THIS MANUAL HAS BEEN PREPARED FOR PERSONNEL QUALIFIED TO INSTALL GAS
EQUIPMENT, WHO SHOULD PERFORM THE INITIAL FIELD START-UP AND
ADJUSTMENTS OF THE EQUIPMENT COVERED BY THIS MANUAL.
POST IN A PROMINENT LOCATION THE INSTRUCTIONS TO BE FOLLOWED IN THE
EVENT THE SMELL OF GAS IS DETECTED. THIS INFORMATION CAN BE OBTAINED
FROM THE LOCAL GAS SUPPLIER.
IMPORTANT
IN THE EVENT A GAS ODOR IS DETECTED, SHUT
DOWN UNITS AT MAIN SHUTOFF VALVE AND
CONTACT THE LOCAL GAS COMPANY OR GAS
SUPPLIER FOR SERVICE.
FOR YOUR SAFETY
DO NOT STORE OR USE GASOLINE OR OTHER
FLAMMABLE VAPORS OR LIQUIDS IN THE
VICINITY OF THIS OR ANY OTHER APPLIANCE.
WARNING
IMPROPER INSTALLATION, ADJUSTMENT,
ALTERATION, SERVICE OR MAINTENANCE CAN
CAUSE PROPERTY DAMAGE, INJURY OR DEATH.
READ THE INSTALLATION, OPERATING AND
MAINTENANCE INSTRUCTIONS THOROUGHLY
BEFORE INSTALLING OR SERVICING THIS
EQUIPMENT.
IN THE EVENT OF A POWER FAILURE, DO NOT
ATTEMPT TO OPERATE THIS DEVICE.
3
INSTALLATION, OPERATION, SERVICE & PARTS MANUAL
CONVECTION FOOD STEAMERS
GAS, ELECTRIC, REGENERATIVE OR DIRECT STEAM
MODELS VSX24, VSX36 & VSX42INDEX
PLEASE KEEP THIS MANUAL FOR FUTURE REFERENCE
Your Vulcan Steam Cooker is produced with quality
workmanship and material. Proper installation, usage
and maintenance of your steam cooker will result in
many years of satisfactory performance.
The manufacturer suggests that you thoroughly read
this entire manual and carefully follow all of the instructions provided.
DESCRIPTIONPAGE
INDEX4, 5
INSTALLATION6
UNPACKING6
LOCATION6
INSTALLATION CODES AND STANDARDS6, 7
LEVELING AND ANCHORING7
SERVICE CONNECTIONS7-19
Steam Connections7
Gas Connections7
Electrical Connections8
Drain Connections8
Plumbing Connections8
VENT HOOD8
SERVICE CONNECTION DIAGRAMS9-19
START-UP TEST RUN20, 21
BLOW DOWN BOILER21
OPERATION22
CONTROLS - CABINET BASE GENERATOR22, 23
CONTROLS - COMPARTMENT24
LIGHTING STANDING PILOT (GAS BASE GENERATORS ONLY)24
4
DESCRIPTIONPAGE
OPERATION (CONT’D.)
OPERATING STEAMERS WITH INTERMITTENT PILOTS (GAS BASE GENERATORS ONLY)24, 25
DAILY STARTING PROCEDURE25
CLEANING25, 26
MAINTENANCE26
COOKING CHART27-29
TROUBLESHOOTING30-32
SERVICE33
COOKING COMPARTMENT33
CABINET BASE GENERATOR33-38
All Generators33-37
Gas Generators37, 38
Electric Generators38
Regenerating (Steam Coil) Generators38
REPLACEMENT PARTS LIST39-70
5
INSTALLATION
UNPACKING
This steam cooker was inspected before leaving the
factory. The transportation company assumes full
responsibility for safe delivery upon acceptance of the
shipment. Immediately after unpacking, check for
possible shipping damage. If the cooker is found to be
damaged after unpacking, save the packaging material
and contact the carrier within 15 days of delivery.
Before installing, verify that the gas (natural or propane)
and/or electrical supplies agree with the specifications
on the rating plate which is located on the inside base
cabinet door. If the supply and equipment requirements
do not agree, do not proceed with the installation.
Contact your dealer or Vulcan-Hart immediately.
LOCATION
Position the steamer in its final location. Check that
there are sufficient clearances to service the controls,
for door swings, etc., so there will be no problem in
making the required supply and drain connections.
Recommended clearances are 18" on the sides and
back and 36" in the front.
The steamer must be installed so that the flow of
combustion and ventilation air will not be obstructed.
Adequate clearance for air openings into the combustion
chamber of the gas cabinet base generator must be
provided. The floor area beneath the burners must be
kept free and clear. Make sure there is an adequate
supply of air in the room to allow for combustion of the
gas at the burners.
When steamers are mounted on casters, you must use
a connector that complies with the Standard for
Connectors of Movable Gas Appliances, ANSI-Z21.69
(latest edition), and a quick-disconnect device that
complies with the Standard for Quick-Disconnect
Devices for Use With Gas Fuel, ANSI-Z21.41 (latest
edition).
Provide a gas line strain relief to limit movement of the
steamer without depending on the connector and/or any
quick-disconnect device or its associated piping to limit
movement of the steamer. Attach the gas line strain
relief to the rear of the steamer (Fig. 1).
Allow enough space between any other piece of
equipment or a wall for access. All service on the
compartment controls begins by removing the panel on
the right side of the compartments. Service on the
cabinet base may require the removal of the panel on
either or both the left or right sides.
A floor drain (open gap) is required immediately below
the steamer drain.
An exhaust system should be located directly above
the steamer to exhaust steam and heat generated by
the steamer.
For Gas Powered Steam Generators Only
The equipment area must be kept free and clear of
combustible substances.
The steamer, when installed, must have a minimum
clearance from combustible and noncombustible
construction of 6" at the sides and 6" at the back. It
must be installed on a noncombustible floor. The
installation location must allow adequate clearances
for servicing and proper operation.
1/2 IN. DIA. HOLE
PROVIDED FOR
STRAIN RELIEF
Should it be necessary to disconnect the restraint, turn
off the gas supply before disconnection. Reconnect the
restraint before turning the gas supply on and returning
the steamer to its installation position.
INSTALLATION CODES AND STANDARDS
Your Vulcan steamer must be installed in accordance
with:
PL-51218
6
In the United States:
STEAM CONNECTIONS
1. State and local codes.
2. National Fuel Gas Code, ANSI-Z233.1 (latest
edition). Copies may be obtained from The
American Gas Assoc., Inc., 1515 Wilson Blvd.,
Arlington, VA 22209.
3. National Electrical Code, ANSI/NFPA No. 70 (latest
edition). Copies may be obtained from The
National Fire Protection Assoc., Batterymarch Park,
Quincy, MA 02269.
In Canada:
1. Local codes.
2. CAN/CGA-B149.1 Installation for Natural Gas
Burning Appliances and Equipment (latest edition).
3. CAN/CGA-B149.2 Installation for Propane Burning
Appliances and Equipment (latest edition). Copies
may be obtained from The Canadian Gas Assoc.,
55 Scarsdale Road, Don Mills, Ontario, Canada
M3B 2R3.
Provide dry steam to the inlets. If the steam is heavy
with condensate, install a ball float trap before the
pressure regulator valve. To ensure rapid heat-up of
heavy cold loads, the steam supply line must be sized
to maintain pressure and flow as follows:
Direct Connected Steamers (Fig’s. 2-4)
Supply steam at a pressure of 10-12 psi and at a
minimum flow rate of 50 lb. per hour per compartment.
A pressure reducing valve is furnished and set at 10 psig.
Additional steam kettles and kettle modules can
be interconnected to the steamer. Consult Vulcan-Hart
for recommendations.
The steam supply to the steam coils must be 15 psi at
a minimum flow rate of 125 lb. per hour to the coil.
GAS CONNECTIONS (Fig’s. 7, 8 & 9)
All gas supply connections and any pipe joint
compound used must be resistant to the action of
propane gases.
4. The Canadian Electrical Code, Part 1, C22.1 (latest
edition). Copies may be obtained from the
Canadian Standards Assoc., 178 Rexdale Blvd.,
Rexdale, Ontario, Canada M9W 1R3.
LEVELING AND ANCHORING
Using a spirit level, adjust the feet to level the steamer
left-to-right and front-to-back. Steamers should be
elevated in the front just enough (about 1/16" to 1/8") to
give proper drainage. To do this, rotate rear leg
adjusting nut by 1 to 11⁄2 turns clockwise after leveling.
(Check by pouring a little water in the compartment; all
the water should drain.)
The rear feet have holes in the flanges for anchor bolts.
DIRECT STEAM COOKERS (STEAMERS WITHOUT
GENERATORS) MUST BE ANCHORED TO THE
FLOOR.
SERVICE CONNECTIONS (See Fig’s. 2-12)
Connect gas supply to the gas cabinet base generator
using 3⁄4” pipe. Make sure the pipes are clean and free
of obstructions.
Codes require that a gas shutoff valve be installed in
the gas line ahead of the steam generator.
This gas cabinet base generator is equipped with fixed
orifices for use with natural or propane gas and no
adjustment is necessary.
The gas line must be capable of delivering gas to the
generator without excessive pressure drop at the rate
specified on the rating plate. The generator is equipped
with a factory preset pressure regulator. Natural gas
pressure regulators are preset for 3.5" W.C. (Water
Column) for natural gas. Propane gas pressure
regulators are preset for 10" W.C. No further adjustment
should be required.
