120W Single Output Industrial DIN RAIL
NDR-120 series
■ Features ■ Applications
Universal AC input / Full range
Protections: Short circuit / Overload / Over voltage
/ Over temperature
Cooling by free air convection
Industrial control system
Semiconductor fabrication equipment
Factory automation
Electro-mechanical apparatus
Can be installed on DIN rail TS-35/7.5 or 15
UL 508 (industrial control equipment) approved
EN61000-6-2(EN50082-2) industrial immunity level
100% full load burn-in test
3 years warranty
Bauar
Sicherheit
egel gema
od
be
wac g
www.
ID 2000000000
tgepruf t
os
tuv.com
■ Description
NDR-120 is one economical slim 120W DIN rail power supply series, adapt to be installed on TS-35/7.5
or TS-35/15 mounting rails. The body is designed 40mm in width, which allows space saving inside the
cabinets. The entire series adopts the full range AC input from 90VAC to 264VAC and conforms to
EN61000-3-2, the norm the European Union regulates for harmonic current.
NDR-120 is designed with metal housing that enhances the unit's power dissipation. With working efficiency
up to 89%, the entire series can operate at the ambient temperature between -20 and 70 under air ℃℃
convection. It is equipped with constant current mode for over-load protection, fitting various inductive
or capacitive applications. The complete protection functions and relevant certificates for industrial control
apparatus (UL508, TUV EN60950-1, and etc.) make NDR-120 a very competitive power supply solution for
industrial applications.
■ Model Encoding
-12NDR - 120
Output voltage
Output wattage
Series name
File Name:NDR-120-SPEC 2014-09-16
SPECIFICATION
120W Single Output Industrial DIN RAIL
NDR-120 series
MODEL
DC VOLTAG E
RATED CURRENT
CURRENT RANGE
RATED POWER
RIPPLE & NOISE (max.)
OUTPUT VOLTAGE ADJ. RANGE
VOLTAGE TOLERANCE
LINE REGULATION
LOAD REGULATION
SETUP, RISE TIME
HOLD UP TIME (Typ.)
VO LTAG E R AN GE
FREQUENCY RANGE
INPUT
PROTECTION
ENVIRONMENT
SAFETY &
EMC
(Note 4)
NOTE
EFFICIENCY (Typ.)
AC CURRENT (Typ.)
INRUSH CURRENT (Typ.)
LEAKAGE CURRENT
OVERLOAD
OVER VOLTAGE
OVER TEMPERATURE
WORKING TEMP.
WORKING HUMIDITY
STORAGE TEMP., HUMIDITY
TEMP. COEFFICIENT
VIBRATION
SAFETY STANDARDS
WITHSTAND VOLTAGE
ISOLATION RESISTANCE
EMC EMISSION
EMC IMMUNITY
MTBF
DIMENSIONOTHERS
PACKING
1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25 of ambient temperature.℃
2. Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor.
3. Tolerance : includes set up tolerance, line regulation and load regulation.
4. The power supply is considered a component which will be installed into a final equipment. The final equipment must be re-confirmed that it still meets
EMC directives.
5. Installation clearances : 40mm on top, 20mm on the bottom, 5mm on the left and right side are recommended when loaded permanently with full power.
In case the adjacent device is a heat source, 15mm clearance is recommended.
6. Derating may be needed under low input voltage. Please check the derating curve for more details.
NDR-120-12
12V
10A
0 ~ 10A
120W
Note.2
100mVp-p
12 ~ 14V
Note.3
±2.0%
±0.5%
±1.0%
1200ms, 60ms/230VAC 2500ms, 60ms/115VAC at full load
16ms/230VAC 10ms/115VAC at full load
Note.6
90 ~ 264VAC 127 ~ 370VDC [DC input operation possible by connecting AC/L(+), AC/N(-)]
47 ~ 63Hz
85.5%
2.25A/115VAC 1.3A/230VAC
20A/115VAC 35A/230VAC
<1mA / 240VAC
105 ~ 130% rated output power
Protection type : Constant current limiting, recovers automatically after fault condition is removed
14 ~ 17V
Protection type : Shut down o/p voltage, re-power on to recover
Shut down o/p voltage, re-power on to recover
-20 ~ +70 (Refer to "Derating Curve")℃
20 ~ 95% RH non-condensing
-40 ~ +85 , 10 ~ 95% RH℃
±℃ ℃0.03%/ (0 ~ 50 )
Component:10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X, Y, Z axes; Mounting: Compliance to IEC60068-2-6
UL508, TUV EN60950-1 approved
I/P-O/P:3KVAC I/P-FG:2KVAC O/P-FG:0.5KVAC
I/P-O/P, I/P-FG, O/P-FG:>100M Ohms / 500VDC / 25 / 70% RH℃
Compliance to EN55022 (CISPR22), EN61204-3 Class B, EN61000-3-2,-3
Compliance to EN61000-4-2,3,4,5,6,8,11, EN55024, EN61000-6-2 (EN50082-2), EN61204-3, heavy industry level, criteria A
456.3K hrs min. MIL-HDBK-217F (25 )℃
40*125.2*113.5mm (W*H*D)
0.6Kg; 20pcs/13Kg/1.16CUFT
NDR-120-24 NDR-120-48
24V 48V
5A 2.5A
0 ~ 5A 0 ~ 2.5A
120W 120W
120mVp-p 150mVp-p
24 ~ 28V 48 ~ 55V
±1.0% ±1.0%
±0.5% ±0.5%
±1.0% ±1.0%
88%
29 ~ 33V
89%
56 ~ 65V
File Name:NDR-120-SPEC 2014-09-16