The information contained in this document is subject to change
without notice and may not be suitable for all applications. While
every precaution has been taken to ensure the accuracy and
completeness of this document, Vertiv assumes no responsibility
and disclaims all liability for damages resulting from use of this
information or for any errors or omissions. Refer to other local
practices or building codes as applicable for the correct methods,
tools, and materials to be used in performing procedures not
specifically described in this document.
The products covered by this instruction manual are manufactured
and/or sold by Vertiv. This document is the property of Vertiv and
contains confidential and proprietary information owned by Vertiv.
Any copying, use or disclosure of it without the written permission
of Vertiv is strictly prohibited.
Names of companies and products are trademarks or registered
trademarks of the respective companies. Any questions regarding
usage of trademark names should be directed to the original
manufacturer.
Technical Support Site
If you encounter any installation or operational issues with your product, check the pertinent
section of this manual to see if the issue can be resolved by following outlined procedures.
Visit https://www.VertivCo.com/en-us/support/ for additional assistance.
Vertiv | Liebert® DCD™Installer/UserGuide
TABLE OF CONTENTS
1 Important Safety Instructions5
2 Nomenclature and Components9
2.1 Model Number Nomenclature9
2.2 Component Locations10
3 General Product Information13
3.1 Product/System Description13
3.1.1 Cooling Principle14
3.2 DCD Active with Fan Module16
4 Pre-installation Preparation and Guidelines19
4.1 Planning Dimensions19
4.2 UnitWeights19
4.3 Room Preparation19
4.4 Air-flow Considerations20
4.5 Water-supply Considerations20
4.5.1 Water Quality Requirements21
4.5.2 Water Temperature Requirements22
5 Equipment Inspection and Handling23
5.1 Storing the Unit24
5.2 Packaging Material24
5.3 Handling the Unit while Packaged24
5.4 Unpacking the Module25
6 Installation29
6.1 DCD Frame Preparation29
6.2 Installing the DCD Frame on a DCM Rack30
6.2.1 Required Tools30
6.3 Installing the DCD Door34
6.4 Installing the DCD Swivel-joint Covers40
6.5 Reversing the Door Handle44
6.6 Installing the Active Fan Module44
6.6.1 Mounting the Active Fan Module on DCD45
6.6.2 Connecting Supply Power and Sensors47
7 Piping Considerations and Connections49
7.1 System Connection Configuration49
7.1.1 Using Chilled-water Distribution Units51
7.1.2 Using Open-loop Chilled-water Systems51
7.2 Connection Methods and Points51
7.3 Floor Cut-out Dimensions for Units with Bottom Connections52
This manual contains important safety instructions that should be followed during the installation and
maintenance of the Liebert®DCD. Read this manual thoroughly before attempting to install or operate
this unit.
Only qualified personnel should move, install or service this equipment.
Adhere to all warnings, cautions, notices and installation, operating and safety instructions on the unit
and in this manual. Follow all installation, operation and maintenance instructions and all applicable
national and local building, electrical and plumbing codes.
WARNING! Arc flash and electric shock hazard. Open all local and remote electric power
disconnect switches, verify with a voltmeter that power is Off and wear personal protective
equipment (PPE) per NFPA 70E before working with the module. Failure to comply can cause
serious injury or death. Follow all local codes.
WARNING! Risk of heavy module falling. Can cause equipment damage, injury and death. Two
properly-trained and qualified people are required to move and install the module. The DCD™
weighs in excess of 210lb(95kg). Do not leave a DCD™ standing unattended on its side or its
end without adequate support to prevent it from falling over. The module must be supported at
all times or laid flat on protective material until it is installed. Read all instructions before
attempting to move, lift, remove packaging from, or prepare the module for installation. See
Table 4.2 on page19, for unit weights based on model.
