WAC Lighting EN-1260-RB2 Instructions For Use Manual

INSTRUCTIONS Class II Electronic Transformer
Model EN-1260-RB2
CAUTION – TO REDUCE RISK OF FIRE AND ELECTRICAL SHOCK
Always turn off power at main switch prior to installation. Intended for installation by a qualified electrician. System is intended for installation in accordance with National Electric Code, and local
regulations. Consult with local inspector to assure compliance.
MAX LOAD 60W MIN LOAD 20W INPUT VOLTAGE 120V INPUT CURRENT 0.53A OUTPUT VOLTAGE 11.6V CASE TEMP AMBIENT TEMP
FEATURES:
Electronic short circuit protection with auto-reset. Overload protection with auto-reset. Automatic thermal regulation.
Soft start delay to preserve bulb life, for use with tungsten filament lamps.
INSTALLATION
1. Use a minimum of #18 AWG for the output wire.
2. Transformers must be installed away from heat sources and accessible for service.
3. Note: Enclosed transformer is UL listed. The transformer box has a separate line volt, and low volt wiring compartments. Trade size knock out are provided on both compartments. Connect building wires to like color transformer wires with wire nuts. Building ground wire may be green or un-insulated, and attaches to green wire from transformer box.
4. Connect out put wires from transformer to fixture wires with wire nuts. Where multiple
fixtures are involved several fixtures wires can be joined by use of the same wire nut. Wires to fixture
90ºC (194F)
-20ºC TO 50ºC (-4F TO 122F)
Retain these instructions for future service and adjustments
44 Harbor Park Drive, Port Washington, NY 11050
Tel: (800) 526-2588 Fax (800) 526-2585
www.waclighting.com
INSTRUCTIONS Class II Electronic Transformer
Model EN-12300-RB2
CAUTION – TO REDUCE RISK OF FIRE AND ELECTRICAL SHOCK
Always turn off power at main switch prior to installation. Intended for installation by a qualified electrician. System is intended for installation in accordance with National Electric Code, and local
regulations. Consult with local inspector to assure compliance.
MAX LOAD 5 X 60W MIN LOAD 1 X 20W INPUT VOLTAGE 120V INPUT CURRENT 2.5A OUTPUT VOLTAGE 11.6V CASE TEMP AMBIENT TEMP
FEATURES:
Electronic short circuit protection with auto-reset. Overload protection with auto-reset. Automatic thermal regulation.
Soft start delay to preserve bulb life, for use with tungsten filament lamps.
INSTALLATION
1. Use a minimum of #18 AWG for the output wire.
2. Transformers must be installed away from heat sources and accessible for service.
3. Connect building wires to like color transformer wires with wire nuts. Building ground wire may be green or un-insulated, and attaches to green wire from transformer box.
4. Connect fixture wires to pairs of output wires from the transformer.
5. Each wire pair represents is a 60-watt circuit.
6. Wires to fixtures may be chain wired or “ home run” wired back to the transformer.
7. Note: Heavy gauge wires introduce more electrical resistance to the line, which acts as
an additional load to the transformer. If using 14 or 12 gauge wire do not use the maximum 60 watt load. High frequency output is only readable with a true RMS meter, with sufficient range
8.
capability.
WIRE SIZE 20 WATT 40 WATT 60 WATT
18 GAUGE 9 FT 8 FT 6 FT 16 GAUGE 14 FT 13 FT 11 FT 14 GAUGE 21 FT 19 FT 15 FT 12 GAUGE 28 FT 25 FT 21 FT
85ºC (185F)
-20ºC TO 50ºC (-4F TO 122F)
MAXIMUM LENGTH / VOLTAGE DROP GUIDELINE
Retain these instructions for future service and adjustments
44 Harbor Park Drive, Port Washington, NY 11050
Tel: (800) 526-2588 Fax (800) 526-2585
www.waclighting.com
9. es may be chain wired or “ home run” wired back to the transformer. High frequency
output is only readable with a true RMS meter, with sufficient range capability.
MAXIMUM LENGTH / VOLTAGE DROP GUIDELINE
WIRE SIZE 35 WATT 50 WATT 60 WATT
18 GAUGE 10 FT 9 FT 8 FT 16 GAUGE 14 FT 13 FT 11 FT 14 GAUGE 21 FT 19 FT 15 FT 12 GAUGE 28 FT 25 FT 21 FT
Retain these instructions for future service and adjustments
44 Harbor Park Drive, Port Washington, NY 11050
Tel: (800) 526-2588 Fax (800) 526-2585
www.waclighting.com
Loading...