Viessmann Vitodens 200-W, B2HB Technical Manual

Page 1
Technical Data Manual
Model Nos. and pricing: see Price List
For Natural Gas and Liquid Propane Gas Gas-fired wall-mounted condensing boiler 12 to 125 MBH (3.5 to 37 kW)
VITODENSr 200-W
Product may not be exactly as shown
Vitodens 200-W Series B2HB, Models 19, 26 and 35
Gas-Fired Wall-Mounted Condensing Boiler with modulating MatriX cylinder burner for room air independent operation (using a direct vent system) or room air dependent operation.
5461 883 - 02 04/2015
H
Page 2
Product Information
Vitodens 200-W
Equipped with the industry’s first intelligent combustion management system and powerful control technology, the new generation Vitodens 200-W gas-fired wall-mount condensing boiler delivers unparalleled performance, reliability and comfort.
The benefits at a glance:
Vitodens 200-W, B2HB 19 to 35 Technical Data
Best value in its class with new industry-leading technology and the most standard features.
Highest Efficiency up to 98% at full modulation and up to 95% A.F.U.E.
Lasting performance with industry-leading Viessmann made SA240 316 Ti stainless steel Inox-Radial heat exchanger constructed to CSA B51 and ASME Section IV.
Low Emission Combustion with Viessmann made stainless steel MatriX cylinder burner. Factory calibrated.
Fast Installation and Reduced Maintenance with Lambda Pro, industry-first intelligent combustion management system: Adjusts automatically to gas type and quality. No fuel conversion kit required.
Powerful and User-friendly Viessmann Vitotronic on-board multi-function outdoor reset boiler and system control for multi-temperature space and DHW heating.
Greater Venting Flexibility with increased vent length up to 180 ft. (55 m) and multiple venting options.
- Horizontal or vertical sealed combustion coaxial venting (field supplied).
- Horizontal, vertical or hybrid sealed combustion double-pipe venting (field supplied).
- Horizontal or vertical single-wall venting (field supplied).
Compact, Esthetic Product Design and zero clearance to combustibles.
Extremely Quiet Operation; quieter than most refrigerators.
True High-Altitude Operation up to 10,000 ft. (3,000 m) with simple electronic adjustment.
Efficiency up to 98% through intensive condensation. The flue gas temperature is only approximately 9-27ºF (5-15ºC) above boiler return temperature (see chart below).
2
2
5461 883 - 02
Page 3
Vitodens 200-W, B2HB 19 to 35 Technical Data
Cross-Section
Vitodens 200-W B2HB 19, 26, 35
Product Information
A Inox-Radial heat exchanger made from stainless steel – for high operational reliability and a long service life. Large heating output in the smallest of spaces
B Modulating MatriX cylinder burner for extremely clean combustion and quiet operation
C Variable speed combustion fan for quiet and economical operation
D Gas and water connections E Digital boiler control unit
Delivered condition
Wall mounted gas condensing boiler with Inox-Radial heat exchanger, modulating MatriX cylinder burner for natural gas and LPG, plus wall mounting bracket. Vitotronic 200 for weather-compensated operation. Preset for operation with natural gas. Fully plumbed and wired. White epoxy­coated casing.
Product may not be exactly as shown
The flue gas temperature is only approximately 9-27ºF (5-15ºC) above boiler return temperature (see chart below).
5461 883 - 02
3
3
Page 4
Technical Data
Vitodens 200-W, B2HB 19 to 35 Technical Data
Technical Data
Boiler Model No. 200-W B2HB 19 26 35
Natural Gas / Liquid Propane Gas CSA input
CSA output/DOE *1 heating capacity
Net AHRI rating *2
Heat exchanger surface area ft.
Min. gas supply pressure
Natural gas Liquid propane gas
Max. gas supply pressure *3
Natural gas Liquid propane gas
A.F.U.E. % 95 95 95 Weight lbs
Boiler water content USG
Boiler max. flow rate *4 GPM
Max. operating pressure
at 210ºF (99ºC)
Boiler water temperature
- Adjustable high limit (AHL) range space heating (steady state)
DHW production
- Fixed high limit (FHL)
Boiler connections
Boiler heating supply and return Pressure relief valve Drain valve
Boiler supply/return for indirect-fired DHW storage tank (field supplied) Gas valve connection
MBH (kW) MBH (kW)
MBH (kW)
(m
“w.c. “w.c.
“w.c. “w.c.
(kg)
(L)
(L/h)
psig
(bar)
ºF
(ºC)
ºF
(ºC)
ºF (ºC)
NPTM”
NPTF”
(male
thread)
NPT”
NPTF”
12-68
(3.5-20)
11-64
(3.2-19)
55
(16)
2
2)
12.96 (1.2)
4
10
14 14
110 (50)
1.02
(3.88)
6.2
(1400)
45 (3)
68 to 165 (20 to 74)
165 (74)
210 (99)
¾ ¾ ¾
¾
¾
19-94
(5.5-27)
18-89 (5-26)
76.5 (22)
12.96 (1.2)
10
14 14
110 (50)
1.02
3.88)
6.2
(1400)
45 (3)
68 to 165 (20 to 74)
165 (74)
210 (99)
¾ ¾ ¾
¾
¾
19-125
(5.5-37)
18-117
(5-34)
102 (30)
12.96 (1.2)
4
110 (50)
1.02
3.88)
(1400)
68 to 165 (20 to 74)
165 (74)
210 (99)
4
10
14 14
6.2
45 (3)
¾ ¾ ¾
¾
¾
*1 Output based on 140ºF (60ºC), 120ºF (49ºC) system supply/return temperature.
*2 Net AHRI rating based on piping and pick-up allowance of 1.15.
*3 If the gas supply pressure exceeds the maximum gas supply pressure value, a separate gas pressure regulator
must be installed upstream of the heating system.
*4 See “Waterside Flow” starting on page 8 in this manual.
4
4
5461 883 - 02
Page 5
Vitodens 200-W, B2HB 19 to 35 Technical Data
Technical Data
Technical Data
Boiler Model No. 200-W B2HB 19 26 35
Dimensions
Overall depth
Overall width
Overall height
Flue gas *5
Temperature (at boiler return temperature of 86ºF (30ºC)
- at rated full load
- at rated partial load
Temperature (at boiler return temperature of 140ºF (60ºC)
Max. condensate flow rate *6
with natural gas and TS/TR =122/86ºF (50/30ºC) USG/h
Condensate connection *7 hose
Boiler flue gas connection *8 Ø
Combustion air supply connection (coaxial)
Sound Rating
- at maximum input
- at minimum input
inches
(mm)
inches
(mm)
inches
(mm)
ºF (ºC) ºF (ºC)
ºF (ºC)
(L/h)
nozzle
Ø in
in (mm) 23/8 (60) 23/8 (60) 23/8 (60)
outer
Ø in (mm) 4 (100) 4 (100) 4 (100)
dB dB
15.7
(400)
17¾
(450)
41
(1040)
113 (45)
95 (35)
154 (68)
0.66
(2.5)
15.7
(400)
17¾
(450)
41
(1040)
113 (45)
95 (35)
154 (68)
0.97 (3.7)
¾-1 ¾-1 ¾-1
41 35
48 36
15.7
(400)
17¾
(450)
(1040)
113 (45)
95 (35)
154 (68)
1.21 (4.6)
41
51 36
*5 Measured flue gas temperature with a combustion air temperature of 68°F (20°C).
*6 Based on maximum input rate.
*7 Requires 1 inch (25 mm) tubing. See the Installation Instructions of the Vitodens 200-W, B2HB for details.
*8 For side wall vent installations (coaxial system):
Do not exceed max. equivalent length specified in the Installation Instructions of the Vitodens 200-W, B2HB Venting System. Do not attempt to common-vent Vitodens 200-W with any other appliance. Side wall co-axial vent installation must include Viessmann protective screen! For details refer to the Installation Instructions for the Vitodens 200-W, B2HB Venting System.
For information regarding other Viessmann System Technology componentry, please reference documentation of respective product.
Note: For high altitude installation at 10,000 ft. the input for model B2HB 19 to 35 will have an altitude de-ration of 21%.