WARNING: PRIOR TO LIGHTING, CHECK ALL
JOINTS IN THE GAS SUPPLY LINE FOR LEAKS.
USE SOAP AND WATER SOLUTION. DO NOT USE
AN OPEN FLAME.
After piping has been checked for leaks, all piping
receiving gas should be fully purged to remove air.
7
Testing The Gas Supply System
1
When test pressures exceed
⁄2 psig (3.45 kPa), the
generator and its individual shutoff valve must be
disconnected from the gas supply piping system.
When test pressures are 1⁄2 psig (3.45 kPa) or less, the
generator must be isolated from the gas supply system
by closing its individual manual shutoff valve.
DRAIN CONNECTIONS (Fig’s. 2-12)
Drain connections must be the open air gap type.
Provide a suitable drain under the drain pipes. For
proper drainage, a floor sink with minimum of 12" depth
is recommended.
CAUTION: In order to avoid any back pressure in
the steamer, do not connect solidly to any drain
connection.
ELECTRICAL CONNECTIONS (Fig’s. 2-12)
WARNING: ELECTRICAL AND GROUNDING
CONNECTIONS MUST COMPLY WITH THE
APPLICABLE PORTIONS OF THE NATIONAL
ELECTRICAL CODE ANSI/NFPA-70 (LATEST
EDITION) AND/OR OTHER LOCAL ELECTRICAL
CODES.
WARNING: DISCONNECT ELECTRICAL POWER
SUPPLY AND PLACE A TAG AT THE DISCONNECT
SWITCH TO INDICATE THAT YOU ARE WORKING
ON THE CIRCUIT.
Do not connect the steamer to electrical supply until
after gas connections (if applicable) have been made.
All Models
Unless otherwise specified, field wire electrical
connection is to be 120 volts, 60 Hertz, single phase,
with grounding wire. Connect electrical supply to the
pigtail leads in the supply junction box located next to
the boiler control box for electric generators in a 24"
wide base, and under the boiler control box for all other
generator bases. The supply junction box is located on
the underside of the cabinet top on direct steam
models. Use copper wire suitable for at least 75°C
temperature. A grounding wire must be connected to
the ground lug in the junction box.
When optional step down transformer is used on
electrically heated generators, the 120 volt connection
is not required.
PLUMBING CONNECTIONS (Fig’s. 2-12)
WARNING: PLUMBING CONNECTIONS MUST
COMPLY WITH APPLICABLE SANITARY, SAFETY
AND PLUMBING CODES.
Before connecting the steamer to water, the water
supply should be analyzed to make sure hardness is
less than 2.0 grains per gallon and pH of 7.5. The water
supply should be clear with no sediment or suspended
material present. If the water supply fails to meet these
standards, it will be necessary to install a water
conditioner on the boiler water feed. APPLIANCE
FAILURE CAUSED BY INADEQUATE WATER
QUALITY IS NOT COVERED UNDER WARRANTY.
The use of strainers or filters will not remove minerals
from the water.
Cold Water
Used as boiler fill water and cold water condenser on
boiler blowdown line. Connect a
1
⁄4” N.P.T. cold water condensor line. Twenty (20) psig
cold water line to the
minimum water pressure is required at the connections.
VENT HOOD
Information on the construction and installation of
ventilating hoods may be obtained from the standard
for “Vapor Removal from Cooking Equipment,” NFPA
No. 96 (latest edition).
Electrically Heated Generators
Make the electrical supply connection in the junction
box on the contactor box. The supply wiring and circuit
protection must be adequate for the kilowatt load drawn
by the cooker. A grounding wire must be connected to
the ground lug in the junction box. Use copper wire of
the size and temperature rating marked on the supply
label.
8
SERVICE CONNECTIONS
DIRECT STEAM, VSX24DFIG. 2
LEGEND
A.COLD SUPPLY WATER CONNECTION:
CONDENSER SUPPLY, AND BOILER FEED.
B.STEAM SUPPLY CONNECTION:
PRESSURE REDUCING VALVE IS MOUNTED AS STANDARD AND SET FOR 10
PSI MAXIMUM INPUT TO UNIT).
C.ELECTRICAL CONNECTION FOR CONTROLS: 120V/60HZ/1PH/300 WATT
MAXIMUM, POWER SUPPLY WITH GROUNDING WIRE REQUIRED. (FOR
OTHER THAN 120 VOLT SUPPLY CONSULT FACTORY FOR LOCATION OF
THIS CONNECTION.)
D.DRAIN: COPPER TUBE COMPARTMENT & EXHAUST GROUP APPROXIMATELY
2" IN DIAMETER. (PROVIDE AN OPEN AIR GAP TYPE DRAIN DIRECTLY
UNDER THE UNIT FRAME. DO NOT CONNECT SOLIDLY TO ANY DRAIN
CONNECTION.)
NOTE: DIMENSIONS WHICH LOCATE THE ABOVE CONNECTIONS HAVE A
TOLERANCE OF ± 3 IN. (± 75 MM). NORMAL DIMENSIONS ARE IN INCHES.
DIMENSIONS IN ( ) ARE IN MILLIMETERS.
EQUIPMENT CLEARANCES
TO COMBUSTIBLE CONSTRUCTION
REAR: 2 IN. MIN. (50 MM.)
3
⁄4” NPT FOR STEAM COOKING (A STEAM
1
⁄4” TUBING FOR COLD WATER
9
SERVICE CONNECTIONS
DIRECT STEAM, VSX36DFIG. 3
LEGEND
A.COLD SUPPLY WATER CONNECTION:
CONDENSER, AND BOILER FEED.
B.STEAM SUPPLY CONNECTION:
PRESSURE REDUCING VALVE IS MOUNTED AS STANDARD AND SET FOR
10 PSI MAXIMUM INPUT TO UNIT.)
C.ELECTRICAL CONNECTION FOR CONTROLS: 120V/60HZ/1PH/300 WATT
MAXIMUM, POWER SUPPLY WITH GROUNDING WIRE REQUIRED. (FOR
OTHER THAN 120 VOLT SUPPLY CONSULT FACTORY FOR LOCATION OF
THIS CONNECTION.)
D.DRAIN: COPPER TUBE COMPARTMENT & EXHAUST GROUP APPROXIMATELY
2" DIAMETER. (PROVIDE AN OPEN AIR GAP TYPE DRAIN DIRECTLY UNDER
UNIT FRAME. DO NOT CONNECT SOLIDLY TO ANY DRAIN CONNECTION.)
NOTE: DIMENSIONS WHICH LOCATE THE ABOVE CONNECTIONS HAVE A
TOLERANCE OF ± 3 IN. (± 75 MM). NORMAL DIMENSIONS ARE IN INCHES.
DIMENSIONS IN ( ) ARE IN MILLIMETERS.
EQUIPMENT CLEARANCES
TO COMBUSTIBLE CONSTRUCTION
REAR: 2 IN. MIN. (50 MM.)
3
⁄4” NPT FOR STEAM COOKING. (A STEAM
1
⁄4” TUBING FOR COLD WATER
10
SERVICE CONNECTIONS
DIRECT STEAM, VSX42DTFIG. 4
LEGEND
A.COLD SUPPLY WATER CONNECTION:
CONDENSER, AND BOILER FEED.
B.STEAM SUPPLY CONNECTION:
PRESSURE REDUCING VALVE IS MOUNTED AS STANDARD AND SET FOR
10 PSI MAXIMUM INPUT TO UNIT.)
C.ELECTRICAL CONNECTION FOR CONTROLS: 120V/60HZ/1PH/300 WATT
MAXIMUM, POWER SUPPLY WITH GROUNDING WIRE REQUIRED. (FOR
OTHER THAN 120 VOLT SUPPLY CONSULT FACTORY FOR LOCATION OF
THIS CONNECTION.)
D.DRAIN: COPPER TUBE COMPARTMENT & EXHAUST GROUP APPROXIMATELY
2" DIAMETER. (PROVIDE AN OPEN AIR GAP TYPE DRAIN DIRECTLY UNDER
UNIT FRAME. DO NOT CONNECT SOLIDLY TO ANY DRAIN CONNECTION.)
NOTE: DIMENSIONS WHICH LOCATE THE ABOVE CONNECTIONS HAVE A
TOLERANCE OF ± 3 IN. (± 75 MM). NORMAL DIMENSIONS ARE IN INCHES.
DIMENSIONS IN ( ) ARE IN MILLIMETERS.
EQUIPMENT CLEARANCES
TO COMBUSTIBLE CONSTRUCTION
REAR: 2 IN. MIN. (50 MM.)
3
⁄4” NPT FOR STEAM COOKING. (A STEAM
1
⁄4” TUBING FOR COLD WATER
11
SERVICE CONNECTIONS
REGENERATING STEAM, VSX36RFIG. 5
LEGEND
A.STEAM SUPPLY CONNECTION:
STEAM PRESSURE REDUCING VALVE IS SHIPPED WITH THE UNIT AND
MUST BE FIELD INSTALLED AND ADJUSTED FOR 15 PSI MAXIMUM TO THE
UNIT.)
B.ELECTRICAL CONNECTION FOR CONTROLS: 120V/60HZ/1PH/300 WATT
MAXIMUM, POWER SUPPLY WITH GROUNDING WIRE REQUIRED. (FOR
OTHER THAN 120 VOLT SUPPLY CONSULT FACTORY FOR LOCATION OF
THIS CONNECTION.)