WARNING! Risk of improper operation and overpressurization. Can cause equipment or other
property damage, injury and death. Only personnel properly trained and qualified in HVAC
installation or service should installor service this equipment
WARNING! Risk of contact with high-speed, rotating fan impeller blades. Can cause injury or
death. Open all local and remote electric power-supply disconnect switches, verify with a
voltmeter that power is off, and verify that all fan impellers have stopped rotating before
working in the unit cabinet.
CAUTION: Risk of contact with sharp edges, splinters, and exposed fasteners. Can cause
injury. Only properly trained and qualified personnel wearing appropriate, OSHA-approved PPE
should attempt to move, lift, remove packaging from or prepare the unit for installation.
1 Important Safety Instructions
5
NOTICE
NOTICE
NOTICE
CAUTION: Risk of improper repair and maintenance. Can cause reduced unit performance,
equipment damage and injury.
All maintenance and repair jobs must be performed by properly trained and qualified personnel.
All actions must be in accordance with regulations and the manufacturer’s instructions. Use
only Vertiv-approved tools and parts for maintenance and repair.
Risk of improper power-supply connection. Can cause equipment damage and loss of warranty
coverage.
Prior to connecting any equipment to a main or alternate power source (for example: back-up
generator systems) for start-up, commissioning, testing, or normal operation, ensure that these
sources are correctly adjusted to the nameplate voltage and frequency of all equipment to be
connected. In general, power-source voltages should be stabilized and regulated to within
±10% of the load nameplate nominal voltage. Also, ensure that no three-phase sources are
single-phased at any time.
Risk of passageway interference. Can cause unit and/or structure damage. The unit may be
too large to fit through a passageway while on or off the skid. Measure the unit and passageway
dimensions, and refer to the installation plans prior to moving the unit to verify clearances.
NOTICE
Risk of damage from forklift. Can cause unit damage. Keep tines of the forklift level and at a
height suitable to fit below the skid and/or unit to prevent exterior and/or underside damage.
Risk of improper storage. Keep the unit upright, indoors and protected from dampness,
freezing temperatures and contact damage.
6
Vertiv | Liebert® D CD™Installer/User G uide
NOTICE
Risk of piping-system corrosion and freezing fluids. Can cause leaks resulting in equipment
and very expensive building damage. Cooling coils and piping systems are at high risk of
freezing and premature corrosion. Fluids in these systems must contain the proper antifreeze
and inhibitors to prevent freezing and premature coil and piping corrosion. The water or
water/glycol solution must be analyzed by a competent local water treatment specialist before
start up to establish the inhibitor and antifreeze solution requirement and at regularly
scheduled intervals throughout the life of the system to determine the pattern of inhibitor
depletion.
The complexity of water/glycol solution condition problems and the variations of required
treatment programs make it extremely important to obtain the advice of a competent and
experienced water treatment specialist and follow a regularly scheduled coolant fluid system
maintenance program.
Water chemistry varies greatly by location, as do the required additives, called inhibitors, that
reduce the corrosive effect of the fluids on the piping systems and components. The chemistry
of the water used must be considered, because water from some sources may contain corrosive
elements that reduce the effectiveness of the inhibited formulation. Sediment deposits prevent
the formation of a protective oxide layer on the inside of the coolant system components and
piping. The water/coolant fluid must be treated and circulating through the system
continuously to prevent the buildup of sediment deposits and or growth of sulfate reducing
bacteria.
Proper inhibitor maintenance must be performed in order to prevent corrosion of the system.
Consult glycol manufacturer for testing and maintenance of inhibitors.
Commercial ethylene glycol, when pure, is generally less corrosive to the common metals of
construction than water itself. It will, however, assume the corrosivity of the water from which it
is prepared and may become increasingly corrosive with use if not properly inhibited.
We recommend installing a monitored fluid-detection system that is wired to activate the
automatic-closure of field-installed coolant-fluid supply and return shut-off valves to reduce
the amount of coolant-fluid leakage and consequential equipment and building damage. The
shut-off valves must be sized to close-off against the maximum coolant-fluid system pressure
in case of a catastrophic fluid leak.