5461 883 - 02
5
5
Page 6
Dimensional Information
Models 200-W, B2HB 19, 26, 35
Vitodens 200-W, B2HB 19 to 35 Technical Data
Legend
A Boiler Supply B Gas Connection,
C Boiler Return D Recommended height (single boiler system)
6
¾” NPTF
E Condensate drain F Combustion air intake (left or right) G Combustion air intake (through co-axial)
5461 883 - 02
Page 7
Vitodens 200-W, B2HB 19 to 35 Technical Data
Recommended Minimum Service Clearances
Minimum Clearances to Combustibles
Top Front Rear Left Right Vent
pipe *1
0 0 AL, CL 0 0 0 0
Minimum Clearances
AL= Alcove CL= Closet
*1 Refer to the Installation Instructions of the Vitodens 200-W, B2HB Venting System for details.
Note:The Vitodens boiler has passed the zero inches vent clearance to combustibles testing requirements dictated by the Harmonized Standard ANSI Z21.13. CSA 4.9.2000 and therefore is listed for zero clearance to combustibles when vented with a single wall special venting system (AL-29-4C material). The zero inches vent clearance to combustibles for the Vitodens boiler supercedes the clearance to combustibles listing that appears on the special venting system label.
5461 883 - 02
7
7
Page 8
Waterside Flow
Waterside Flow (primary circuit)
Vitodens 200-W, B2HB 19 to 35 Technical Data
The Vitodens 200-W, B2HB is designed for closed loop, forced circulation hot water heating systems only. Use standard friction loss method for pipe sizing. Observe boiler maximum and minimum flow rate limitations. If system flow rate exceeds boiler maximum flow rate (as stated above), falls below the minimum flow rate or if system flow rate is unknown, Viessmann strongly recommends the installation of a low-loss header. An alternative method may be used, such as primary secondary piping using closely spaced tees.
Supply head pressure (water)
A low-loss header offers additional benefits not provided by a pair of closely spaced tees. Viessmann therefore strongly recommends and prefers the use of a low-loss header over closely spaced tees. See pages 25 and 26 for low-loss header information. Once the low-loss header is connected, the built-in low-loss header logic of the Vitodens 200-W boiler ensures the required rt across the system through the sensory communication between the low-loss header and the boiler.
Pressure drop (primary circuit) for Vitodens 200-W, B2HB 19, 26, 35 For sizing an on-site circulation system. Max. flow rate: 6.2 GPM (1400 L/h)
Flow rate
Typical System Flow Rates
Boiler maximum flow rate 6.2 GPM (1400 L/h)
Model B2HB 19 1 boiler
Output (NG/LPG) MBH 64
rt for NG/LPG 20ºF (11ºC) rise GPM (L/h) 6.4 (1453) 25ºF (14ºC) rise GPM (L/h) 5.1 (1163) 30ºF (17ºC) rise GPM (L/h) 4.3 (969) 35ºF (19.5ºC) rise GPM (L/h) 3.7 (830) 40ºF (22ºC) rise GPM (L/h) 3.2 (727)
Boiler maximum flow rate 6.2 GPM (1400 L/h)
Model B2HB 26 1 boiler
Output (NG/LPG) MBH 88
rt for NG/LPG 20ºF (11ºC) rise GPM (L/h) 8.8 (1999)
Boiler maximum flow rate 6.2 GPM (1400 L/h)
Model B2HB 35 1 boiler
Output (NG/LPG) MBH 117
rt for NG/LPG 20ºF (11ºC) rise GPM (L/h) 11.7 (2657) 25ºF (14ºC) rise GPM (L/h) 9.4 (2126) 30ºF (17ºC) rise GPM (L/h) 7.8 (1771) 35ºF (19.5ºC) rise GPM (L/h) 6.7 (1518) 40ºF (22ºC) rise GPM (L/h) 5.9 (1328)
25ºF (14ºC) rise GPM (L/h) 7.0 (1599) 30ºF (17ºC) rise GPM (L/h) 5.9 (1332) 35ºF (19.5ºC) rise GPM (L/h) 5.0 (1142) 40ºF (22ºC) rise GPM (L/h) 4.4 (999)
8
5461 883 - 02
Page 9
Vitodens 200-W, B2HB 19 to 35 Technical Data
Heating Circuit / Boiler Pumps
System Flow Rates
Viessmann offers a variety of Grundfos heating circuit/ boiler pumps which meet typical Vitodens system installation requirements (see “Heating circuit pump (field supplied)” or “Boiler pump (field supplied)” in the Installation Examples starting on page 28). See tables below for recommended pumps. Refer to the graph on page 8 for the proper waterside boiler friction loss calculations. The following pumps have been selected based on boiler heat exchanger head loss and boiler piping to a low-loss header.
Model B2HB 19 B2HB 26 B2HB 35 Flow rate
20ºF rt GPM (L/h) 25ºF rt GPM (L/h) 30ºF rt GPM (L/h) 35ºF rt GPM (L/h) 40ºF rt GPM (L/h)
Flow limitation GPM (L/h) 6.2 (1400) 6.2 (1400) 6.2 (1400) Recommended boiler pumps Grundfos UPS 15-58 (3-speed), Taco 0015, Wilo Star S 21 FX
6.4 (1453) -- --
5.1 (1163) -- --
4.3 (969) 5.9 (1332) --
3.7 (830) 5.0 (1142) --
3.2 (727) 4.4 (999) 5.9 (1328)
Before using the following pumps for a DHW tank application, find out the proper pressure drop through the tank, the required temperature difference through the coil and system piping head loss of the domestic hot water.
IMPORTANT
Pump selection must be based on accurate system flow and pressure drop calculations (includes DHW sizing).
Low-Loss Header Application
Sizing of Low-Loss Header in a Residential Single-Boiler Application
Boiler
Model
B2HB 191 6.2
B2HB 261 6.2
B2HB 351 6.2
*1 For system rt < 20° F use low-loss header sizes for rt 20° F. *2 Low-Loss temperature sensor - is included with the boiler for use in a single boiler application.
No. of Boilers
Boiler
Max. Flow
Rate
GPM
(L/h)
(1400)
(1400)
(1400)
Typical System Flow Rates
rt *1
System Flow Rate LLH Required LLH Model
System Flow Rate LLH Required LLH Model
System Flow Rate LLH Required LLH Model
°F
(°C)
GPM
(L/h)
GPM
(L/h)
GPM
(L/h)
20
(11.0)
6.4
(1453)
Yes
80/60
8.8
(1999)
Yes
80/60
11.7
(2657)
Yes
80/60
25
(14.0)
5.1
(1163)
Optional
80/60
7.0
(1599)
Yes
80/60
9.4
(2126)
Yes
80/60
30
(17.0)
4.3
(969)
Optional
80/60
5.9
(1332)
Optional
80/60
7.8
(1771)
Yes
80/60
35
(19.5)
3.7
(830)
Optional
80/60
5.0
(1142)
Optional
80/60
6.7
(1518)
Yes
80/60
40
(22.0)
3.2
(727)
Optional
80/60
4.4
(999)
Optional
80/60
5.9
(1328)
Optional
80/60
Viessmann Low-loss Temp. Sensor Required*2
Included
Included
Included
5461 883 - 02
9
9
Page 10
DHW Production
Domestic Hot Water Production
Vitodens 200-W, B2HB 19 to 35 Technical Data
Vitodens 200-W boilers can be used in conjunction with the stand-alone DHW storage tanks offered by Viessmann. All Viessmann DHW storage tanks sold in North America are available in “Vitosilver” finish only.
Size and select the DHW storage tank based on the forecasted DHW consumption of the building in question. For further technical information on DHW storage tanks, see the Vitocell-V Technical Data Manuals.
For the connection of a stand-alone DHW tank, installation fittings (field supplied), an external circulating pump for DHW production (field supplied) and a DHW temperature sensor (optional equipment, see Viessmann Price List for order information) are required.
*2
*1 DHW
Connections
(Field Supplied)
Legend
DR Boiler heating return for domestic hot water production DS Boiler heating supply for domestic hot water production HR Heating Return HS Heating Supply BD Boiler Drain BR Boiler Return BS Boiler Supply GC Gas Connection PRV Pressure Relief Valve BF Boiler Fill PG Pressure Gage (not shown) *1 See page 45 for alternate DHW connection. *2 Temperature guage
10
IMPORTANT
An adequately sized pre-charged expansion tank must be used. See Installation Examples for details.
Note:Install the temperature guage (supplied) anywhere in the supply piping near the boiler (not shown).
5461 883 - 02
Page 11
Vitodens 200-W, B2HB 19 to 35 Technical Data
Domestic Hot Water Recirculation
DHW Recirculation
Vitocell-V stand-alone DHW storage tank
DHW recirculation lines increase the level of comfort and convenience of the domestic hot water supply and reduce water consumption. These advantages directly derive from the immediate availability of domestic hot water at all draw points.
