TM
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
• Follow safe electrical work practices.
See NFPA 70E in the USA, or applicable local codes.
• This equipment must only be installed and serviced by qualified electrical personnel.
• Read, understand and follow the instructions before installing this product.
• Turn off all power supplying equipment before working on or inside the equipment.
• Use a properly rated voltage sensing device to confirm power is off.
DO NOT DEPEND ON THIS PRODUCT FOR VOLTAGE INDICATION
• Only install this product on insulated conductors.
Failure to follow these instructions will result in death or serious injury.
DANGER
CURRENT MONITORING
INSTALLATION GUIDE
H709
TM
709
Solid-Core Current Switch, Adjustable Trip Point
Installer’s Specifications
Amperage Range 1-135 A Continuous*
External Supply Voltage Induced from monitored conductor
Frequency 50/60 H z
Insulation Class 600 VAC RMS (UL)
Temperature Range -15° to 60 °C (5° to 140°F)
Humidity Range 10-90% RH non-condensing
Hysteresis 10% typical
Status Output Ratings N.O. 0.2 A@120 VAC/DC
On-State Resistance (max.) 20 Ω
O-S tate Resistance (min.) 1 MΩ
Terminal Block Max. Wire Size 14 AWG
Terminal Block Torque (nom.) 4 in-lbs (0.45 N-m)
Agency Approvals UL 508, E150462
The unit design provides for b asic insulation only.
* When operating at 50 Hz, low threshold may be 1.2A.
INSTALLATION
Disconnect and lock out power to the enclosure containing the
conductor to be monitored.
1. Locate a mounting surface for the removable mounting bracket that will allow
the monitored conductor to pass through the center window when it is installed
and that will keep the product at least 1/2” from any uninsulated conductors.
Determine cable routing for the controller connection, allowing wiring to reach
the mounting location.
NOTICE
• This product is not intended for life or safety applications.
• Do not install this product in hazardous or classified locations.
• The installer is responsible for conformance to all applicable codes.
• Mount this product inside a suitable fire and electrical enclosure.
WIRING EXAMPLE
Insulated Conductor Only
CONTACTOR
DDC CONTROLLER
DI
Z201485-0B PAGE 1 ©2012 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com 01121
Alta Labs, Enercep t, Enspector, Hawkeye, Trustat, Veris, and the Veris ‘ V’ logo are trademark s or registered tradema rks of Veris Industries, L.L .C. in the USA and /or other countri es.
Motor
Fan or Pump
2. Drill holes to mount the bracket to the chosen surface using the included screws.
3. Wire the output connections between the sensor and the controller (solid-state
contact).
4. Route the conductor through the sensor’s center window and slip the assembly
into the mounting bracket.
5. Calibrate the sensor (see page 2) with the load running normally.
6. Secure enclosure and reconnect power.
DIMENSIONS
0.2” x 0.15”
slot (2x)
Removable/Adjustable Mounting Bracket
0.7"
(19 mm)
2.8"
(68 mm)
(106 mm)
3.8"
(95 mm)
4.2"
0.9"
(23 mm)
3.0"
(75 mm)
1.1"
(27 mm)
TM
H709
INSTALLATION GUIDE
OPERATION
The H709 is a current-sensitive switching device that monitors current (amperage) in
the conductor passing through it. A change in the conductor’s amperage that crosses
the adjustable switch threshold plus the hysteresis value causes the resistance of
the FET status output to change state, similar to the action of a mechanical switch.
In this model, the setpoint is adjustable through the action of a twenty (20) turn
potentiometer (see the CALIBRATION section). The status output is suitable for
connection to building controllers or other appropriate data acquisition equipment
operating at up to 120 volts. The H709 requires no ex ternal power supply to generate
its output.
NOTES
For load currents greater than sensor maximum rating:
Use a 5 Amp (H68xx series) Current Transformer (CT) as shown. This technique can be
combined with wrapping (see below) to add range for a low current load on a high
current source.
> 135 A (Sensor max.)
240A
300A:
5A
H68xx-5A CT
DANGER: 5A CTs can present hazardous voltages.
Install CTs in accordance with manufacturer's instructions.
Terminate the CT secondary before applying current.
CAUTION
RISK OF EQUIPMENT DAMAGE
• Derate the product’s maximum current for the number of turns
through the sensing window using the following formula.
Rated Max. Amps ÷ Number of Turns = Max. monitored Amps
e.g. : 100A ÷ 4 Turns = 25 Amps max. in monitored conductor
• Failure to follow these instructions can result in overheating
and permanent equipment damage.
For load currents less than sensor minimum rating:
Wrap the monitored conductor through the center window and around the sensor
body to produce multiple turns. This increases the current measured by the
transducer.
< 1 A (Sensor Min.)
4x
0.5A
CALIBRATION
Before beginning calibration, establish normal load conditions.
OK!
A
OK!
Then choose either A or B below.
A. To monitor under-current (belt loss, coupling shear, status)
Status
Open
Setpoint
1/4
STATUS
OK!
Setpoint
STOP
3.Turn the screw an
additional 1/4 turn
counter-clockwise for
operational margin.
!
OK!
A
1. Turn setpoint screw
clockwise until Status Open
LED turns ON.
2. Slowly turn the screw counter-clockwise until the Status Closed LED just
turns ON.
Setpoint
Status
Closed
+
STOP
B. To monitor over-current (mechanical problems, seized impeller)
Setpoint
1/4
STATUS
OK!
STOP
3. Turn the
setpoint screw
an additional 1/4
turn clockwise
for operational
margin.
!
OK!
A
1. Turn setpoint screw
counter-clockwise until Status
Setpoint
Status
Closed
Closed LED turns on.
2. Slowly turn the setpoint screw clockwise until the Status Open LED
just turns on.
Status
Setpoint
Open
+
STOP
TROUBLESHOOTING
Problem Solution
No Reading at Controller • Check sensor calibration (see above)
• Check for control voltage at sensor (<120 VAC/DC, <0.2 A)
• Check for amperage in monitored conductor (>1 A)
Setpoint screw has no
stops
Both LEDs are lit Setpoint screw is too far clockwise. See solution above.
The setpoint screw has a slip-clutch at both ends of its travel to
avoid damage. Twenty turns CCW will reset the sensor to be
most sensitive. Repeat calibration above.
Z201485-0B PAGE 2 ©2012 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com 01121
Alta Labs, Enercep t, Enspector, Hawkeye, Trustat, Veris, and the Veris ‘ V’ logo are trademark s or registered tradema rks of Veris Industries, L.L .C. in the USA and /or other countri es.