Vivotek NDR-240-48 Specsheet

Page 1
240W Single Output Industrial DIN RAIL
NDR-240 series
Bauar
tgepruft
Sicherheit
o s
be
wac g
www.
tuv.com
ID 2000000000
File Name:NDR-240-SPEC 2015-05-04
Page 2
240W Single Output Industrial DIN RAIL
SPECIFICATION
MODEL
DC VOLTAGE
RATED CURRENT
CURRENT RANGE
RATED POWER
RIPPLE & NOISE (max.)
OUTPUT VOLTAGE ADJ. RANGE
VOLTAGE TOLERANCE Note.3
LINE REGULATION
LOAD REGULATION
SETUP, RISE TIME
HOLD UP TIME (Typ.)
VOLTAGE RANGE
FREQUENCY RANGE
POWER FACTOR (Typ.) PF>0.98/115VAC, PF>0.95/230VAC at full load
INPUT
PROTECTION
ENVIRONMENT
SAFETY &
EMC
(Note 4)
EFFICIENCY (Typ.)
AC CURRENT (Typ.) INRUSH CURRENT (Typ.)
LEAKAGE CURRENT
OVERLOAD
OVER VOLTAGE
OVER TEMPERATURE
WORKING TEMP.
WORKING HUMIDITY
STORAGE TEMP., HUMIDITY
TEMP. COEFFICIENT
VIBRATION
SAFETY STANDARDS WITHSTAND VOLTAGE
ISOLATION RESISTANCE EMC EMISSION
EMC IMMUNITY MTBF
DIMENSIONOTHERS
PACKING
NDR-240 series
84-042-RDN42-042-RDN
V84V42
A5A01
A5 ~ 0A01 ~ 0
W042W042
Note.2
±1.0% ±1.0% ±0.5% ±0.5% ±1.0% ±1.0%
1500ms, 100ms/230VAC 3000ms, 100ms/115VAC at full load
28ms/230VAC 22ms/115VAC at full load
90 ~ 264VAC 127 ~ 370VDC
Note.4
47 ~ 63Hz
88.5%
2.5A/115VAC 1.3A/230VAC 20A/115VAC 35A/230VAC
<1mA / 240VAC
105 ~ 130% rated output power
Protection type : Constant current limiting, recovers automatically after fault condition is removed
29 ~ 33V
Protection type : Shut down o/p voltage, re-power on to recover
Shut down o/p voltage, recovers automatically after temperature goes down
-20 ~ +70 (Refer to "Derating Curve")
20 ~ 95% RH non-condensing
-40 ~ +85 , 10 ~ 95% RH
± 0.03%
/ (0 ~ 50 )
Component:10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X, Y, Z axes; Mounting: Compliance to IEC60068-2-6
UL508, TUV EN60950-1 approved
I/P-O/P:3KVAC I/P-FG:2KVAC O/P-FG:0.5KVAC
I/P-O/P, I/P-FG, O/P-FG:>100M Ohms / 500VDC / 25 / 70% RH
Compliance to EN55022 (CISPR22), EN61204-3 Class B, EN61000-3-2,-3
Compliance to EN61000-4-2,3,4,5,6,8,11, EN55024, EN61000-6-2 (EN50082-2), EN61204-3, heavy industry level, criteria A
230.2K hrs min. MIL-HDBK-217F (25 )
63*125.2*113.5mm (W*H*D)
1Kg; 12pcs/13Kg/1.1CUFT
p-pVm051p-pVm051
V55 ~ 84V82 ~ 42
90%
56 ~ 65V
NOTE
File Name:NDR-240-SPEC 2015-05-04
Page 3
Block Diagram
240W Single Output Industrial DIN RAIL
NDR-240 series
fosc : 70KHz
I/P
FG
)%( DAOL
EMI FILTER
&
RECTIFIERS
100
80
60
50
40
20
-20 0 10 20 30 40 50 60 70
PFC
CIRCUIT
AMBIENT TEMPERATURE ( )
O.L.P.
O.T.P.
POWER
SWITCHING
PWM & PFC
CONTROL
(VERTICAL)
RECTIFIERS
&
FILTER
O.C.P.
DETECTION
CIRCUIT
O.V.P.
egatlov tupni SV gnitared tuptuOevruC gnitareD
100
90
80
70
)%( DAOL
)%( DAOL
60
50
40
90 100 125 135 145 155 165 175 180 200 230 264
INPUT VOLTAGE (V) 60Hz
175
+V
-V
File Name:NDR-240-SPEC 2015-05-04
Page 4
240W Single Output Industrial DIN RAIL
Mechanical SpecificationMechanical Specification
113.5
Top View
63
3
2
1
NDR-240 series
Case No.979C Unit:mm
4
93
Installation Instruction
TB2
2.521
1
+V ADJ.
DC OK
TB1
2
+
3
Side ViewweiV tnorFweiV ediS
Terminal Pin No. Assignment (TB1)
Assignment
Pin No.
FG
1 2
AC/N or DC -
3
AC/L or DC +
Terminal Pin No. Assignment (TB2)
Assignment
Pin No.
DC OUTPUT -V
1,2
DC OUTPUT+V
3,4
Bottom View
Back View
53
ADMISSIBLE DIN-RAIL:TS35/7.5 OR TS35/15
(For reference only. Not included with unit.)
This series fits DIN-RAIL TS35/7.5 or TS35/15. For installation details, please refer to the USER MANUAL on http://www.meanwell.com/search/NDR-240/NDR_manual.pdf
File Name:NDR-240-SPEC 2015-05-04
Loading...