Poor insulation of the DHW recirculation line, however, can result in considerable heat loss. Viessmann therefore recommends that effective insulation be provided and used for DHW recirculation lines of 23 ft. (7 m) in length or longer.
Legend
DCW Domestic Cold Water DHW Domestic Hot Water TPV Temperature and Pressure Relief Valve (on tank - not shown) R DHW Recirculation Line RP DHW Recirculation Pump
5461 883 - 02
11
Page 12
Wall Mounting
Mounting Bracket
Vitodens 200-W, B2HB 19 to 35 Technical Data
Fitting the wall mounting bracket
See the installation instructions applicable to the mounting bracket on each type of material.
CAUTION
Whichever mounting method is used, ensure that the bracket is tightly and securely fastened to wall. Failure to secure boiler properly could cause boiler to loosen, posing a severe safety hazard.
Models B2HB 19, 26, 35
1. Remove the external accessories connection box cover.
2. Loosen the screws at the bottom of the boiler (do not remove completely).
3. Remove the front encloser panel (lift up and pull away from the boiler).
4. Mount boiler onto the mounting bracket and connect boiler to the installation fittings.
5. Ensure the boiler is securely mounted.
CAUTION
The boiler must be level both vertically and horizontally to ensure proper draining of the condensate.
12
5461 883 - 02
Page 13
Vitodens 200-W, B2HB 19 to 35 Technical Data
Boiler Stand for B2HB 19 to 35
Frame Mounting
The boiler stand is used for free-standing installation of a single boiler within the mechanical room.
When using the boiler stand, ensure that the stand is securely fastened to the floor (recommended concrete expansion anchors are Hilti model KB-TZ e x 4 or equivalent.
The Vitodens 200-W, model B2HB does not come with a mounting template. The wall location for the frame, mounting bracket and all vents must be field calculated.
Boiler mounting bracket and frame
1. Attach the wall mounting bracket (supplied with the boiler) to the boiler mounting frame using the supplied hardware. Ensure that the wall mounting bracket is level.
2. Move the rack into position and secure to the floor (and to the wall if needed).
5461 883 - 02
13
Page 14
Frame Mounting
Models B2HB 19, 26, 35
Vitodens 200-W, B2HB 19 to 35 Technical Data
1. Remove the external accessories connection box cover.
2. Loosen the screws at the bottom of the boiler (do not remove completely).
3. Remove the front encloser panel (lift up and pull away from the boiler).
4. Mount boiler onto the mounting bracket and ensure the boiler is securely mounted. Then install the holding bracket to the frame on top of the boiler.
5. Connect the boiler to the installation fittings.
CAUTION
The boiler must be level both vertically and horizontally to ensure proper draining of the condensate.
14
5461 883 - 02
Page 15
Vitodens 200-W, B2HB 19 to 35 Technical Data
Condensate Connection
Condensate Connection for Vitodens 200-W, models B2HB 19, 26, 35
Install the condensate drain pipe with a suitable gradient. Discharge condensate from the boiler into the drainage system, either directly or (if required) via a neutralization unit (accessory).
IMPORTANT
Pipe ventilation must take place between the siphon trap and the neutralization unit (if applicable).
Condensate Connection/Neutralization Unit
Condensate Drainage and Neutralization
The condensate formed both in the condensing boiler and in the flue gas pipe must be discharged into the public sewage system in accordance with all applicable local regulations. The condensate produced by a gas-fired heating system has a pH value between 3 and 4.
Some local codes may require the use of a separate neutralization unit to treat the aggressive and corrosive nature of the condensate. With a neutralization unit installed, all condensate from the boiler and the flue gas pipe enters into the neutralization unit where it is treated and released into the public sewage system with a safe pH value of above 6.5.
The use of neutralization granulate (performing the neutralizing process) is dependent on the operation of the heating system. To determine the required refill amount, check granulate level several times during the first year of operation. In some cases one granulate fill may last an entire year.
Contact Viessmann to order a neutralization unit for the Vitodens 200-W boiler. See Viessmann Price List for order information.
The condensate discharge outlet to the drainage system connection must be clearly visible. It must be installed with a suitable gradient and provided with a stench trap.
If the condensate outlet of the Vitodens 200-W boiler is lower than the drain, a condensate pump must be used.
Only corrosion-resistant materials must be used for condensate drainage purposes (e.g. braided hose). Do not use galvanized materials or materials containing copper for piping, couplings etc. The condensate drain must have a trap to prevent flue gas leakage.
Please note that other requirements might apply depending on local regulations and/or project-specific details.
It is advisable to contact your local waterworks office (authority responsible for waste water regulations) well before commencing with the installation of the neutralization unit in order to establish details of local regulations that apply.
The following table shows the concentration of (effluent) substances (e.g. heavy metals) contained in the waste water from the Vitodens 200-W condensing boiler.
5461 883 - 02
Condensate (effluent) substances
Lead Cadmium Chromium Copper Nickel Zinc Tin
Values measured in mg/L
Vitodens 200-W
< 0.01
< 0.005
< 0.01 < 0.01 < 0.01 < 0.05 < 0.05
15
Page 16
Venting Options/Electrical Connection/Control
Vitodens 200-W, B2HB 19 to 35 Technical Data
Venting Options
For detailed information refer to the Installation Instructions for the Vitodens 200-W, B2HB Venting System.
Vent Connection, (with optional air intake openings on sides) for models B2HB 19, 26, 35
Electrical Connections
Power Supply
The Vitodens 200-W requires a standard 120 VAC power outlet 15A fuse protected circuit. Refer to the installation instructions shipped with the boiler for wiring details, or reference the “Overview of Electrical Connections” on pages 38 and 39 of this manual.
Power Supply Connection of Accessories
The power supply connection of accessories can be made directly at the boiler control. The connection is activated and deactivated with the system on/off switch. The mixing valve accessory kit and the Vitosolic control (if used) will require a separate 120 VAC power supply from the wall receptacle.
Wire cabling required for:
Outdoor temperature sensor
Vitotronic 200-H, HK1B mixing valve control
Accessory kit for heating circuit with mixing valve
Vitotrol 200 remote control
Vitotrol 300 remote control
Remote switching of operating mode
Remote disable
Alarm output
16
5461 883 - 02
Page 17
Vitodens 200-W, B2HB 19 to 35 Technical Data
On-Board Vitotronic 200, HO1B Control
Boiler Control
Modular structure
The control unit is integrated into the boiler. The control unit comprises a standard unit, electronics modules and a programming unit.
Standard unit:
ON/OFF switch
Optolink laptop interface
Operating and fault indicators
Reset button
Fuses
Programming unit:
Easy operation through: – Plain text display with graphic ability – Large font and black & white depiction for good contrast – Context-sensitive help text – Removable programming unit; can be mounted on the wall with separate accessory
With digital time switch
Control keys for:
– Navigation – Confirmation – Help and additional information – Menu
Setting the: – Room temperature – Reduced room temperature – DHW temperature – Heating program – Time programs for central heating, DHW heating and DHW recirculation – Economy mode – Party mode – Holiday program – Heating curves – Codes – Actuator tests – Test mode
Displaying the: – Boiler water temperature – DHW temperature – Operating details – Diagnostic details – Fault messages
5461 883 - 02
17
Page 18
Boiler Control
Design and Function
Vitodens 200-W, B2HB 19 to 35 Technical Data
Functions
Weather-compensated control of the boiler water and/or flow temperature
Control of one heating circuit without mixer and two heating circuits with mixer
Control of one heating circuit without mixer and two heating circuits with mixer
Demand-dependent heating circuit pump and burner off control
Adjustment of a variable heating limit
Anti-seizing pump protection
Integral diagnostic system
Maintenance display
DHW temperature control with priority
Control of solar DHW heating and central heating
backup in conjunction with the solar control module, type SM1
Display of the solar energy yield
Auxiliary function for DHW heating (short-term
heating to a higher temperature)
Slab curing program
0-10V External signal input
Control Characteristics
PI characteristics with modulating output.
Time Switch
Digital time switch.
Individual and 7-day program
Automatic daylight savings time changeover
Automatic function for DHW heating and DHW
recirculation pump
Time, day and standard switching times for space heating, DHW heating and the DHW recirculation pump are factory-set
Switching times are individually programmable, i.e. up to four switching periods per day
Shortest switching interval: 10 minutes
Power backup: 14 days.