C.DRAIN: COMPARTMENT, BOILER AND EXHAUST GROUP APPROXIMATELY
2" IN DIAMETER. (PROVIDE AN OPEN AIR GAP TYPE DRAIN DIRECTLY
UNDER UNIT FRAME. DO NOT CONNECT SOLIDLY TO ANY DRAIN
CONNECTION.)
D.COLD SUPPLY WATER CONNECTION:
COMPARTMENT DRAIN COLD WATER CONDENSERS, AND BOILER FEED.
NOTE: DIMENSIONS WHICH LOCATE THE ABOVE CONNECTIONS HAVE A
TOLERANCE OF ± 3" (±75MM). NORMAL DIMENSIONS ARE IN INCHES. DIMENSIONS
IN ( ) ARE IN MILLIMETERS.
EQUIPMENT CLEARANCES
TO COMBUSTIBLE CONSTRUCTION
REAR: 2 IN. MIN. (50 MM.)
3
⁄4” NPT FOR STEAM INLET TO BOILER. (A
1
⁄4” NPT FOR BOILER DRAIN &
12
SERVICE CONNECTIONS
REGENERATING STEAM, VSX42RTFIG. 6
LEGEND
A.STEAM SUPPLY CONNECTION:
STEAM PRESSURE REDUCING VALVE IS SHIPPED WITH THE UNIT AND
MUST BE FIELD INSTALLED AND ADJUSTED FOR 15 PSI MAXIMUM TO THE
UNIT.)
B.ELECTRICAL CONNECTION FOR CONTROLS: 120V/60HZ/1PH/300 WATT
MAXIMUM, POWER SUPPLY WITH GROUNDING WIRE REQUIRED. (FOR
OTHER THAN 120 VOLT SUPPLY CONSULT FACTORY FOR LOCATION OF
THIS CONNECTION.)
C.DRAIN: COMPARTMENT, BOILER AND EXHAUST GROUP APPROXIMATELY
2" IN DIAMETER. (PROVIDE AN OPEN AIR GAP TYPE DRAIN DIRECTLY
UNDER UNIT FRAME. DO NOT CONNECT SOLIDLY TO ANY DRAIN
CONNECTION.)
D.COLD SUPPLY WATER CONNECTION:
COMPARTMENT DRAIN COLD WATER CONDENSERS, AND BOILER FEED.
NOTE: DIMENSIONS WHICH LOCATE THE ABOVE CONNECTIONS HAVE A
TOLERANCE OF ± 3" (± 75MM). NORMAL DIMENSIONS ARE IN INCHES. DIMENSIONS
IN ( ) ARE IN MILLIMETERS.
EQUIPMENT CLEARANCES
TO COMBUSTIBLE CONSTRUCTION
REAR: 2 IN. MIN. (50 MM.)
3
⁄4” NPT FOR STEAM INLET TO BOILER. (A
1
⁄4” NPT FOR BOILER DRAIN &
13
SERVICE CONNECTIONS
GAS HEAT, VSX24GFIG. 7
LEGEND
A.GAS CONNECTION:
B.ELECTRICAL CONNECTION FOR CONTROLS: 120V/60HZ/1PH/300 WATT
MAXIMUM, POWER SUPPLY WITH GROUNDING WIRE REQUIRED. (FOR
OTHER THAN 120 VOLT SUPPLY CONSULT FACTORY FOR LOCATION OF
THIS CONNECTION.)
C.DRAIN: COMPARTMENT, BOILER AND EXHAUST GROUP APPROXIMATELY
1
3
⁄2” IN DIAMETER. (PROVIDE AN OPEN AIR GAP TYPE DRAIN DIRECTLY
UNDER UNIT FRAME. DO NOT CONNECT SOLIDLY TO ANY DRAIN
CONNECTION.)
D.COLD SUPPLY WATER CONNECTION:
COMPARTMENT DRAIN COLD WATER CONDENSERS, AND BOILER FEED.
NOTE: DIMENSIONS WHICH LOCATE THE ABOVE CONNECTIONS HAVE A
TOLERANCE OF ± 3 IN. (± 75 MM). NORMAL DIMENSIONS ARE IN INCHES.
DIMENSIONS IN ( ) ARE IN MILLIMETERS.
3
⁄4” NPT.
1
⁄4” NPT FOR BOILER DRAIN &
EQUIPMENT CLEARANCES
TO COMBUSTIBLE CONSTRUCTION
REAR: 6 IN. MIN. (150 MM.)
LEFT SIDE: 6 IN. MIN. (150 MM.)
RIGHT SIDE: 6 IN. MIN. (150 MM.)
14
SERVICE CONNECTIONS
GAS HEAT, VSX36GFIG. 8
LEGEND
A.GAS CONNECTION:
B.ELECTRICAL CONNECTION FOR CONTROLS: 120V/60HZ/1PH/300 WATT
MAXIMUM, POWER SUPPLY WITH GROUNDING WIRE REQUIRED. (FOR
OTHER THAN 120 VOLT SUPPLY CONSULT FACTORY FOR LOCATION OF
THIS CONNECTION.)
C.DRAIN: COMPARTMENT, BOILER AND EXHAUST GROUP APPROXIMATELY
1
3
⁄2” IN DIAMETER. (PROVIDE AN OPEN AIR GAP TYPE DRAIN DIRECTLY
UNDER UNIT FRAME. DO NOT CONNECT SOLIDLY TO ANY DRAIN
CONNECTION.)
D.COLD SUPPLY WATER CONNECTION:
COMPARTMENT DRAIN COLD WATER CONDENSERS, AND BOILER FEED.
NOTE: DIMENSIONS WHICH LOCATE THE ABOVE CONNECTIONS HAVE A
TOLERANCE OF ± 3 IN. (± 75 MM). NORMAL DIMENSIONS ARE IN INCHES.
DIMENSIONS IN ( ) ARE IN MILLIMETERS.
3
⁄4” NPT.
1
⁄4” NPT FOR BOILER DRAIN &
EQUIPMENT CLEARANCES
TO COMBUSTIBLE CONSTRUCTION
REAR: 6 IN. MIN. (150 MM.)
LEFT SIDE: 6 IN. MIN. (150 MM.)
RIGHT SIDE: 6 IN. MIN. (150 MM.)
15
SERVICE CONNECTIONS
GAS HEAT, VSX42GTFIG. 9
LEGEND
A.GAS CONNECTION:
B.ELECTRICAL CONNECTION FOR CONTROLS: 120V/60HZ/1PH/300 WATT
MAXIMUM, POWER SUPPLY WITH GROUNDING WIRE REQUIRED. (FOR
OTHER THAN 120 VOLT SUPPLY CONSULT FACTORY FOR LOCATION OF
THIS CONNECTION.)
C.DRAIN: COMPARTMENT, BOILER AND EXHAUST GROUP APPROXIMATELY
1
3
⁄2” IN DIAMETER. (PROVIDE AN OPEN AIR GAP TYPE DRAIN DIRECTLY
UNDER UNIT FRAME. DO NOT CONNECT SOLIDLY TO ANY DRAIN
CONNECTION.)
D.COLD SUPPLY WATER CONNECTION:
COMPARTMENT DRAIN COLD WATER CONDENSERS, AND BOILER FEED.
NOTE: DIMENSIONS WHICH LOCATE THE ABOVE CONNECTIONS HAVE A
TOLERANCE OF ± 3 IN. (± 75 MM). NORMAL DIMENSIONS ARE IN INCHES.
DIMENSIONS IN ( ) ARE IN MILLIMETERS.
3
⁄4” NPT.
1
⁄4” NPT FOR BOILER DRAIN &
EQUIPMENT CLEARANCES
TO COMBUSTIBLE CONSTRUCTION
REAR: 6 IN. MIN. (150 MM.)
LEFT SIDE: 6 IN. MIN. (150 MM.)
RIGHT SIDE: 6 IN. MIN. (150 MM.)
16
SERVICE CONNECTIONS
ELECTRIC HEAT, VSX24EFIG. 10
LEGEND
A.JUNCTION BOX: J.I.C. 6X6X4 FOR ELECTRICAL SUPPLY CONNECTION FOR
HEAT.
B.ELECTRICAL CONNECTION FOR CONTROLS: 120V/60HZ/1PH/300 WATT
MAXIMUM, POWER SUPPLY WITH GROUNDING WIRE REQUIRED. (NOT
PROVIDED IF A STEP DOWN TRANSFORMER IS FURNISHED.)
C.COLD SUPPLY WATER CONNECTION:
COMPARTMENT DRAIN COLD WATER CONDENSERS.
D.DRAIN: COMPARTMENT, BOILER AND EXHAUST GROUP APPROXIMATELY
1
3
⁄2” IN DIAMETER. (PROVIDE AN OPEN AIR GAP TYPE DRAIN DIRECTLY
UNDER UNIT FRAME. DO NOT CONNECT SOLIDLY TO ANY DRAIN
CONNECTION.)
NOTE: DIMENSIONS WHICH LOCATE THE ABOVE CONNECTIONS HAVE A
TOLERANCE OF ± 3 IN. (± 75 MM). NORMAL DIMENSIONS ARE IN INCHES.
DIMENSIONS IN ( ) ARE IN MILLIMETERS.
EQUIPMENT CLEARANCES
TO COMBUSTIBLE CONSTRUCTION
REAR: 2 IN. MIN. (50 MM.)
1
⁄4” NPT FOR BOILER DRAIN AND
17
SERVICE CONNECTIONS
ELECTRIC HEAT, VSX36EFIG. 11
LEGEND
A.JUNCTION BOX: J.I.C. 6X6X4 FOR ELECTRICAL SUPPLY CONNECTION FOR
HEAT.
