Warner Electric CBC-200 Series, CBC-200-C Series, CBC-200, CBC-200-1, CBC-200-2 Installation & Operating Instructions Manual

...
CBC-200 Series & CBC-200C Series Single
Channel Adjust Clutch/Brake Controls
Installation & Operating Instructions
P-269 819-0407
An Altra Industrial Motion Company
DIST. AUTORIZADO
MEX (55) 53 63 23 31 QRO (442) 1 95 72 60
MTY (81) 83 54 10 18 ventas@industrialmagza.com
2
Warner Electric • 800-825-9050 P-269
Contents
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Specifications . . . . . . . . . . . . . . . . . . . . . . . . . 3
Mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Electrical Connections . . . . . . . . . . . . . . . . . . . 6
Internal Adjustments . . . . . . . . . . . . . . . . . . . 11
Troubleshooting Checklist . . . . . . . . . . . . . . . 12
Warranty . . . . . . . . . . . . . . . . . . . . . . Back Page
or control panel. The standard version is offered the same as before, but with the chassis version added. The CBC-200-1 and CBC-200-C1 version is being offered where an external limit adjustment potentiometer is required. The CBC-200-2 and CBC-200-C2 version maintains the limit adjust potentiometer on the PC board but allows for an external potentiometer for level adjustment of the output. This allows the output to be controlled from zero to maximum level on both the current adjust channel and steady state output channel. The CBC-200-3 and CBC-200-C3 allow for both the current limit and level adjustment potentiometers to be mounted remotely.
Operations of all units are identical except for the method of the control potentiometer mounting. All units that have external poten­tiometer options have terminal blocks mounted on the PC boards for connection of the poten­tiometers.
The potentiometers used can be supplied either as optional accessory items or be obtained from a local electronic supply house.
A short circuit protection scheme is integral which trips on occurrence of line to line shorts on the output. No protection is provided for line to ground shorts because the unit is not isolated.
Two LED indicators are provided on the front panel of the control for “POWER” and “SHORT” indications. The green indicator marked “POWER” is illuminated whenever the AC input power is applied to the control. A red indicator marked “SHORT” is illuminated whenever a short circuit condition occurs in either of the outputs. To reset, power must be removed, the shorted condition cleared, and the AC input power reapplied to the control.
The enclosed version may be used with or without the cover. Removal of the plastic cover when the control is used in an enclosure will increase the operating temperature range of the control.
The chassis mount version does not have a cover and must be mounted in an enclosure or control panel.
Failure to follow these instructions may result in product dam­age, equipment damage, and serious or fatal injury to personnel.
Introduction
Warner Electric’s CBC-200 series Constant Current Clutch Brake Controls are solid-state electronic power supplies designed to operate any of the Warner Electric 90 Volt clutches and brakes, including fail safe designs. They can operate a single clutch or brake, two clutches, two brakes, a combination clutch and brake, or a combination clutch and fail safe brake, depending on the switching arrangement used and the application requirements.
The CBC-200 series controls operate from 120 VAC single-phase input power. They provide constant current output as set by the torque adjustment potentiometers on the front panel or remote potentiometer. Additionally, on some versions a level adjust can be used to set the operating level with the torque adjustment setting the maximum current level. On the CBC-200 series Channel 2 is a fixed output level and an adjustable output on Channel 1. Output current ranges are selectable for the adjustable output channels in one of five ranges by the DIP switches located on the control’s printed circuit board.
Several versions of the CBC-200 are provided to handle a wide range of applications. These include both enclosed and chassis mount versions for mounting in an external enclosure
DIST. AUTORIZADO
MEX (55) 53 63 23 31 QRO (442) 1 95 72 60
MTY (81) 83 54 10 18 ventas@industrialmagza.com
Specifications
Input Power: 120 VAC, +10%, -15%, 50/60 Hz,
single phase, 215 VA maximum.
