Vertiv Liebert CRV User manual

Page 1
Vertiv™ Liebert® CRV
from 10 to 60 kW
Eicient Cooling for IT Equipment
Page 2
Vertiv™ Liebert® CRV from 10 to 60 kW
Vertiv™
Vertiv designs, builds and services mission critical technologies that enable the vital applications for data centers, communication networks, and commercial and industrial environments. We support today's growing mobile and cloud computing markets with our portfolio of power, thermal, infrastructure management products, software and solutions, all complemented by our global service network. Bringing together global reach and local knowledge, and our decades-long heritage including brands like Chloride®, Liebert® and NetSure™, our team of experts is ready to take on your most complex challenges, creating solutions that keep your systems running—and your business moving. Together, we’re building the future of a world where critical technologies always work.
YOUR VISION, OUR PASSION.
Vertiv.com
Liebert® CRV Row-Based Cooling
The Liebert CRV, row-based cooling
unit is optimized to ensure maximum cooling capacity in a minimal footprint. Targeted for small and medium data centers, as well as edge computing locations the unit provides cooling at the server rack level.
The Liebert CRV has been designed to deliver the highest eiciency and availability, by removing heated air from the data center hot aisles, using it to return cooled air to the servers (cold aisle). The Liebert CRV is available in Direct Expansion, as well as Chilled Water versions and in two frame widths - 600 mm and a compact 300 mm. Providing full capacity and airflow modulation to match the servers' load, the unit is able to deliver energy savings via its compressor with capacity modulation, Electronic Expansion Valve and variable speed EC Fans. All this leads to very low operating
costs with maximum availability. The Liebert CRV is a omprehensive row-based solution that includes all of the main functions fundamental to cooling units, such as cooling, humidification, dehumidification, re-heating, air filtration, condensation management, temperature and humidity control, alarm functions and data communications.
Furthermore, the unit enhances its performances and energy eiciency through the Vertiv™ ICOM™ Control, capable of optimizing unit operations by leveraging on its intelligent management of system components. All components are easily accessible from the front and the rear of the unit, granting simplified service intervention.
The unit also allows ease of installation, through simplified cable and pipes routing from top and bottom of the unit.
10kW CRV DX
2
Page 3
Designed to Optimize IT Performance
The Liebert® CRV, row cooling unit Thermal Management unit is ideal for the cooling of data center rack rows
The Liebert CRV is a multi-option, precision air conditioner that delivers temperature and humidity control, as well as filtration and notification management, ensuring that data center temperatures are maintained at an optimum level.
The unit is designed to continuously monitor variations in heat loads and instantly deliver the most eicient and eective cooling necessary.
Liebert CRV: Simple, Safe, Adaptable
The Liebert CRV is a plug-and-play unit with the capability of addressing the needs of both open and contained applications.
Cooling is provided at the server rack level rather than the room level. The Liebert CRV removes and filters hot air from the data center aisles, using it to return cooled air to the servers.
The integrated air diusers accurately direct the airflow towards the necessary direction of the heat load.
Furthermore, Liebert CRV is designed to comply with mission-critical requirements and ensure that servers are maintained at the correct temperature and humidity levels.
For low operational costs, the Liebert CRV provides the exact level of cooling required by servers, modulating the airflow and cooling capacity.
The unit is available in two versions to meet various installation demands:
y A stand-alone, direct expansion
y A chilled water system with up to 60
system with variable capacity up to 36kW, available in both 300 mm and 600 mm versions, complete with roof or wall-mounted condenser
kW of capacity available in both 300 mm and 600 mm versions.
Features and Performance
y Units ranging from 10 to 60
kW with chilled water and direct expansion versions
y Industry's highest energy
saving levels achieved ­increase of up to 50% when the Liebert CRV is combined with Vertiv™ SmartAisle™ cold aisle containment
y Best-in-class Thermal
Management unit for row­based applications
y On-site adjustment capability
of air diuser distribution direction maximizes cooling results
y Integrated Vertiv ICOM™
Control for management of capacity and airflow through EC Fans and variable capacity Compressor
y Ideal for scalable IT
infrastructure - increased cooling capacity, reduced noise levels and enhanced eiciency when compared with similar chilled water and direct expansion configurations.
