Veris H614 Datasheet

H614
VERIS INDUSTRIES
VFD Current Switch Auto Calibration
Automatically Learns Load At Initial Power-Up
DESCRIPTION
The Hawkeye H614 is a microprocessor based, self-learning, self-calibrating current­sensitive switching device designed for use with VFD systems. It is equipped with an auto calibration feature that allows the device to distinguish between a reduced amp draw due to normal changes in frequency (e.g., gradual lter restrictions) and a sudden drop (e.g., belt loss or other mechanical failure). At initial power-up, the
H614 automatically learns the average current on the line with no action required by the installer. Once a current is learned, the switch monitors for changes in current
greater than ±20% of the learned load.
APPLICATIONS
Detecting belt loss, coupling shear, and mechanical failure
HVAC fan/blower motor failure
current monitoring
Detecting unauthorized duct access
TM
H614
FEATURES
Microcontroller based learning technology...automatically learns load upon
initial power-up...eliminates labor associated with calibration
Automatic trip point (1.5 to 150 Amps, 12 to 115 Hz)...reduced errors
Monitors current for both under- and over-load in one package
Small size ts easily inside small starter enclosures...saves space
100% solid state...no moving parts to fail
Removable mounting bracket for installation exibility
5-year warranty
PRODUCT FUNCTIONS
+20%
Constant Torque Constant Power
-20%
Learned Current
Elbow
Current
Band 12
Band 11
Band 10
Band
Band 6
Band 7
Band 8
Band 9
Band 1
Band 2
Band 3
Band 4
Maximize Reliability
Minimize Installed Cost
Year
5
SPECIFICATIONS
Sensor Power Induced from monitored conductor Response Time 1 sec. Learn Time 15 sec. learn period after f requency stabilizes Frequency Range 12 to 115 Hz Temperature Range -15° to 60° C (5° to 140°F) Humidity Range 10-90% RH non-condensing Alarm Limits ±20% of learned current in every 5 Hz freq. band NORMAL-to-ALARM Status Output Delay ~7 second max. ALARM-to-NORMAL Status Output Delay 1 sec. nominal* O Delay <30 sec. nominal Contact Ratings 30VAC/DC, 1A Insulation Class 600VAC (UL); 300VAC RMS (CE) Terminal Block Maximum Wire Size 14 AWG Terminal Block Torque (nominal) 3.54 to 4.43 in-lbs (0.4 to 0.5 N-m) Agency Approvals UL508 open device, CE: EN61010-1:2001-02, CAT III, pollution degree 2
Warranty
Band 5
Elbow
Band 15
Band 14
Band 13
Frequency
Band 16
Band 17
Band 18
Band 19
Band 20
*If the H614 experiences a momentary loss of power, the Alarm-to-Normal output delay may exceed 1 sec. Specication No te: For CE compliance, conductor sha ll be insulated according to IEC 61010-1:2001. The product d esign provides for basic insul ation only. Use wire with minimum 75°C rated insula tion. Do not use the LED status indicato rs as evidence of applied volta ge. This sensor detec ts abnormal operation by l ooking for sudden chang es in current across the entire fre quency range. In Learn mode, t he sensor calculates a margin 20% ab ove and 20% below the learned f requency curve. An abnormal con dition in the circuit is one th at falls outside this margin.
800.354.8556
+1 503.598.4564
www.veris.com
HQ0002067.A 09121
800.354.8556
Fan or Pump
CONTROL
DI
Motor
VERIS INDUSTRIES
Portland, Oregon 97223
1-800-354-8556
Hawkeye
®
614
VFD
BYPASS DEVICE
(if used)
E150462
+1 503.598.4564
www.veris.com
DIMENSIONAL DRAWING
Removable Mounting Bracket
0.6"
(16 mm)
2.1"
(54 mm)
0.4” x 0.2”
(10 mm x 5 mm)
Slot (2x)
* Terminal block may extend up to 1/8” over the height dimensions shown.
0.5"
(13 mm)
2.1"
(54 mm)
2.9"
(74 mm)
(18 mm)
0.7"
3.5"
(89 mm)
1.2"
(31 mm)
2.5" *
(64 mm)
1.0" *
(26 mm)
HOW IT WORKS
The H614 is designed for HVAC fan and blower systems, as well as some pumping systems involving consistent viscosity liquids. If an H614 is installed on one phase of the VFD, it detects changes in that phase that result from the VFD compensating for changes elsewhere in the system. Alternatively, for increased sensitivity, H614s can be used on all three phases for immediate detection of phase balance changes anywhere in the system.
APPLICATION/WIRING DIAGRAM
NOTE: The H614 is not intended for use in staged pump or variable inlet vane applications.
NOTE: (Optional) For added sensitivity in detecting a mperage changes, use H614 devices on all three phases of the VFD (see “How It Works” for details).
During setup, the H614 automatically determines the normal amperage and frequency prole and stores it in nonvolatile memory. Then the microprocessor monitors for amperage changes greater than ±20% of this learned curve.
Sensor Mode Status LED Blink Pattern
Learning Mode (rst 15 sec of operation after
frequency stabilizes)
On/O Status only; Learn mode incomplete.
VFD system does not meet abnormal condition detection criteria
Status OK Green blink (1 per sec.)
Alarm Red blink (1 per sec.)
ORDERING INFORMATION
Alternating Red/Green (1 per sec.)
Green blink (5 times per sec. after
15 sec of stable frequency)
RoHS
Compliant
MODEL AMPERAGE
H614 1.5 - 150A 12 - 115 Hz N.O. 1.0A@30VAC/DC ±20% Split-core
1
Listed for use on 75°C insulated conductors.
RANGE
FREQUENCY
RANGE
STATUS OUTPUT NOMINAL TRIP POINT
TARGET RANGE
HOUSING STATUS
LED
n
UL CE RoHS
1
n n
n
current monitoring
ACCESSORIES
DIN Rail Clip Set (AH01) DIN Rail (AV01) and DIN Stop Clip (AV02)
HQ0002067.A 09121
AH01
AV02
AV01