Output: Pulse-width modulated full wave rectified
DC. Constant current, switch selectable ranges, for one channel and fixed 90VDC second channel, designed for 90 volt DC clutches and brakes.
Ambient Temperature: -32˚ F to + 113˚F (0˚C to + 45˚)
with plastic cover installed. -32˚F to +150˚F (0˚C to +66˚C) with plastic cover removed, or board assembly only.
Circuit Protection: Internal short circuit protection
on outputs, but no circuit protection for AC ground faults. Optional customer supplied fusing on AC line, 1.5 amps, 250 VAC Fast-Acting type fuse recommended.
Control Adjust: CBC-200 and CBC-200-C via front
panel potentiometer for current adjustment. CBC-200-1 and CBC-200-C1 via external mounted potentiometer for current adjustment.
CBC-200-2 and CBC-200-C2 current adjustment via front panel potentiometer and output level adjust via external potentiometer.
CBC-200-3 and CBC-200-C3 both current adjust and limit adjustment are via external potentiometers.
Status Indicators: “POWER” – green LED indicating
AC power is applied to the control.
“SHORT” – red LED indicating that a short circuit condition exists on one or both of the outputs.
Internal Adjustments: Current Range Selection via
DIP switch, SW1
Current Ranges:
Switch Setting 1 2 3 4 5 Max Output, ma 60 175 245 305 533
3
Warner Electric • 800-825-9050 P-269
External Switching: Mechanical or electromechanical
Electromechanical
Customer supplied; 1 amp, 125 V minimum rating.
Solid-state NPN isolated transistor
Customer supplied; 2 amp, 250V minimum rat­ing. Maximum off state leakage current < 1 ma.
External Pots:
Remote current adjust pot
customer supplied; 10,000 ohm, 2 watt, linear, maximum distance from control to potentiome­ter not to exceed 10 feet.
Optional Accessory Pot Kit; part number, 6011-101-002
Remote Level adjust pot
Customer supplied; 5,000 ohm, 2 watt, linear, maximum distance from control to potentiome­ter not to exceed 10 feet.
Optional Accessory Pot Kit; part number, 6011-101-001.
Wiring Entrance: Two 7/8” diameter entrance holes
located on the bottom of the control chassis on enclosed units. No conduit entrances are on chassis mount versions.
Enclosure: Rated NEMA 1 only – Control must be
kept clear of foreign materials, dust, grease and oil which might affect its operation.
Part Numbers:
Enclosed Versions
CBC-200 6011-448-001 CBC-200-1 6011-448-002 CBC-200-2 6011-448-003 CBC-200-3 6011-448-004
Chassis Versions
CBC-200-C 6011-448-005 CBC-200-C1 6011-448-006 CBC-200-C2 6011-448-007 CBC-200-C3 6011-448-008
DIST. AUTORIZADO
MEX (55) 53 63 23 31 QRO (442) 1 95 72 60
MTY (81) 83 54 10 18 ventas@industrialmagza.com
4
Warner Electric • 800-825-9050 P-269
Mounting
Enclosed Units
Any vertical, horizontal, or angled surface is suit­able for mounting the CBC-200, CBC-200-1, CBC-200-2, CBC-200-3 control.
Follow these procedures to mount your control.
1. Remove the front cover by removing the
top and bottom retaining screws.
2. Set the control on the mounting surface
and mark for the three mounting holes in accordance with “Dimensions.” (See Figure 1)
3. Install the top two mounting bolts or
screws until they are nearly flush, set the control over the larger top mounting holes and pull down to position the control.
4. Tighten the top bolts or screws and install
the bottom bolt or screw and tighten.
This completes the mounting of the control. The control is now ready for final wiring. Refer to the wiring section for final wiring.
If the CBC-200-1, CBC-200-2, or the CBC-200-3 control is used, the following additional procedure must be followed.
1. For the CBC-200-2 remove the knob from
the control.
