Viking supervised Double-Interlocked Electric/Pneumatic Release Preaction Systems
utilize the Viking G-4000P Valve.
The small prole, lightweight, pilot operated Viking Model G-4000P Valve comes complete
as shown in Figure 8. The system piping is pressurized with air or nitrogen to serve both as
a means of supervising the integrity of the piping network and as one portion of the system
release operation. This feature serves to prevent undetected leaks on the system piping
network. If the system piping or a sprinkler is damaged, the supervisory pressure is reduced
and a “low air” supervisory alarm is activated.
This pilot-operated externally reset valve also includes an internal check diaphragm,
which eliminates the need for a separate check valve being installed in the system riser.
Double interlocked electric / pneumatic release preaction systems require the use of one 24
VDC normally closed (NC) electric solenoid and one pneumatic actuator. The electric solenoid is connected to a compatible release control panel and compatible detection devices.
The pneumatic actuator is controlled by the air pressure that is contained within the sprinkler
system piping. In re conditions, both the solenoid and a sprinkler must open in order for the
Preaction valve to operate. When both the solenoid and pneumatic actuator open, the priming water is relieved from the internal prime chamber assembly. The prime chamber assembly collapses, and water passes through the G-4000P Valve and internal check diaphragm
to the system piping network. The entire sprinkler system lls with water.
Double interlock electric/pneumatic release preaction systems are commonly used in cold
storage applications and other areas where it is important to control accidental water discharge due to inadvertent damage to the sprinkler piping.
2. LISTING AND APPROVALS
cULus Listed: VLFT
FM Approved: Refrigerated Area Sprinkler Systems
3. TECHNICAL DATA
Specifications:
Pressure Rating: 250 PSI (17.2 bar) Water Working Pressure
Factory Hydrostatically Tested to: 500 psi (34.5 bar)
Friction Loss (Given in feet of Schedule 40 pipe based on Hazen & Williams formula C = 120):
Model G-4000P Valve: 31.2’
12” Section of Pipe: 1’
Water Supply Control Valve: 15’
Model G-4000P Valve Cv Factor: 341
Valve Color: Black
Material Specifications:
Refer to Figure 11.
Ordering Information:
Available since 2009.
Part Number: Double Interlock Electric/Pneumatic Preaction System Riser Assembly (with
Control Valve and Pressure Switches): 15653-1 (Refer to Figure 8.)
Accessories: (Refer to Figure 9.)
Drain Manifold: 15588
Model E-1 Accelerator: 08055
Model LD-1 Anti-Column Device: 14800
4. INSTALLATION:
A. General Installation Instructions
1. For proper operation and approval, the valve must be installed in the vertical position as trimmed from the factory. DO NOT
modify the factory-assembled trim except as described in this technical data sheet.
2. A 12” section of pipe is provided with the G-4000P Double Interlock Electric/Pneumatic Preaction System Riser Assembly.
Prior to G-4000P Valve maintenance, this section of pipe may be removed to provide clearance for lifting the cover from the
Form No. F_112008 18.10.25 P65
Replaces Form No. F_112008 Rev May 28, 2013
Viking Technical Data may be found on
The Web site may include a more recent
Q= C
Q = Flow
Cv = Flow Factor (GPM/1 PSI ∆P)
∆P = Pressure Loss through Valve
S = Specic Gravity of Fluid
The Viking Corporation’s Web site at
http://www.vikinggroupinc.com.
edition of this Technical Data Page.
v
√
(Added P65 Warning.)
∆P
S
Page 2
Page 2 of 12
4” MODEL G-4000P
TECHNICAL DATA
The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058
For Metric Units 1 Ft. = 0.3048 M, 1 Gal. = 3.785L
Schedule 30 (8”)
Gal / FtL / mGal / FtL / m
valve body.
