.0 16.6 79.0 28.0 0.4 5.4 7.0 29.4 33.6 50 208-230/60/1 197/253 31.0 19.8 109.0 38.0 0.4 5.4 4.0 29.6 34.6 50 208-230/60/1 197/253 31.0 19.8 109.0 38.0 0.4 5.4 7.0 32.6 37.6 50 208-230/60/1 197/253 41.2 26.4 134.0 47.0 0.4 5.4 7.0 39.2 45.8 70 208-230/60/1 197/253 44.2 28.3 178.0 63.0 0.4 5.4 7.0 41.1 48.2 70
Voltage
Min/Max
®
MCC RLA LRA LRA**
Single Speed Unit with 5-Speed ECM Motor
Model
022
030
036 042 048 060
070
** With optional IntelliStart Rated voltage of 208/230/60/1 All fuses Class RK-5 HACR circuit breaker in USA only
Rated
Voltage
208-230/60/1 197/253 14.0 9.0 48.0 17.0 0.4 5.4 4.1 18.9 21.1 30 208-230/60/1 197/253 20.0 12.8 58.3 21.0 0.4 5.4 4.1 22.7 25.9 35 208-230/60/1 197/253 22.0 14.1 73.0 26.0 0.4 5.4 4.1 24.0 27.5 40 208-230/60/1 197/253 26.0 16.6 79.0 28.0 0.4 5.4 7.6 30.0 34.2 50 208-230/60/1 197/253 31.0 19.8 109.0 38.0 0.4 5.4 7.6 33.2 38.2 50 208-230/60/1 197/253 41.2 26.4 134.0 47.0 0.4 5.4 7.6 39.8 46.4 70 208-230/60/1 197/253 44.2 28.3 178.0 63.0 0.4 5.4 7.6 41.7 48.8 70
Voltage
Min/Max
®
MCC RLA LRA LRA**
Compressor HWG
Compressor HWG
Pump
FLA
Pump
FLA
5 SERIES 500A11 INSTALLATION MANUAL
Ext
Loop
FLA
Ext
Loop
FLA
Blower
Motor
FLA
Blower
Motor
FLA
Total
Unit FLA
Total
Unit FLA
Min
Circ
Amp
Min
Circ
Amp
Max Fuse/ HACR
4/6/12
Max Fuse/ HACR
4/6/12
Single Speed Unit with PSC Motor
Model Rated Voltage
012
208-230/60/1 197/253 7.7 4.9 25.0 n/a - 5.4 0.6 10.9 12.2 15
018 022
022*
030
030*
036
036*
042
042*
048
048*
060
070
* With optional high static motor ** With optional IntelliStart Rated voltage of 208/230/60/1 All fuses Class RK-5 HACR circuit breaker in USA only
208-230/60/1 197/253 10.4 6.7 33.5 n/a 0.4 5.4 1.1 13.6 15.2 20 208-230/60/1 197/253 14.0 9.0 48.0 17.0 0.4 5.4 1.2 16.0 18.2 25 208-230/60/1 197/253 14.0 9.0 48.0 17.0 0.4 5.4 1.5 16.3 18.5 25 208-230/60/1 197/253 20.0 12.8 58.3 21.0 0.4 5.4 1.5 20.1 23.3 35 208-230/60/1 197/253 20.0 12.8 58.3 21.0 0.4 5.4 2.8 21.4 24.6 35 208-230/60/1 197/253 22.0 14.1 73.0 26.0 0.4 5.4 2.8 22.7 26.2 40 208-230/60/1 197/253 22.0 14.1 73.0 26.0 0.4 5.4 3.5 23.4 26.9 40 208-230/60/1 197/253 26.0 16.6 79.0 28.0 0.4 5.4 3.5 25.9 30.1 45 208-230/60/1 197/253 26.0 16.6 79.0 28.0 0.4 5.4 4.6 27.0 31.2 45 208-230/60/1 197/253 31.0 19.8 109.0 38.0 0.4 5.4 3.5 29.1 34.1 50 208-230/60/1 197/253 31.0 19.8 109.0 38.0 0.4 5.4 4.6 30.2 35.2 50 208-230/60/1 197/253 41.2 26.4 134.0 47.0 0.4 5.4 5.9 38.1 44.7 70 208-230/60/1 197/253 44.2 28.3 158.0 63.0 0.4 5.4 5.9 41.8 49.3 70
Voltage
Min/Max
®
MCC RLA LRA LRA**
Compressor HWG
17
Pump
FLA
Ext
Loop
FLA
Blower
Motor
FLA
Total
Unit FLA
Min
Circ
Amp
Max Fuse/ HACR
4/6/12
5 SERIES 500A11 INSTALLATION MANUAL
Electrical Data cont.