2. On the CBC-200-1, CBC-200-2 or
CBC-200-3 remove the four screws that hold the faceplate bracket and PC board to the chassis plate.
3. Bring the external potentiometer wires
through the conduit entrance hole and wire the potentiometers to the appropriate terminals blocks as shown in (Figure 5) CBC-200-2, (Figure 6) CBC-200-1, or (Figure 7) CBC-200-3.
4. After wiring the external potentiometers,
mount the PC board assembly and faceplate assembly to the chassis with the four screws previously removed. Replace the knob if the CBC-200-2 was installed.
This completes the preliminary wiring of the remote potentiometers. The control is now ready for final wiring. Refer to the wiring section for final wiring.
Note: Be careful not to pinch or crimp the pot wiring to prevent shorting to the housing or components.
Figure 1
DIST. AUTORIZADO
MEX (55) 53 63 23 31 QRO (442) 1 95 72 60
MTY (81) 83 54 10 18 ventas@industrialmagza.com
5
Warner Electric • 800-825-9050 P-269
Chassis Mount PC Board Assemblies
Any vertical, horizontal, or angled surface is suitable for mounting the CBC-200-C, CBC-200-C1, CBC-200-C2, or CBC-200-C3 control.
Follow these procedures to mount your control:
1. Determine the mounting location where the
control will be placed.
2. Layout the mounting hole dimensions and
drill holes and taps using a 4-40 tap. (Figure 2)
3. If the CBC-200-C1, CBC-200-C2 or
CBC-200-C3 controls are used, wire the external potentiometers to the appropriate terminal blocks. (See Figure 2)
4. Place the faceplate over the PC board
assembly aligning the holes on the faceplate with the holes on the PC board.
5. Using the 4-40 screws supplied, mount the
PC board and faceplate assembly to the panel. Insure that the faceplate aligns cor­rectly and does not contact any of the components on the PC board.
6. Tighten all four mounting screws securely.
7. If the CBC-200-C or CBC-200-C2 was
used, insert the knob on the internal poten­tiometer shaft.
8. Attach the switch setting label next to the
control as a reference for switch set up.
Note: Be careful not to pinch or crimp the potentiometer wiring to prevent shorting to the chassis or control components.
This completes the mounting of the control. The unit is now ready for final wiring. Refer to the wiring section for final wiring.
Figure 2
DIST. AUTORIZADO
MEX (55) 53 63 23 31 QRO (442) 1 95 72 60
MTY (81) 83 54 10 18 ventas@industrialmagza.com
6
Warner Electric • 800-825-9050 P-269
Electrical Connections
All electrical current must be off when making electrical connections to prevent injury or death which can result from contact with live wires.
AC Input Power Connections
1. Connect Earth Ground wire to Terminal 1
and tighten securely.
2. Connect the Hot side of the 120 VAC line
to Terminal 2 and tighten securely.
Note: Customer supplied fuse is desirable. See diagram for connection and sizing.
3. Connect the neutral side of the 120 VAC
line to Terminal 3 and tighten securely.
4. For power applied clutch/brake
arrangement proceed to the wiring diagram and section below.
Normal Clutch/Brake Wiring (Power applied clutches or brakes)
Figure 3
1. Connect either the clutch or brake magnet to
Terminals 4 and 5. Tighten Terminal 4 securely.
2. Connect the other magnet, either brake or
clutch to Terminals 7 and 8. Tighten Terminal 7 securely.
3. Connect switching for Channel 1 to Terminals
5 and 6. Tighten both terminals securely.
4. Connect switching for Channel 2 to Terminals
8 and 9. Tighten both terminals securely.
5. Set DIP Switch, SW1 for proper current
setting before applying power to the control.
See INTERNAL SWITCH SETTINGS CHART for proper DIP Switch settings
6. If external potentiometers are being used,
then proceed to the external potentiometer wiring section. If they are not used, this completes the wiring of the control.
