Veris H280 Datasheet

H280 SERIES
VERIS INDUSTRIES
Load Status Switch
Provides Status For Manually Switched Loads
DESCRIPTION
The H280 load status switch monitors both voltage and current on manually­switched loads (e.g., lights/fans in bathrooms). This device provides status monitoring for loads that are not, or cannot be, controlled by a control system. The H280 also saves cost by eliminating the need to connect a digital output to prove status.
APPLICATIONS
Lighting
Bathroom Fans
Sump Pumps
Trac Lights
Roadside Lighted Areas (e.g., bus stations)
current monitoring
Parking Lots/Garages
TM
H280
FEATURES
Wide voltage range (110-277VAC)...easy to use in many applications
Low current threshold (100mA) oers great sensitivity for those small loads
Nipple mount housing can be connected to any 1/2” conduit knockout for
installation versatility
Dual-color LED for easy visual inspection...control system is not required
Isolated status output protects control system
Year
5
SPECIFICATIONS
Sensor Power Line powered Operating Temperature -15° to 60°C (5° to 140°F) Operating Humidity 10-90% RH noncondensing LED Status GREEN LED=status normal; RED LED=status alarm Frequency 50/60 H z
Wire Specications:
Lead Length 14” (356 mm) min. Gauge UL1015; Neutral: 18 AWG; Line: 12 AWG; Status: 16 AWG Agency Approvals UL 508 open device listing
Do not use the LED status indicators as evidence of applied voltage.
800.354.8556
Warranty
+1 503.598.4564
www.veris.com
HQ00 01773.B 01131
800.354.8556
Current
Switch
Voltage
Switch
Output
Neutral
ORANGE
White
ORANGE
yel
l
ow
yel
l
ow
From Line
To Load
Current Flow
110-277VAC
2.9"
E150462
+1 503.598.4564
www.veris.com
DIMENSIONAL DRAWING
(74 mm)
2.8"
(71 mm)
1/2" NPT Nipple
WIRE COLOR CODES
Line Connections
1.7"
(43 mm)
1.6"
(41 mm)
1.8"
(46 mm)
APPLICATION/WIRING DIAGRAM
Nipple mount to 4x electrical box
Status Output
(Grey) or (Brown)
POWER
SOURCE
NOTE: Incidental loads as small as 30mA AC, such as pilot lamps or control circuits, connected in parallel to the sensed load may draw enough current to give a false load presence signal, even though the true load has been interrupted.
HOW IT WORKS
VOLTAGE CURRENT H280 H280NC LED
ON ON OPEN CLOSED GREEN ON OFF CLOSED OPEN RED OFF OFF OPEN CLOSED OFF
Line
Neutral
Switch
Orange Orange
Wht/Yellow
STATUS O UTPU T
Status Outputs
H280 (NO)
GREY
COMMON
GREY
N.O.
ORDERING INFORMATION
MODEL AMPERAGE RANGE VOLTAGE RANGE STATUS OUTPUT
H280
H280NC N.C. 100mA@120VAC/DC
HQ00 01773.B 01131
0.1 - 20A 110 - 277VAC
N.O. 100mA@120VAC/DC
H280 NC
BROWN
COMMON
BROWN
N.C.
(max.)
TRIP POINT HOUSING STATUS
LED
0.1A or less
Nipple Mount
n n n
n n n
RELAY
POWER LED
current monitoring
UL
Loading...