Liebert® CRV Row-Based Cooling
The Liebert CRV, row-based cooling
unit is optimized to ensure maximum
cooling capacity in a minimal footprint.
Targeted for small and medium data
centers, as well as edge computing
locations the unit provides cooling at the
server rack level.
The Liebert CRV has been designed to
deliver the highest eiciency and
availability, by removing heated air from
the data center hot aisles, using it to
return cooled air to the servers (cold
aisle). The Liebert CRV is available in
Direct Expansion, as well as Chilled Water
versions and in two frame widths - 600
mm and a compact 300 mm. Providing
full capacity and airflow modulation to
match the servers' load, the unit is able to
deliver energy savings via its compressor
with capacity modulation, Electronic
Expansion Valve and variable speed EC
Fans. All this leads to very low operating
costs with maximum availability. The
Liebert CRV is a omprehensive row-based
solution that includes all of the main
functions fundamental to cooling units,
such as cooling, humidification,
dehumidification, re-heating, air filtration,
condensation management, temperature
and humidity control, alarm functions and
data communications.
Furthermore, the unit enhances its
performances and energy eiciency
through the Vertiv™ ICOM™ Control,
capable of optimizing unit operations by
leveraging on its intelligent management
of system components. All components
are easily accessible from the front and
the rear of the unit, granting simplified
service intervention.
The unit also allows ease of installation,
through simplified cable and pipes
routing from top and bottom of the unit.
10kW CRV DX
2
Page 3
Designed to Optimize IT Performance
The Liebert® CRV, row cooling unit
Thermal Management unit is ideal for
the cooling of data center rack rows
The Liebert CRV is a multi-option,
precision air conditioner that delivers
temperature and humidity control, as well
as filtration and notification management,
ensuring that data center temperatures
are maintained at an optimum level.
The unit is designed to continuously
monitor variations in heat loads and
instantly deliver the most eicient and
eective cooling necessary.
Liebert CRV: Simple, Safe, Adaptable
The Liebert CRV is a plug-and-play unit
with the capability of addressing the
needs of both open and contained
applications.
Cooling is provided at the server rack
level rather than the room level. The
Liebert CRV removes and filters hot air
from the data center aisles, using it to
return cooled air to the servers.
The integrated air diusers accurately
direct the airflow towards the necessary
direction of the heat load.
Furthermore, Liebert CRV is designed to
comply with mission-critical requirements
and ensure that servers are maintained
at the correct temperature and
humidity levels.
For low operational costs, the Liebert CRV
provides the exact level of cooling
required by servers, modulating the
airflow and cooling capacity.
The unit is available in two versions to
meet various installation demands:
y A stand-alone, direct expansion
y A chilled water system with up to 60
system with variable capacity up to
36kW, available in both 300 mm and
600 mm versions, complete with roof
or wall-mounted condenser
kW of capacity available in both 300
mm and 600 mm versions.
Features and
Performance
yUnits ranging from 10 to 60
kW with chilled water and
direct expansion versions
yIndustry's highest energy
saving levels achieved increase of up to 50% when
the Liebert CRV is combined
with Vertiv™ SmartAisle™
cold aisle containment
yBest-in-class Thermal
Management unit for rowbased applications
yOn-site adjustment capability
of air diuser distribution
direction maximizes cooling
results
yIntegrated Vertiv ICOM™
Control for management of
capacity and airflow through
EC Fans and variable capacity
Compressor
yIdeal for scalable IT
infrastructure - increased
cooling capacity, reduced noise
levels and enhanced eiciency
when compared with similar
chilled water and direct
expansion configurations.
3
Page 4
Vertiv™ Liebert® CRV from 10 to 60 kW
Ensuring Availability Under All Working Conditions
Maintaining IT Infrastructure
Availability
With integrated Vertiv™ ICOM™ Control,
the Liebert® CRV is able to monitor
variations in temperature and humidity,
instantly adapting its performance to
meet variations in load conditions.
This furthermore ensures increased
availability and safety of protected IT
equipment.
The Liebert CRV's constant temperature
monitoring and control capabilities
ensure the availability of servers in all
working conditions.
Furthermore, its parallel load sharing
functionality enables the management of
N+1 configurations.
Meeting Primary IT Requirements
The Liebert CRV's ability to modulate
capacity allows for constant, accurate
room temperature and humidity levels to
be maintained.
The variable capacity capability of the
Liebert CRV, contributes to increasing
data center availability during both
standard operations and in the event of
load variations.