7. Double check all connections before
applying power.
Clutch/Brake and Switch Wiring
DIST. AUTORIZADO
MEX (55) 53 63 23 31 QRO (442) 1 95 72 60
MTY (81) 83 54 10 18 ventas@industrialmagza.com
7
Warner Electric • 800-825-9050 P-269
Clutch – Electrically Released Brake Wiring (Power on clutch/power off brake)
All electrical current must be off when making electrical connections to prevent injury or death which can result from contact with live wires.
AC Input Power Connections
1. Connect Earth Ground wire to Terminal 1
and tighten securely.
2. Connect the Hot side of the 120 VAC line
to Terminal 2 and tighten securely.
Note: Customer supplied fuse is desirable. See diagram for connection and sizing.
3. Connect the neutral side of the 120 VAC
line to Terminal 3 and tighten securely
4. For electrically released brake-clutch
arrangement proceed to the wiring section below.
1. Connect the Brake to Terminals 4 and 5.
Observe the polarity when making connec­tions. Tighten Terminal 4 securely.
2. Connect the Clutch to Terminals 7 and 8.
Tighten Terminal 7 securely.
3. Connect the switching for Channel 1 to
Terminals 5 and 6. Tighten terminals securely.
4. Connect the switching for Channel 2 to
Terminals 8 and 9. Tighten terminals securely.
5. Set DIP Switch, SW1 for proper current
setting before applying power to the control
See INTERNAL SWITCH SETTINGS CHART for proper DIP Switch settings.
6. If external potentiometers are being used,
then proceed to the external potentiometer wiring section. If external potentiometers are not used, this completes the wiring of the control.
7. Double check all connections before
applying power.
Clutch/Brake and Switch Wiring
Figure 4
DIST. AUTORIZADO
MEX (55) 53 63 23 31 QRO (442) 1 95 72 60
MTY (81) 83 54 10 18 ventas@industrialmagza.com
8
Warner Electric • 800-825-9050 P-269
External Potentiometer wiring for CBC-200 Series Controls
Enclosed Models CBC-200-1 CBC-200-2 CBC-200-3
Depending on which control is being used, options for external potentiometer are available via terminal blocks on the PC board of the unit.
1. For CBC-200-2 only, remove the internal
torque adjust knob.
2. Remove the four screws that hold the
bracket assembly and PC Board to the chassis. This step applies to all versions of the enclosed models.
3. Based on which model used, route the pot
cable through one of the conduit entrance holes on the bottom of the unit and wire to the appropriate terminal block on the PC board. Refer to the wiring diagrams on this page for the proper connections.
CBC-200-1 External Current Limit Adjustment
1. Wire the external current limit potentiome-
ter to Terminal Block TB-3 for Channel 1 as shown in the diagram. (See Figure 6)
2. If the accessory pot kit is used, then wire
per the colors as shown in the diagram.
3. Make sure all terminals are securely
fastened and the wiring cable is secured so that it can’t pull out of the terminals.
Figure 6
Figure 5
Figure 7
DIST. AUTORIZADO
MEX (55) 53 63 23 31 QRO (442) 1 95 72 60
MTY (81) 83 54 10 18 ventas@industrialmagza.com
9
Warner Electric • 800-825-9050 P-269
CBC-200-2 External Level Adjust with Internal Current Limit Adjust
1. Wire the external level adjust potentiome-
ter on Terminal Block TB-2 as shown in the diagram. (See Figure 5)
2. If the accessory pot kit is used, wire
according to the colors as shown in the diagram.
3. Make sure all terminals are securely fas-
tened and the wiring cable is secured so that it can’t pull out of the terminals.
Note: The level adjustment controls both the current adjustable output, channel 1 as well as the steady state output, channel 2.
4. After the pot(s) has been wired to the
appropriate terminal block, mount the PCB and bracket assembly and reattach to the chassis with the four screws removed in step 2 above.