B.ELECTRICAL CONNECTION FOR CONTROLS: 120V/60HZ/1PH/300 WATT
MAXIMUM, POWER SUPPLY WITH GROUNDING WIRE REQUIRED. (NOT
PROVIDED IF A STEP DOWN TRANSFORMER IS FURNISHED.)
C.COLD SUPPLY WATER CONNECTION:
COMPARTMENT DRAIN COLD WATER CONDENSERS.
D.DRAIN: COMPARTMENT, BOILER AND EXHAUST GROUP APPROXIMATELY
1
3
⁄2” IN DIAMETER. (PROVIDE AN OPEN AIR GAP TYPE DRAIN DIRECTLY
UNDER UNIT FRAME. DO NOT CONNECT SOLIDLY TO ANY DRAIN
CONNECTION.)
NOTE: DIMENSIONS WHICH LOCATE THE ABOVE CONNECTIONS HAVE A
TOLERANCE OF ± 3 IN. (± 75 MM). NORMAL DIMENSIONS ARE IN INCHES.
DIMENSIONS IN ( ) ARE IN MILLIMETERS.
EQUIPMENT CLEARANCES
TO COMBUSTIBLE CONSTRUCTION
REAR: 2 IN. MIN. (50 MM.)
1
⁄4” NPT FOR BOILER DRAIN AND
18
SERVICE CONNECTIONS
ELECTRIC HEAT, VSX42ETFIG. 12
LEGEND
A.JUNCTION BOX: J.I.C. 6X6X4 FOR ELECTRICAL SUPPLY CONNECTION FOR
HEAT.
B.ELECTRICAL CONNECTION FOR CONTROLS: 120V/60HZ/1PH/300 WATT
MAXIMUM, POWER SUPPLY WITH GROUNDING WIRE REQUIRED. (NOT
PROVIDED IF A STEP DOWN TRANSFORMER IS FURNISHED.)
C.COLD SUPPLY WATER CONNECTION:
COMPARTMENT DRAIN COLD WATER CONDENSERS.
D.DRAIN: COMPARTMENT, BOILER AND EXHAUST GROUP APPROXIMATELY
1
3
⁄2” IN DIAMETER. (PROVIDE AN OPEN AIR GAP TYPE DRAIN DIRECTLY
UNDER UNIT FRAME. DO NOT CONNECT SOLIDLY TO ANY DRAIN
CONNECTION.)
NOTE: DIMENSIONS WHICH LOCATE THE ABOVE CONNECTIONS HAVE A
TOLERANCE OF ± 3 IN. (± 75 MM). NORMAL DIMENSIONS ARE IN INCHES.
DIMENSIONS IN ( ) ARE IN MILLIMETERS.
EQUIPMENT CLEARANCES
TO COMBUSTIBLE CONSTRUCTION
REAR: 2 IN. MIN. (50 MM.)
1
⁄4” NPT FOR BOILER DRAIN AND
19
START-UP TEST RUN
After the appliance is installed and proper service
connections have been made, thoroughly test the
steam cooker before operation.
8. When timer knobs are on “0”, each buzzer will
sound, steam generation will cease, COOKING
lights will go off and READY lights will come on.
To silence buzzers, turn timer knobs to OFF
position.
Gas Powered Steam Generator
1. Open manual gas shutoff valve, and if the
appliance has a manual blowdown valve, close it.
Open left cabinet door and turn water fill and power
switch ON. The red light will come on and water
will fill boiler to the required level in about 15
minutes. Observe water level gauge glass to
verify. Both valves on gauge glass assembly must
be open.
2. The dial on the gas combination control valve has
three positions (On-Pilot-Off) for manual gas control
of main burners and pilot. Turn dial on gas
combination valve to PILOT. Depress dial and light
pilot burner; maintain dial in depressed position for
about 30 seconds and release. Observe that pilot
burner flame stays on. If the flame should go out,
wait 5 minutes before relighting.
3. Turn gas combination control valve dial to ON and
burners will ignite. Steam generation will begin and
be completed in about 15 minutes. Observe that
the boiler pressure gauge indicates steam pressure
in the range of 9-12 psi (9-13 psi if a kettle is
connected to the steamer).
9. During simulation of cooking cycle, burners will
cycle on and off to maintain steam pressure in
boiler.
10. Turn power switch OFF. Amber light will go out.
11. Blow down boiler (see BLOW DOWN BOILER in
this manual).
Electrically Powered Steam Generator
1. If steamer has a manual blowdown valve, close it.
Open left cabinet door and turn power switch ON.
Water will fill boiler to the required level in about 15
minutes. Observe water level gauge glass to
verify. Both valves on gauge glass assembly must
be open. Steam generation will begin and be
completed in about 15 minutes.
2. Set both timer knobs to “0”. Open both
compartment doors and observe that no steam has
entered the cooking compartments. Close doors.
3. Set both timer knobs to 2 minutes. READY lights
will go off, COOKING lights will come on, and
steam will be heard entering the compartments.
4. Set both timer knobs to “0”. Open both
compartment doors and observe that no steam has
entered the cooking compartments. Close doors.
5. Set both timer knobs to 2 minutes. The READY
lights will go off, the COOKING lights will come on,
and steam will be heard entering the
compartments.
After one minute, open each door and observe that
steam has ceased to enter each compartment, but
COOKING lights and cooking times at “01” are
maintained.
WARNING: THE COOKING COMPARTMENTS
CONTAIN LIVE STEAM. STAY CLEAR WHILE
OPENING EACH DOOR.
7. Close doors. Steam generation and cook times will
resume. Observe appliance drain that live steam
from compartments is being cooled by cold water
from the cold water solenoid valve.
After one minute, open each door and observe that
steam has ceased to enter each compartment, but
COOKING lights and cooking times at “01” are
maintained.
WARNING: THE COOKING COMPARTMENTS
CONTAIN LIVE STEAM. STAY CLEAR WHILE
OPENING EACH DOOR.
4. Close doors. Steam generation and cook times will
resume. Observe appliance drain that live steam
from compartments is being cooled by cold water
from the cold water solenoid valve.
5. When timer knobs are on “0”, each buzzer will
sound, steam generation will cease, COOKING
lights will go off and READY lights will come on.
To silence buzzers, turn timer knobs to OFF
position.
6. During simulation of cooking cycle, the heating
elements will cycle on and off to maintain steam
pressure in the boiler.
20
7. Turn power switch OFF. Amber light will go out.
8. Blow down boiler (see BLOW DOWN BOILER in
this manual).
Direct Steam Powered Cooker
1. Set both timer knobs to “0”. Open both
compartment doors and observe that no steam has
entered cooking compartments. Close doors.
2. Set both timer knobs to 2 minutes. READY lights
will go off, COOKING lights will come on, and
steam will be heard entering the compartments.
After one minute, open each door and observe that
steam has ceased to enter each compartment, but
COOKING lights and cooking times at “01” are
maintained.
WARNING: THE COOKING COMPARTMENTS
CONTAIN LIVE STEAM. STAY CLEAR WHILE
OPENING EACH DOOR.
3. Close doors. Steam generation and cook times will
resume. Observe appliance drain that live steam
from compartments is being cooled by cold water
from the cold water solenoid valve.
4. When timer knobs are on “0”, each buzzer will sound,
steam generation will cease, COOKING
lights will go off and READY lights will come on.
To silence buzzers, turn timer knobs to OFF
position.
Regenerative Steam Powered Generator
1. If the steamer has a manual blowdown valve, close
it. Turn power switch ON. Water will fill the boiler
to the required level in about 15 minutes. Observe
water level gauge glass to verify. Both valves on
gauge glass assembly must be open. Steam
generation will begin and be completed in about 15
minutes.
2. Set both timer knobs to “0”. Open both
compartment doors and observe that no steam has
entered the cooking compartments. Close doors.
3. Set both timer knobs to 2 minutes. READY lights
will go off, COOKING lights will come on, and
steam will be heard entering the compartments.
After one minute, open each door and observe that
steam has ceased to enter each compartment, but
COOKING lights and cooking times at “01” are
maintained.
WARNING: THE COOKING COMPARTMENTS
CONTAIN LIVE STEAM. STAY CLEAR WHILE
OPENING EACH DOOR.
4. Close doors. Steam generation and cook times will
resume. Observe appliance drain that live steam
from compartments is being cooled by cold water
from the cold water solenoid valve.
5. When timer knobs are on “0”, each buzzer will
sound, steam generation will cease, COOKING
lights will go off and READY lights will come on.
To silence buzzers, turn timer knobs to OFF position.
6. During simulation of cooking cycle, steam coils will
cycle on and off to maintain steam pressure in the
boiler.
7. Turn power switch OFF. Amber light will go out.
8. Blow down boiler (see BLOW DOWN BOILER in
this manual).
BLOW DOWN BOILER
Always blow down boiler when boiler is under maximum
pressure and no steam is being used.
Automatic Blowdown
Turn power switch OFF. Depress blowdown button.
Blowdown timer will operate for 4 minutes. At end of
blowdown, turn fill switch to ON and allow boiler to fill.
Manual Blowdown
Turn power switch OFF. Open blowdown valve. After
boiler has drained completely, close blowdown valve
and turn fill switch to ON and allow boiler to fill.
21
OPERATION
WARNING: THE STEAMER AND ITS PARTS ARE
HOT. USE CARE WHEN OPERATING, CLEANING
OR SERVICING THE STEAMER. THE COOKING
COMPARTMENTS CONTAIN LIVE STEAM. STAY
CLEAR WHILE OPENING EACH DOOR.
