CURRENT MONITORING
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
• Follow safe electrical work practices.
See NFPA 70E in the USA, or applicable local codes.
• This equipment must only be installed and serviced by qualified electrical personnel.
• Read, understand and follow the instructions before installing this product.
• Turn off all power supplying equipment before working on or inside the equipment.
• Use a properly rated voltage sensing device to confirm power is off.
DO NOT DEPEND ON THIS PRODUCT FOR VOLTAGE INDICATION
• Only install this product on insulated conductors.
Failure to follow these instructions will result in death or serious injury.
DANGER
NOTICE
• This product is not intended for life or safety applications.
• Do not install this product in hazardous or classified locations.
• The installer is responsible for conformance to all applicable codes.
• Mount this product inside a suitable fire and electrical enclosure.
0.2” x 0.15”
slot (2x)
1.1"
(27 mm)
2.8"
(68 mm)
0.7" Dia
(19 mm)
0.9"
(23 mm)
3.0"
(75 mm)
Removable/Adjustable Mounting Bracket
3.8"
(95 mm)
4.2"
(106 mm)
Fan or Pump
CONTROL LER
0-5VDC
COMM
+
–
AI
VERIS INDUSTRIES
Portland, Oregon 97223
1-800-354-8556
CONT ACTOR
Insu lated Conduc tor Onl y
INSTALLATION GUIDE
H722LC 722LC
Solid-Core Current Transducer,
0-5VDC Output
Installer’s Specifications
Amperage Range 0-10/20/40 Amps (slide switch selec table)
Sensor Power Induced from monitored conductor
Insulation Class 600VAC RMS (UL), 300VAC RMS (CE)
Frequency 50/60Hz
Temperature Range -15° to 60°C (5° to 140°F)
Humidity Range 10-90% RH, non-condensing
Accuracy ±2% FS from 10% - 100% of selected r ange
Response Time 2 sec.
Terminal Block Maximum Wire Size 14 AWG
Terminal Block Torque (nominal) 4 in-lbs (0.45 N-m)
Agency Approvals UL 508 open device listing
CE: EN61010-1:2001-2, CAT III, deg. 2, basic insulation
quick install
Wiring ExamplE
Z202943-0A PAGE 1 ©2008 Veris Industries USA 800.354.8556 or +1(0)503.598.4564 / support@veris.com 09083
Alta Labs, Enercep t, Enspector, Hawkeye, Trustat, Veris, and the Veris ‘ V’ logo are trademark s or registered tradema rks of Veris Industries, L.L .C. in the USA and/or othe r countries.
Disconnect and lock out power.1.
Install the mounting bracket to the back of the electrical enclosure, no closer than 2.
½” (12mm) to an uninsulated conductor.
Slide the conductor to be monitored through the sensing hole of the current 3.
switch. Terminate the conductor. See Notes (page 2) for currents under 1 Amp or
above 40 Amp.
Set the desired amperage range on the H722LC (10, 20, or 40 Amps).4.
Wire the output connec tions between the H722LC and the controller (0-5VDC).5.
Reconnect power.6.
Scale the controller software to match the H722LC’s output.7.
DimEnsions
H722LC
SENSED AMPS
Selected Range*
0 VDC
0A
5 VDC
SENSOR OUTPUT
*Factory calibrated ranges selected
with the amperage range switch
DDC
CONTROLLER
AI
COMM
0-5VDC Input
CAUTION: Consult
instructions prior
to installation
!
Use min. 75º C insulated conductor
ig20
AMPERAGE
RANGE
40
20
10
OUTPUT
0-10VDC
+
–
+
–
Self-Powered Output
Amperage Range
Selector Switch
INSTALLATION GUIDE
opEration
The H722LC is a current transducer that senses current (amperage) in any of three
field-selectable ranges: 0-10, 0-20, or 0-40 amperes. These ranges represent the
maximum current that can be applied to the monitored conductor. The H722LC
transforms the monitored current into a 0-5VDC output suitable for connection to
building controllers or other appropriate data acquisition equipment. The H7 22LC
requires no external power to generate its output.
notEs
For load currents greater than sensor maximum rating:
Use a 5 Amp (H681x series) Current Transformer (CT) as shown.
> 40A (H722LC max.)
H681x-5A CT
Wiring
calibration/scaling
Set the amperage range selector switch to a level appropriate for your load. The
H723LC is available with three choices, 0-10, 0-20, or 0-40 Amps.
DANGER: 5A CTs can present hazardous voltages.
Install CTs in accordance with manufacturer's instructions.
Terminate the CT secondary before applying current.
RISK OF EQUIPMENT DAMAGE
• Derate the product’s maximum current for the number of
turns through the sensing window using the following
formula.
Rated Max. Amps ÷ Number of Turns = Max. monitored Amps
e.g. : 30A ÷ 4 Turns = 7.5 Amps max. in monitored conductor
Failure to follow these instructions can result in overheating
and permanent equipment damage.
For load currents less than sensor minimum rating:
Wrap the monitored conductor through the center hole and around the sensor body
to produce multiple turns through the "window." This increases the current measured
by the transducer.
• Controller must be
programmed to account
for the extra turns. e.g., if
four turns pass through
the sensor (as shown) the
normal controller reading
must be divided by 4.
Z202943-0A PAGE 2 ©2008 Veris Industries USA 800.354.8556 or +1(0)503.598.4564 / support@veris.com 09083
Alta Labs, Enercep t, Enspector, Hawkeye, Trustat, Veris, and the Veris ‘ V’ logo are trademark s or registered tradema rks of Veris Industries, L.L .C. in the USA and/or othe r countries.
CAUTION
Scale the output as shown below.
troublEshooting
Problem Solution
No Reading at Controller • Conrm measured current is within the selected
range on the product.
• Check polarity of sensor output connections.