See NFPA 70E in the USA, or applicable local codes.
• This equipment must only be installed and serviced by qualified electrical personnel.
• Read, understand and follow the instructions before installing this product.
• Turn off all power supplying equipment before working on or inside the equipment.
• Use a properly rated voltage sensing device to confirm power is off.
DO NOT DEPEND ON THIS PRODUCT FOR VOLTAGE INDICATION
• Only install this product on insulated conductors.
Failure to follow these instructions will result in death or serious injury.
DANGER
CURRENT MONITORING
INSTALLATION GUIDE
H535NS
TM
535NS
Enclosed Relay
Installer’s Specifications
Sensor Power Induced from the monitored conductor
Amperage Range 0.25 to 15 A
Frequency Range 50-60 Hz
Operating Temperature Range -15° to 50°C (5° to 122°F)
Operating Humidity Range 10-90%, noncondensing
Wire to Relay Contact s Use 12 AWG (3.3 mm2) wire or larger*
Relay Switching C apacity at 120 VAC 1 HP
Relay Switching C apacity at 277 VAC 1.5 HP
Relay Outpu t SPDT, 15 Amps
Relay Coil 24 VAC/DC; 36 mA nom.
Terminal Block Torque Relay control ter minals: 3.5 in-lb (0.4 N-m)
All other terminals: 12 in-lb (1.35 N-m)
Agency Approvals UL508, Installation Categor y III
* For current loads up to 10 A, use 75°C rated wire insulation. For loads greater than 10 A, use
90°C rated wire insulation.
The product design provi des for basic insulation only.
quick install
1. Disconnect power sources prior to installation.
NOTICE
• This product is not intended for life or safety applications.
• Do not install this product in hazardous or classified locations.
• The installer is responsible for conformance to all applicable codes.
• Mount this product inside a suitable fire and electrical enclosure.
Alta Labs, Enercep t, Enspector, Hawkeye, Trustat, Veris, and the Veris ‘ V’ logo are trademark s or registered tradema rks of Veris Industries, L.L .C. in the USA and /or other countri es.
(108 mm)
L
1.16"
(30 mm)
4.25"
1.53"
(39 mm)
2. Remove the sensor lid. Wire the command relay connections and relay controls to
the base.
3. This device has four wiring options, detailed on page 2-3 of this installation guide.
Choose the option appropriate to the application and follow instructions.
operation
The H535NS is an enclosed switching relay that is connected in series between the
power source and the motor device. It operates at amperage loads up to a maximum
of 15A, and the relay controls the on/o functioning of the motor. The H535NS
requires no additional power source for operation.
Wire
Opening
C
L
2.13"
(55 mm)
Page 2
Wiring board
TM
H535NS
INSTALLATION GUIDE
4. Select one of the following mounting congurations (a, b, c, or d) to match your
installation.
1
2
1. Line current terminals:
Common
Normally Open
Normally Closed
2. 24 VAC/DC Relay
installation
Prior to installation, disconnect and lock out all power sources.
1. Open the device. Set aside the lid and the bag of hardware enclosed.
VERIS INDUSTRIES, INC.
POR TLA ND, ORE GON US A
TOLL FREE USA 1.800.354.8556
RS
OC
TEL USA 1.503.598.4564
SO
FAX USA 1.503.598.4664
SP
SC
540NS
a.) duplex box:
Mounting slot
Connect line voltage wires
to line current terminals
Line Voltage
Wires
Mounting hole
Wire the 12 AWG lines from the controller through the back of the device, to
the line current terminals. Tighten line current terminal blocks to 12 in-lb
(1.35 N-m) torque.
Use the base as a template for mounting to the wall using the mounting hole
and slot shown.
b.) 4S junction box:
Mounting hole
CAUTION: Consult instructions
prior to installation
!
STATUS OUTPUT: 1A@30VAC/DC
RELAY COIL: 24VAC/DC; 16mA nom.
RELAY OUTPUT: 16(8)A@250VAC; 3/4 H P
2. Wire the 24 AC/DC relay control through the top hole of the device. Use only copper
conductors for command relay inputs. Tighten terminal blocks to 3.5 in-lb (0.4
N-m) torque. See Specications for wire insulation requirements.
Status Output & Relay Coil
(Low Voltage Wires Only)
24VAC/DC Relay Control
3. Wire the line current from the controller to the Common terminal. Wire the second
line to either the N. O. terminal or the N. C. terminal. The device is shown here as
wired to the N.O. block. Tighten line current terminal blocks to 12 in-lb (1.35 N-m)
torque.
Common
N.O. block
N.C. block
Line Voltage
Wires
Connect line voltage wires
to line current terminals
Mounting hole
Wire the 12 AWG lines from the controller through the back of the device, to
the line current terminals. Tighten line current terminal blocks to 12 in-lb
(1.35 N-m) torque.
Use the base as a template for mounting to the wall using the mounting holes
shown.
Alta Labs, Enercep t, Enspector, Hawkeye, Trustat, Veris, and the Veris ‘ V’ logo are trademark s or registered tradema rks of Veris Industries, L.L .C. in the USA and /or other countri es.
Page 3
TM
Connect line voltage wires
H535NS
c.) surface mounting:
Connect line voltage wires
to line current terminals
Line Voltage
Wires
Wire the 12 AWG lines from the controller through the side of the device, onto
the line current terminals. Tighten line current terminal blocks to 12 in-lb
(1.35 N-m) torque.
d.) nipple mount to another enclosure:
INSTALLATION GUIDE
Wiring example
C
N.C.
N.O.
Insert the conduit nuts (provided) into the slots in the side hole of the device
for additional weight support.
ENCLOSURE
Line voltage wires
Nipple to existing enclosure
(conduit nipple fitting not
provided)
to line current terminals
Wire the 12 AWG lines from the controller through the side of the device,
from the enclosure to the line current terminals. Tighten line current terminal
blocks to 12 in-lb (1.35 N-m) torque.
5. Use the knockout seal to cover any unused holes in the housing. Attach the cover,
securing with the screws provided.
1. Relay Contacts: Wire the H535NS in series with the motor using these terminals.
Choose from N.O. or N.C.
2. Relay: Enables actuation of the circuit by a control system
3. Relay Coil Terminal Blocks: Wire the output signal from the control panel to
actuate the relay. 24 VAC/DC; 36 mA nominal
4. Relay Status LED: For positive indication of energized coil.
CAUTION!
Do not rely on status indicators to de termine whether or n ot the relay contacts are
connected to a power source. Doing so may result in i njury or death from electrical
shock.
If the connections to the unit a re made through more than one metallic conduit, bond
the conduits to prevent the hazard of elec tric shock. A bonding plate is available (Veris
pa rt AH10 ).
NOTE: If a conduit is used, connect the conduit to the mounti ng hub before connecting it to the
device. Be sure to support the H535NS housing when nipple-mounted to another en closure, or the
unit may shift on o pening, potentially causing undue stress on the wiring a nd the terminals.
Alta Labs, Enercep t, Enspector, Hawkeye, Trustat, Veris, and the Veris ‘ V’ logo are trademark s or registered tradema rks of Veris Industries, L.L .C. in the USA and /or other countri es.
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.