3. The G-4000P Valve must be installed in an area not subject
to freezing temperatures or physical damage. If required,
Schedule 10
Table 2 - Air
Pressure Settings
For Systems with Tank Mounted Compressors:
Air Maintenance Device30 PSI (2.1 bar)50 PSI (3.5 bar)
Air Supervisory Switch25 PSI (1.7 bar)45 PSI (3.1 bar)
For Systems with Riser Mounted Compressors:
Compressor On/Off
Switch
Air Supervisory Switch25 PSI (1.72 bar)45 PSI (3.10 bar)
Up to 175 PSI
30 PSI (2.1 bar)
/ 40 PSI (2.8 bar)
Table 3 - Quick Reference Compressor Size
Compressor
Size (HP)
1/61.090
1/32.0180
1/23.1300
15.9600
Free Air @
40 PSI (cfm)
System Pressure
(12 bar)
Max System Size to Pump
to 40 psi in 30 Minutes (Gal)
175 PSI (12 bar)
to 250 PSI (17 bar)
50 PSI (2.1 bar) /
60 PSI (2.8 bar)
provide a valve house (enclosure) with adequate heat around
the G-4000P Valve and trim. Freezing temperatures will dam- age the G-4000P Valve. When corrosive atmospheres and/or
contaminated water supplies are present, it is the owner’s responsibility to verify compatibility with the Model G-4000P Valve
and associated equipment.
4. The Viking E-1 Accelerator should be installed at the location indicated in Figure 1 when required.
B. Air Supply Design
1. Air Compressor Size
Viking recommends tank mounted air compressors for Double Interlock Electric/Pneumatic Release Preaction Systems. The pneumatic actuator requires at least 30 psi (2.1 bar) of air pressure be established within the piping network for systems with water pressure
up to 175 psi (12.1 bar) and 50 psi (3.45 bar) of air pressure for systems with water pressures up to 250 psi (17.2 bar).
NFPA 13 requires the air supply to be capable of lling the entire sprinkler system to its required air pressure within 30 minutes. A
common method of sizing an air compressor is to use the following formula:
Compressor
Size (cfm) =
V x P
7.48 x 14.7 x T
Therefore, the compressor shall be capable of providing 7 cfm.
2. Nitrogen Cylinder Gas Supply (See Figure 1)
Nitrogen may be used in place of air compressors. Nitrogen is supplied in pressurized cylinders in various sizes and pressures. Some
of the most common are 122 Cu. Ft. at 1,900 PSI (3,455 Ltrs. at 131 bar), 225 Cu. Ft. at 2,100 PSI (6,372 Ltrs. at 145 bar), and 280
Cu. Ft. at 2,300 PSI (7,930 Ltrs. at 159 bar).
When nitrogen cylinders are used as a primary air supply, spare cylinders should be furnished and located at the valve location.
To determine the approximate amount of nitrogen to be furnished, the following formula may be used:
English Units
Where:
Vc= Volume of Cylinder (ft3)
P = Required Nitrogen Pressure (psig)
Vc =
Vs x P
100
V = Volume of System (gal)
Form No. F_112008 18.10.25 P65
Where:
V= Volume
P = Required Air Pressure
T = Fill time (typically 30 min.)
7.48 = gal. / ft.
3
14.7 = atmospheric pressure
Example:
System volume as determined by table 1 = 750 gallons
Required Air pressure = 30 psi
Compressor Size (cfm) =
(750 x 30)
7.48 x 14.7 x 30
Metric Units
Where:
Vc= Volume of Cylinder (L)
P = Required Nitrogen Pressure (bar)
Vc =
Vs x P
108
V = Volume of System (L)
= 6.8 cfm
Page 4
Page 4 of 12
4” MODEL G-4000P
TECHNICAL DATA
The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058
FIELD ADJUSTMENTS:
Alarm Pressure Switch: The operating point of the switch can be
adjusted to any point between 4 PSI (0.27 bar) and 8 PSI (0.55 bar)
by turning the adjustment knob(s) clockwise to raise the actuation
point or counter-clockwise to lower the actuation point.
