Veris H120 Datasheet

H120 SERIES
VERIS INDUSTRIES
Field Mount Status Relay
SPST Status Relay With Integral Current Switch
DESCRIPTION
The H120 and H120NC oer a xed current switch and SPST relay in a single externally mounted housing. Combining the current sensor and relay in one easy­to-install package eliminates the need to t multiple devices into small electrical enclosures and simplies the installation. Eliminate the labor associated with installing a separate current sensor.
APPLICATIONS
Unit Ventilators
Fan Coil Units
Exhaust Fans
Fan Terminal Units
Fractional HP Motors
current monitoring
Light Resistive Loads
TM
H120
FEATURES
The current switch and relay are in series...connect the contacts to the load and
your current switch is automatically installed
The nipple mount housing can be connected to any 1/2” conduit knockout for
installation versatility
Relay coil LED streamlines job commissioning and check out
HP ratings make the H120 ideal for control and status of fractional HP motors
5-year warranty
NEMA 1 rated housing may be used in plenum spaces
Can be externally mounted to the electrical enclosure...space saver
0.1A turn-on...easily monitors the smallest motors
SPECIFICATIONS
Sensor Power Induced from relay coil power Operating Temperature -15° to 60°C (5° to 140°F) (13.8A max.), -15° to 50°C (5° to 122°F) (20A max.) Operating Humidity 10-90% RH non-condensing Expected Relay Life (mechanical) 10 million cycles Relay Status LED ON=energized
Wire Specications:
Lead Length 14” (356 mm) min. Gauge UL1015; Coil: 18 AWG; Contacts: 12 AWG; Status: 16 AWG Agency Approvals UL 508 open device listing
Do not use the LED status indicators as evidence of applied voltage.
800.354.8556
Year
5
Warranty
+1 503.598.4564
www.veris.com
HQ00 01772.B 01131
800.354.8556
Common
24VAC/DC
VOLTAGE
wht/blue
COMM
wht/yellow
Common
N.O.
CONTACT OUTPUTCONTROL SYSTEM INPUT
White
ORANGE
White
ORANGE
b
l
u
e
b
l
u
e
ye
l
l
o
w
ye
l
l
o
w
*Isolation…600VAC
*
E150462
+1 503.598.4564
www.veris.com
DIMENSIONAL DRAWING
2.9"
(74 mm)
2.8"
(71 mm)
1/2" NPT Nipple
1.7"
(43 mm)
1.6"
(41 mm)
1.8"
(46 mm)
APPLICATION/WIRING DIAGRAMS
Nipple mount directly to a panel
R
C
E
O
To Load
To Controls
Nipple mount to 4x electrical box
POWER
SOURCE
L
A
N
Y
T
A
C
T
S
DO (coil)
DI (current switch)
Relay Contacts
Current Switch
Fractional HP Motor
WIRE COLOR CODES
H120 STATUS OUTPUT
GREY
COMMON
GREY
N.O.
H120NC STATUS OUTPUT
BROWN
COMMON
BROWN
N.C.
RELAY CONTACT RATINGS (N.O.)
Resistive........................ 20A(r)*@277VAC/28VDC
(250,000 Cycles)
Motor............................. 120VAC, 1HP
208VAC, 1HP 250VAC, 2HP 277VAC, 2HP
Ballast........................... 277VAC, 20A
Tungsten....................... 120VAC, 10A
TYPICAL COIL PERFORMANCE
Voltage Coil Current AC DC
24V.................................. 75mA 32mA
*See operating temperature specification
current monitoring
ORDERING INFORMATION
ORDERING INFORMATION
0.1A - 20A
MODEL AMPERAGE RANGE COIL RELAY STATUS OUTPUT TRIP POINT HOUSING RELAY POWER LED UL
H120
H120 NC N.C. 100mA@30VAC/DC
HQ00 01772.B 01131
24VAC/DC SPST, N.O.
N.O. 100mA@30VAC/DC
0.1A or less Nipple Mount
n n
n n
Loading...