CONTROLS — CABINET BASE GENERATOR (Fig. 13)
Handhole Cover Assembly — when unbolted and
removed, allows internal examination and cleaning of
boiler if required.
Water Level Gauge Assembly — permits visual
confirmation that water level is being maintained in the
boiler during operation. The correct water level is a
point one-half of the height of the glass. The manual
valves at the top and bottom of this assembly must be
fully open, and only closed if the glass tube should be
damaged.
Observe that the water is clean and clear in the
glass tube. The appearance of extreme murkiness
in the water indicates inadequate water quality and
will cause failure of controls and the steamer.
Warranty does not cover malfunction due to poor
water conditions. Blow down and/or clean the
generator.
Pilot Burner (Gas Base Generator Only) — should
remain lit at all times unless the steamer will not be in
use for an extended period of time. If at any time the
flame goes out, wait 5 minutes before relighting.
Drain Solenoid Valve — a quick acting drain valve
provided for daily blowdown of the generator.
Strainers — a strainer is used in the water inlet line to
prevent foreign matter from becoming lodged in the
inlet solenoid valve. A “Y” strainer is inserted upstream
of the drain solenoid valve to allow the valve to operate
smoothly. A strainer is used in the pressure regulating
valve on models using direct steam supply.
Boiler Fill Solenoid Valve — admits water to the
boiler when demanded by the automatic fill controls in
order to maintain the correct water level in the steam
generator.
Blowdown Drain CWC Solenoid Valve — allows cold
water to flow to boiler blowdown drain and helps cool
the boiler water prior to its discharge into the drain.
Cycling Pressure Switch — controls boiler pressure
between prescribed limits by turning the heat source on
and off. A back-up switch of identical design is provided
and has a higher high setting and a lower low setting
than the primary control.
Power Switch — when turned ON will automatically
begin the steam generating process in the boiler. The
power switch is fastened to the front face of the
generator control box.
Pressure Regulating Valve — used to control
manifold steam pressure at 10-12 psi on models using
direct steam supply.
Main Burners (Gas Base Generator Only) — cycle
on and off to maintain steam pressure in the boiler.
Gas Combination Control Valve (Gas Base
Generator Only) — regulates flow of gas to burners.
Low Water Cutoff/Automatic Fill Control — Level
Sensing Probes — these controls allow the feed water
to enter the generator when the water level is low.
They will also shut off the heat source to the boiler if
the water level drops too low. The level sensing probes
may be easily removed to inspect for lime build-up. As
a rule, the condition of these devices will indicate the
overall water condition of the boiler. Clean the probes
if needed. Controls may not function and serious
clogging will occur if a daily blowdown procedure
is not followed.
22
Water Inlet Ball Valve — water service valve which
can be used to stop water flow to the steamer when the
steamer is being serviced.
High Limit Thermostat — a protective device which
shuts off the gas or electric power if the boiler
overheats.
Descaler — hangs submerged in water inside the
generator and helps control scaling.
Drain — drains steam condensate and water from
cooking compartments and boiler.
Boiler Blowdown Valve — plumbed to the drain pipe
of the boiler, and when specified as automatic, will be
a solenoid (electrically operated) valve which will close
to assist in maintaining proper water level in the boiler
and open whenever the steamer is turned off to blow
down sediment and scalant that may be lodged in the
chamber of the boiler.
Pressure Gauge — indicates boiler steam pressure.
Normal operating pressure range is 9-12 psi for the
steamer, or 9-13 psi if a kettle is connected to the
steamer.
Fig. 13
23
CONTROLS — COMPARTMENT (Fig. 14)
The upper section of the steamer consists of two
cooking compartments. Each compartment functions
independently with its own controls, and is a separated,
sealed steam chamber during the cooking operation.
Gasket Plate Screw (Not Shown) — a stainless steel
screw on the gasket plate immediately adjacent to each
corner of the gasket allows adjustment of the gasket if
necessary.
Door Gasket (Not Shown) — provided on each
compartment door and ensures proper sealing of the
cooking compartment. CAUTION: Damage to the
gasket sealing surface, such as nicks or cuts, will
cause steam leakage.
Door Striker (Not Shown) — provides positive
latching of door.
LIGHTING THE STANDING PILOT (GAS BASE
GENERATORS ONLY) (On Steamers So Equipped)
1. Before lighting the pilot, both the burner and the
pilot must have been off for at least 5 minutes.
2. Turn power switch (upper left of generator cabinet)
to OFF. Be sure gas to the steamer is turned ON.
3. Turn knob of combination control valve to PILOT.
With a lit taper, ignite pilot while depressing knob of
combination control valve. Keep knob depressed
for about 1 minute after pilot is lit.
4. Release knob. Pilot should continue burning. If
not, repeat Steps 1 through 3.
5. Turn knob counterclockwise to ON.
Shutdown
Ready Light (Green) — when lit, indicates appliance
is ready for the cooking cycle.
Cooking Light (Red) — when lit, indicates appliance
is in the cooking phase.
Timer — use to set desired cooking cycle time. Timer
range is 0-60 minutes.
Ready
Light
Timer
Ready
Light
Timer
READY
READY
COOKING
TIMER
COOKING
TIMER
Cooking
Light
Cooking
Light
1. Turn gas service valve and power switch OFF.
2. Close water inlet valve.
OPERATING STEAMERS WITH INTERMITTENT
PILOTS (GAS BASE GENERATORS ONLY)
1. Before lighting the pilot, both the burner and the
pilot must have been off for at least 5 minutes. Do
not attempt to manually light the pilot.
2. Turn knob of gas combination control valve
counterclockwise until it stops at the ON position.
3. Turn boiler power switch to ON position (light on).
4. The electrode will begin sparking and pilot will light.
5. Ensure pilot light has lit by observing pilot flame.
6. The pilot light will remain lit as long as the boiler
power switch is in the ON position.
7. The cycling pressure switch will open and close the
gas combination control valve, which will in turn
cycle the main burner.
24
PL-50860
Fig. 14
Shutdown
1. Turn the boiler power switch to the OFF position
to extinguish the pilot light.
2. To make the pilot light and main burners
inoperable, turn the gas combination control valve
clockwise until it stops (OFF position).
CLEANING
Never use steel wool on stainless steel surfaces.
Never apply food oils or petroleum lubricants directly
to the door gasket.
Daily
3. To completely shut off pilot light and main burners,
close the main gas valve.
DAILY STARTING PROCEDURE
1. If boiler has manual blowdown drain valve, close
it.
2. On gas powered generators, ensure that pilot
burner flame is ON. If flame is out, a 5-minute
period of complete shutoff of gas supply is required
before relighting.
3. Turn power switch ON.
4. Wait 20 minutes before starting cooking operation.
5. This step is required only when the cooking
chamber is cold or when cooker is first used for
the day. When READY light is on, preheat cooking
compartment(s) for 1 minute. Turn timer knob to
“1”. READY light will go off and COOKING light
will come on. Make sure door is closed. When
buzzer sounds, open and close door to silence
buzzer.
6. With compartment(s) preheated and READY light
on, place pans of food into cooking compartment
and shut door. Refer to COOKING CHART in this
manual and set desired cooking time.
7. Turn timer knob to desired cooking time. Cooking
cycle will begin.
Cooking cycle may be interrupted at any time by
opening door and resumed again by closing door.
8. The buzzer will sound when the cooking cycle ends
and no more steam is entering the cooking
compartment(s). The buzzer must be silenced by
opening the door. Remove cooked food. The
COOKING light will go off and the READY light will
come on indicating the cooker is now ready for the
next cooking cycle.
At the end of each day, or more often if necessary,
turn steamer OFF and allow compartments to cool.
Remove pans and side racks from compartments and
clean in a sink.
Remove food sediment from compartment bottoms.
Wipe all solids away from the drain opening, especially
any large particles, to prevent possible clogging of the
drain.
Clean the drain screen at least daily, or more often if
required. Remove drain screen by pulling straight
out. Clean drain screen in a sink.
Wash compartment interiors with mild detergent.
Rinse thoroughly and wipe dry with a soft clean cloth.
Replace racks.
After cooking grease-producing foods, pour one-half
gallon of soapy water down the drain and rinse with
one-half gallon of hot clear water.
For maximum gasket life, wash gasket sealing surface
of compartment doors with mild detergent to remove
harmful food acids. Follow with a warm water rinse to
remove all traces of detergent. Then wipe with a soft,
dry cloth. Leave the door slightly open when not in
use.
Use a clean damp cloth to wipe down the exterior.
Polish with a soft dry cloth. Remove discolorations
with a non-abrasive cleaner.
If the water in the sight glass becomes extremely
murky, the generator should be blown down and/or
cleaned.
As Required
After a period of time, all gas burners accumulate
carbon in their ports and this restricts performance.
To clean burners, boil them in a strong solution of lye
water for 1⁄2 hour. Then clean gas ports with a sharp
pointed metal instrument to ensure open ports. Clean
as needed (usually about once a year will be often
enough).
25
Remove the “Y” strainer upstream of the drain solenoid
valve by unscrewing the cap on the section protruding
down towards the floor. Remove the screen and any
foreign particles. Rinse the screen thoroughly and
replace. Replace cap.
MAINTENANCE
The pressure regulating valve strainer will become
clogged if dirty steam lines are connected to direct
steam models. Remove the hex nut on the bottom of
the pressure regulating valve to clean the strainer and
valve seat.