3
Page 4
Vertiv™ Liebert® CRV from 10 to 60 kW
Ensuring Availability Under All Working Conditions
Maintaining IT Infrastructure Availability
With integrated Vertiv™ ICOM™ Control, the Liebert® CRV is able to monitor variations in temperature and humidity, instantly adapting its performance to meet variations in load conditions.
This furthermore ensures increased availability and safety of protected IT equipment.
The Liebert CRV's constant temperature monitoring and control capabilities ensure the availability of servers in all working conditions.
Furthermore, its parallel load sharing functionality enables the management of N+1 configurations.
Meeting Primary IT Requirements
The Liebert CRV's ability to modulate capacity allows for constant, accurate room temperature and humidity levels to be maintained.
The variable capacity capability of the Liebert CRV, contributes to increasing data center availability during both standard operations and in the event of load variations.
A reduction in its start/stop cycling function further contributes to increasing data center availability, as well as lengthening the life of critical components.
Extreme Flexibility for Open and Closed Architectures
The integrated compressors with cooling capacity modulation are designed to avoid peaks in absorbed power, thus reducing the stress placed on components. The Liebert CRV uses a dedicated control that also enables the compressor to operate when the external air temperature increases above standard limits.
Suitable For a Wide Range of Installations
The Liebert® CRV addresses the cooling needs of both new and existing data center space, regardless of raised floor availability. It is ideally suited to data centers with up to 50 racks, irrespective of heat load.
Configuration Flexibility
The Liebert CRV can be configured to perform temperature as well as humidity control. The Liebert CRV 300 mm and 600 mm width versions have been designed to specifically meet the requirements of data centers in need of optimizing space occupancy, as well as capital and running costs.
The Ideal Airflow
EC Fans and compressors with variable cooling capacity, managed through integrated Vertiv™ ICOM™ Control, achieve flexible capacity and airflow for the ideal operating conditions of IT equipment.
The Liebert CRV, designed using advanced, computer-aided dynamic fluid technology, delivers optimum air distribution across rack installations. The exceptional levels of air distribution have been proven as a result of wide-scale laboratory and field testing.
4
Page 5
Optimizing Total Cost of Ownership
Delivering Optimized Results
Ideally suited for rack-level cooling and specifically designed for high return air temperatures, the Liebert CRV optimizes air distribution and maximizes eiciency, delivering both cost and energy-related savings.
Eiciency is further enhanced through the use of the environmentally friendly R410A refrigerant which ensures constant operation at the highest eiciency levels.
The Liebert CRV is also designed to optimize installation and minimize start up, connection and labor investments. The unit is available for integration with existing racks or as a bundled solution combined with racks, UPS and monitoring capabilities.
Customer Monitoring Interfaces
Monitoring and Control Through Existing Network Via your Web Browser
The Liebert® CRV system can be fitted with a Vertiv monitoring card allowing full advantage to be taken of the Ethernet network and remote monitoring from your computer desktop, network operations center or any network access simply utilizing a standard web browser. A standard web browser, via HTTP protocol or Network Management System software via SNMP protocol, can be used to access the unit information.
Energy Eicient Cooling
The integrated Vertiv ICOM Control, equipped with up to 10 rack temperature sensors, continuously monitors the heat load of the racks and regulates the Liebert CRV, ensuring it provides the most eective level of cooling while at the same time delivering energy savings. Variable capacity compressors modulate the cooling capacity, thus reducing input power with partial loads. EC Fan technology regulates airflow and reduces fan input power.
Monitoring Integration with Existing Building Management System
If required, by installing the optional monitoring card, the Liebert CRV can be monitored and controlled by an existing Building Management System. The monitoring card provides Modbus, Bacnet and SNMP protocol support.