5. For the CBC-200-2 reattach the internal
potentiometer knob.
6. Double check all wiring for both the poten-
tiometer and the main terminal block to insure proper connections.
CBC-200-3 External Current Limit and Level Adjust
1. Wire the external current limit adjust
potentiometer to Terminal Block TB-3 for Channel 1 as shown in the diagram. (See Figure 7)
2. If the accessory pot kit is used, wire per
the color codes as shown.
3. Make sure all terminals are securely
fastened and the wiring cable is secured so that it can’t pull out of the terminals.
4. Wire the external level adjust potentiome-
ter to Terminal Block TB-2 as shown in the diagram. (See Figure 7)
5. If the accessory pot kit is used, wire per
the color codes as shown.
6. Make sure all terminals are securely
fastened and the wiring cable is secured so that it can’t pull out of the terminals.
Note: The level adjustment controls both the current adjustable output, channel 1 as well as the steady state output, channel 2.
DIST. AUTORIZADO
MEX (55) 53 63 23 31 QRO (442) 1 95 72 60
MTY (81) 83 54 10 18 ventas@industrialmagza.com
10
Warner Electric • 800-825-9050 P-269
CBC-200-C2 External Level Adjust with Internal Current Limit Adjust
1. Wire the external level adjust potentiome-
ter on Terminal Block TB-2 as shown in the diagram. (See Figure 5)
2. If the accessory pot kit is used, then wire
according to the colors as shown in the diagram
3. Make sure all terminals are securely fas-
tened and the wiring cable is secured so that it can’t pull out of the terminals.
Note: The level adjustment controls both the current adjustable output, channel 1 as well as the steady state output, channel 2.
CBC-200-3 External Current Limit and Level Adjust
1. Wire the external current limit adjust
potentiometer to Terminal Block TB-3 for Channel 1 as shown in the diagram. (See Figure 7)
2. If the accessory pot kit is used, wire per
the color codes as shown.
3. Make sure all terminals are securely
fastened and the wiring cable is secured so that it can’t pull out of the terminals.
4. Wire the external level adjust potentiome-
ter to Terminal Block TB-2 as shown in the diagram. (See Figure 7)
5. If the accessory pot kit is used, wire per
the color codes as shown.
6. Make sure all terminals are securely
fastened and the wiring cable is secured so that it can’t pull out.
Note: The level adjustment controls both the current adjustable output, channel 1 as well as the steady state output, channel 2.
Chassis Mount Models CBC-200-C1 CBC-200-C2 CBC-200-C3
1. The CBC-200-C series chassis mount
version controls are shipped with the face plate bracket assembly loose.
2. Wire the control per the appropriate Wiring
configuration for the type of external poten­tiometer being used.
3. Based on which model used, route the pot
cable accordingly. Make sure to keep the cable away from components which may get hot during operation or points where the cable may become pinched. Refer to the wiring diagrams for the proper connection.
4. After the pot(s) have been wired to the
appropriate terminal blocks, mount the PCB and bracket assembly and attach to the mounting surface with the four screws provided.
CBC-200-C1 External current limit adjustment
1. Wire the external current limit potentiome-
ter to Terminal Block TB-3 for Channel 1 as shown in the diagram. (See Figure 6)
2. If the accessory pot kit is used, wire per
the colors as shown in the diagram.
3. Make sure all terminals are securely
fastened and the wiring cable is secured so that it can’t pull out of the terminals.
DIST. AUTORIZADO
MEX (55) 53 63 23 31 QRO (442) 1 95 72 60
MTY (81) 83 54 10 18 ventas@industrialmagza.com
11
Warner Electric • 800-825-9050 P-269
Internal Adjustments
The internal DIP Switch on the control circuit board adjusts the control for the proper current range to the clutch and/or brake coil being used. The chart below indicates the proper setting based on coil resistance and Warner Electric product. To adjust for products not listed, obtain coil resistance information and set switches per coil resistance.