A reduction in its start/stop cycling
function further contributes to increasing
data center availability, as well as
lengthening the life of critical
components.
Extreme Flexibility for Open and Closed Architectures
The integrated compressors with cooling
capacity modulation are designed to
avoid peaks in absorbed power, thus
reducing the stress placed on
components. The Liebert CRV uses a
dedicated control that also enables the
compressor to operate when the external
air temperature increases above
standard limits.
Suitable For a Wide Range of Installations
The Liebert® CRV addresses the cooling needs of both new and existing data center
space, regardless of raised floor availability. It is ideally suited to data centers with up to
50 racks, irrespective of heat load.
Configuration Flexibility
The Liebert CRV can be configured to perform temperature as well as humidity control.
The Liebert CRV 300 mm and 600 mm width versions have been designed to
specifically meet the requirements of data centers in need of optimizing space
occupancy, as well as capital and running costs.
The Ideal Airflow
EC Fans and compressors with variable
cooling capacity, managed through
integrated Vertiv™ ICOM™ Control,
achieve flexible capacity and airflow for
the ideal operating conditions of IT
equipment.
The Liebert CRV, designed using
advanced, computer-aided dynamic fluid
technology, delivers optimum air
distribution across rack installations. The
exceptional levels of air distribution have
been proven as a result of wide-scale
laboratory and field testing.
4
Page 5
Optimizing Total Cost of Ownership
Delivering Optimized Results
Ideally suited for rack-level cooling and specifically designed for high return air
temperatures, the Liebert CRV optimizes air distribution and maximizes eiciency,
delivering both cost and energy-related savings.
Eiciency is further enhanced through the use of the environmentally friendly R410A
refrigerant which ensures constant operation at the highest eiciency levels.
The Liebert CRV is also designed to optimize installation and minimize start up,
connection and labor investments. The unit is available for integration with existing racks
or as a bundled solution combined with racks, UPS and monitoring capabilities.
Customer Monitoring Interfaces
Monitoring and Control Through Existing Network Via your Web Browser
The Liebert® CRV system can be fitted with a Vertiv monitoring card allowing full
advantage to be taken of the Ethernet network and remote monitoring from your
computer desktop, network operations center or any network access simply utilizing a
standard web browser. A standard web browser, via HTTP protocol or Network
Management System software via SNMP protocol, can be used to access the
unit information.
Energy Eicient Cooling
The integrated Vertiv ICOM Control,
equipped with up to 10 rack temperature
sensors, continuously monitors the heat
load of the racks and regulates the
Liebert CRV, ensuring it provides the most
eective level of cooling while at the same
time delivering energy savings. Variable
capacity compressors modulate the
cooling capacity, thus reducing input
power with partial loads. EC Fan
technology regulates airflow and reduces
fan input power.
Monitoring Integration with
Existing Building Management
System
If required, by installing the optional
monitoring card, the Liebert CRV can be
monitored and controlled by an existing
Building Management System.
The monitoring card provides Modbus,
Bacnet and SNMP protocol support.
5
Page 6
Vertiv™ Liebert® CRV from 10 to 60 kW
Data Center Rooms and Edge Locations With Up to 10 Racks
The Liebert® CRV is installed in close proximity to servers for installations relating to network access cabinets and small computer
rooms, regardless of the presence of a raised floor. The cooling unit, equipped with ten temperature sensors, modulates the airflow to
match the real-time cooling requirements of the server.
Direct Expansion Solution
When a chilled water system and physical
building limitations restrict the installation
of chillers, a direct expansion solution is
the ideal choice.
In the event that internal and external
units are installed in close proximity,
direct expansion units are able to deliver
significant reductions in installationrelated time and costs. One of the
N° of Racks1 to 4
Scenario
1
Heat LoadUp to 20kW
SpaceFrom 5m2 and 15m
Raise Floor
Recommended SolutionDirect Expansion
-
advantages of the Liebert CRV with a
direct expansion solution is the
eco-friendly refrigerant R410A. The unit
also oers variable capacity compressor,
which has the capability of immediately
modulating and adapting its operation
according to server cooling requirements.
It significantly minimizes start/stop
cycling, extending the life cycle of your
cooling equipment. The Liebert CRV,
N° of RacksUp to 10
2
Scenario
2
Heat LoadUp to 100kW
SpaceUp to 30m
Raise Floor
Recommended SolutionDirect Expansion
operates with a significant return air
temperature, which contributes to
maximizing cooling capacity and
increasing eiciency without placing
additional stress on compressors.