5
Page 6
Vertiv™ Liebert® CRV from 10 to 60 kW
Data Center Rooms and Edge Locations With Up to 10 Racks
The Liebert® CRV is installed in close proximity to servers for installations relating to network access cabinets and small computer rooms, regardless of the presence of a raised floor. The cooling unit, equipped with ten temperature sensors, modulates the airflow to match the real-time cooling requirements of the server.
Direct Expansion Solution
When a chilled water system and physical building limitations restrict the installation of chillers, a direct expansion solution is the ideal choice.
In the event that internal and external units are installed in close proximity, direct expansion units are able to deliver significant reductions in installation­related time and costs. One of the
N° of Racks 1 to 4
Scenario
1
Heat Load Up to 20kW
Space From 5m2 and 15m
Raise Floor
Recommended Solution Direct Expansion
-
advantages of the Liebert CRV with a direct expansion solution is the eco-friendly refrigerant R410A. The unit also oers variable capacity compressor, which has the capability of immediately modulating and adapting its operation according to server cooling requirements. It significantly minimizes start/stop cycling, extending the life cycle of your cooling equipment. The Liebert CRV,
N° of Racks Up to 10
2
Scenario
2
Heat Load Up to 100kW
Space Up to 30m
Raise Floor
Recommended Solution Direct Expansion
operates with a significant return air temperature, which contributes to maximizing cooling capacity and increasing eiciency without placing additional stress on compressors.
2
-
6
Page 7
Data Center Rooms and Density Areas with up to 50 Racks
The Liebert® CRV's integration with Vertiv™ SmartAisleTM proves to be the ideal cold aisle containment approach for small data centers requiring heat density increases. This solution has the added advantage of avoiding the installation of raised floors or heightening roof levels. CRV is also very well suited for the installation of high-density areas in data centers.
Chilled Water Solution with Vertiv™ SmartAisle™
The Vertiv SmartAisle separates hot returning air and cold supply air, optimizing the entire cooling solution. By increasing the room temperature, the floor-mounted cooling units can be significantly downsized, reducing the overall level of investment. The higher Energy Eiciency Ratio also improves energy savings and dramatically reduces running costs. The solution delivers the best results when combined with the Liebert HPC - maximizing the freecooling eect and reducing running costs.
N° of Racks 10 to 20
Scenario
3
Heat Load Up to 200kW
Space Up to 50 m
Raise Floor
Recommended Solution Chilled Water
-
Combining the Liebert® CRV with the Liebert HPC Freecooling Chiller for Increased Advantages
Chilled water solutions are optimized to reduce energy consumption:
With the use of EC Fans and the unit’s
close proximity to the racks, the Liebert CRV minimizes fan power input and can be regulated based on server load levels.
As it is specifically designed for high
return air temperatures, the Liebert CRV can operate at high chilled water temperatures while maintaining capacity, thus maximizing the chiller freecooling eect.
N° of Racks Up to 50
2
Scenario
4
Heat Load Up to 300kW
Space Up to 100m
Raise Floor
Recommended Solution Chilled Water
2
-
7
Page 8
Vertiv™ Liebert® CRV from 10 to 60 kW
Liebert® CRV Technical Data
DIRECT EXPANSION (DX) MODELS CHILLED WATER (CW) MODELS
CRD10 CR025RA CR020RA/W CR035RA/W CR030RC CR052 CR060RC CR040 CR050
Net Sensible Cooling Capacity [kW] 11.9 22.5 24.2 37.7 39.2 54.0 57. 0 46.6 57. 9
Nominal Airflow m3/h 3200 4000 4170 5540 5900 7200 7758 5650 7410
Weight [kg] 220 260 335 / 350 365 / 385 180 230 230 330 365
Humidity Control No Yes Ye s Yes Ye s No Ye s Yes No
Dimensions H x W x D [mm] 2000x300x1100 (*) 2000x600x1175 2000x300x1100 (*) 2000x600x1175
Note: The pe rformanc es shown above refer to an air inlet tem perature of 38° C, condens ing temperatur e for air and water-gl ycol cooled u nits of 45°C and a c hilled water tem perature of 7/12°C . (*) Unit available also with a 2200 mm he ight and 1200 mm d epth.
