Veris H681x-A Datasheet

AL, BL, CL, & Hx-ASERIES
VERIS INDUSTRIES
Current Transfomers, 5A Output
Split-Core and Solid-Core Designs for Flexibility
DESCRIPTION
Veris’ split-core and solid-core current transformers provide a 0-5AAC output for use with transducers, data loggers, and chart recorders.
APPLICATIONS
Data logging
Recording
Power monitoring
Energy management
Alternative energy monitoring
Cost allocation
POWER Metering CTS
H681x -5A
AL BL CL
FEATURES
Unique hinge design on split-cores...easy installation
5 Amp standard output...compatible with existing systems
UL recognized
Yea r
1
SPECIFICATIONS (Solid-Core)
Frequency Range 50-40 0 Hz Leads 2 ft (0.6 m)
Accuracy:
Accurac y Varies at 60 Hz (see Ordering Infor mation)
Outputs:
Output at Rated Current 5A
Mechanical:
Insulation 60 0VAC
Environmental:
Operating Temperature Range -30° to 55°C (-22° to 131°F) Storage Temperature Range -30° to 105°C (-22° to 221°F) Agency Approvals UL61010
Warranty
SPECIFICATIONS (Split-Core)
Frequency Range 50/60 H z Leads 6 ft (1.8 m)
Accuracy:
Accurac y ±1% of reading from 10% to 100% of rated current
Outputs:
Output at Rated Current 5A
Mechanical:
Insulation 60 0VAC
Environmental:
Operating Temperature Range 2400A models only: -15° to 50°C (5° to 122°F); All other models: -15° to 60°C (5° to 140°F) Storage Temperature Range -40° to 70°C (-4 0° to 158°F) Humidity Range 0-95% noncondensing Agency Approvals UL61010, E N61010
800.354.8556
+1 503.598.4564
www.veris.com
HQ0001817.B 01131
800.354.8556
A
B
E
F
C
D
B
E
F
C
D
A
A
B
E
C
F
D
X2 Black
+1 503.598.4564
DIMENSIONAL DRAWINGS
www.veris.com
H681x-5A Split-coreAL/BL/CL Solid-core
AL/SMALL
A = 2.7” (70 mm) B = 2.5” (63 mm) C = 1.1” (26 mm) D = 1.1” (26 mm)
BL/MEDIUM
A = 3.7” (90 mm) B = 3.4” (88 mm) C = 2” (52 mm) D = 1.1” (26 mm)
CL/LARGE
A = 4.9” (124 mm) B = 4.5” (115 mm) C = 3” (76 mm) D = 1.1” (26 mm)
APPLICATION/WIRING EXAMPLE
One turn
Customer supplied
X1 White
ORDERING INFORMATION
H6810/SMALL
200 Amp 300 Amp
A = 3.8” (96 mm) B = 1.2” (30 mm) C = 1.3” (32 mm) D = 1.2” (30 mm) E = 4.0" (100 mm) F = 4.8" (121 mm)
H6811/MEDIUM
400 Amp 600 Amp 800 Amp
A = 4.9” (125 mm) B = 2.9” (73 mm) C = 2.5” (62 mm) D = 1.2" (30 mm) E = 5.2” (132 mm) F = 6.0" (151 mm)
H6812/LARGE 800 Amp/1000 Amp/ 1200 Amp/1600 Amp/ 2000 Amp/2400 Amp
A = 4.9” (125 mm) B = 5.5” (139 mm) C = 2.5” (62 mm) D = 1.2” (30 mm) E = 7.9" (201 mm) F = 6.0" (151 mm)
Solid-Core Split-Core
E93779
HQ0001817.B 01131
MODEL RAT IO ACCURAC Y
AT 60 Hz
AL500 50:5 3% 2.0 AL101 100:5 AL151 150:5 4.0 AL201 200:5 4.0 AL251 250:5 6.0
AL301 300:5 8.0 AL401 400:5 10.0 BL501 500:5 12.5 BL601 600:5 15.0 BL801 800:5 8.0 BL102 1000:5 10.0 BL122 1200:5 12.5 CL122 1200:5 10.0 CL152 1500:5 12.5 CL162 1600:5 12.5 CL202 2000:5 15.0
1%
BURDEN CAPACITY IN VA
2.0
E207042
MODEL RAT IO ACCURACY
FROM 10% TO 100% OF MAX LOAD
H6810-200A-5A 200:5 H6810-300A-5A 300:5 2.5 H6811-400A-5A 400:5 5.0 H6811-600A-5A 600:5 5.0 H6811-800A-5A 800:5 12.5 H6812-800A-5A 800:5 5.0
1%
H6812-1000A-5A 1000:5 22.5 H6812-1200A-5A 1200:5 22.5 H6812-1600A-5A 1600:5 22.5 H6812-2000A-5A 2000:5 22.5 H6812-2400A-5A 2400:5 22.5
ACCESSORIES
Universal Mounting Bracket Kit for H681x CTs (AH06)
POWER Metering CTS
BURDEN CAPACITY IN VA
2.5
AH06