1 Important Safety Instructions
7
NOTICE
NOTICE
Risk of clogged or leaking drain lines and leaking water-supply lines. Can cause equipment and
building damage.
This unit requires a water drain connection. Drain lines must be inspected at start-up and
periodically, and maintenance must be performed to ensure that drain water runs freely
through the drain system and that lines are clear and free of obstructions and in good
condition with no visible sign of damage or leaks. This unit may also require an external water
supply to operate.
Improper installation, application and service practices can result in water leakage from the
unit. Water leakage can result in catastrophic and expensive building and equipment damage
and loss of critical data center equipment.
Do not locate unit directly above any equipment that could sustain water damage.
We recommend installing a monitored fluid-detection system to immediately discover and
report coolant-fluid system and condensate drain-line leaks.
Risk coil and piping rupture. Can cause equipment damage and major fluid leaks resulting in
serious building damage, expensive repair costs and costly system down time.
Thermal expansion of the cooling fluid without means of expansion can cause the coil and
piping to rupture, spilling cooling fluid in the conditioned space. This can be caused, among
other ways, by closing the ball valves on both the supply and the return pipes. Always allow for
thermal expansion either by leaving at least one of the valves open or by opening the DCD™
bleed valve.
NOTE: This document is intended to be used together with site-specific documentation and
documentation for other parts of the system.
8
Vertiv | Liebert® D CD™Installer/User G uide
2 NOMENCLATURE AND COMPONENTS
This section describes the model number for Liebert® DCD units and components.
2.1 Model Number Nomenclature
Table 2.2 on the next page describes each digit of the model number.
Table 2.1 Liebert DCD Model-number Example
Model Number Digits 1 to 10Model Det ailsModel Number Digits 11 to 14
123456789101112 13 14 15 16 17 18 19 202122232425
DCD35A603000000G0000SA002
Table 2.2 Model-number Digit Definitions for Liebert DCD
DigitDescription
Digits 1, 2, 3 = the base unit
DCD = Data Center Door
Digit 4, 5 = Nominal Capacity
35 = 35kW
50 = 50kW
Digit 6 = Rack Height
A = 42U, 78-6/8 in. (2000mm)
Digit 7 = Rack Width
6 = 23-5/8 in. (600mm), onlyavailable on 35 models.
8 - 32-1/2 in. (800mm)
Digit 8 = Cabinet Type
0 = No aluminum frame
Digit 9 = Chilled-water Connection/Hinge Position
1 = Top connection/Hinges left
3 = Bottom connection/Hinges left
Digit 10 = Options
0 = None
Digits 11 to 15 = Not Used
0 = No options
Digit 16 = Color
G = RAL 7021 (dark gray)
2 Nomenclature and Components
9
Table 2.2 Model-number Digit Definitions for Liebert DCD (continued)
DigitDescription
Digits 17 to 20 = Not Used
0 = No options
Digit 21 = Packaging Type
S = Seaworthy (air freight), Long distance (wooden crate)
Digit 22 = SFA (SpecialFeatures)
A = Standard, no SFA
X = SFA(s) included
Digits 23 to 25 = Revision Identifier
2.2 Component Locations
Figure 2.1 Liebert DCD Component locations
ItemDescription
1Upper and Lower swivel joints
2Door handle
3Door
4Upper piping
5DCD frame
6Lower Piping
7Aluminum profile
10
Vertiv | Liebert® D CD™Installer/User G uide
ItemDescription
8Condensate tray
9Condensate drain plug
10Chilled-water outlet
11Chilled-water inlet
12Condensate-hose adapter (on the bottom of the unit)
2 Nomenclature and Components
11
This page intentionally left blank
12
Vertiv | Liebert® D CD™Installer/User G uide
3 GENERAL PRODUCT INFORMATION
3.1 Product/System Description
The Liebert® DCD™ is an air-water heat exchanger that is integrated into the rear door of a server rack.