STANDARD FEATURES AND OPTIONS
DX Ve rsi on CW Ve rsion
y High Eiciency Scroll/Rotary
Compressor with Capacity
Modulation
y Electronic expansion valvey EC plug fansy R410A Refrigeranty Adjustable modular bale systemy Top/Bottom connections
H
y Levelling feety Filters with up to F5 filtration
class and clog filter switch
y Electrode humidifiery Electric reheat 1-stagey Internal condensate pumpy User Friendly Displayy Remote rack temperature sensors
y EC plug fansy 3-way or 2-way valve with 0-10V
actuator
y Adjustable modular bale systemy Top / Bottom connectionsy Levelling feety Filters with up to F5 filtration
class and clog filter switch
y Electrode humidifiery Electric reheat 1-stagey Internal condensate pumpy User Friendly Displayy Remote rack temperature sensorsy Monitoring card for WEB,
Modbus and BACnet
y Teamworking functionality
y Monitoring card for WEB,
Modbus and BACnet
y Teamworking functionality
D
W
Liebert® CRV 300 mm CW
DX Ve rsi on CW Ve rsion
y Additional remote rack
temperature sensors
y Compressor jacket (600mm models)y Dual power supply with ATS on
ADDITIONAL OPTIONS
y Additional remote rack
temperature sensors
y Dual power supply with ATSy Cooling Capacity Meter
selected models
y Optional extension frame for
height 2200 mm and depth 1200 mm
8
Page 9
Coupling Air Cooled Liebert CRV Units with Air Cooled Condensers
Model
CRD102
CR025RA
CR020RA
CR035RA
up to 35°C up to 40°C up to 45°C
CCD10 CCD10 CCD10
HCR33 HCR43 HCR51
HCR33 HCR43 HCR51
HCR51 HCR51 HCR76
Outdoor Temperature
Condensers Dimensions
Width Depth Height Weight
CCD10 [mm] / [kg] 74 5 1300 1005 66
HCR33 [mm] / [kg] 1112 1340 910 75
HCR43 [mm] / [kg] 1112 2340 910 92
HCR51 [mm] / [kg] 1112 2340 910 93
HCR59 [mm] / [kg] 1112 2340 910 102
HCR76 [mm] / [kg] 1112 3340 910 136
Coupling Water/Glycol Cooled Liebert CRV Units with Drycoolers
Model
CR20RW
CR35RW
Ambient Temperature up to 30° C Ambient Temperature up to 35° C Ambient Temperature up to 40° C
Standard Noise Low Noise Standard Noise Low Noise Standard Noise Low Noise
1 x ESM018 1 x ELM018 1 x EST028 1 x ELM027 1 x EST050 1 x ELT047
1 x EST028 1 x ELM027 1 x EST050 1 x ELT055 1 x EST070 1 x ELT065
Dry Cooler Dimensions
Width Depth Height Weight
ESM018 [mm] 2236 820 1030 82
EST028 [mm] 2866 1250 1070 133
EST050 [mm] 2866 1250 1070 193
EST070 [mm] 4066 1250 1070 283
ELM018 [mm] 2236 820 1030 94
ELM027 [mm] 3136 820 1030 139
ELT 047 [mm] 4066 1250 1070 225
ELT 05 5 [mm] 4066 1250 1070 254
ELT 06 5 [mm] 5266 1250 1070 302
Chilled Water Cooling
Chilled water cooling units may be coupled with Vertiv™ chillers (Liebert HPC or Liebert AFC series). The Liebert HPC chiller series oers a wide range of air cooled or water cooled solutions. Available with various noise thresholds and with freecooling modes, these units significantly enhance the system's energy saving capabilities. Liebert HPC freecooling chillers are available from 40 kW to 1600 kW. The Liebert AFC, Adiabatic Freecooling Chillers, are available from 500 kW to 1700 kW and are designed to maximize data center eiciency and availability.