2
-
6
Page 7
Data Center Rooms and Density Areas with up to 50 Racks
The Liebert® CRV's integration with Vertiv™ SmartAisleTM proves to be the ideal cold aisle containment approach for small data
centers requiring heat density increases. This solution has the added advantage of avoiding the installation of raised floors or
heightening roof levels. CRV is also very well suited for the installation of high-density areas in data centers.
Chilled Water Solution with Vertiv™
SmartAisle™
The Vertiv SmartAisle separates hot
returning air and cold supply air,
optimizing the entire cooling solution. By
increasing the room temperature, the
floor-mounted cooling units can be
significantly downsized, reducing the
overall level of investment. The higher
Energy Eiciency Ratio also improves
energy savings and dramatically reduces
running costs. The solution delivers the
best results when combined with the
Liebert HPC - maximizing the freecooling
eect and reducing running costs.
N° of Racks10 to 20
Scenario
3
Heat LoadUp to 200kW
SpaceUp to 50 m
Raise Floor
Recommended SolutionChilled Water
-
Combining the Liebert® CRV with
the Liebert HPC Freecooling Chiller
for Increased Advantages
Chilled water solutions are optimized to
reduce energy consumption:
• With the use of EC Fans and the unit’s
close proximity to the racks, the
Liebert CRV minimizes fan power
input and can be regulated based on
server load levels.
• As it is specifically designed for high
return air temperatures, the Liebert
CRV can operate at high chilled water
temperatures while maintaining
capacity, thus maximizing the chiller
freecooling eect.
N° of RacksUp to 50
2
Scenario
4
Heat LoadUp to 300kW
SpaceUp to 100m
Raise Floor
Recommended SolutionChilled Water
2
-
7
Page 8
Vertiv™ Liebert® CRV from 10 to 60 kW
Liebert® CRV Technical Data
DIRECT EXPANSION (DX) MODELSCHILLED WATER (CW) MODELS
Dimensions H x W x D[mm]2000x300x1100 (*)2000x600x11752000x300x1100 (*)2000x600x1175
Note: The pe rformanc es shown above refer to an air inlet tem perature of 38° C, condens ing temperatur e for air and water-gl ycol cooled u nits of 45°C and a c hilled water tem perature of 7/12°C . (*) Unit available also with a
2200 mm he ight and 1200 mm d epth.
y Levelling feet
y Filters with up to F5 filtration
class and clog filter switch
y Electrode humidifier
y Electric reheat 1-stage
y Internal condensate pump
y User Friendly Display
y Remote rack temperature sensors
y EC plug fans
y 3-way or 2-way valve with 0-10V
actuator
y Adjustable modular bale system
y Top / Bottom connections
y Levelling feet
y Filters with up to F5 filtration
class and clog filter switch
y Electrode humidifier
y Electric reheat 1-stage
y Internal condensate pump
y User Friendly Display
y Remote rack temperature sensors
y Monitoring card for WEB,
Modbus and BACnet
y Teamworking functionality
y Monitoring card for WEB,
Modbus and BACnet
y Teamworking functionality
D
W
Liebert® CRV 300 mm CW
DX Ve rsi onCW Ve rsion
y Additional remote rack
temperature sensors
y Compressor jacket (600mm models)
y Dual power supply with ATS on
ADDITIONAL OPTIONS
y Additional remote rack
temperature sensors
y Dual power supply with ATS
y Cooling Capacity Meter
selected models
y Optional extension frame for
height 2200 mm and depth 1200 mm
8
Page 9
Coupling Air Cooled Liebert CRV Units with Air Cooled Condensers
Model
CRD102
CR025RA
CR020RA
CR035RA
up to 35°C up to 40°C up to 45°C
CCD10CCD10CCD10
HCR33HCR43HCR51
HCR33HCR43HCR51
HCR51HCR51HCR76
Outdoor Temperature
Condensers Dimensions
WidthDepthHeightWeight
CCD10[mm] / [kg]74 51300100566
HCR33[mm] / [kg]1112134091075
HCR43[mm] / [kg]1112234091092
HCR51[mm] / [kg]1112234091093
HCR59[mm] / [kg]11122340910102
HCR76[mm] / [kg]11123340910136
Coupling Water/Glycol Cooled Liebert CRV Units with Drycoolers
Model
CR20RW
CR35RW
Ambient Temperature up to 30° CAmbient Temperature up to 35° CAmbient Temperature up to 40° C
Standard NoiseLow NoiseStandard NoiseLow NoiseStandard NoiseLow Noise
1 x ESM0181 x ELM0181 x EST0281 x ELM0271 x EST0501 x ELT047
1 x EST0281 x ELM0271 x EST0501 x ELT0551 x EST0701 x ELT065