Setting the Operating Programs
The heating system frost protection (see frost protection function) applies to all heating programs. You can select the following heating programs with the program keys:
Heating and DHW
DHW only
Standby mode
External heating program changeover.
Frost protection
The frost protection function will be started when the outside temperature drops below approx. 34°F (1°C). With the frost protection function, the heating circuit pump will be switched ON and the boiler water is maintained at a lower temperature of approx. 68°F (20°C). The DHW tank will be heated to approx. 68°F (20°C).
The frost protection function will be stopped when the outside temperature rises above approx. 37°F (3°C) (default settings).
Summer Operation
Heating program “w” The burner is only activated upon a call for domestic hot
water from the DHW storage tank (controlled by DHW tank temperature sensor).
18
5461 883 - 02
Page 19
Vitodens 200-W, B2HB 19 to 35 Technical Data
Design and Functions (continued)
Boiler Control
Technical Data
Rated supply voltage: 120 VAC Rated frequency: 60 Hz Rated current: 12 A Max. ambient temp.
- at operation: 32 to 104ºF (0 to 40ºC) Installation in living spaces or boiler rooms (standard ambient conditions)
- when storing or transporting: -4 to +158ºF (-20 to +70ºC)
Max. operating temp. setting (space heating): Models B2HB 19-35 165ºF (74ºC)
DHW production: Models B2HB 19-35 165ºF (74ºC)
Setting fixed high limit: 210ºF (99ºC) (not adjustable)
Adjustment range of DHW tank set-point temperature: 50 to 154ºF (10 to 68ºC)
Heating curve settings
- Heating curve slope: 0.2 to 3.5
- Heating curve shift: -12 to +33ºC
-13 to 40 K
Heating Curve Adjustment (slope and shift)
The control unit regulates the boiler water temperature (= supply temperature of heating circuit without mixing valve) and the supply temperature of the heating circuit with mixing valve (in conjunction with the accessory mixing valve extension kit) according to the outdoor temperature. The boiler water temperature is automatically raised by 0 to 72 F / 0 to 40 K higher than the currently required set supply termperature (in the factory default setting the differential temperature is 14.4 F / 8 K). See Service Instructions for coding address “9F” in coding level 2.
The supply temperature that is required to achieve a given room temperature depends on the heating system and the thermal insulation of the building that is being heated. The adjustment of the two heating curves is used to match the boiler water temperature and the supply temperature to these conditions. The boiler water temperature is limited upwards by the fixed high limit and the temperature set for the electronic high limit. The supply temperature cannot rise above the boiler water temperature.
Boiler water or supply
temperature
Room set-point
temperature
Outdoor temperature
Legend
A Low temperature heating system, e.g. radiant floor heating
B Medium temperature heating system, e.g. cast iron radiation, staple-up radiant floor heating
C High temperature heating system, e.g. fintube radiation, fan coils
5461 883 - 02
19
Page 20
Accessories
Sensors (supplied)
Vitodens 200-W, B2HB 19 to 35 Technical Data
Boiler Temperature Sensor
The boiler temperature sensor is connected at the control unit for weather-responsive operation and is built into the boiler.
Specification sensor type: Viessmann NTC 10K ohms at 77ºF (25ºC)
Max. ambient temp.
- at operation: 32 to 266ºF (0 to 130ºC)
- when storing
or transporting: - 4 to+158ºF (-20 to+70ºC)
DHW Tank Temperature Sensor
(immersion temperature sensor) Supplied with:
- Cable length approx. 13 ft. (3.75 m), ready to plug in
- All pipe connections are field supplied.
Specification
Max. ambient temp.
- at operation: 32 to 194ºF (0 to 90ºC)
- when storing
or transporting: - 4 to+158ºF (-20 to+70ºC)
- Sensor type: Viessmann NTC 10K ohms @ 77ºF (25ºC)
Outdoor Temperature Sensor
Sensor location:
- North or northwest wall of building
- 6.6 to 8.2 ft. (2 to 2.5 m) above ground or in case
of a multi-storey building approximately halfway up the second floor
Electrical connection:
- 2-wire cable, max. cable length 115 ft. (35 m) with a wire size of min. AWG 16 copper
- Cable to the outdoor sensor must not be laid near line voltage wiring (120/240 V)
Max. ambient temp.
- at operation: 32 to 194ºF (0 to 90ºC)
- when storing
or transporting: - 4 to+158ºF (-20 to+70ºC)
Immersion Temperature Sensor
To capture the low loss temperature (if low-loss header is used)
Specification Lead length fully wired: 12 ft. (3.75 m),
Permissable ambient temp.
- during operation: 32 to 194°F (0 to 90°C)
- when storing
or transporting: - 4 to+158° F (-20 to+70° C)
20
5461 883 - 02
Page 21
Vitodens 200-W, B2HB 19 to 35 Technical Data
Optional Accessories
Accessories
Supply Temperature Sensor
(strap-on sensor, included with mixing valve actuator accessory kit),
- when storing or transporting: -4 to+158° F (-20 to+70ºC)
Installed with a strapping band. Cable length 19.7 ft. (6 m), ready to plug in. Max. ambient temp.
- at operation: 32 to 212ºF (0 to 100ºC)
- when storing
or transporting: -4 to+149ºF (-20 to+70ºC)
Room Temperature Sensor,
Mixing Valve Motor Kit
The mixing valve actuator is mounted directly on the Viessmann ¾ to 2½” mixing valve. The mixing valve actuator is a motor-driven control unit. The rotational direction is reversible.
Rated voltage: 120 VAC Rated frequency: 60 Hz
Power consumption: 4W max. ambient temperature
- at operation: 32ºF to 104ºF (0ºC to 40ºC)
application in living areas and installation sites (normal ambient conditions)
-storage & shipping: -4ºF to 149ºF (-20ºC to 65ºC)
Separate room temperature sensor as supplement to the Vitotrol 200A and 300A; to be used if the Vitotrol 200A or 300A cannot be installed inside the main living room or in a suitable position where the unit can capture and adjust the temperature. Installation in the main living room on an internal wall opposite radiators. Never install inside shelf units, recesses, immediately by a door or heat source (e.g. direct sunlight, fireplace, TV set, etc.). Connect the room temperature sensor to the Vitotrol 200A or 300A. Electrical connection:
- 2-wire cable with a wire size of min. AWG 18 copper
- The cable length between the control unit, remote
control unit and room temperature sensor must not exceed 98 ft. (30 m)
Max. ambient temp.
- at operation: 32 to 104ºF (0 to 40ºC)
- when storing or transporting: -4 to+149ºF (-20 to +65ºC)
5461 883 - 02
21
Page 22
Accessories
Optional Accessories (continued)
Vitodens 200-W, B2HB 19 to 35 Technical Data
Mixing Valve Extension Module
Rated voltage: 120 VAC Rated frequency: 60 Hz Rated current: 2 A Power consumption: 4 W Max. ambient temp.
- at operation: 32 to 104ºF (0 to 40ºC)
- when storing
or transporting: -4 to+149ºF (-20 to+65ºC) Relay output for
heating circuit pump: 2 A, 120 VAC
Actuator torque: 3 Nm
Time of 90º: 120 seconds
KM BUS Expansion Module
To connect 2 to 9 devices (mixing valve actuator, Vitotrol, input module, etc.) to the single KM BUS connection of the boiler.
Specification Lead length 10 ft. (3.0 m), fully wired
Permissable ambient temp.
- during operation 32 to 104°F (0 to 40°C)
- during storage and transport: - 4 to+149°F (-20 to+65°C)
LON Communication Module
Electronic PCB for data exchange with the Vitotronic 200-H, Vitocom 200 and for connecting to a higher level building management system.
LON Connecting Cable
(for data exchange between control units) Cable length 23 ft. (7 m), fully wired
LON Terminal End Resistor
To terminate the LON BUS at the first and the last control unit.
22
5461 883 - 02
Page 23
Vitodens 200-W, B2HB 19 to 35 Technical Data
Optional Accessories (continued)
Vitotrol 200A
One Vitotrol 200A can be used for every heating circuit in a heating system. The Vitotrol 200A can regulate one heating circuit and up to two remote controls may be connected to the control unit.
KM BUS Participant The Vitotrol 200A remote control regulates the required set room temperature in standard mode, from any room in the house.