9
Page 10
Vertiv™ Liebert® CRV from 10 to 60 kW
Thermal Management Data Center Infrastructure for Small and Large Applications
Liebert® HPC
Wide range of high eiciency Freecooling Chillers from 40 kW to 1600 kW
Designed specifically for data center applications
and to work with Vertiv™ SmartAisle™
Premium energy eiciency version
Unique control capabilities with the Vertiv
ICOM™ Control.
Liebert PDX Liebert PCW
Available from 5-220 kW
Premium energy
eiciency
Eurovent certified
performance
Unique control
capabilities with the Vertiv ICOM Control
Liebert® EconoPhase™
available for the direct expansion system.
Vertiv™ Environet Alert
Liebert EFC
Indirect evaporative freecooling unit leveraging on data center know-how. Available from 100 to 450 kW
Unique control capabilities optimizing water and
energy costs
Substantial reductions and savings in terms of
10
electrical infrastructure.
Vertiv™ Environet™ Alert provides industr y companies with critical facility monitoring sof tware that is aordable and easy to use. This solution delivers superior monitoring, alerting, trending and data organization capabilities for all types of companies, helping them protect and grow their business. Customers get monitoring, alerting and trending at a price that’s right for their business.
Page 11
Liebert AFC
The Adiabatic Freecooling Chiller available from 500-1700 kW
Integrated adiabatic pad system
High freecooling capacity
100% compressor back up.
Vertiv SmartAisle™
Aisle containment
Provides highest energy
eiciency
Works with any Liebert Thermal
Management unit.
Services
Vertiv supports entire critical
infrastructures with the largest global service organization and an extensive service oering, enhancing network availability and ensuring total peace of mind 24/7.
Our approach to servicing critical
infrastructure covers all aspects of availability and performance: from single power and thermal management equipment to entire mission-critical systems.
The most comprehensive insurance
for business protection can be obtained with a service program from Vertiv which includes access to Vertiv LIFE™ Services.
Liebert CRV
Row-based high eiciency cooling units available from 10-60 kW in DX and CW versions
Full airflow and cooling capacity modulation to
match server load and to save energy
Best footprint capacity with the highest eiciency
Six dierent control modes to ensure
greater flexibility.
Liebert DCL
Closed loop rack cooling
Two dierent architectures:
Closed Loop Hybrid Loop
Multiple combinations for up to 4 server racks
Available as direct expansion or chilled water version
Vertiv™ Life™ Services
Vertiv LIFE Services provides
Remote Diagnostics and Preventive Monitoring for UPS and thermal management equipment.
Vertiv LIFE Services delivers
increased uptime and operational eiciency by enabling continuous monitoring of your equipment, expert data analysis and field engineering expertise.
Through the data transferred from
your equipment via Vertiv LIFE Services, our Remote experts gain the real-time insight and information needed to quickly identify, diagnose, and resolve any irregularities that may arise in operation, ultimately taking responsibility for your critical assets 24/7.
11
Page 12
Vertiv.com | Vertiv Headquarters, 1050 Dearborn Drive, Columbus, OH, 43085, USA
© 2021 Vertiv G roup Corp. All right s reserved. Verti v™ and the Vertiv logo are tr ademarks or regis tered trademarks o f Vertiv Group Corp. Al l other names and log os referred to are trad e names, tradema rks or registered tr ademarks of their res pective owners . While every precauti on has been taken to en sure accuracy and c ompleteness he re, Vertiv Group Cor p. assumes no resp onsibility, and dis claims all liabili ty, for damages resu lting from use of this inf ormation or for any erro rs or omissions . Specificatio ns, rebates and oth er promotional oers are su bject to change at Ver tiv’s sole discret ion upon notice.
MKA4L0UKCRV (R01/21)