Air Supervisory Switch: The operating point of the switches can
be adjusted to any point between 10 PSI (0.7 bar) and 60 PSI
(4.1 bar) by turning the adjustment knob(s) clockwise to raise the
actuation point or counter-clockwise to lower the actuation point.
The high and low switches are adjusted independently.
Figure 3 - Air Supervisory Switch Wiring
Special attention must be given to systems employing a bottled-gas supply. Because only a limited amount of gas is available, small
leaks which normally would go unnoticed in systems being supplied by mechanical compressors, can become critical to the system’s
overall performance. If the system is to function at temperatures as low as -40 °F (-40 °C), and, if bottled nitrogen is the gas supply, the
system is particularly susceptible to leakage, and special care should be taken to ensure against leaks throughout the entire system.
C. Air Supply Installation
1. Install the required air supply as described in section 4.B. The size of the compressor and amount of air required should be
determined in accordance with Tables 1, 2 & 3. The air or nitrogen supply to the Preaction System must be clean, dry, and
oil free.
2. Automatic air supplies must be regulated, restricted, and from a continuous source. A Viking Air Maintenance Device should
be installed on each system equipped with a tank mounted compressor, plant air or nitrogen. For compressors with a capacity
less than 5.5 ft3/min at 10 psig (0.154 m3/min at 0.69 bar), NFPA 13 does not require an air maintenance device. The use of
an air maintenance device with riser mounted compressors can lead to compressor “short cycling”. Viking always recommends that a tank mounted compressor with air maintenance device be used. This can become critical when accelerators
are installed on the system.
D. Pressure Switch Wiring;
Wire the Alarm Pressure Switch (PS10) and Air Supervisory Switch (PS40), and adjust pressure settings as shown in Figures 2 - 4.
E. Hydrostatic Test:
The Preaction System, including Sprinkler Piping and Sprinklers shall be hydrostatically tested at 200 psi (13.79 bar) and maintained
for 2 hours, in accordance with NFPA 13. Systems normally subjected to working system pressures in excess of 150 psi (10.34 bar)
shall be tested at a pressure of 50 psi (3.45 bar) in excess of system working pressure.
F. Placing the Valve in Service: (Refer to Figure 5)
When the Preaction System is ready to be placed in service, verify that the pneumatic release system is in a normal condition and
that the electric release system has been reset.
1. Verify that the water supply main control valve supplying the G-4000P Valve is closed.
2. Close the prime valve.
3. Open the main drain valve.
4. Open the flow test valve.
Figure 4 - Pressure Adjustment
Form No. F_112008 18.10.25 P65
Page 5
Page 5 of 12
4” MODEL G-4000P
TECHNICAL DATA
The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058
5. Drain all water from the Preaction System. If the system has operated, or if water has entered the system, allow enough time
to completely drain the system.
6. Close the main drain valve.
7. Open the priming valve. Prime water pressure will enter and expand the valve’s internal diaphragm assembly onto the valve
seat, effectively closing the valve. Verify prime pressure has been established on the prime pressure gauge.
8. Establish air pressure on the system.
9. Verify that no water flows from the drip check when the plunger is pushed.
10. When the priming pressure has been verified as being established, slowly open the water supply control valve.
11. When flow is developed from the flow test valve, CLOSE the flow test valve.
12. Fully open the water supply main control valve.
13. Secure all valves in their normal operating position.
14. Reset the Release Control Panel.
15. Notify Authorities Having Jurisdiction and those in the affected area that the system is in service.
16. The system is now fully operational.
G. Operational Test:
An operational test shall be performed on the system in accordance with NFPA 13. Refer to Section 6 for Inspection and Operation
Test Procedures.