Switch DIP No. 1 2 3 4 5
Coil Resistance 1000-1550 350-999 250-349 205-249 100-204 at 20° C (W)
Current Range 0 - 60 ma 0 - 175 ma 0 - 245 ma 0 - 305 ma 0 - 533 ma
Warner Electric SF-120 EC-375 ATC-25 SF-500 ATC-115 Clutch Models SF-170 EC-475 PC-500 SF-650 SF-1525HT
SF-250 EM-50 SF-825 SF-825BM SF-400 EM-100 PC-1000 PC-825
EM-180 SF-1225 SF-1000
UM-50 PC-1225 SF-1525 UM-100 PC-1525 EC-650 UM-180 EC-1000 EC-825
UM-50C EM-210 EC-1225
UM-180C UM-210 ATC-55
EUM-50 UM-215 EUM-100 UM-210C EUM-180 EUM-210
EUM-215
Warner Electric PB-120 EB-375 ATB-25 EB-825 EMFB-210 Brake Models PB-170 EB-475 PB-500 EMFB-180 UMFB-210
PB-250 EM-50 PB-650 UMFB-180 ER/FB-650 PB-400 EM-100 PB-1000 ER/FB-475 ATB-115
EM-180 PB-1225 ATB-55 ER-1225
UM-50 PB-1525 ER-825 UM-100 EB-650 UM-180 EB-1000
UM-50C EB-1225
UM-180C EMFB-50
EUM-50 UMFB-50 EUM-100 ER/FB-375 EUM-180 EM-210
UM-210
UM-215 UM-210C EUM-210 EUM-215
Note: Only one switch number is to be set to the “on” position at any time.
DIST. AUTORIZADO
MEX (55) 53 63 23 31 QRO (442) 1 95 72 60
MTY (81) 83 54 10 18 ventas@industrialmagza.com
12
Warner Electric • 800-825-9050 P-269
System Troubleshooting
A. Symptom: Green LED indicator marked “Power” does not come on when power is applied to the CBC-200 Controller.
Probable Cause Solution
No Power is applied to the Control • Check that AC power is applied to the control.
• Incorrect wiring on AC power to the control.
• Check for 120 VAC at Terminals 2 and 3 with an AC Voltmeter.
Optional line fuse is blown • Check for blown fuse – replace.
Indicator LED is defective • Check for 120 VAC at Terminals 2 and 3 of the control.
• Check for output voltage at output terminals for Channel 1 and Channel 2. If voltage is not present, replace control or board.
B. Symptom: Red LED marked “short” illuminates
Probable Cause Solution
Shorted magnet coil • Check resistance of magnet coil used and replace if necessary.
Wiring between control and magnet shorting • Check for shorted conditions in wiring between the magnets and
the control, and wiring to chassis ground.
Improper magnet coil voltage • Check magnet for proper coil voltage rating.
Transient noise • Check for source of transient noise and suppress. Wire control
using shielded cables. Segregate wiring runs.
C. Symptom: Magnets do not engage when power is applied.
Probable Cause Solution
External switching improperly wired • Check wiring and switch connections and rewire if necessary.
Torque adjust set to zero (0) • Set torque adjustment potentiometer to maximum level.
Current range switch improperly set • Check DIP Switch settings per chart and reset if required.
No power applied to the control • Refer to Symptom A above.
System incorrectly wired • Check wiring per the wiring diagram and rewire if necessary.
Fail Safe brake used in place • Check to insure that a fail safe brake is not being used in place of of power applied brake a power applied brake. Replace brake with correct brake.
D. Symptom: Magnets do not disengage when power is removed
Probable Cause Solution
External switches incorrectly wired • Check wiring of switching circuits and rewire if necessary.
Fail Safe brake magnet being used • Check to see if fail safe brake is being used in place of power
applied brake.