The DCD™ meets the requirements of the EN 60950 standard. The design allows installation on the back
of a server cabinet and maintains access to the back of the servers while the chilled water connections
remain stationary. The DCD35 is suitable for absorbing up to 35-kW heat loads from server racks 24in.
(600mm) x 42U. The DCD50 is suitable for absorbing up to 50-kW heat loads from server racks 31.5in.
(800mm) x 42U. It can be configured so that no heat is released in the installation area with proper
cabinet sealing.
Heat produced by internal components (for example, servers), is reliably removed by the door with a builtin chilled water system or a chilled-water distribution unit, such as the Liebert® DCP™ (see Figure 3.1
below). A chilled-water distribution unit provides these benefits:
•Isolates the building’s chilled-water circuit from the chilled-water circuit in the data center. The
DCP circulates chilled water to DCD while preventing condensation by maintaining the water
temperature above the room dew point.
•Ensures the proper flow rate to the DCD. This is critical to achieve and maintaining the needed
capacity.
•Minimizes the possibility of a leak within the data center by separating the data center from
the building chilled-water circuit. Should a leak occur within the data center, the volume of
water is limited to the amount in the secondary piping system instead of the amount in the
entire-building chilled-water system.
Figure 3.1 Generic piping layout
Room air is drawn in through the front of the rack and picks up heat from the servers. Cooling occurs
when the server exhaust air passes through the DCD™ heat exchanger (see Figure 3.2 on the next
page). The air is moved through the heat exchanger by the server fans.
3 General Product Information
13
The DCD™ is not expected to produce any condensation because of its location within the conditioned
space and connected to a Liebert® DCP or if the chilled-water temperature is maintained above the dew
point, A condensate pan is provided as a precaution. It has a drain fitting to allow any condensate to be
emptied.
Figure 3.2 Top view of air flow and cooling of rack with Liebert DCD
ItemDescription
1DCD unit
2Server
3Warm air
4Air barrier
5Coldair
6Recirculation prevented
3.1.1 Cooling Principle
The server fans force air heated by the rack equipment through the unit’s air-water heat exchanger
where it is cooled. The air-side pressure-drop flow-rate dependency curve is shown in Figure B.7 on
page77.
14
Vertiv | Liebert® D CD™Installer/User G uide
Figure 3.3 Cooling principle shown in side-view diagram of rack/DCD
ItemDescription
1Air intake
2Air outlet
3Air barrier
4Cold air
5Warm air
6Top cooling-water connections
7DCD unit
8Bottom cooling-water connections
NOTE: Before using the DCD™, check the system and rack equipment and make sure that they match
hydraulically. In particular, the server fans must be able to generate sufficient pressure to drive the air
through the DCD™.
NOTE: Cooling-water supply and return connections are supplied at each end of the DCD™, but
connections must be made at only one end, either the top or the bottom of the DCD™.
NOTE: In case of chilled-water supply-system failure, the cooling is provided either by adjacent DCD™
modules and/or the room cooling system. In this example, the equipment waste heat is released into
the room.
3 General Product Information
15
3.2 DCD Active with Fan Module
The DCD Active is an option which includes a fan module to be attached to the DCD cooling coil. See
Table 3.1 on the facing page, for the physical and environmental data and requirements of the module.
The active-fan module operates by measuring pressure differential between ambient pressure and the
pressure inside the cabinet and modulating fan speed to reach a predefined pressure setpoint. The
default setpoint is 0-Pa pressure differential. There are two versions of active-fan module:
•Standard—actively maintains a 0-Pa pressure differential by modulating fan speed, and
indicates operating status via a green "operating"LED and a red "disturbance" LED.
•TFT—includes a touch-screen display and temperature sensors for precise control of the
pressure differential and fan speed based on pressure and temperature readings. See Using
the DCD Active TFT Display on page61, for details.