WARNING: THE STEAMER AND ITS PARTS ARE
HOT. USE CARE WHEN OPERATING, CLEANING
OR SERVICING THE STEAMER. THE COOKING
COMPARTMENTS CONTAIN LIVE STEAM. STAY
CLEAR WHILE OPENING EACH DOOR.
DOOR GASKET
If door gasket is nicked or cut or at the end of its useful
life, it must be replaced. Damage to the gasket
sealing surface will cause steam leakage.
However, if a leak occurs in one corner only and
gasket appears serviceable, turn the stainless steel
screw on the gasket plate immediately adjacent to the
leaking corner one-half turn counterclockwise. Do
not attempt excessive turning of screws since
misalignment of door is likely.
BOILER BLOWDOWN VALVE
Turn the steamer off at least once daily and blow
down the boiler in order to remove sediments, scalants
and lime build-up in the boiler. If the steamer is
supplied with a manual valve, open it daily when the
steamer is shut down. The manual blowdown valve is
located on the bottom front of the cabinet base.
DESCALER
Inspect the descaler every three months. Replace it
when it has shrunk to one-half its original size. Local
water conditions generally determine the life of the
descaler.
LEVEL SENSING PROBES
Inspect level sensing probes for lime build-up once a
month. Clean probes if needed.
WATER LEVEL GAUGE ASSEMBLY
Check sight glass assembly daily. Extreme murkiness
indicates the generator should be blown down and/or
cleaned, and is an indication of bad water conditions.
The correct water level is a point one-half of the height
of the glass.
FLUE (GAS BASE GENERATOR ONLY)
Annually check the flue when cool to be sure it is free
of obstructions.
Contact your Vulcan-Hart service representative for
any other maintenance required.
26
COOKING CHART
The following table lists suggested cooking times and weights. These times, which will vary depending on initial
product temperature, size, shape, etc., are approximate and should be adjusted to suit your operation.
PRODUCTS TO BE COOKED IN SOLID PANS
TIMER SETTINGWEIGHT
PRODUCTIN MINUTESPER PAN
Eggs, Scrambled10-128 Dozen
Rice, Long Grain (Cover with 4 cups water/lb.)252 Lb.
Pasta (Place perforated pan inside solid pan, cover pasta
with cold water)
Where possible, spread food out evenly in pans. Do
not allow food to protrude above pans, since this will
interfere with steam circulation between pans in the
compartment.
Always preheat compartments for satisfactory results.
When time does not allow for defrosting of frozen
vegetables, such as loose-pack peas, corn, diced
carrots, etc., they may be cooked at once provided
just half of the suggested portions in the cooking chart
are used.
29
TROUBLESHOOTING
PROBLEMCAUSECORRECTIVE MEASURES
Steamer Will Not Heat or Build
Pressure
1. Problem with low water cut-off.Replace low water cut-off control.
2. Problem with pressure switch.Replace pressure switch.
3. Loose wiring.Check against diagram and tighten
connections.
4. Problem with combination controlReplace valve.
valve on gas base generator.
5. Problem with pressure reducingClean strainer on pressure reducing
valve on steam generator.valve and adjust to spec or replace.
6. Problem with pressure gauge.Replace gauge.
7. Problem with contactor onReplace contactor.
electric generator.
8. Problem with auto blow-downReplace auto blow-down control.
control on steamers so equipped.
9. Problem with heat switch.Replace heat switch.
10. Problem with heating elements.Replace heating elements.
11. Pressure control set too high andAdjust to specification. Some high
operating on back-up.input units may need to be set below
spec to compensate for overshoot.
12. Pilot not lit on gas generators.Light pilot. See lighting instructions in
this manual.
13. Generator not filling.Check fill valve and water level
controls.
14. Power/steam/gas off to steamer.Check that power, steam or gas
supply is on.
Pilot Won’t Light1. Problem with combination controlReplace combination control valve.
valve.
2. Gas leak in pilot tubing.Tighten.
3. Obstruction in gas line orLocate and remove obstruction.
combination control valve.
4. Pilot flame adjusted too small.Adjust pilot flame.
5. Thermocouple not completelyPush thermocouple completely into
inserted into holder.holder.
Generator Leaks Water1. Problem with boiler hand holeTighten or replace gasket.
gasket.
2. Problem with fitting on water orTighten or replace fitting.
steam lines.
3. Leak at gauge glass.Replace gauge glass and seals.
30
PROBLEMCAUSECORRECTIVE MEASURES
Compartment Won’t Heat1. Loose or misadjusted door switchAdjust and tighten bracket on door.
striker.
2. Boiler not building pressure.Adjust pressure switch.
3. Problem with steam solenoidReplace steam solenoid valve.
valve.
Generator Off, Won’t Heat1. No electric power to controls.Check connections.
2. No fuel supply to steamer (steamExamine physical plant for flow
to steam heated generator, gasproblems.
to gas heated generators, power
to heating elements).
3. Problem with pressure switch.Check pressure switch.
4. Water level too low.Turn water supply on, or check for
stuck water feeder.
5. Problem with low water cut-off.Check low water cut-off for operation.
6. On gas heated generator only,Check around unit for drafts, or vapor
burner ignition pilot out (due tofrom drain causing pilot outage.
drafts, problem with combination
control valve or interruption of
gas supply).
7. Open circuit or short in controlCheck wiring.
circuit.
Generator Water Level Too High 1. Water feeder solenoid valve notClean or replace water feeder
closing properly.solenoid valve.
Generator Steam Pressure Too1. Problem with pressure switch.Properly set Hi-Lo limits on pressure
High (Pressure Relief Valveswitch.
Leaking), or Too Low (Below 10
psi When Controls Cut Heat Off)
Steam Output Low as1. For cause and cure, seeCheck for blockage in fuel or steam
Compared to Usual GeneratorCABINET BASE GENERATOR inline.
Performancethe Service section of this
manual.
Door Won’t Stay Closed1. Door liner spring adjusted tooLift liner out of door and bend springs
tightly.to loosen.
2. Latch out of adjustment or loose.Adjust latch and tighten.
3. Latch worn.Dress retaining surface of latch or
replace.
4. Striker plate out of adjustment.Adjust plate to obtain good latching.
31
PROBLEMCAUSECORRECTIVE MEASURES
Steam Leak Around Door1. Worn gasket.Replace gasket.
2. Drain line obstructed or not to anClean or open drain line.
open gap drain.
3. Cold water condenser notCheck solenoid valve and spray
spraying properly.nozzle for proper operation. Replace
as required.
4. Door liner needs adjustment.Lift off door liner and adjust pressure
springs to obtain uniform seal.
Heat Coming On Without Water1. Dirty low water cut-off probes.Remove probes and clean insulator
(Dry Firing)with soft clean cloth.
2. Retention of water in probeRemove housing or housing cover
housing.and mechanically clean interior.
3. Sticking low water cut-offReplace contactor.
contactor.
Pressure Gauge Not Working1. Problem with pressure gauge.Replace pressure gauge.
2. Tubing crimped, plugged orRepair or replace tubing.
broken.
Steam Leaking Inside Unit1. Problem with fitting or valve.Tighten or replace fitting or valve.
2. Steam pressure too high.Adjust pressure switches.
32
SERVICE
These service procedures should only be performed
by a qualified servicer.
WARNING: THE STEAMER AND ITS PARTS ARE
HOT. USE CARE WHEN OPERATING, CLEANING
OR SERVICING THE STEAMER. THE COOKING
COMPARTMENTS CONTAIN LIVE STEAM. STAY
CLEAR WHILE OPENING EACH DOOR.
WARNING: BEFORE SERVICING, DISCONNECT
ELECTRICAL POWER SUPPLY AND PLACE A TAG
AT THE DISCONNECT SWITCH TO INDICATE THAT
YOU ARE WORKING ON THE CIRCUIT. TURN
WATER SUPPLY OFF, RELIEVE LINES OF
PRESSURE AND ALLOW HOT PARTS TO COOL.
COOKING COMPARTMENT
CONTROLS
For access to compartment controls, remove two
screws holding compartment control panel and remove
control panel.
Check for failure of the control circuit in the following
order:
1. Check that electric power is reaching control
circuit through compartment switch when it is
turned ON.
7. Check that all connections and terminals are
securely fastened (no open circuits).
8. Check that all connections are made according to
compartment control wiring diagram.
WATER ACCUMULATION ON BOTTOM OF
COMPARTMENT
Water accumulation on the bottom of the cooking
compartment(s) is primarily condensed steam. Failure
to drain out quickly and completely may be due to
clogged debris on the compartment drain screen.
Pull screen straight out and thoroughly clean, then
replace.
Failure to drain completely may also be due to
improperly levelled steamer.
COOKING CYCLE CANNOT BE ACTIVATED
Inspect all wire terminations to ensure they are positive
and secure before assuming any other problem.
When power switch on base generator is ON, set the
timer knob to 2 minutes. Both READY lights should
go off, COOKING lights should come on and steam
should be entering both compartments.
2. On electric heat models with a transformer, check
step down transformer for proper operation.
3. Check limit switch, operated by a tab on the
compartment door, for proper function.
4. Check that timer switches are functioning as
shown on the wiring diagram.
5. Check that timer motor operates when connected
to power.
If problem is found in timer, replace it; do not take
timer apart.
6. Check wiring for damaged insulation (no short
circuit).
CABINET BASE GENERATOR
ALL GENERATORS
Removal of Scalants From Boiler
It is recommended that the boiler be thoroughly
inspected on at least three-month intervals, and more
frequently in hard water areas and/or for units heavily
used. This inspection consists of an internal
examination and cleaning of the generator shell, an
examination and possible replacement of the descaler,
a check of lime build-up on the level sensing probes,
and a check of all generator controls, including the
pressure switches.