- Party and economy mode can be enabled via keys
- Only for heating circuit with mixing valve Fitted room temperature sensor for room temperature hook-up
Accessories
Connection:
- 2-core lead 18 AWG, length max. 164 ft.(50 m) (even if connecting several remote control units)
- Never route this lead immediately next to 120/208/460 V cables
- LV plug as standard delivery must be installed in the main living room (lead room).
Specification: Power supply via KM BUS Power consumption: 0.2 W Protection class: III
Max. ambient temp.
- at operation: 32 to 104ºF (0 to 40ºC)
- when storing or transporting: -4 to+149ºF (-20 to+65ºC)
Set room temp. range 37 to 99ºF (3 to 37ºC)
The set room temperature for reduced mode is adjusted at the control unit.
WS function: Installation anywhere in the building.
RS function: Note: Never activate the RS function for underfloor heating circuits (inertia). In heating systems with a heating circuit without mixing valve and heating circuits with mixing valve, the RS function must only affect the heating circuit with mixing valve.
Room temperature hook-up: Installation in the main living room on an internal wall opposite radiators. Never install inside shelf units, recesses, immediately by a door or heat source (e.g. direct sunlight, fireplace, TV set, etc.). The integral room temperature sensor captures the actual room temperature and effects any necessary corrections of the supply temperature as well as a rapid heat-up at the start of the heating operation (if appropriately programmed).
5461 883 - 02
23
Page 24
Accessories
Vitodens 200-W, B2HB 19 to 35 Technical Data
Optional Accessories
Vitotrol 300A
One Vitotrol 300A can be used for every heating circuit in a heating system. The Vitotrol 300A can regulate up to three heating circuits. Up to two remote controls may be connected to the control unit.
KM BUS Participant The Vitotrol 300A remote control regulates the required set room temperature for one heating circuit in standard and reduced mode, the heating program and the switching times for central heating, DHW heating and the DHW recirculation pump.
Displaying:
- Room temperature
- Outside temperature
- Heating program
- Operating condition
- Solar yield as graphic display
Settings:
- Set room temperatures for standard mode (day temperature) and reduced mode (night temperature) via the standard display
- Heating program, switching times for heating circuits, DHW heating and DHW recirculation pump plus further settings via plain text menu on the display
- Party and economy mode can be enabled via the menu
- Only for heating circuit with mixer: Fitted room temperature sensor for room temperature hook-up
Note: For room temperature hook-up, the Vitotrol 300A must be installed in the main living room (lead room).
(continued)
RS function: Installation in the main living room on an internal wall opposite radiators. Never install inside shelving units, in recesses, or immediately by a door or heat source (e.g. direct sunlight, fireplace, TV set, etc.). The fitted room temperature sensor captures the actual room temperature and effects any necessary correction of the flow temperature.
WS function: Installation anywhere in the building.
Connection:
- 2-core lead 18 AWG, length max. 164 ft. (50 m) (even if connecting several remote control units)
- Never route this lead immediately next to 120/208/460 V cables
- LV plug as standard delivery must be installed in the main living room (lead room).
Specification: Power supply via KM BUS Power consumption: 0.2 W Protection class: III
Max. ambient temp.
- at operation: 32 to 104ºF (0 to 40ºC)
- when storing or transporting: -4 to+149ºF (-20 to+65ºC)
Set room temp. range 37 to 99ºF (3 to 37ºC)
The set room temperature for reduced mode is adjusted at the control unit.
24
5461 883 - 02
Page 25
Vitodens 200-W, B2HB 19 to 35 Technical Data
Accessories for Vitodens 200-W
Accessories
LON Communication Module
Electronic PCB for data exchange with the Vitotronic 200-H, Vitocom 200 and for connecting to a higher level building management system.
Neutralization Unit for Single-Boiler Applications
with neutralizing granulate
for models B2HB 19, 26, 35
Neutralization Pellets
for models B2HB 19, 26, 35 2 x 1.3 kg for refill or replacement purposes
Fuel Conversion Label Kit (NG>LPG)
(included in boiler technical literature set) The Vitodens 200-W, B2HB boiler comes factory set for operation with natural gas. All B2HB models can be field converted to operate with liquid propane gas (as well as back to natural gas as required). The kit includes instructions and labels for field conversion.
Low-Loss Header
When used in conjunction with the Vitodens 200-W boiler, the low-loss header acts as hydraulic break, decoupling boiler and system circuits from each other. It is recommended to use the low-loss header in applications in which the total system flow rate exceeds the maximum (or minimum) boiler flow rate. For maximum boiler flow rates, starting on page 9 of this manual.
Viessmann strongly recommends the use of a low-loss header in cases where the system head and flow rates are unknown.
The temperature sensor connection [TS] typically located at the top of the low-loss header ensures low return temperatures to the Vitodens 200-W boiler at all times, increasing operational efficiency. In addition, the low-loss header helps eliminate air and debris [D] from the heating system. See illustrations for design and principle of operation on page 26.
The low-loss header is available in various sizes (see page 26). Select the size based on the maximum system flow rate of your application.
5461 883 - 02
25
Page 26
Accessories
Accessories for Vitodens 200-W
Low-Loss Header (continued)
Vitodens 200-W, B2HB 19 to 35 Technical Data
IMPORTANT
Low-loss header design (Typical)
Principle of Operation
Use only a Viessmann supplied temperature sensor. Do not use any other manufacturer’s temperature sensor.
Legend
AB Air Bleed BR Boiler Return BS Boiler Supply BY Bypass (with laminar flow) D Debris DV Drain Valve SC Sensor Cable SR System Return SS System Supply TS Viessmann Temperature Sensor SW Sensor Well
IMPORTANT
When installing a low-loss header, the system mixed supply temperature (T3) must be calculated as follows:
Legend
T1 Boiler supply temperature T2 Boiler return temperature T3 System supply temperature T4 System return temperature Vprimary Boiler circuit flow rate Vsecondary Heating circuit flow rate Vbypass Bypass flow rate Qprimary Heat supplied by boiler Qsecondary Heat consumed by system
26
Vprimary < Vsecondary T1 > T3 T2 = T4 Qprimary = Qsecondary
T1 167° F (75° C) Vsecondary=Vprimary+Vbypass
Model No. Max. system flow rate
Type 80/60 19.5 GPM (4.4 m3/h) Type 120/80 35.2 GPM (8 m3/h) Type 160/80 *1 44 GPM (10 m3/h)
3
Type 200/120 *1 80 GPM (18 m
*1 Floor-mounted version (typically used for multiple-boiler installations).
/h)
5461 883 - 02
Page 27
Vitodens 200-W, B2HB 19 to 35 Technical Data
Standard Equipment
Standard Equipment
The Vitodens 200-W gas-fired condensing boiler with Inox-Radial heat exchanger, modulating MatriX cylinder burner for liquid propane gas and natural gas (available on all models), comes standard with:
pressure gage
installation fittings with 30 psig pressure
relief valve and air vent
thermometer guage (field installation on supply pipe)
LLH immersion sensor (if LLH is used)
DHW sensor
boiler control unit with outdoor
temperature sensor
- The boiler comes prewired and fully piped
internally for field connections and prewired.
- Side wall co-axial vent installations must include Viessmann protective screen!
- Enclosure finish:
black steel, powder-coated white
- The Vitodens 200-W comes ready for use with natural gas and can be fuel converted to liquid propane gas in the field.
- Air vent
Combustion Management System
The combustion management system utilizes the physical correlation between the level of the ionization current and the air factor λ. For all gas qualities, the maximum ionization current results with air factor λ. The ionization signal is evaluated by the combustion management system, and the air factor is adjusted to between λ=1.24 and 1.44. This range provides for an optimum combustion quality. Thereafter, the electronic gas valve regulates the required gas volume based on the prevailing gas quality. To check the combustion quality, the CO O2 content of the flue gas is measured. The actual values enable the prevailing air factor to be determined. The relationship between the CO
2 or O2 content and
air factor λ is illustrated in the table below.
2 content or the
Wall mounting componentry The following wall mounting components are supplied with the Vitodens 200-W boiler:
Mounting bracket
Mounting bolts
Installation fittings
Screws for mounting bracket on
- wood studs (2” x 4”)
- metal studs
- brick/concrete wall
To achieve an optimum combustion control, the system regularly performs an automatic self-calibration; also after a power failure (shutdown). For this, the combustion is briefly regulated to max. ionization current (equals air factor λ=1). The automatic calibration is performed shortly after the burner starts and lasts approximately 5 seconds. During the calibration, higher than normal CO emissions may occur briefly.
