Veris H11D Datasheet

H11D
VERIS INDUSTRIES
Current Switch: Auto Calibration, Automation Systems
LCD Display
DESCRIPTION
The Hawkeye TruStat H11D is a microprocessor based, self-learning, self-calibrating current switch. It is designed for user ease, providing calibration-free status for both under and overcurrent, an LCD display, and slide-switch selectable trip point limits. At initial power-up, the H11D automatically learns the average current on the line with no action required by the installer. Once a current is learned, the switch monitors for changes in current greater than the selected range.
APPLICATIONS
HVAC fans, pumps, and blowers
Monitoring status of industrial process equipment
current monitoring
H11D
LCD
LCD
DISPLAY!
DISPLAY!
FEATURES
Backlit LCD display...view the monitored current (up to 200A)...eliminates the
need for expensive handheld meters and oers easy visibility in dark enclosures
Automatic calibration...reduced errors and installation costs
Slide-switch selectable trip point limits...application versatility
Microcontroller based learning technology...automatically learns load upon
initial power-up...eliminates labor associated with calibration
Records and displays the amperage level that trips the alarm...simplies
troubleshooting
Reset function can be used when unpowered...reduces the possibility of an
undesirable arc ash incident
Monitors current for both under- and over-load in one package
100% solid state...no moving parts to fail
Small size ts easily inside small starter enclosures...saves space
Self-gripping iris for easy installation
Bracket can be installed in three dierent congurations...added exibility
5-year warranty
TM
Maximize Reliability
Minimize Installed Cost
SPECIFICATIONS
Sensor Power Induced from monitored conductor Response Time 1 sec. Accurac y ±2% of full scale Frequency Range 50/60 H z Temperature Range -15° to 60°C (5° to 140°F) Humidity Range 10-90% RH non-condensing LCD Backlight O at low currents; illuminate s when monitored current exceeds 4.5A; ashes during an alarm state while cur rent remains above 4.5A On-State Resistance ≤1.0 Ω O-State Resistance ≥1.0 MΩ Setpoint Target Range, Switch Setting A* ±40% of learned nominal cur rent; max. learned current of 142A to enable an upper trip limit at or below 200A Setpoint Target Range, Switch Setting B* ±60% of learned nominal current;max. learned cur rent of 125A to enable an upper trip limit at or below 200A Switch Set ting C* On/O Status; contacts are closed while amperage is above 2.5A Alarm Reset Range ±5% of learned nominal current ** Setpoint Calibration Learn Period 30 sec.; self-learning, pushbutton reset Normal-to-Alarm Output Delay 1 sec. maximum Alarm-to-Normal Output Delay 30 sec. nominal Insulation Class 600VAC RMS (UL); 300VAC RMS (CE) Terminal Block Wire Size 24-14 AWG (0.2 to 2.1 mm2) Terminal Block Torque 3.5 to 4.4 in-lbs (0.4 to 0.5 N-m) Agency Approvals UL508 open device, CE: EN61010-1:2001-02, CAT III, pollution degree 2
Year
5
Warranty
* Trip point switch positions A and B are not for use in applications where the current will uctuate by more than 40% (A) or 60% (B) of the nominal current. If the current will uctuate by more than 60%, use the H11D for on/ o status (position C) only. ** The upper trip limit alarm resets when the current drops by 5% of the learned nominal current limit. The lower trip limit alarm resets when the current rises by 5% of learned nominal current limit. Specication Note: For CE compliance, conductor shall be insulated according to IEC 61010‑1:2001. The product design provides for basic insulation only. Do not use the LCD as evidence of applied voltage.
800.354.8556
+1 503.598.4564
www.veris.com
HQ0003679.C 01131
800.354.8556
E212445
+1 503.598.4564
www.veris.com
DIMENSIONAL DRAWING
Removable Mounting Bracket
3.1”
(79 mm)
Ø 0.3”
(8 mm)
1.1”
(26 mm)
(21 mm)
(70 mm)
3.0”
(76 mm)
0.8”
2.8”
2.5”
(64 mm)
1.0”
(25 mm)
Bracket can be mounted on three sides for added installation exibility.
Self-gripping Iris
1.4”*
(36 mm)
APPLICATION/WIRING DIAGRAM
CONTACTOR
Insulated Conductor
CONTROLLER
Digital Input
MOTOR
Fan or Pump
FUNCTIONAL ILLUSTRATION
ALARM RESET 5% Typical
NOMINAL LEARNED CURRENT
NORMAL
ØAAC ØAAC
POWER
ON
LEARN (MODE) 30 SEC
(CURRENT MONITOR MODE)
ALARM (MODE)
1 SEC. DELAY 30 SEC. DELAY
NORMAL (CURRENT MONITOR MODE)
POWER LOSS
ORDERING INFORMATION
MODEL AMPERAGE
RANGE
H11D 2.5 - 200A @ 60 Hz
3.0 - 200A @ 50 Hz
STATUS OUTPUT NOMINAL TRIP POINT
1
N.O. 1.0A@30VAC/DC ±40%, ±60%, or on/off
TARGET RANGE
(user selectable)
ALARM (MODE)
RoHS
Compliant
HOUSING STATUS
Split-core
LED
n
UL CE
2
n
current monitoring
n
1
To enable the upper trip limit alarm, the max. learned current for switch setting “A” is 142A, and the max. learned current for switch setting “B” is 125A.
Switch setting “C” is for on/o status only, so the upper trip limit alarm does not apply.
2
Listed for use on 75°C insulated conductors.
ACCESSORIES
DIN Rail Clip Set (AH01) DIN Rail (AV01) and DIN Stop Clip (AV02)
HQ0003679.C 01131