Faulty control • Replace control and see if problem is resolved.
E. Symptom: Magnets do not appear to have enough torque
Probable Cause Solution
DIP Switch improperly set • Check DIP switch setting per chart and reset if necessary.
Magnets incorrectly wired • Check wiring between control and magnets and rewire if required.
Torque adjust potentiometer set too low • Check setting of torque adjust potentiometer and set to maximum
if required. Check for correct wiring if external pots are used.
Magnets are incorrectly sized • Verify sizing is correct by repeating selection process.
DIST. AUTORIZADO
MEX (55) 53 63 23 31 QRO (442) 1 95 72 60
MTY (81) 83 54 10 18 ventas@industrialmagza.com
13
Warner Electric • 800-825-9050 P-269
Notes:
DIST. AUTORIZADO
MEX (55) 53 63 23 31 QRO (442) 1 95 72 60
MTY (81) 83 54 10 18 ventas@industrialmagza.com
Warranty
Warner Electric LLC warrants that it will repair or replace (whichever it deems advisable) any product manufactured and sold by it which proves to be defective in material or workmanship within a period of one (1) year from the date of original purchase for consumer, commercial or industrial use.
This warranty extends only to the original purchaser and is not transferable or assignable without Warner Electric LLC’s prior consent.
Warranty service can be obtained in the U.S.A. by returning any defective product, transportation charges prepaid, to the appropriate Warner Electric LLC factory. Additional warranty information may be obtained by writing the Customer Satisfaction Department, Warner Electric LLC, 449 Gardner Street, South Beloit, Illinois 61080, or by calling 815-389-3771.
A purchase receipt or other proof of original purchase will be required before warranty service is rendered. If found defective under the terms of this warranty, repair or replacement will be made, without charge, together with a refund for transportation costs. If found not to be defective, you will be notified and, with your consent, the item will be repaired or replaced and returned to you at your expense.
This warranty covers normal use and does not cover damage or defect which results from alteration, accident, neglect, or improper installation, operation, or maintenance.
Some states do not allow limitation on how long an implied warranty lasts, so the above limitation may not apply to you.
Warner Electric LLC’s obligation under this warranty is limited to the repair or replacement of the defective product and in no event shall Warner Electric LLC be liable for consequential, indirect, or incidental damages of any kind incurred by reason of the manufacture, sale or use of any defective product. Warner Electric LLC neither assumes nor authorizes any other person to give any other warranty or to assume any other obligation or liability on its behalf.
WITH RESPECT TO CONSUMER USE OF THE PRODUCT, ANY IMPLIED WARRANTIES WHICH THE CONSUMER MAY HAVE ARE LIMITED IN DURATION TO ONE YEAR FROM THE DATE OF ORIGINAL CONSUMER PURCHASE. WITH RESPECT TO COMMERCIAL AND INDUSTRIAL USES OF THE PRODUCT, THE FOREGOING WARRANTY IS IN LIEU OF AND EXCLUDES ALL OTHER WARRANTIES, WHETHER EXPRESSED OR IMPLIED BY OPERATION OF LAW OR OTHERWISE, INCLUDING, BUT NOT LIMITED TO, ANY IMPLIED WARRANTIES OF MERCHANTABILITY OR FITNESS.
Some states do not allow the exclusion or limitation of incidental or consequential damages, so the above limitation or exclusion may not apply to you. This warranty gives you specific legal rights and you may also have other rights which vary from state to state.
Changes in Dimensions and Specifications
All dimensions and specifications shown in Warner Electric catalogs are subject to change without notice. Weights do not include weight of boxing for shipment. Certified prints will be furnished without charge on request to Warner Electric.
Warner Electric LLC
449 Gardner Street • South Beloit, IL 61080 815-389-3771 • Fax: 815-389-2582 www.warnerelectric.com
An Altra Industrial Motion Company
P-269 819-0407 9/07 Printed in USA