33
Local water conditions may cause excessive boiler
scale build-up and cause the generator and
compartment controls not to work. Proper periodic
service must be performed as outlined in the operating
and service instructions. It may also be necessary to
install a water conditioner on the generator water
feed. Contact your local water conditioner dealer.
Inspect and Clean Inside of Generator Shell
Flush (blow down) steam generator. Drain water from
the shell with the electric power OFF (no heat on).
Hold the pressure relief valve open to allow air to
enter for better drainage.
Remove generator hand hole cover (top front of shell)
by removing the nut and clamp, then tapping the
cover lightly to free it while holding the cover stud (this
prevents cover from dropping into generator). When
replacing cover, clean gasket seating surfaces.
Always use a new cover gasket.
Use wire brushes to free the scale. Loose material
must be either scooped from the steam generator or
flushed through the drain.
A suitable agent for removing lime may be used to
remove scale build-up, but use caution to avoid
damage to brass and copper parts of generator
controls, etc.
If a solvent is used, it is recommended that the
generator be removed (see REMOVING
GENERATOR ASSEMBLY), the descaler, sensing
probes and heating elements or steam coils, if
furnished, be removed, and that the shell be stood on
its end and filled with the solvent. One solvent
commonly used for removing lime is muriatic
(hydrochloric) acid (two parts of commercial muriatic
acid to 14 parts of cold water should be strong
enough). A heavily scaled shell may require a soaking
period of several hours.
When using these solvents, carefully read and follow
the instructions provided with the product. Perform
work in a well ventilated area.
Descaler
The descaler is accessible through the hand hole
opening. It is a coiled wire wound around a solid
cylindrical core, and hangs by an open loop from the
shell’s horizontal stay rod, about 4" from the front of
the shell. If the wire is eaten through, or if the core of
the descaler is eaten away to half its original size, a
new descaler should be installed. To install a new
descaler, stretch its wire coil so that the descaler
hangs with its core completely below the minimum
water level in the generator, but hanging free. The
descaler must not contact the bottom of the generator
shell, or the electric heating elements or regenerator
steam coils (if applicable).
Low Water Cutoff/Automatic Fill Control
The steam generator is equipped with level sensing
probes and relays for controlling the flow of feed
water to the boiler and to turn off the heat source when
the level is too low.
The low level control is a simple series circuit with a
transformer, secondary coil, relay coil, electrode,
metal boiler and water. When water is below the low
level cutoff electrode probe, the circuit is open and the
coil is deactivated. When the water level is at or
above the electrode probe, the circuit is closed by a
path through the liquid from the probe to the metal
boiler. The relay coil and the n.o. relay contacts 7 &
8 transfer positions, activating the heating contactor,
or combination control, or solenoid valve.
The differential level control relay coil activates and
the n.c. contacts 3 & 4 transfer positions once the
water level reaches the top probe.
The relay coil will deactivate when the water level
goes below the low level probe. This is achieved by
holding the circuit closed with the use of an additional
lower electrode probe through the n.o. contacts 7 & 8
on the relay. The relay activates when the water level
reaches the top high level electrode probe, but does
not deactivate until the level recedes below the low
level electrode probe.
Drain completely and thoroughly flush shell with fresh
water, repeating several times to be sure all traces of
the lime removing agent are flushed away.
34
Loose electrical connections may prevent the heat
from coming on or may cause the boiler to overfill.
Accumulation of boiler scale on or near the sensing
probes may cause them to retain water on the insulator
surface. This may prevent the boiler from filling or
cause dry firing. DRY FIRING WILL RESULT IN
DAMAGE TO HEATING ELEMENTS OR TO THE
BOILER SHELL.
With the probe wire removed, check the probes and
contactors in the following manner:
1. With an ohmmeter, check the probe at wire
connection and shell. There should be no
resistance present when the boiler is empty. If
resistance is present, remove and clean the
probes. Also check for a cracked insulator, then
reinstall probes and check. You should read
continuity between the probes and shell only
when the boiler shell is full
of water.
2. Check low level and differential contactors. With
a voltmeter, check across terminals 1 & 2. Meter
should read 115 V. Across terminals 9 & 10, you
should read 350 V. Using a jumper wire, jump
terminals 9 & 10. Contactor should engage. If
contactor does not engage, replace contactor.
3. Remove sensing probe. First remove the bolted
cover over the sensor cluster. Then remove the
wire from the probe and unscrew the probe with a
wrench. Be careful to note the location of each
probe and the number of the wire connected to it.
Incorrectly connected wires will cause the controls
to malfunction.
4. Clean probe thoroughly, removing ALL deposits
from the insulator. Do not use an abrasive on the
insulator; use a soft cloth.
5. Inspect through the probe socket for the presence
of water. Water must drain from the probe
housing. If in doubt, pour water into the housing
and observe that it drains quickly. If the housing
fails to drain, remove the housing or housing
cover and clean the interior mechanically.
Water Level Gauge Assembly
Close the valve at the top and at the bottom of the
gauge assembly. Unscrew the packing nuts at the top
and bottom of the glass tube. Slide the glass tube up
until the bottom of the tube is clear of the fitting. When
reinstalling the tube, use new sealing washers. Do
not overtighten the packing nuts; it could break the
gauge glass. Check that both top and bottom valves
are fully open.
Pressure Switches
WARNING: DISCONNECT ELECTRICAL POWER
SUPPLY BEFORE REMOVING BOILER CONTROL
BOX COVER.
There are two pressure switches located inside the
boiler control box. One pressure switch is the cycling
or primary control; the other is the high limit control.
They are identical switches, differing only in their
settings. Each one is identified by a label attached to
the switch case. The labels show the proper setting
for:
Cycling Switch: Off at 10 psi and on at 8 psi
High Limit Switch: Off at 15 psi and on at 6 psi
There are two square head slotted adjustment screws
which project through the top of the switch case and
a dial with pointers that indicate the approximate
setting. The adjustment screw directly above the dial
changes both the cut-out (off) and the cut-in (on)
points. Set it first to give the proper OFF setting.
Turning the screw clockwise increases the pressure.
Then set the second adjustment screw to give the
proper ON setting.
To check the wiring, remove the switch cover (held in
place by one captive screw). If wiring is correct and
an adjustment of the setting does not correct the
problem, replace the control. DO NOT attempt to
disassemble the switch or its operating mechanism.
High Limit Thermostat
Remove thermostat and inspect flat surface of
thermostat for corrosion or rust. Replace if rusted.
Clean thermostat mounting and thermostat surfaces
before remounting or replacing. A good metal-tometal contact is essential for proper functioning of the
thermostat. This service must be performed at least
once a year.
On gas boilers, the high limit thermostat is located on
the face of the boiler close to the sight glass on the
right. For access, remove the approximately 2" x 2"
metal cover placed over the thermostat.
35
On electric boilers, the high limit thermostat is located
behind the contactor box cover. On electric boilers
with two heating elements, the thermostat is connected
to one of the heating element lugs. On electric boilers
with four heating elements, the thermostat is located
between the center pair of elements at the top of the
elements.
Steam Supply Solenoid
Fill Solenoid Valve
It is not necessary to remove the valve body from the
supply line to disassemble it. Remove the retaining cap
and remove coil assembly. Unscrew the stem from the
valve body. All parts are now accessible for inspection
and cleaning. Do not reuse damaged or worn parts.
Pay careful attention to proper orientation and
placement of parts during reassembly.
The magnetic coil of a solenoid valve is removed from
the valve by removing the snap catch at the center
top. Unions are provided to allow easy removal of the
valve bodies. The solenoid valves must be removed
to disassemble them.
Remove the two screws and remove the inlet part of
the body, the compression spring on the back of it and
the plastic part now exposed.
Unscrew and remove the plunger tube. Remove the
plunger (the valve blade is pinned to the lower end of
the plunger). The plastic seat at the exhaust side of
the valve blade may now be removed from the body.
This is a direct acting valve.
The blade must be clean and the blade mating surfaces
of the plastic seat members must be flat and
undamaged. The plunger and plunger tube must be
clean and the plunger must slide freely in the tube.
The compression spring which fits in the hole in the
top of the plunger must be clean and move freely.
Removing the Generator Assembly
Turn off the gas and electrical supplies and close the
water inlet valve. Drain the generator. Remove the
screws holding any control box which would obstruct
removal of the boiler through the front of the generator
base.
Disconnect the 1⁄4” diameter water inlet tubing.
Disconnect the wire and conduit from the low water
cut-off probes, high limit thermostat, and the automatic
blow down valve (if so equipped). Uncouple the union
on the steam outlet and blow down the lines.
Remove all the screws holding the flue and flue
collector to the generator. Remove the anchor screws
holding the generator to the frame. Slide the generator
forward. The burner box, anchored only by the
generator, must be prevented from sliding forward
with the generator.
Water is Not Being Supplied to Boiler
Turn steamer ON. Check that water supply is available
to the steamer. If after 20 minutes no water can be
observed in the water level gauge sight glass, then
check for a problem with the water solenoid valve or
water level control float and/or probe.
The water level control probe may be covered by
scalant, thereby falsely indicating sufficient water is
present in the boiler. Detach, remove and thoroughly
clean the water level control assembly to remove scalants
and lime build-up. This condition indicates extremely
poor water quality being supplied to the boiler. Water
must be cleared up immediately with a proper water
conditioner to avoid complete breakdown of the steamer.