Air factor λ - CO
Air factor λ
/O2 content
2
O2 content (%) CO
content (%) for natural gas CO2 content (%) for liquid propane gas
2
1.20 3.8 9.6 11.3
1.24 4.4 9.2 10.9
1.27 4.9 9.0 10.6
1.30 5.3 8.7 10.3
1.34 5.7 8.5 10.0
1.37 6.1 8.3 9.8
1.40 6.5 8.1 9.6
1.44 6.9 7.8 9.3
1.48 7.3 7.6 9.0
The Vitodens 200-W, B2HB boilers come equipped with Lambda Pro, the industry’s first intelligent combustion management system. The boiler adjusts automatically to any gas type and quality without the need for a fuel conversion kit.
5461 883 - 02
27
Page 28
Installation
Vitodens 200-W, B2HB 19 to 35 Technical Data
Hydraulic Connection
System design
Viessmann condensing boilers can generally be installed in any pumped hot water heating system (closed system). The circulation pump is an integral part of the appliance. Minimum system pressure 14 psi (1.0 bar). The boiler water temperature is limited to 180ºF (82ºC). To minimise distribution losses, we recommend that you size the heat distribution system to a max. flow temperature of 158ºF (70ºC).
To reduce burner cycling in low energy houses with a correspondingly low heat demand, we recommend the use of a low loss header.
Installation Examples
Please note that in the following piping layout examples all pumps are field supplied.
IMPORTANT IMPORTANT
The examples on the following pages depict possible piping layouts of the Vitodens 200-W boiler equipped with Viessmann System Technology. For boiler and tank combinations, please install only feasible combinations listed in the Viessmann Price List.
Please note that the following examples are simplified conceptual drawings only! Piping and necessary componentry must be field verified. A low water cut-off (LWCO) must be installed where required by local codes. Proper installation and functionality in the field is the responsibility of the heating contractor.
WARNING
If a DHW storage tank other than a Viessmann Vitocell 100 or 300 tank is used, the installer must verify proper operation of the Viessmann DHW tank temperature sensor with the original manufacturer of the tank. Viessmann strongly recommends the installation of a temperature tempering valve in the DHW supply line.
DHW supply and return piping between boiler DHW connections and the Viessmann DHW tank connections, shall be a minimum of 1” nominal pipe diameter (for models B2HB 19 to 35) DHW connection outlet sizes provided on the boiler and the DHW tank). This will ensure the residual head of the field supplied pump is fully utilized to overcome the resistance of the DHW heat exchanger coil and to provide sufficient water flow to the boiler heat exchanger. In non-Viessmann DHW tank applications, perform, in addition to the above, accurate calculations for DHW tank coil pressure drop versus boiler pump (field supplied) residual head to ensure sufficient water flow to the boiler heat exchanger. Failure to heed the above instructions may cause boiler short-cycling and inadequate DHW supply.
28
5461 883 - 02
Page 29
Vitodens 200-W, B2HB 19 to 35 Technical Data
System Layout 1
Vitodens 200-W, B2HB with a direct-connected heating circuit
Installation Examples
Legend
A Vitodens 200-W B2HB boiler with Vitotronic 200, HO1B outdoor reset control
B Outdoor temperature sensor ! C Vitotrol remote (optional) D Heating circuit E Heating circuit pump 20 F DHW circulating pump sA G DHW storage tank H DHW tank temperature sensor % I Expansion tank J Flow check valve K DHW recirculation pump * L Temperature and pressure relief valve M Pressure relief valve
* Function based on coding of address 33
5461 883 - 02
28/20
Installation of ...
radiator heating circuit (high-temp. circuit)
DHW production
... with the following flow conditions: The flow rate of the heating circuit is less than the maximum possible water flow rate of the Vitodens 200-W B2HB boiler (see page 8 for maximum water flow rate of boiler).
The use of a low-loss header is strongly recommended if the maximum water flow rate in the application concerned exceeds the values shown in the applicable table on page 8, or if the system flow rates are unknown. The low-loss header is available as accessory part.
See following pages for installation examples with a low­loss header.
IMPORTANT
DHW circulating pump F must pump into the Vitodens 200-W boiler (as illustrated).
29
Page 30
Installation Examples
System Layout 2
Vitodens 200-W, B2HB with one heating circuit and low-loss header
Vitodens 200-W, B2HB 19 to 35 Technical Data
Legend
A Vitodens 200-W B2HB boiler with Vitotronic 200, HO1B outdoor reset control
B Outdoor temperature sensor ! C Vitotrol remote (optional) D Heating circuit E Boiler pump 20 F DHW circulating pump sA G DHW storage tank H DHW tank temperature sensor % I Expansion tank J Temperature and pressure relief valve K DHW recirculation pump 28/20 * L Low-loss header M Pressure relief valve N Viessmann temperature sensor for
low-loss header ? O Heating circuit pump 28/20 *
* Function based on coding of address 33
30
Installation of ...
radiator heating circuit (high-temp. circuit)
DHW production
... with the following flow conditions: The flow rate of the heating circuit is greater than the maximum possible water flow rate of the Vitodens 200-W B2HB boiler (see page 8 for maximum water flow rate of boiler). The use of a low-loss header is strongly recommended if the maximum water flow rate in the application concerned exceeds the values shown on page 8, or if the system flow rates are unknown. The low-loss header is available as accessory part.
IMPORTANT
Please note location of expansion tank. DHW circulating pump F must pump into the Vitodens 200-W B2HB boiler (as illustrated).
5461 883 - 02
Page 31
Vitodens 200-W, B2HB 19 to 35 Technical Data
System Layout 3
Vitodens 200-W, B2HB with...
- DHW storage tank
- one heating circuit with mixing valve and system separation
Installation Examples
Legend
A Vitodens 200-W B2HB boiler with Vitotronic 200, HO1B outdoor reset control
B Outdoor temperature ! C Vitotrol remote (optional) D Underfloor heating circuit E Mixing valve temperature sensor ? F Pressure relief valve G Plate heat exchanger for system
separation H Accessory kit for heating circuit with mixing valve
I DHW circulating pump sA J DHW storage tank K DHW tank temperature sensor % L Expansion tank M DHW recirculation pump 28/20 * N Temperature and pressure relief valve O Flow check valve P Heating circuit pump 20 Q Heating circuit pump
* Function based on coding of address 33
IMPORTANT
DHW circulating pump must pump I into the Vitodens 200-W B2HB boiler (as illustrated).
5461 883 - 02
Installation of ...
underfloor heating circuit with 3-way mixing valve and system separation (low-temp. circuit)
DHW production ... with the following flow conditions:
The flow rate of the heating circuit is less than the maximum possible water flow rate of the Vitodens 200-W B2HB boiler.
See page 8 for maximum water flow rate of the Vitodens 200-W B2HB boilers. The use of a low-loss header is recommended if the system water flow rate is unknown. The low-loss header is available as accessory part.
See following pages for installation examples with a low-loss header.
IMPORTANT
System separation is required of underfloor heating systems employing non-oxygen diffusion barrier tubing. All components on the secondary side of the heat exchanger must be made of corrosion-resistant materials.
IMPORTANT
Sizing of field-supplied pump P is critical for proper boiler operation in this system layout. See page 8 for the supply head pressure drop of the boiler. An undersized pump may cause short-cycling and/or improper operation of the boiler. Viessmann STRONGLY recommends using a low-loss header and a boiler pump in this system layout.
31
Page 32
Installation Examples
System Layout 4
Vitodens 200-W, B2HB with...
- DHW storage tank
- one direct-connected heating circuit
- one heating circuit with a mixing valve
Vitodens 200-W, B2HB 19 to 35 Technical Data
Legend
A Vitodens 200-W B2HB boiler with Vitotronic 200, HO1B outdoor reset control
B Outdoor temperature sensor ! C Vitotrol remote (optional) D Under floor heating circuit E Radiator heating circuit F Heating circuit pump G Mixing valve temperature sensor ? H Accessory kit for heating circuit with mixing valve I Domestic hot water storage tank J DHW tank temperature sensor % K Expansion tank L Temperature and pressure relief valve M Pressure relief valve N DHW recirculation pump 28/20 * O Boiler pump 20 P DHW circulating pump sA
* Function based on coding of address 33
IMPORTANT
DHW circulating pump P must pump into the Vitodens 200-W B2HB boiler (as illustrated).
