H10 F
Current Switch: Auto
Calibration, Process Control
VERIS INDUSTRIES
Automatically Learns At
Initial Power-Up
DESCRIPTION
The Hawkeye TruStat H10F is a microprocessor based, self-learning, self-calibrating
current switch. It provides calibration-free status, for both under-current and overcurrent conditions. At initial power-up, the H10F automatically learns the average
current on the line with no action required by the installer. Once a current is learned,
the switch monitors for changes in current greater than ±20% of the learned load.
APPLICATIONS
● Verifying lighting circuit and other electrical service run times
● Monitoring status of industrial process equipment
● Monitoring status of critical motors (compressor, fuel, etc.)
current monitoring
PRODUCT FUNCTIONS
ALARM RESET
5% Typical
+20%
+15%
H10F
Hawkeye® TruStat™
FEATURES
● Automatic adjustable trip point (3.5-100A)...precise control of current trip point
● 100% solid state...no moving parts to fail
● Removable mounting bracket for installation exibility
● 5-year warranty
● Automatic calibration...reduced errors and installation costs
● Microcontroller based learning technology...automatically learns load upon
initial power-up...eliminates labor associated with calibration
● Monitors current for both under- and over-load in one package
● Small size ts easily inside small starter enclosures...saves space
NOMINAL
LEARNED
CURRENT
-15%
-20%
ØAAC ØAAC
POWER
LEARN
ON
(MODE)
30 SEC
SPECIFICATIONS
Sensor Power Induced from monitored conductor
Isolation 600VAC RMS (UL); 300VAC RMS (CE)
Temperature Range -15° to 60° C (5° to 140°F)
Humidity Range 10-90% RH non-condensing
Frequency Range 50/60 H z
Trip Point Calibration Learn Period 30 sec. learn period
Normal-to-Alarm Status Output Delay 1 second max.
Alarm-to-Normal Status Output Delay 30 seconds nominal*
Status Output ±20% of learned current to trigger alarm; ±15% of learned current to release alarm (see graph)
Terminal Block Wire Size 24-14 AWG (0.2 to 2.1 mm2)
Terminal Block Torque 3.5 to 4.4 in-lbs (0.4 to 0.5 N-m)
Agency Approvals UL 508 open device listing; CE: EN61010-1:2001-02, CAT III, pollution degree 2, basic insulation
NORMAL
(CURRENT
MONITOR
MODE)
1 SEC. DELAY 30 SEC. DELAY
Year
5
Warranty
ALARM
(MODE)
NORMAL
(CURRENT
MONITOR MODE)
POWER LOSS
ALARM
(MODE)
Maximize Reliability
Minimize Installed Cost
*If current switch experiences a momentary loss of power, 30 second delay may or may not apply.
Do not use the LED status indicators as evidence of applied voltage.
800.354.8556
+1 503.598.4564
www.veris.com
HQ00 01757.B 01131
800.354.8556
+1 503.598.4564
www.veris.com
DIMENSIONAL DRAWING
H10F
Removable Mounting Bracket
0.6"
(16 mm)
2.1"
(54 mm)
0.4” x 0.2”
(10 mm x 5 mm)
Slot (2x)
* Terminal block may extend up to 1/8” over the height dimensions shown.
0.5"
(13 mm)
2.1"
(54 mm)
2.9"
(74 mm)
(18 mm)
0.7"
3.5"
(89 mm)
1.2"
(31 mm)
2.5" *
(64 mm)
1.0" *
(26 mm)
HOW IT WORKS
The compact split-core H10F current switch monitors a learned load current to detect
power loss and electrical overload of fans, blowers, pumps, chillers, or any other
critical motor functions. The push-button initiated LEARN MODE allows resetting of
the monitored current when the load changes due to system alterations.
LEARN MODE
● Unit automatically enters LEARN MODE upon initial power-up
● Auto-calibration is achieved by averaging the load current for 30 seconds
● During this stage, green and red LEDs blink on/o
● STATUS OUTPUT contacts are closed
● LEARN MODE may be initiated manually
NORMAL MODE
● Initiated after the 30-second learning period, or immediately upon power-up if
sensor has already learned a load
● The red LED is o, and the green LED is blinking
● STATUS OUTPUT contacts are closed
APPLICATION/WIRING DIAGRAM
Monitoring Fan /Pump Motors for Positive Proof of Flow
CONTACTOR
Insulated
conductor
only
Motor
ALARM MODE
● The ALARM state signals low current, high current, or power loss conditions
● Initiated within 1 second when any load current excursion exceeds a nominal
±20%
● ALARM will persist until the load current returns to within a nominal ±15% of
the learned current value, or when power is restored to normal
● The 5% ALARM-to-NORMAL MODE reentry margin prevents alarm signal
oscillations. This feature is enhanced by a 30 second delay, to insure true
nominal load current conditions when returning to NORMAL MODE from an
ALARM state
● The green LED shuts o, and the red LED blinks
● STATUS OUTPUT contacts are open
OPERATING MODES STATUS LEDS STATUS
GREEN RED
LEARN (30 sec s) Alternating Blink On/O Contacts Closed
NORMAL Blink O Contacts Closed
ALARM* O Blink Contacts Open
DDC CONTROLLER
DI
Pump or Fan
OUTPUT
current monitoring
* 1 sec maximum after detection.
ORDERING INFORMATION
MODEL AMPERAGE
RANGE
STATUS OUTPUT NOMINAL TRIP POINT
TARGET RANGE*
RoHS
Compliant
NOMINAL
ALARM RESET
RANGE*
H10F 3.5 - 100A N.O. 1.0A@30VAC/DC ±20% ±15% Split-core
*For best performance, monitor 5A or more current. At currents less than 5A, these ranges are approximate.
1
Listed for use on 75°C insulated conductors.
ACCESSORIES
DIN Rail Clip Set (AH01)
DIN Rail (AV01) and DIN Stop Clip (AV02)
HQ00 01757.B 01131