Dimensions (LxWxH)DCD35, in. (mm)76.9 x16.5x4.9 (1954 x 420 x 125)
Dimensions (LxWxH)DCD50, in. (mm)76.9x 22 .8X4.9 (1954 x 579 x 125)
Weight DCD35, lb(kg)77(35)
Weight DCD50, lb(kg)88.2 (40)
Degree of protectionIP2 0
Degree of containment2
Ambient Conditions
Operating temperature50 to 104°F (10 to 40°C)
Liebert® SN-T
Maxim DS28EA00, DS18B20
Storage temperature–13 to 176°F (–25 to 80°C)
Relative humidity0 to 95% non-c ondensing
16
Vertiv | Liebert® D CD™Installer/User G uide
Table 3.1 DCD Active Specifications (continued)
ItemSpecification
Altitude above sea level, ft (m)maximum 6,562 (2000)
Pressure Connection
Operating pressure,–1.005 to 1.005 inAq(–250 to 250Pa)
Maximum pressure permitted± 14.5psi (1bar)
Tolerance3% of the measured value ± 0.0008 inAq (0.2Pa)
Working gasesAir, Nitrogen
Hose—outer diameter, in. (mm)0.24 (6)
3 General Product Information
17
This page intentionally left blank
18
Vertiv | Liebert® D CD™Installer/User G uide
4 PRE-INSTALLATION PREPARATION AND GUIDELINES
The Liebert DCD attaches to the rear of a computer cabinet with side panels. See the dimensional-data
drawings in the Submittal Drawings on page83.
NOTE: The cooling with Liebert DCD works only if a strict air separation exists between server cold air
intake and server warm air outlet. Unused rack spaces must be blocked with blanking plates. All
bushings (network cables, piping, etc.) must be sealed to prevent air leakage. Racks must have side
panels. The tops and bottoms of the racks must be sealed.
4.1 Planning Dimensions
Refer to site-specific drawings for exact placement. Efficient cooling depends on proper equipment
placement, proper use of plates in any voids in the rack and good cable management.
Ensure that there is 25.6-in.(649mm) clearance in the rear to allow the door to open fully.
The unit dimensions are described in the submittal documents included in the Submittal Drawings on
page83.
The following table lists the relevant documents by number and title.
Table 4.1 Dimension Planning Drawings
Document NumberTitle
DPN004112Dimensional Data, DCD35
DPN004113DimensionalData, DCD50
4.2 UnitWeights
Table 4.2 Liebert DCD unit weights
Model NumberWeight, lb (kg)
DCD35210 (95)
DCD50230 (104)
4.3 Room Preparation
The room should be well-insulated and must have a sealed vapor barrier. The vapor barrier in the ceiling
and walls can be a polyethylene film. Paint on concrete walls and floors should contain either rubber or
plastic.
NOTE: The vapor barrier is the most important factor in maintaining environmental control in the
conditioned space.
Outside or fresh air should be kept to a minimum when temperature and humidity must be tightly
controlled. Outside air adds to the site’s cooling, heating, dehumidifying and humidifying loads. Doors
must be properly sealed to minimize leaks and must not contain ventilation grilles.
4 Pre-installation Preparation and Guidelines
19
4.4 Air-flow Considerations
The server fans draw air into the rack where the equipment heats it. The server fans force the heated air
across the DCD™ coil. The DCD™ has a low air-side pressure drop, similar to a rack with perforated doors.
Figure 4.1 Generic airflow diagram—enclosure/rack shown from side
ItemDescription
1Front of rack
2Rear of rack
3DCD
4Cooling water connections
5Criticalequipment
NOTE: To provide optimal cooling, strict separation between the hot and cold air must exist within the
rack and all the bushings (network cables, piping, etc.) must be sealed to prevent air leakage. Air
bypass and recirculation can severely reduce the cooling effectiveness of the DCD™. Install blanking
plates in any voids in the rack to prevent air bypass and air recirculation. Keep the coils clear of any
obstructions that may block the airflow. Contact the factory for further information. Refer to the user
manual supplied with the rack on which the DCD™ is mounted.
4.5 Water-supply Considerations
For reliable function of the DCD™, chilled water must be available in an appropriate amount, of the
required quality, and at the appropriate temperature and pressure.
