Veris H721 Datasheet

H721 SERIES & H921
VERIS INDUSTRIES
Current Sensors: 4-20mA Analog Output
Load Trending With 4-20mA Output
The Hawkeye 721LC, 721HC, and 921 provide accurate load trending information with a proportional 4-20mA output signal. Preset slide-switches provide easy eld setup of sensed amperage range with no need for jumpers.
APPLICATIONS
Load trending
Motor control
Fan/Pump Status
EXAMPLE LINEAR OUTPUT
Scale software as shown
current monitoring
20mA
TM
H921
H721H C
FEATURES
Power the sensor, and receive the signal with only two wires...lower cabling
and commissioning costs than with traditional 3-wire sensors
Self-gripping split-core for fast retrot installation...no need to remove
conductor (H921)
Economical solid-core features adjustable bracket for easy alignment (H721)
Factory calibrated switch-selectable ranges for high resolution and
installation ease
Three eld-selec table ranges per unit...fewer versions to choose from, stock,
and install
Removable mounting bracket for installation exibility
Bracket on H921 can be installed in three dierent congurations...
added exibility
100% solid state, no moving parts to fail
5-year warranty
SENSOR OUTPUT
4mA
0A
SENSED AMPS
*Factory calibrated ranges selected
with the amperage range switch
SPECIFICATIONS
Sensor Power 30mA (max)@12-30VDC Insulation Class 600VAC RMS (UL), 300VAC RMS (CE) Frequency 50/60 Hz Temperature Range -15° to 60°C (5° to 140°F) Humidity Range 10-90% RH non-condensing Accurac y ±2% F.S. from 10% to 100% of selec ted range, but not less than ±0.4A Response Time 2 sec. Terminal Block Wire Size 24-14 AWG (0.2 to 2.1 mm2) Terminal Block Torque 3.5 to 4.4 in-lbs (0.4 to 0.5 N-m) Agency Approvals UL 508 open device listing; CE: EN61010-1:2001-2, CAT III, pollution degree 2, basic insulation
5
Year
Warranty
Selected Range*
Maximize Reliability
Minimize Installed Cost
For applications requiring double or reinforced insulation, please contact the factory.
800.354.8556
+1 503.598.4564
www.veris.com
HQ00 01762.B 01131
800.354.8556
+1 503.598.4564
DIMENSIONAL DRAWINGS
www.veris.com
H721LC/H721HC
Removable/Adjustable Mounting Bracket
0.9"
 0.7"
(19 mm)
4.2"
(106 mm)
2.8"
(68 mm)
3.8"
(95 mm)
0.2” x 0.15” slot (2x)
* Terminal block may extend up to 1/8” over the height dimensions shown. ** Slide switch may extend up to 1/4” over the height dimensions shown.
(23 mm)
APPLICATION/WIRING DIAGRAM
Monitoring Fan /Pump Motors for Positive Proof of Flow
3.0" **
(75 mm)
1.1" *
(27 mm)
**3.1”
(79 mm)
Ø 0.3”
(8 mm)
Removable Mounting Bracket
1.1”
(26 mm)
(21 mm)
(70 mm)
3.0”
(76 mm)
H921
0.8”
2.8”
2.5”
(64 mm)
1.0”
(25 mm)
Bracket can be mounted on three sides for added installation exibility.
Self-gripping Iris
1.4”*
(36 mm)
CONTACTOR
DDC CONTROLLER
AI
Fan or Pump
Motor
ORDERING INFORMATION
E2124 45 E1504 62
MODEL AMPERAGE RANGE SENSOR OUTPUT HOUSING UL CE
H721LC 0 - 10/20/40A
H721HC 0 - 50/100/200A Solid-Core
H921 0 - 30/60/120A Split-Core
4-20mA DC
Solid-Core
n n
n n
n
current monitoring
1
Listed for use on 75°C insulated conductors.
1
n
Note: For 10-80 Hz applications, see the H720 VFD sensor.
ACCESSORIES
DIN Rail Clip Set (AH01) DIN Rail (AV01) and DIN Stop Clip (AV02)
HQ00 01762.B 01131
AH01
AV02
AV01
Loading...