32
Installation of ...
underfloor heating circuit with 3-way mixing valve and system separation (low-temp. circuit)
DHW production ... with the following flow conditions:
The flow rate of the heating circuit is less than the maximum possible water flow rate of the Vitodens 200-W B2HB boiler.
See page 8 for maximum water flow rate of the Vitodens 200-W B2HB boilers. The use of a low-loss header is recommended if the system water flow rate is unknown. The low-loss header is available as accessory part.
See following pages for installation examples with a low-loss header.
IMPORTANT
System separation is required of underfloor heating systems employing non-oxygen diffusion barrier tubing. All components on the secondary side of the heat exchanger must be made of corrosion-resistant materials.
IMPORTANT
Sizing of field-supplied pump P is critical for proper boiler operation in this system layout. See page 8 for the supply head pressure drop of the boiler. An undersized pump may cause short-cycling and/or improper operation of the boiler. Viessmann STRONGLY recommends using a low-loss header and a boiler pump in this system layout.
5461 883 - 02
Page 33
Vitodens 200-W, B2HB 19 to 35 Technical Data
System Layout 5
Vitodens 200-W, B2HB with...
- DHW storage tank
- one heating circuit with mixing valve
- one heating circuit without mixing valve and low-loss header
Installation Examples
Legend
A Vitodens 200-W B2HB boiler with Vitotronic 200, HO1B outdoor reset control
B Outdoor temperature sensor ! C Vitotrol remote (optional) D Under floor heating circuit E Radiator heating circuit F Boiler circuit pump 20 G Mixing valve temperature sensor ? H Kit for heating circuit with mixing valve I Domestic hot water storage tank J DHW tank temperature sensor % K Expansion tank L Temperature and pressure relief valve M Pressure relief valve N DHW recirculation pump 28/20 * O DHW circulating pump sA P Heating circuit pump Q Low-loss header R Viessmann temperature sensor for low-loss header ? S Heating circuit pump 28/
* Function based on coding of address 33
5461 883 - 02
20 *
Installation of different heating circuits...
radiator heating circuit (high-temp. circuit)
under floor heating circuit with 3-way mixing valve
(low-temp. circuit)
DHW production ... with the following flow conditions:
The total flow rate of the two heating circuits is greater than the maximum possible water flow rate of the Vitodens 200-W B2HB boiler (see page 8 for maximum water flow rate of boiler). The use of a low-loss header is strongly recommended. The low-loss header is available as accessory part.
The 3-way mixing valve, built-in to achieve the low­temperature level of the under floor heating circuit, is controlled by an accessory kit for a heating circuit with mixing valve.
IMPORTANT
DHW circulating pump O must pump into the Vitodens 200-W B2HB boiler (as illustrated).
33
Page 34
Installation Examples
System Layout 6
Vitodens 200-W, B2HB with...
- DHW storage tank
- one heating circuit without a mixing valve
- two heating circuits with a mixing valve
- low-loss header
Vitodens 200-W, B2HB 19 to 35 Technical Data
Legend
A Vitodens 200-W B2HB boiler with Vitotronic 200, HO1B outdoor reset control
B Outdoor temperature sensor ! C Vitotrol remote (optional) D Under floor heating circuit E Heating circuit pump 28/20 * F Mixing valve temperature sensor ? G Accessory kit for heating circuit with mixing valve H Heating circuit pumps I DHW storage tank J DHW tank temperature sensor % K Expansion tank L Temperature and pressure relief valve M Low-loss header N Viessmann temperature sensor for low-loss header ? O Pressure relief valve P DHW recirculation pump 28/20 * Q Radiator heating circuit R Boiler pump 20 S DHW circulating pump sA
* Function based on coding of address 33
Installation of different heating circuits...
two heating circuits with 3-way mixing valve (low-temp. circuit)
DHW production ... with the following flow conditions:
The total flow rate of the two heating circuits is greater than the maximum possible water flow rate of the Vitodens 200-W B2HB boiler (see page 8 for maximum water flow rate of boiler). The use of a low-loss header is strongly recommended. The low-loss header is available as accessory part.
The 3-way mixing valve, built-in to achieve the low­temperature level of the under floor heating circuit, is controlled by an accessory kit for a heating circuit with a mixing valve.
IMPORTANT
DHW circulating pump S must pump into the Vitodens 200-W B2HB boiler (as illustrated).
34
5461 883 - 02
Page 35
Vitodens 200-W, B2HB 19 to 35 Technical Data
System Layout 7
Vitodens 200-W, B2HB with...
- direct-connected heating circuit
- one heating circuit with system separation
Installation Examples
Legend
A Vitodens 200-W B2HB boiler with Vitotronic 200, HO1B outdoor reset control
B Outdoor temperature sensor ! C Vitotrol remote (optional) D Under floor heating circuit E Radiator heating circuit F Plate heat exchanger for system separation G Heating circuit pump H Mixing valve temperature sensor ? I Accessory kit for heating circuit with mixing valve J DHW storage tank K DHW tank temperature sensor % L Expansion tanks M Temperature and pressure relief valve N Pressure relief valve O DHW recirculation pump 28/20 * P Boiler pump 20 Q DHW circulating pump sA
* Function based on coding of address 33
IMPORTANT
DHW circulating pump Q must pump into the Vitodens 200-W B2HB boiler (as illustrated).
5461 883 - 02
Installation of different heating circuits...
radiator heating circuit (high-temp. circuit)
under floor heating circuit with 3-way mixing valve
(low-temp. circuit)
DHW production ... with the following flow conditions:
The total flow rate of the two heating circuits is less than the maximum possible water flow rate of the Vitodens 200-W B2HB boiler (see page 8 for maximum water flow rate of boiler). The use of a low-loss header is strongly recommended if the maximum water flow rate in the application concerned exceeds the max. boiler flow rate, or if the system flow rates are unknown. The low-loss header is available as accessory part.
The 3-way mixing valve, built-in to achieve the low­temperature level of the under floor heating circuit, is controlled by an accessory kit for a heating circuit with mixing valve I. The boiler pump 20 supplies the radiator heating circuit and the plate heat exchanger for system separation.
IMPORTANT
The pressure drop (secondary circuit) of the plate heat exchanger F must be less/equal to the pressure drop of the 3-way mixing valve. This must be taken into account when sizing the plate heat exchanger.
35
Page 36
Installation Examples
System Layout 8
Vitodens 200-W, B2HB with...
- DHW storage tank
- low-loss header
- multiple heating circuits with mixing valves
- one heating circuit without mixing valve
Vitodens 200-W, B2HB 19 to 35 Technical Data
When designing a system as illustrated above, please contact your local Viessmann Sales Representative for assistance.
Legend
A Vitodens 200-W B2HB boiler with Vitotronic 200, HO1B outdoor reset control
B Outdoor temperature ! C Boiler pump 20 D Vitotronic 200-H, HK1B *1 E Mixing valve temperature sensor ? F Heating circuit pumps G Accessory kit for heating circuit with mixing valve H Heating circuits with mixing valves I Viessmann temperature sensor for low-loss header ? J Low-loss header K DHW circulating pump sA L DHW tank temperature sensor % M DHW storage tank N Expansion tank O DHW recirculation pump sK P Heating circuit pump 28/20 * Q Vitotrol remote (optional) R Radiator heating circuit S Temperature and pressure relief valve T Pressure relief valve
* Function based on coding of address 33
*1 Contact your local Sales Representative for details.
Vitotronic 200-H, HK1B mixing valve control with LON communication module can be used instead of the accessory kit and Vitocontrol.
IMPORTANT
Please note location of expansion tank N.
IMPORTANT
Pumps C and K must pump into the Vitodens 200-W B2HB boiler (as illustrated).
36
5461 883 - 02
Page 37
Vitodens 200-W, B2HB 19 to 35 Technical Data
Installation Examples
Alternative DHW Connection
The following piping diagram reflects an alternative connection for the DHW tank only and applies to system layouts 2, 5, 6 and 8. The boiler control pump logic function must be programmed in the Service Instructions.
5461 883 - 02
*Note: When using a low loss header in the system, the DHW connections can be made downstream of the low loss header. See Vitodens 200-W B2HB Service Instructions for applicable system coding information (see coding level 2): 00: ... A2: ... 5b: ...
37
Page 38
Wiring Diagram
Vitodens 200-W, B2HB 19 to 35 Technical Data
Overview of Electrical Connections, Models B2HB 19, 26, and 35
38
WARNING
DISCONNECT POWER BEFORE SERVICING BOILER.