Dual Capacity Unit with Variable Speed ECM Motor
Model
026
038
038*
049
049*
064
072
* With optional 1 hp ECM motor ** With optional IntelliStart Rated voltage of 208/230/60/1 All fuses Class RK-5 HACR circuit breaker in USA only
Rated
Voltage
208-230/60/1 197/253 18.2 11.6 58.3 21.0 0.4 5.4 4.0 21.4 24.4 35 208-230/60/1 197/253 23.8 15.2 83.0 30.0 0.4 5.4 4.0 25.0 28.8 40 208-230/60/1 197/253 23.8 15.2 83.0 30.0 0.4 5.4 7.0 28.0 31.8 50 208-230/60/1 197/253 33.0 21.1 104.0 37.0 0.4 5.4 4.0 30.9 36.2 50 208-230/60/1 197/253 33.0 21.1 104.0 37.0 0.4 5.4 7.0 33.9 39.2 60 208-230/60/1 197/253 42.3 27.1 152.9 54.0 0.4 5.4 7.0 39.9 46.6 70 208-230/60/1 197/253 46.3 29.6 179.2 63.0 0.4 5.4 7.0 42.4 49.8 70
Voltage
Min/Max
®
MCC RLA LRA LRA**
Dual Capacity Unit with 5-Speed ECM Motor
Model
026 038 049
064
072
** With optional IntelliStart Rated voltage of 208/230/60/1 All fuses Class RK-5 HACR circuit breaker in USA only
Rated
Voltage
208-230/60/1 197/253 18.2 11.6 58.3 21.0 0.4 5.4 4.1 21.5 24.5 35 208-230/60/1 197/253 23.8 15.2 83.0 30.0 0.4 5.4 4.1 25.1 28.9 40 208-230/60/1 197/253 33.0 21.1 104.0 37.0 0.4 5.4 7.6 34.5 39.8 60 208-230/60/1 197/253 42.3 27.1 152.9 54.0 0.4 5.4 7.6 40.5 47.2 70 208-230/60/1 197/253 46.3 29.6 179.2 63.0 0.4 5.4 7.6 43.0 50.4 80
Voltage
Min/Max
®
MCC RLA LRA LRA**
Compressor HWG
Pump
Compressor HWG
Pump
FLA
FLA
Ext
Loop
FLA
Ext
Loop
FLA
Blower
Motor
FLA
Blower
Motor
FLA
Total
Unit FLA
Total
Unit FLA
Min
Circ
Amp
Min
Circ
Amp
Max Fuse/ HACR
4/6/12
Max Fuse/ HACR
4/6/12
18
5 SERIES 500A11 INSTALLATION MANUAL
Blower Performance Data
Single Speed Unit with Variable Speed ECM Motor
Model
018
022
030
036
036
w/1hp*
042
042
w/1hp*
048
048
w/1hp*
060
070
Factory settings are at recommended G-L-H-Aux speed settings
L-H settings MUST be located within boldface cfm range
“Aux” is factory setting for auxiliary heat and must be equal to or above the “H” setting as well as at least the minimum re­quired for the auxiliary heat package “G” may be located anywhere within the airflow table Cfm is controlled within ±5% up to the maximum ESP Max ESP includes allowance for wet coil and standard filter
Max ESP
0.50
0.50
0.50
0.50
0.75
0.50
0.75
0.50
0.75
0.75
0.75
123456789101112
300 400
G
400 500
400 500 600
650 750 850 1000
800 1000
G
650 800 900 1050
800 900 1000
G
650 800 900 1050 1150
800 900 1000 1200
800 950 1100 1300
800 950 1100 1300
500 600 700 800
LH
600 700 800 900
G
G
G
1100 1300 1500 1600
LH
G
G
G
G
LH
1200 1400 1600 1700 1850
LH
G
Airflow Speed Settings
875 950 1025 1125
1000 1100 1200
700 800 900 1000 1100
LH
1100 1200 1300 1400 1500
LH
1800 1950 2100 2200
1150 1250 1350 1450 1550
LH
2000 2200 2300 2400
1250 1350 1450 1550
LH
1400 1600 1700 1850
LH
1500 1750 1950 2100 2300
LH
1500 1750 1950 2100 2300
LH
2000 2200 2300 2400
Aux
Aux
1200
Aux
1550
Aux
Aux
1600
Aux
Aux
1600
Aux
Aux
2325
Aux
2325
Aux
6/8/12
Dual Capacity Unit with Variable Speed ECM Motor
Model Max ESP
026
038
038
w/1hp*
049
049
w/1hp*
064
072
Factory settings are at recommended G-L-H-Aux speed settings
L-H settings MUST be located within boldface cfm range
