If you encounter any installation or operational issues with your product, check the pertinent section of
this manual to see if the issue can be resolved by following outlined procedures. For additional assistance,
visit https://www.VertivCo.com/en-us/support/
TABLE OF CONTENTS
1 Important Safety Instructions5
2 General Description7
2.1 System Description7
2.1.1 Features7
2.1.2 Standard Components7
2.1.3 Options7
3 Modes of Operation11
3.1 UPS Mode11
3.2 Bypass Mode11
4 Major Components13
4.1 Bypass Switch13
4.2 User Selectable Output Distribution13
4.2.1 Optional Transformer13
5 Preparation15
5.1 Inspection15
5.2 Environment15
5.3 Required Setup Equipment15
5.4 Site Preparation15
6 Unloading17
6.1 Unloading the Maintenance Bypass Cabinet17
6.2 Stationary Mounting18
7 Cable Installation21
7.1 Wiring Preparation21
7.2 Preparing Internal Wiring21
7.3 Dual Source Configuration21
7.4 Removing the Cover Plates23
7.5 REPO Connection23
7.6 Input and Output Wiring23
8 Operation29
8.1 Start-Up and Initialization29
8.2 Shutting Down the UPS29
8.3 Transferring the System fromUPStoMaintenanceBypassOperation30
8.4 Transferring the System fromMaintenanceBypasstoUPSOperation30
9 Maintenance31
9.1 Proper Care31
9.2 Scheduled Maintenance31
9.2.1 Replacing Fan Filters—Transformer Models Only31
This manual contains important instructions that should be closely followed during installation and
maintenance of this Maintenance Bypass Cabinet.
This product is designed for commercial/industrial use only. This product is not intended for use with life
support and other designated “critical” devices. Maximum load must not exceed that shown on the UPS
and the Maintenance Bypass Cabinet rating label.
WARNING! Lethal voltages may be present within this unit even when it is apparently not
operating. Observe all cautions and warnings in this manual. Failure to do so may result in
serious injury or death. Never work alone.
The Liebert Maintenance Bypass Cabinet is designed for use on properly grounded (earthed)
208/240VAC, 60Hz supply, for installation by qualified personnel. This UPS equipment is intended to be
installed by a qualified / certified electrician who must review and approve customer supplied wiring,
circuit breakers, intended loads and verify correct input, output and grounded (earthed) connections to
ensure compliance with technical standards and national and local electrical codes. Installation
instructions and warning notices are located in the Installation section of this manual.
WARNING! To reduce the risk of fire:
The NMB1x and NMB4x models must be connected to a circuit provided with 100 amperes
maximum branch circuit overcurrent protection in accordance with applicable national and local
electrical codes.
The NMB5x and NMB8x models must be connected to a circuit provided with 125 amperes
maximum branch circuit overcurrent protection in accordance with applicable national and local
electrical codes.
Operate the UPS equipment in an indoor environment only in an ambient temperature range of 32°F to
104°F (0°C to 40°C). Install it in a clean environment, free from conductive contaminants, moisture,
flammable liquids, gases, or corrosive substances.
Never block or insert any object into the ventilation holes or other openings.
Table 1.1 Glossary of Symbols
SYMBOLDESCRIPTION
Risk ofElectrical Shock
Indicates Warningor Caution
Followed by ImportantInstructions
Congratulations on your purchase of Liebert’s Maintenance Bypass Cabinet with Configurable Output
Distribution. As with every Vertiv™ product, we stand behind our quality. If you have any questions
concerning this Maintenance Bypass Cabinet, please feel free to contact your local dealer, Vertiv™
representative, or call Technical Support at 1-800-222-5877.
To ensure proper installation and operation of this unit, please read this manual thoroughly.
Installation must be done by a qualified/certified electrician, but general operation may be performed
without special training.
2.1 System Description
The Liebert Maintenance Bypass Cabinet is intended for use with the Liebert UPS units. Typical
applications include supporting workstations, servers, network, telecom or other sensitive electronic
equipment.
The Maintenance Bypass Cabinet was designed to provide maximum system availability to business
critical equipment. The Maintenance Bypass Cabinet allows for transfer of connected loads to an
alternate power path allowing full isolation of the UPS. The UPS can then be turned “OFF” and removed
from service with no interruption of power to connected loads.
2.1.1 Features
•Supports up to 20 kVA loads
•High speed transfer switch
•Compact design
•Highly configurable
•Multiple power path indicators
2.1.2 Standard Components
•Casters and leveling feet
•Easily accessible terminal blocks
•Supports Lockout/Tagout Program
•Support/mounting brackets for additional stability
The Maintenance Bypass Cabinet is designed to operate in two modes: UPS Mode and Bypass Mode.
3.1 UPS Mode
While the Maintenance Bypass Cabinet is in UPS Mode, the UPS is supplying the connected load with
continuous, high quality AC power. In this mode of operation, the load is protected by the UPS. The Bypass
Switch rotated toward the green lamp indicates this mode.
3.2 Bypass Mode
When the Maintenance Bypass Cabinet is in the Bypass Mode, it provides an alternate path for power to
the connected equipment. Should the UPS need to be taken out of service for limited maintenance or
repair, manual activation of the bypass will cause an immediate transfer of the equipment from the UPS
inverter to the bypass source.
The amber lamp illuminated in the Maintenance Bypass Switch compartment indicates bypass is
available. In this mode of operation the load is NOT protected by the UPS. The Bypass Switch rotated
toward the amber lamp indicates this mode. See Operation on page29 for instructions on use.