Dry Cooler Dimensions
WidthDepthHeightWeight
ESM018[mm]2236820103082
EST028[mm]286612501070133
EST050[mm]286612501070193
EST070[mm]406612501070283
ELM018[mm]2236820103094
ELM027[mm]31368201030139
ELT 047[mm]406612501070225
ELT 05 5[mm]406612501070254
ELT 06 5[mm]526612501070302
Chilled Water Cooling
Chilled water cooling units may be coupled with Vertiv™ chillers (Liebert
HPC or Liebert AFC series). The Liebert HPC chiller series oers a wide
range of air cooled or water cooled solutions. Available with various noise
thresholds and with freecooling modes, these units significantly enhance
the system's energy saving capabilities. Liebert HPC freecooling chillers
are available from 40 kW to 1600 kW. The Liebert AFC, Adiabatic
Freecooling Chillers, are available from 500 kW to 1700 kW and are
designed to maximize data center eiciency and availability.
9
Page 10
Vertiv™ Liebert® CRV from 10 to 60 kW
Thermal Management Data Center Infrastructure for Small and Large Applications
Liebert® HPC
Wide range of high eiciency Freecooling Chillers
from 40 kW to 1600 kW
• Designed specifically for data center applications
and to work with Vertiv™ SmartAisle™
• Premium energy eiciency version
• Unique control capabilities with the Vertiv
ICOM™ Control.
Liebert PDX
Liebert PCW
Available from 5-220 kW
• Premium energy
eiciency
• Eurovent certified
performance
• Unique control
capabilities with the
Vertiv ICOM Control
• Liebert® EconoPhase™
available for the direct
expansion system.
Vertiv™ Environet Alert
Liebert EFC
Indirect evaporative freecooling unit leveraging on data
center know-how. Available from 100 to 450 kW
• Unique control capabilities optimizing water and
energy costs
• Substantial reductions and savings in terms of
10
electrical infrastructure.
Vertiv™ Environet™ Alert provides industr y companies with critical facility monitoring sof tware
that is aordable and easy to use. This solution delivers superior monitoring, alerting, trending
and data organization capabilities for all types of companies, helping them protect and grow
their business. Customers get monitoring, alerting and trending at a price that’s right for
their business.
Page 11
Liebert AFC
The Adiabatic Freecooling Chiller available
from 500-1700 kW
• Integrated adiabatic pad system
• High freecooling capacity
• 100% compressor back up.
Vertiv SmartAisle™
• Aisle containment
• Provides highest energy
eiciency
• Works with any Liebert Thermal
Management unit.
Services
Vertiv supports entire critical
infrastructures with the largest
global service organization and an
extensive service oering,
enhancing network availability and
ensuring total peace of mind 24/7.
Our approach to servicing critical
infrastructure covers all aspects of
availability and performance: from
single power and thermal
management equipment to entire
mission-critical systems.
The most comprehensive insurance
for business protection can be
obtained with a service program
from Vertiv which includes access
to Vertiv LIFE™ Services.
Liebert CRV
Row-based high eiciency cooling units available
from 10-60 kW in DX and CW versions
• Full airflow and cooling capacity modulation to
match server load and to save energy
• Best footprint capacity with the highest eiciency
• Six dierent control modes to ensure
greater flexibility.
Liebert DCL
Closed loop rack cooling
• Two dierent architectures:
Closed Loop
Hybrid Loop
• Multiple combinations for up to 4 server racks
• Available as direct expansion or chilled water version
Vertiv™ Life™ Services
Vertiv LIFE Services provides
Remote Diagnostics and Preventive
Monitoring for UPS and thermal
management equipment.
Vertiv LIFE Services delivers
increased uptime and operational
eiciency by enabling continuous
monitoring of your equipment,
expert data analysis and field
engineering expertise.
Through the data transferred from
your equipment via Vertiv LIFE
Services, our Remote experts gain
the real-time insight and
information needed to quickly
identify, diagnose, and resolve any
irregularities that may arise in
operation, ultimately taking
responsibility for your critical
assets 24/7.