If any of the original wires as supplied with the appliance must be replaced, it must be replaced with the exact equivalent.
CAUTION
Label all wires prior to disconnection when servicing controls. Wiring errors can cause improper and dangerous operation. Verify proper operation after servicing.
Only one function/accessory may
*
be assigned to each connection.
5461 883 - 02
Page 39
Vitodens 200-W, B2HB 19 to 35 Technical Data
Wiring Diagram
Overview of Electrical Connections, Models B2HB 19, 26 and 35 (continued)
Legend
1 Outdoor Temperature Sensor 2 Supply Temperature Sensor/Low Loss Header 3 Boiler Temperature Sensor 5 DHW Temperature Sensor 11 Ionization Electrode 15 Flue Gas temperature Sensor 20 Boiler Pump 21 DHW Pump [21] Pump Output Connection 28/20 Programmable Pump Output* 33 Flow Switch 35 Gas Valve 40 Power Supply 40A Accessory Power Output 47 Fixed High Limit [53] Powered Accessory Connection 54 Ignition Transformer 96 Powered Accessory Connection 100 Fan Motor 100A Fan Motor Control 111 Not Used 145 KM BUS Multi Powered Accessory Connection 156A Switched Output F2 156B Switched Output F1 DE1 Digital Input 1 (Dry Contact) DE2 Digital Input 2 (Dry Contact) DE3 Digital Input 3 (Dry Contact) 0-10V 0-10VDC Input 157 Fault Alarm/DHW Recirc. Pump* 190 Gas Modulation Coil
* See wiring diagram
A Boiler Control B External Accessory Connection Board C Pump Connection Interface D Extension Module EA1 E KM-BUS for External Devices F Electrical Junction Box G Field Wiring Connections
A1 Main Board A2 Internal Power Supply Unit A3 Optolink A4 Burner Control Unit A5 Programming Unit A6 Coding Card A7 Connection Adaptor A8 LON Communication Module S1 ON/OFF Switch S2 Reset Button
X.. Electrical Interface
5461 883 - 02
39
Page 40
System Design
System Design Considerations
Vitodens 200-W, B2HB 19 to 35 Technical Data
IN THE COMMONWEALTH OF MASSACHUSETTS...
- this product shall be installed by a licensed plumber or gas fitter.
- the flexible connector (if used) cannot exceed 36”.
- any level type shutoff used must be of tee handle type.
Boiler location
As a direct vent appliance, the Vitodens 200-W can be installed for room air independent operation (sealed combustion) regardless of size and ventilation method of the room in which it is located. The Vitodens 200-W can be installed, for example, in the main living area of a house, in non-ventilated utility rooms, cupboards, closets and alcoves with no clearance required from combustible materials, as well as in attics with a direct outlet for the flue gas/fresh air system. Follow all local and national codes.
Flue gas system
PPS (Polypropylene) concentric flue gas/fresh air systems for room air independent operation (sealed combustion) and side wall venting are tested to ANSI Z21.13 - CSA
4.9 - 2000 standards and are certified together with the Vitodens 200-W boiler as a constructional unit. The Vitodens 200-W boiler may also be vented vertically, using an AL29-4C® special stainless steel, single-wall, room air dependent venting system (UL listed for category IV). For a more detailed description of the direct vent and single-wall vent system, please refer to the Vitodens 200-W Venting System Installation Instructions.
Flue gas temperature protection
Flue pipes used for the Vitodens 200-W are suitable for max. flue gas temperatures of up to 230°F (110°C). No flue gas temperature protection is required as the maximum permissible flue gas temperature is not exceeded in any operating condition or in the event of malfunctioning.
Low water cut-off
A low water cut-off may be required by local codes. If the boiler is installed above the radiation level, a low water cut-off device of approved type must be installed in all instances. An approved type low water cut-off device must be provided by the heating contractor. Do not install an isolation valve between the boiler and the low water cut-off.
Water connections
Vitodens 200-W boilers can be used in any fully pumped hot water heating system. Minimum system pressure is 0.8 bar (12 psig). Chemical corrosion protection products Corrosion does not typically occur in sealed heating systems which have been correctly installed and are correctly operated. Many manufacturers of plastic pipes recommend the use of chemical additives. In this case, only those commercially available corrosion protection products approved for boilers with domestic hot water heating via single-wall heat exchangers (instantaneous plate heat exchangers or DHW tanks) must be used.
Water quality
Treatment for boiler feed water should be considered in areas of known problems, such as where a high mineral content and hardness exist. In areas where freezing might occur, an antifreeze may be added to the system water to protect the system. Please adhere to the specifications given by the antifreeze manufacturer. Do not use automotive silicate based antifreeze. Please observe that an antifreeze/water mixture may require a backflow preventer within the automatic water feed and influence components such as diaphragm expansion tanks, radiation, etc. Maximum antifreeze content is 50% for the Vitodens 200-W boiler. Do not use antifreeze other than specifically made for hot water heating systems. System also may contain components which might be negatively affected by antifreeze. Check total system frequently when filled with antifreeze. Advise system operator/ultimate owner that system is filled with a glycol mix. The heating contractor must provide a MSDS (Material Safety Data Sheet) for the antifreeze used to the system operator/ultimate owner.
Total permissible hardness of the fill and top-up water
Total heating output Specific heating volume
MBH <5 USG per 3412 BTU
[ 170
>170 to [ 682
>
682 to [170
>2050
ppm - parts per million gpg - grains per gallon
40
300 ppm 17.5 gpg 200 ppm 11.7 gpg 2 ppm 0.11 gpg
200 ppm 11.7 gpg 150 ppm 8.8 gpg 2 ppm 0.11 gpg
150 ppm 8.8 gpg 2 ppm 0.11 gpg 2 ppm 0.11 gpg
2 ppm 0.11 gpg 2 ppm 0.11 gpg 2 ppm 0.11 gpg
m 5USG per 3412 BTU to
<13USG per 3412 BTU
m 13USG per 3412 BTU
5461 883 - 02
Page 41
Vitodens 200-W, B2HB 19 to 35 Technical Data
System Design Considerations
System Design
(continued)
System layout
The max. boiler water temperature for space heating and DHW production is 165° F (74° C) for models B2HB 19 to 35. To minimize distribution losses, Viessmann recommends that the heating and domestic hot water systems be based on a maximum boiler supply temperature of 158° F (70° C).
Due to the low return temperatures required for gas condensing, no mixing valves should be used in the heating circuit whenever possible. If mixing valves are required, e.g. for multi-circuit systems or underfloor heating systems, only 3-way mixing valves must be used. Do not use 4-way mixing valves with condensing boilers.
Underfloor heating systems
For underfloor heating systems Viessmann recommends the use of plastic tubing with an oxygen diffusion barrier in order to prevent the diffusion of oxygen through tubing. If plastic tubing without an oxygen diffusion barrier is used in underfloor heating systems, Viessmann recommends that such systems be separated from the boiler with a heat exchanger. Underfloor heating systems and heating circuits containing a very large volume of water must be connected to the boiler via a 3-way mixing valve; please refer to the applicable installation example in this manual.
Oxygen diffusion barrier underfloor tubing
The boiler warranty does not cover leaks resulting from corrosion caused by the use of underfloor plastic tubing without an oxygen diffusion barrier. Such systems must have the non-oxygen diffusion barrier tubing separated from the boiler with a heat exchanger. Viessmann recommends the use of underfloor plastic tubing with an oxygen diffusion barrier.
Warranty
Our warranty does not cover damages resulting from the following:
- installation or service by unqualified and unlicensed personnel.
- attempting to perform any repair work on the boiler other than that mentioned in the boiler literature.
- tampering with or attempting, without Viessmann permission, to readjust the factory settings of the;
-combination gas valve
-combustion air opening of the burner blower
- leaks resulting from corrosion caused by the use of underfloor plastic tubing without an oxygen diffusion barrier. For detailed warranty information, please read warranty sheet supplied with product.
5461 883 - 02
41
Page 42
Vitodens 200-W, B2HB 19 to 35 Technical Data
42
5461 883 - 02
Page 43
Vitodens 200-W, B2HB 19 to 35 Technical Data
5461 883 - 02
43
Page 44
Vitodens 200-W, B2HB 19 to 35 Technical Data
(recycled and recyclable) paper.
Technical information subject to change without notice. Printed on environmentally friendly
5461 883 - 02