20
Vertiv | Liebert® D CD™Installer/User G uide
4.5.1 Water Quality Requirements
To safeguard the maximum lifetime of air/water heat exchangers, the water used for chilling purposes
must meet the VGB Chilled Water Guidelines (VGB-R 455 P). The chilled water used must be soft enough
to prevent deposits, but it must not be too soft because that would lead to corrosion of the heat
exchanger.
Table 4.3 below, lists the most important impurities and measures for their removal.
Table 4.3 Water Impurity
Water Impurity or ConditionCorrective Method
Particles (dp < 0.3 mm)Filter the water
Excessive hardnessSoften the water by ion exchange
Moderate level of particles and hardenersAdd dispersion or stabilization agents
Moderate level of chemicalimpuritiesAdd deadening agents and inhibitors
Biologicalimpurities (bacteria and algae)Add biocides
We recommend treating water to it get as closest as possible to the values in Table 4.4 on the next page.
Table 4.4 Hydrological data
HydrologicalData
Recommended
Purity Levels
pH values(7 - 10,5)
Carbonate hardness(3 - 8) °dH
Free carbon dioxide(8 - 15) mg/dm3
Combined carbon dioxide
Aggressive carbon dioxide
Sulfides
Oxygen
Chloride ions
Sulphate ions
Nitrates and nitrites
COB
Ammonia
Iron
Manganese
8 - 15mg/dm
0mg/dm
< 10mg/dm
< 50mg/dm
< 250mg/dm
< 10mg/dm
< 7mg/dm
< 5mg/dm
< 5mg/dm
< 0.2mg/dm
< 0.2mg/dm
3
3
3
3
3
3
3
3
3
3
3
Conductivity< 30S/cm
Solid residue from evaporation
4 Pre-installation Preparation and Guidelines
< 500mg/dm
3
21
Table 4.4 Hydrological data (continued)
HydrologicalData
Potassium manganese consumption
Suspended matter
PartialFlow Cleaning Recommended
FullFlow Cleaning
Recommended
Purity Levels
< 25mg/dm
< 3mg/dm
3 -15 mg/dm
> 15mg/dm
3
3
3
3
4.5.2 Water Temperature Requirements
The cold water supply temperature must be higher than the dew point temperature of the cold space.
Failure to maintain the cold water supply temperature above the room dew point will result in
condensation. The DCD™ provides only for sensible cooling. You must avoid dehumidification of the room
by the DCD™. The built-in condensate tray with condensate drain is designed only for a short-term
condensation.
WARNING! Risk of top-heavy unit falling over. Improper handling can cause equipment
damage, injury or death. Read all of the following instructions and verify that all lifting and
moving equipment is rated for the weight of the unit before attempting to move, lift, remove
packaging from or prepare the unit for installation. Unit weights are specified in Table 4.2 on
page19.
CAUTION: Risk of contact with sharp edges, splinters, and exposed fasteners. Can cause
injury. Only properly trained and qualified personnel wearing appropriate, OSHA-approved PPE
should attempt to move, lift, remove packaging from or prepare the unit for installation.
NOTICE
Risk of passageway interference. Can cause unit and/or structure damage. The unit may be
too large to fit through a passageway while on or off the skid. Measure the unit and passageway
dimensions, and refer to the installation plans prior to moving the unit to verify clearances.
NOTICE
Risk of damage from forklift. Can cause unit damage. Keep tines of the forklift level and at a
height suitable to fit below the skid and/or unit to prevent exterior and/or underside damage.
NOTICE
Risk of improper storage. Keep the unit upright, indoors and protected from dampness,
freezing temperatures and contact damage.
NOTICE
Risk of a leaking coil due to freezing during improper storage. Can cause equipment and
serious building damage.
The heat exchanger and the supply pipes must be cleared of any water before the unit is
stored, either before storage or after removal from a cabinet. Compressed air can be used to
remove the water. Remove all the vents and the screws before storing.