Form No. F_112008 18.10.25 P65
Page 6
Page 6 of 12
4” MODEL G-4000P
TECHNICAL DATA
The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058
When air pressure is introduced into the sprinkler piping, the sensing end of the pneumatic actuator is pressurized. This closes
the pneumatic actuator. The closed pneumatic actuator, and the normally closed solenoid valve prevent prime water from escaping the prime chamber of the G-4000P Valve. When prime water enters the prime chamber, the rolling diaphragm is pressurized,
causing it to expand downward onto the water seat.
Form No. F_112008 18.10.25 P65
Figure 6 - Set Position
Page 7
Page 7 of 12
4” MODEL G-4000P
TECHNICAL DATA
The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058
When the detection system operates, the normally closed solenoid valve is powered open. At this point, the prime water is still held
in the prime chamber by the closed pneumatic actuator. When a sprinkler operates, air pressure is lost on the sensing end of the
pneumatic actuator, causing the pneumatic actuator to open. With both the pneumatic actuator and solenoid valve open, prime
water is drained from the prime chamber, causing the G-4000P Valve to open, lling the sprinkler piping with water. Water from
the intermediate chamber of the G-4000P Valve pressurizes the sensing end of the PORV causing the PORV to open. The open
PORV prevents water pressure from building in the prime chamber should the solenoid or pneumatic actuator close.
DOUBLE INTERLOCK PREACTION
WITH ELECTRIC/PNEUMATIC RELEASE
Form No. F_112008 18.10.25 P65
Figure 7 - Fire Condition
Page 8
Page 8 of 12
4” MODEL G-4000P
TECHNICAL DATA
The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058
NOTICE: THE OWNER IS RESPONSIBLE FOR MAINTAINING THE FIRE PROTECTION SYSTEM AND DEVICES IN PROPER
OPERATING CONDITION. It is imperative that the system be inspected and tested on a regular basis in accordance with NFPA 25.
The frequency of the inspections may vary due to contaminated water supplies, corrosive water supplies, corrosive atmospheres, as
well as the condition of the air supply to the system. For minimum maintenance and inspection requirements, refer to NFPA 25. In addition, the Authority Having Jurisdiction may have additional maintenance, testing, and inspection requirements that must be followed.
Viking does not require internal inspection of the valve as part of routine inspection and testing. Internal maintenance is generally only
required for valve repairs and internal component replacement.
WARNING: Any system maintenance that involves placing a control valve or detection system out of service may eliminate the re
protection capabilities of that system. Prior to proceeding, notify all Authorities Having Jurisdiction. Consideration should be given to
employment of a re patrol in the affected areas.
A. Low Air Pressure Alarm Test: (Refer to Figure 5.)
Quarterly testing of low air alarms is recommended.
To Test Sprinkler System “Low Supervisory Air” Alarm:
1. To prevent operation of the G-4000P Valve and filling the system with water during the test, DO NOT operate the electric
detection system during test. Consider closing the main water supply control valve.
2. Fully open the sprinkler system test connection.
3. Verify that low air alarms operate within an acceptable time period and continue without interruption.
4. Close the test connection.
5. Establish recommended pneumatic supervisory pressure to be maintained. Refer to section 4. INSTALLATION.
6. Reset the system release control panel. Alarms should stop.
When testing is complete, return the system to service following steps 1 through 8 below.
B. Full Flow Trip Test: (Refer to Figure 5)
Performance of a trip test is recommended annually during warm weather. Consider coordinating this test with operation testing
of the detectors.
CAUTION! PERFORMANCE OF THIS TEST WILL CAUSE THE G-4000P VALVE TO OPEN AND THE SPRINKLER SYSTEM TO
FILL WITH WATER.
To Trip Test the Electric / Pneumatic Double-Interlock Preaction System:
1. Notify the Authority Having Jurisdiction and those in the area affected by the test.
2. Trip the G-4000P Valve by performing option “a” or “b” below.
a. Operate the electric release control system according to the manufacturer’s instructions, and open the sprinkler system
test connection.
b. Operate the emergency release Valve .