“Aux” is factory setting for auxiliary heat and must be equal to or above the “H” setting as well as at least the minimum required for the auxiliary heat package “G” may be located anywhere within the airflow table Cfm is controlled within ±5% up to the maximum ESP Max ESP includes allowance for wet coil and standard filter
0.50
0.50
0.75
0.50
0.75
0.75
0.75
123456789101112
400 500 600
G
650 750 850 1000
G
800 1000
G
650 800 900 1050 1150
G
800 900 1000 1200
G
800 950 1100 1300
G
800 950 1100 1300
1100 1300 1500 1600
LH
G
Airflow Switch Settings
700 800 900 1000
LH
1100 1200 1300 1400 1500
LH
1800 1875 1925 2000
1250 1350 1450 1550
LH
1400 1600 1700 1850
LH
1500 1750 1950 2100 2300
LH
1500 1750 1950 2100 2300
LH
1100 1200
2000 2200 2300 2400
Aux
1550
Aux
Aux
1575
Aux
Aux
2325
Aux
2325
Aux
6/8/12
19
5 SERIES 500A11 INSTALLATION MANUAL
Blower Performance Data cont.
Setting Blower Speed - ECM
The ABC board’s Yellow Config LED will flash the current ECM blower speed selections for “G”, low, and high continuously with a short pause in between. The speeds can also be confirmed with the AID Tool under the Setup/ ECM Setup screen. The Aux will not be flashed but can be viewed in the AID Tool. The ECM blower motor speeds can be field adjusted with or without using an AID Tool.
ECM Setup without an AID Tool
The blower speeds for “G”, Low (Y1), High (Y2), and Aux can be adjusted directly at the Aurora ABC board which utilizes the push button (SW1) on the ABC board. This procedure is outlined in the ECM Configuration Mode portion of the Aurora ‘Base’ Control System section. The Aux cannot be set manually without an AID Tool.
ECM Setup with an AID Tool
A much easier method utilizes the AID Tool to change the airflow using the procedure below. First navigate to the Setup screen and then select ECM Setup. This screen displays the current ECM settings. It allows the technician to enter the setup screens to change the ECM settings. Change the highlighted item using the and buttons and then press the button to select the item.
ECM Speed Info
Blower Only Speed 3 Lo Compressor 6 Hi Compressor 9 Aux Heat 10
Selecting YES will enter ECM speed setup, while selecting NO will return to the previous screen.
ECM Speed Setup - These screens allow the technician to select the “G”, low, high, and auxiliary heat blower speed for the ECM blower motor. Change the highlighted item using the and buttons. Press the button to select the speed.
ECM Speed Info
1
2 ◀ G 3 4 5 6 7 8 9 10 11 12
Option ◀▶ Enter
ECM Speed Info
1 2 G
3 ◀ Lo
4 5 6 7 8 9 10 11 12
Option ◀▶ Enter
ECM Speed Info
1 2 G 3 Lo 4 5
6 ◀ Hi 7 8 9 10 11 12
Option ◀▶ Enter
ECM Speed Info
1 2 G 3 Lo 4 5 6 Hi 7 8 9
10
◀ Aux 11 12
Option ◀▶ Enter
After the auxiliary heat speed setting is selected the AID Tool will automatically transfer back to the ECM Setup screen.
Cooling Airflow Setup - These screens allow the technician to select -15%, -10%, -5%, None or +5%. Change the adjustment percentage using the and buttons. Press the button to save the change.
Cooling Airflow Setup
--- ECM Only ---
The airflow will be
adjusted by the chosen
amount in cooling mode.
Adjustment:
-15%
Want To Change?
Yes
Option ◀▶No Enter
Cooling Airflow Setup
--- ECM Only ---
The airflow will be
adjusted by the chosen
amount in cooling mode.
Adjustment:
-15%
Change ▼▲ Enter
Want To Change?
Yes
Option ◀▶NoEnter
20
Loading...
+ 44 hidden pages