Upon arrival of the unit and before unpacking:
•Verify that the labeled equipment matches the bill of lading.
•Carefully inspect all items for visible or concealed damage.
•Report damage immediately to the carrier and file a damage claim with a copy sent to Vertiv or
to your sales representative.
Equipment Recommended for Handling the Unit:
•Forklift
•Pallet jack
5 Equipment Inspection and Handling
23
5.1 Storing the Unit
•Keep the unit in its original packaging, protected from the weather and in dry conditions.
•Protect the unit’s working parts from sand, rain, dust and other particles and contaminants.
•Store at temperatures between -22°F and +122°F (-30°C and +50°C). The chilled-water circuit
must be empty during storage.
•After storage for a year or longer, the water-bearing hinges must be inspected for functionality.
•Remove all packaging before starting the unit.
•Chilled-water connections are not load-bearing. Do not use the connections as handles.
•When transporting the unit, always make sure the device is properly fastened and secured
against slipping.
NOTICE
Risk of a leaking coil due to freezing during improper storage. Can cause equipment and
serious building damage.
The heat exchanger and the supply pipes must be cleared of any water before the unit is
stored, either before storage or after removal from a cabinet. Compressed air can be used to
remove the water. Remove all the vents and the screws before storing.
5.2 Packaging Material
All material used to package this unit is recyclable. Please save for future use or dispose of the
material appropriately.
5.3 Handling the Unit while Packaged
Transport the unit with a forklift or pallet jack.
When using a forklift or pallet jack:
•If multiple units are delivered, they ship on a pallet with up to 4 modules, and a pallet jack is
required to move these to the installation location.
•Make sure that the fork tine length is suitable to move the packaged module.
•When moving the packaged unit, do not lift the unit any higher than 6in.(152mm). All
personnel except those moving the unit must be kept 20ft(5m) or more from the unit while it
is being moved.
•If the unit must be lifted higher than 6in.(152mm), all personnel not directly involved in
moving the unit must be 20ft (5m) or farther from the unit.
•Do not use piping on the module to lift or move the unit.
24
Vertiv | Liebert® D CD™Installer/User G uide
5.4 Unpacking the Module
The following equipment is required to unpack the module:
•Utility knife
•Flat-blade screwdriver, claw hammer, pliers or crowbar
•Forklift, pallet jack or similar device
Do not unpack the unit before moving it to the installation location. Once at the installation point, refer to
Figure 5.1 on the next page, and the following steps:
NOTE: Two properly-trained and qualified personnel must lift the unit.
1.For multiple-unit shipments, cut the bands and place all packaged modules on the floor for
unpacking.
2. On each module, slide the upper row of spring clips upward and remove them.
5 Equipment Inspection and Handling
25
3. Remove the top cover and cross brace from the package, then remove and set aside the
hardware and key package.
4. Remove the remaining spring clips, side panels and any spacers from the package.
Figure 5.1 Removing packaging
ItemDescription
1Cut and remove shipping bands if necessary, andlayeach module on the floor for unpacking.
2Remove the top row of springclips from the packaging.
3Remove the cover and cross brace, then remove the hardware/key kit package and set aside.
4Remove the remainingspring clips, side panels, andanyspacers.
5Shipping bands
6Top spring clip
7Top cover
8Hardware/key kit
9Cross brace
10Spacer (8 places)
11Side panel
26
Vertiv | Liebert® D CD™Installer/User G uide
5. Lay two pieces of protective material, each longer and wider than the module frame, on the
floor.
6. Remove foam packaging from both sides of the unit.
7. Using two people, lift the module frame off the pallet and lay it on one piece of protective
material.
8. Compare the serial tag information on the module to the bill of lading. If the information does
not match the product specified, contact your Vertiv sales representative.
9. Using two people, lift the module and lay it on the second piece of protective material with the
door handle facing up.
5 Equipment Inspection and Handling
27
This page intentionally left blank
28
Vertiv | Liebert® D CD™Installer/User G uide
Loading...
+ 63 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.