Veris H40 Installation Instructions

Installation Guide
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
See NFPA 70E in the USA, or applicable local codes.
• This equipment must only be installed and serviced by qualified electrical personnel.
• Read, understand and follow the instructions before installing this product.
• Turn off all power supplying equipment before working on or inside the equipment.
• Use a properly rated voltage sensing device to confirm power is off. DO NOT DEPEND ON THIS PRODUCT FOR VOLTAGE INDICATION
• Only install this product using insulated conductors.
Failure to follow these instructions will result in death or serious injury.
DANGER
A qualied person is one who has skills and knowledge related to the construction and operation of this electrical equipment and the installation, and has received safety training to recognize and avoid the hazards involved. NEC2009 Article 100
No responsibility is assumed by Veris Industries for any consequences arising out of the use of this material.
Current Monitoring
RoHS
Compliant
NOTICE
• This product is not intended for life or safety applications.
• Do not install this product in hazardous or classified locations.
• The installer is responsible for conformance to all applicable codes.
Z205741-0D Page 1 of 3 ©2013 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com 09131
Alta Labs, E nercept, Ensp ector, Hawkeye, Trus tat, Aerospo nd, Veris, and th e Veris ‘V’ log o are tradema rks or registe red tradema rks of Veris Ind ustries, L. L.C. in the USA and /or other countri es.
TM
H40 Series
Fractional Motor Control With Command Relay
Product Overview
H40NEXA and H40BAXA devices combine a switching relay and a Hand-O-Auto (HOA) switch into a single housing. The H40MEXX and H40AAXX include only the switching relay. The low voltage and line voltage wires are electrically separated from each other. A hinged lid on the low voltage side allows easy connection, while the high voltage side is closed for added safety.
The H40 is connected in series between the power source and the motor device, and the relay and HOA switch (if applicable) control the on/o functioning of the motor. The H40AAXX and H40BAXA have a maximum load of 10 A, and the H40MEXX and H40NEXA have a maximum load of 16 A.
Product Identification
Part Number Description
H40NEXA Fractional motor control with command relay and HOA switch
H40MEXX Fractional motor control with command relay
H40BAXA Fractional motor control with command relay and HOA switch
H40AAXX Fractional motor control with command relay
Specifications
Amperage Range
Wire to Relay Contacts
H40NEXA, H40MEXX
H40BAXA, H40AAXX
Low Voltage Terminal Block Wire Size
Low Voltage Terminal Block Torque
H40NEXA, H40BAXA
H40MEXX, H40AAXX
Contact Ratings
H40NEXA
H40MEXX
H40BAXA H40AAXX
Coil Ratings
H40NEXA, H40MEXX
H40BAXA, H40AAXX
Operating Temperature Range
Operating Humidity Range
Frequency
Approvals
* In addition, coil input from other sources may be used as detailed in NEC Article 725.121.
Other companies’ trademarks are hereby acknowledged to belong to their respective owners.
0.25 to 16 A
12 AWG (3. 3 mm2) or larger 16 AWG (1.3 mm2) or larger
24 to 14 AWG (0.2 to 2.1 mm2)
3.5 to 4.4 in-lb ( 0.4 to 0.5 N-m)
RE L AY
Typ e
SP ST, N.O.
SPST, N.O. or N.C. (field selectable)
16A @120 /25 0VAC, 12A@ 277 VAC, 1HP@120 VAC, 8 A@ 28V DC 16A @120 /27 7VAC , 1HP@ 120VAC, 2HP@277VAC, 16A@ 28VDC 10A@120/ 240/ 277VAC, 1/3HP@120VAC, 8A@28VDC 10A@120/ 240/ 277VAC, 1/3HP@120VAC, 10A@28V DC
24VDC 4 5mA nom. ; 24VAC 78mA nom.; Class 2* 10-30 VAC@ 24 -38mA ; 10- 30VDC @10 -16mA ; Class 2*
OPERATING CO NDITIONS
-15° to 50°C ( 5° to 122°F)
0-95% RH noncondensing
50 /60 Hz
COMPLIANCE INFORMATION
UL508, RoHS
TM
Installation Guide
In Series
Current Monitoring H40 Series
TM
Dimensions
Product Diagram
1.6”
(40 mm)
Class 1 Voltage
(106 mm)
Power Source
4.2”
1/2” NPT
4.2”
(106 mm)
Fan/Motor
4.0”
(101 mm)
1
2
Class 2 Voltage
1. Relay: Enables actuation of circuit by a control system
2. HOA Switch: Provides local control of the motor (H40NEXA and H40BAXA only)
HAND - When the switch is in this position, the motor is always on.
OFF - When the switch is in this position, the motor is always o.
AUTO - When the switch is in this position, the control system commands the motor.
3. Relay Coil terminal block: Wire output signal from control panel to actuate the relay.
4. Status LED:
Right side of V: Green = Coil is energized
Only the low voltage terminal bl ocks are accessible through the hinged lid. Other compone nts are in the sealed high voltage compartment.
4
= Circuit Path
3
Z205741-0D Page 2 of 3 ©2013 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com 09131
Alta Labs, E nercept, Ensp ector, Hawkeye, Trus tat, Aerospo nd, Veris, and th e Veris ‘V’ log o are tradema rks or registe red tradema rks of Veris Ind ustries, L. L.C. in the USA and /or other countri es.
Other companies’ trademarks are hereby acknowledged to belong to their respective owners.
Loading...
+ 1 hidden pages