Current Switches: Adjustable Trip Point
Detect Belt Loss, Coupling Shear, And Mechanical Failure
DESCRIPTION
Hx08 Series and H701 adjustable current switches oer high performance, with a wide array of amperage range options. These products can accurately detect belt loss, coupling shear, or other mechanical failure on loads from 1/5 to 100 HP.
APPLICATIONS
Detecting belt loss, coupling shear, and mechanical failure
Verifying lighting circuit and other electrical service run times
Monitoring status of industrial process equipment
Monitoring status of critical motors (compressor, fuel, etc.)
current monitoring
DETECTS BELT LOSS/COUPLING SHEAR!
DETECTS BELT LOSS/COUPLING SHEAR!
Fan/pump
Calibrated
Trip Point
On
Electrical Failure
H808
H608
H308
H908
H708
FEATURES
High performance devices in split- and solid-core housings
Adjustable trip point...precise current trip point setting
Minimum trip point as low as 0.5A (H608)...eliminates the need for multiple
wraps of the conductor through the sensor even on loads as small as 1/5 HP
Small size...ts easily inside small enclosures
Self-gripping iris on the split-core housing for easy installation
Status LEDs available for easy setup and local indication
Bracket on H908 can be installed in three dierent congurations...installation
exibility in tight spaces
1 Amp status output...increased application exibility
All devices are 100% solid state for high reliability and polarity insensitive for
trouble-free installation, with a 5-year warranty
TM
O O
Now you can easily detect when drive belts slip, break, or pump couplings shear. In fact, a typical HVAC motor that loses its load has a reduction of current draw of up to 50%. That’s why our sensors are the industry standard for status.
SPECIFICATIONS
Sensor Power Induced from monitored conductor Insulation Class 600VAC RMS (UL), 300VAC RMS (CE) Frequency Range 50/60 H z Temperature Range -15° to 60°C (5° to 140°F) Humidity Range 10-90% RH, non-condensing Hysteresis 10% (typical) Terminal Block Wire Size H608, H701, H708, H808, H908: 24-14 AWG (0.2 to 2.1 mm2); H308: 22-16 AWG (0.3 to 1.3 mm2) Terminal Block Torque H608, H701, H708, H808, H908: 3.5 to 4.4 in-lbs (0.4 to 0.5 N-m); H308: 7 in-lbs (0.8 N-m) Agency Approvals UL 508 open device listing; CE: EN61010-1:2001-02, CAT III, pollution degree 2, basic insulation
Loss of Belt/Coupling Shear
5
Warranty
Maximize Reliability
Minimize Installed Cost
Do not use the LED status indicators as evidence of applied voltage.
800.354.8556
+1 503.598.4564
www.veris.com
HQ00 01754.B 01131
800.354.8556
E150462
+1 503.598.4564
DIMENSIONAL DRAWINGS
H308
Removable Mounting Bracket
www.veris.com
H608
Removable Mounting Bracket
Removable/Adjustable Mounting Bracket
H808
0.3”
(8 mm)
6 AWG max.
1.5”
Ø 0.18” (x2)
(5 mm)
* Terminal block may extend up to 1/8” over the height dimensions shown.
(38 mm)
1.8”
(46 mm)
1.6”
(40 mm)
0.6”
(15 mm)
H708/701 H908
Removable/Adjustable Mounting Bracket
0.9"
 0.7"
(19 mm)
0.2” x 0.15” slot (2x)
4.2"
(106 mm)
2.8"
(68 mm)
3.8"
(95 mm)
(23 mm)
3.0" **
(75 mm)
1.1" *
(27 mm)
2.1"
(54 mm)
0.4” x 0.2”
(10 mm x 5 mm)
Slot (2x)
1.1”
(26 mm)
**3.1”
(79 mm)
Ø 0.3”
(8 mm)
0.6"
(16 mm)
0.7"
(18 mm)
0.5"
(13 mm)
2.1"
(54 mm)
2.9"
(74 mm)
3.5"
(89 mm)
Removable Mounting Bracket
1.0”
(25 mm)
0.8”
(21 mm)
2.8”
(70 mm)
2.5”
(64 mm)
3.0”
(76 mm)
1.2"
(31 mm)
Self-gripping Iris
1.4”*
(36 mm)
 0.7" (18 mm)
2.5" *
(64 mm)
1.7
1.0" *
(26 mm)
0.4” x 0.2” Slot (x2)
(43 mm)
2.3"
(58 mm)
APPLICATION/WIRING DIAGRAM
Monitoring Fan /Pump Motors for
Bracket can be mounted on three sides for added installation exibility.
Positive Proof of Flow
CONTACTOR
9
Fan or Pump
Motor
0.9"
(23 mm)
2.8" *
(71 mm)
1.1" *
(27 mm)
CONTROLLER
DI
current monitoring
ORDERING INFORMATION
RoHS
Compliant
MODEL AMPERAGE RANGE STATUS OUTPUT (max.) MIN. TRIP POINT HOUSING STATUS LED UL CE RoHS
H308 0.75 - 50A
H608 0.5 - 175A 0.5A or less Split-Core
H701 1 - 135A 1.0A or less Solid-Core
H708 1 - 135A 1.0A or less Solid-Core
H808 0.75 - 50A 0.75A or less Solid-Core
H908 2.5 - 135A 2.5A or less Split-Core
N.O. 1.0A@30VAC/DC
0.75A or less Split-Core
1
Listed for use on 75°C insulated conductors.
2
Product provides functional insulation only.
n n
n
n n n
n n n n
n n n n
n
n n
1
n
n n
ACCESSORIES
DIN Rail Clip Set (AH01 for H6xx, H8xx , H9x x; AH27 for H3xx) DIN Rail (AV01) and DIN Stop Clip (AV02)
HQ00 01754.B 01131
AH27
AH01
AV01
2
n
AV02
Loading...