3. The G-4000P Valve should open, filling the sprinkler system with water. Water flow alarms should operate.
4. Verify that there is adequate flow from the sprinkler system test valve.
When Trip Testing is complete:
5. Perform steps 1 through 13 of section 4.F. PLACING THE SYSTEM IN SERVICE to return the system to service.
6. Notify the Authority Having Jurisdiction and those in the affected area that testing is complete.
7. MAINTENANCE
Viking does not require an internal inspection of the G-4000P Valve unless there is an indication of damage to internal components.
A. Taking the system out of service: (Refer to Figure 5.)
1. Close the water supply main control valve, placing the system out of service.
2. Open the flow test valve located in the base of the G-4000P Valve.
3. Close the air (or nitrogen) supply to the preaction system piping.
4. Close the priming valve.
5. Relieve all pressure from the preaction system piping. If the system has operated, open main drain valve to allow the system
to drain completely.
B. Removing the Cover from the Valve Body: (Refer to Figures 1 & 11.)
1. Remove the 4” coupling from the top of the G-4000P Valve.
2. Remove the section of pipe directly above the G-4000P Valve.
3. Break the 1/2” coupling between the air pressure gauge and air pressure supervisory switch.
4. Remove the 2” coupling below the main drain.
Form No. F_112008 18.10.25 P65
Page 9
Page 9 of 12
4” MODEL G-4000P
TECHNICAL DATA
The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058
6. The cover (11) and trim that is still connected may now be removed from the body. (It may be necessary to pry the valve open
as the diaphragm may bond itself to the cover (11) and valve body over time.)
C. Removing / Replacing the Check Diaphragm: (Refer to Figure 11.)
1. The check diaphragm (10) may be lifted from the valve body (1).
2. If necessary, replace the check diaphragm (10).
D. Inspecting the Prime Chamber and Coupling for leaks: (Refer to Figure 11.)
If desired, it is possible to set the G-4000P Valve and inspect for leaks with the cover (11) removed.
1. Slowly open the prime valve.
2. With prime water established, partially open the main water supply control valve.
3. Visually inspect the inside of the G-4000P Valve for leaks.
E. Removing / Replacing the Prime Coupling: (Refer to Figure 11.)
1. Open the 1/2” union on the prime line.
2. Using a wrench on the flats of the coupling (7), remove the coupling (7) from the valve body (1).
3. Inspect the coupling (7) and two O-rings (5 & 6). Replace if necessary, using the instructions in O-Ring Replacement Bulletin
F_120611.
F. Removing / Replacing the Prime Chamber Assembly: (Refer to Figure 11.)
1. The prime chamber assembly (4) is now held in place by two flanges on the outside diameter of the assembly. Slide the prime
chamber assembly (4) toward the prime line and remove from the body.
2. Inspect and replace if necessary.
3. Inspect the seat. The seat should be clean and free of foreign material. If the seat is damaged, the G-4000P Valve must be
replaced.
G. Re-Assembling the Valve: (Refer to Figure 11.)
1. Place the prime chamber assembly (4) in the valve body (1). Make sure the two flanges are positioned in the groove.
2. Thread the prime coupling (7) into the valve body (1). Make sure the end of the prime coupling (7) is inserted into the prime
chamber assembly (4).
3. Tighten the 1/4” socket set screw (8).
4. Lay the check diaphragm (10) into the valve body (1).
5. Position the cover (11) onto the valve body (1), and install and tighten the cover screws (12).
6. Re-install any trim that was removed.
7. Place the valve in service by following the steps in Section 4.F.
DOUBLE INTERLOCK PREACTION
WITH ELECTRIC/PNEUMATIC RELEASE
8. AVAILABILITY
The Viking Model G-4000P Valve is available through a network of domestic and international distributors. See the Viking Corp. Web
site for closest distributor or contact The Viking Corporation.
Form No. F_112008 18.10.25 P65
Page 10
Page 10 of 12
4” MODEL G-4000P
TECHNICAL DATA
The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058