Water may be draining through an open boiler
blowdown solenoid valve as quickly as it is fed to the
boiler. Loose wiring or a burned out coil may prevent the
valve from closing. This valve contains a movable blade
and when closed, the blade reacts as a guillotine which
should be free to move fully down into the valve pocket
(projection at bottom of valve) so that the pierced hole
in the blade aligns perfectly with the body opening. If
debris has accumulated in the bottom of the valve
pocket, then the blade will not be able to move into the
pocket completely.
If the valve coil needs to be replaced, remove valve
from cooker body and remove retaining clip at top of
solenoid. Grasp cover and housing (green) intact
with coil inside and slide off from valve. Unscrew
projecting tube from top of valve body and remove
internal mechanism together with blade assembly.
Next, unscrew both assembly bolts and split brass
body of valve, removing loose internal parts. Flush
and clean pocket thoroughly. Reassemble all parts in
reverse order of disassembly. Energize valve with
120 volt power, and if valve fails to close, replace coil.
Reconnect all plumbing.
36
Boiler Blowdown Solenoid Valve Does Not Drain
If your steamer has an automatic blowdown drain
valve, when the blowdown button is depressed, the
boiler blowdown valve opens. If your steamer has a
manual blowdown drain valve, close it. The water
contained in the boiler, being under pressure, should
be blown through this valve and be noticeably visible
exhausting out the steamer drain. If the blowdown
operation appears to function sluggishly or not at all,
considerable scalant may be lodged in the drain pipe
and/or the valve. Disconnect the valve from the drain
line and inspect both the valve and the drain pipe
fixed to the boiler. If considerable scalant or lime
build-up is apparent, then not only the valve, but also
the boiler and water level control must be thoroughly
cleaned. Refer to “Water Is Not Being Supplied To
Boiler” for cleaning procedure of valve and “Removal
of Scalants from Boiler.”
Boiler Achieves Pressure Slower Than Normal
If the boiler requires more than 15 minutes to achieve
normal operating pressure (6 to 7 psi), then assume
that heavy build-up of scalant has completely coated
the interior of the boiler. The insulating effect of the
scalant hampers heat transfer.
The pilot burner flame is controlled by an adjustable
valve (under cap screw behind the dial of the
combination control valve). Turn clockwise to
decrease pilot flame. Pilot flame should be a steady
blue flame which envelopes the thermocouple tip.
Pilot flame should be about 1" long. A pilot orifice
fitting is located at the bottom of the pilot and is the
hexagon fitting to which the gas supply tubing to the
pilot is attached.
The main burners are lanced port steel burners (5 or
7 burners, depending on the unit) and have adjustable
air shutters. Fixed orifice-type hoods are used to
establish the gas flow to each burner. Set each
burner air shutter opening just large enough to
eliminate any yellow tip in the burner flame.
Pilot, Thermocouple or Main Burners
To remove the pilot assembly, disconnect thermocouple
and pilot gas supply tubing from the combination control
valve and remove the two screws holding the pilot to
its bracket.
To remove main burners, lift burner and move it to the
rear to clear the orifice hood, then lower front end of
burner and bring it forward under the manifold pipe.
Unbolt and remove the hand hole cover plate and
gasket assembly. Examine interior of boiler, and if
scalant and/or lime build-up is apparent, follow
procedure for removal of scalants from boiler.
If considerable scalant is evident, then both the boiler
blowdown solenoid valve and the water level control
must also be examined.
GAS GENERATORS
The pilot thermocouple supplies power to the gas
valve. A gas pressure regulating valve is an integral
part of the gas control valve and is set for 3.5" Water
Column for natural gas and 10" Water Column for
propane gas. Limited adjustment is provided by a
screw under the cap screw located at the top of the
control body. Turn the screw clockwise to increase
the gas pressure to the main burner.
If pilot keeps going out, first check visually for proper
pilot flame. Check to see that unusually strong floor
drafts are not interfering with proper heating of the
thermocouple by the pilot flame. If the pilot flame is
not the proper height, adjust it. If adjustment does not
result in a pilot flame of proper size, then gas is not
flowing properly to the pilot. Check for a plugged pilot
orifice, a kinked or plugged pilot gas supply tube, a
problem in the combination control valve, or for low or
high gas supply pressure. The pilot operates at gas
supply pressure. The pressure regulator in the
combination control valve regulates only the pressure
of gas to the main burner.
If the pilot flame is correct and there are no drafts,
then the problem is in the thermocouple or the
combination control valve. Check the thermocouple
with a millivoltmeter. If a meter is not available,
replace thermocouple with a new one as a check. The
connection of the tubing from the thermocouple tip to
the control valve is an electrical connection and must
be clean. Do not use any sealing compound on the
threads. With a wrench, tighten the nut finger tight
plus 1⁄4 turn. DO NOT OVERTIGHTEN this nut. To
check a thermocouple with a millivoltmeter, make a
closed circuit check first (an adapter is required).
Closed circuit reading should be 13 to 26 MV.
37
Blow pilot flame out. The reading when the protection
valve closes (drop-out point) should be at least 5 MV
below first reading. If first reading is correct, but dropout point is not, problem is in the combination control
valve. An open circuit check of the thermocouple
should give a meter reading of 30 to 40 MV.
Gas Combination Control Valve Replacement
If removed element shows a pronounced scale buildup on its heating tubes, the other elements should be
removed and mechanically cleaned to remove the
scale. This will prolong their life. DO NOT immerse
elements in a chemical solution to descale.
Inoperative Control Circuit (Generator Control and
Compartment Controls)
Disassembling this control is not recommended. If
the control is not working, replace the entire control.
To remove the control, remove the two screws on the
control box cover on which the generator push button
switches are mounted. Disconnect wires and conduit
running to the combination control valve. Disconnect
thermocouple lead and pilot gas supply tube from
control and uncouple pipe unions on each side of the
control.
ELECTRIC GENERATORS
Magnetic Contactor
The contactor can be serviced by removing the cover
of the contactor box.
A noisy contactor (hum or chatter) is generally due to
enough dust or dirt on the armature pole faces or
around the armature core that the magnet coil cannot
pull the armature into a completely sealed position.
This can usually be corrected by blowing or wiping the
pole faces clean. To inspect contactor contact points,
remove cover at top of contactor by removing two
screws which hold it in place. Replace contactors if
points are pitted or burned.
Electric Element
To determine whether all elements are heating
properly, use an ampmeter with power ON to the
elements. See wiring diagram for amperage ratings.
Always check that the supply voltage and the voltage
rating of the element agree.
To replace an element, drain water from generator
shell. Remove cover of contactor box, remove electric
wires to that element’s terminals, remove bolts through
flange of element and pull element forward. When
replacing an element, always use a new gasket. The
flange and tube surfaces which contact the gasket
must be clean.
If the steamer is equipped with a step down
transformer, check transformer for proper operation.
If there is a separate 120 volt line for control circuit,
check this line for power.
REGENERATING (STEAM COIL) GENERATORS
The steam coils are intended for use at a steam supply
pressure of 15 psi maximum. A pressure regulating
valve is available as optional equipment for steamers
where the steam supply pressure exceeds 15 psi.
Regulators of a different make and type may be
supplied at different times and to meet special
conditions; therefore, no specific service information for
the regulator is included here. The regulator used will
be of the adjustable type and should be set for a
discharge pressure of 15 psi. A pressure gauge is
provided to indicate the regulator discharge pressure.
The regulator should be set when steam is flowing
(steam solenoid valve is open). If steam is heavy with
condensate, install a ball float trap in the steam line
before the pressure regulating valve.
To remove a steam coil, disconnect union in steam
supply line to the coils and in the condensate discharge
line from the coils. Remove header that supplies
steam to coils by disconnecting union at each coil. In
same way, remove coil condensate collection header.
Remove four bolts clamping each coil flange in place
and pull coil forward. Use a new flange gasket when
replacing coil. The faces that mate with gasket must
be clean.
Turn steamer power switch ON, allowing steam
generation and, consequently, pressure to rise to
normal operating level and then turn power switch
OFF for a final purging of boiler and steam supply
lines.
Steamer is now ready for use.
38
REPLACEMENT PARTS LIST
REPLACEMENT PARTS ORDERING
The following information must accompany a replacements parts order or it cannot be filled.
A. Model and style or serial number.
B. Type of gas (natural or propane).
C. Voltage and phase.
D. Appliance finish, permafinish, stainless steel, etc. (if applicable to part to be replaced).
Use rating plate located inside base cabinet door to help you obtain the information listed above. This plate will
provide all the necessary information required by the service agency.
Parts may be ordered only from your authorized parts and service depot. For assistance in locating your nearest
authorized parts and service depot, refer to the enclosed directory.
ALL SERVICE PERSONNEL
WHEN SERVICING THIS EQUIPMENT, USE ONLY
CONTROLS ORIGINALLY SUPPLIED ON THIS EQUIPMENT BY
VULCAN-HART COMPANY.
DO NOT SUBSTITUTE.
SUBSTITUTION OF CONTROLS AS STATED ABOVE
WILL AUTOMATICALLY VOID THIS WARRANTY
AND THE CERTIFICATION ASSOCIATED WITH THIS EQUIPMENT.
10 840491 Rod - Hinge ................................................................................................................................1
11 836975 Spring - Compression ................................................................................................................ 6
1 FP-81-34 Tee .............................................................................................................................................. 4
1 817081 Box - Boiler Control ................................................................................................................... 1
2 WS-3-45 Washer ...................................................................................................................................... AR
3 817081-3 Bracket - Control Box Mounting ................................................................................................ 1