Veris H10F Datasheet

H10 F
Current Switch: Auto Calibration, Process Control
VERIS INDUSTRIES
Automatically Learns At Initial Power-Up
DESCRIPTION
The Hawkeye TruStat H10F is a microprocessor based, self-learning, self-calibrating current switch. It provides calibration-free status, for both under-current and over­current conditions. At initial power-up, the H10F automatically learns the average current on the line with no action required by the installer. Once a current is learned, the switch monitors for changes in current greater than ±20% of the learned load.
APPLICATIONS
Verifying lighting circuit and other electrical service run times
Monitoring status of industrial process equipment
Monitoring status of critical motors (compressor, fuel, etc.)
current monitoring
PRODUCT FUNCTIONS
ALARM RESET
5% Typical +20% +15%
H10F
Hawkeye® TruStat™
FEATURES
Automatic adjustable trip point (3.5-100A)...precise control of current trip point
100% solid state...no moving parts to fail
Removable mounting bracket for installation exibility
5-year warranty
Automatic calibration...reduced errors and installation costs
Microcontroller based learning technology...automatically learns load upon
initial power-up...eliminates labor associated with calibration
Monitors current for both under- and over-load in one package
Small size ts easily inside small starter enclosures...saves space
NOMINAL LEARNED CURRENT
-15%
-20%
ØAAC ØAAC
POWER
LEARN
ON
(MODE) 30 SEC
SPECIFICATIONS
Sensor Power Induced from monitored conductor Isolation 600VAC RMS (UL); 300VAC RMS (CE) Temperature Range -15° to 60° C (5° to 140°F) Humidity Range 10-90% RH non-condensing Frequency Range 50/60 H z Trip Point Calibration Learn Period 30 sec. learn period Normal-to-Alarm Status Output Delay 1 second max. Alarm-to-Normal Status Output Delay 30 seconds nominal* Status Output ±20% of learned current to trigger alarm; ±15% of learned current to release alarm (see graph) Terminal Block Wire Size 24-14 AWG (0.2 to 2.1 mm2) Terminal Block Torque 3.5 to 4.4 in-lbs (0.4 to 0.5 N-m) Agency Approvals UL 508 open device listing; CE: EN61010-1:2001-02, CAT III, pollution degree 2, basic insulation
NORMAL (CURRENT MONITOR MODE)
1 SEC. DELAY 30 SEC. DELAY
Year
5
Warranty
ALARM (MODE)
NORMAL (CURRENT MONITOR MODE)
POWER LOSS
ALARM (MODE)
Maximize Reliability
Minimize Installed Cost
*If current switch experiences a momentary loss of power, 30 second delay may or may not apply. Do not use the LED status indicators as evidence of applied voltage.
800.354.8556
+1 503.598.4564
www.veris.com
HQ00 01757.B 01131
800.354.8556
E150462
+1 503.598.4564
www.veris.com
DIMENSIONAL DRAWING
H10F
Removable Mounting Bracket
0.6"
(16 mm)
2.1"
(54 mm)
0.4” x 0.2”
(10 mm x 5 mm)
Slot (2x)
* Terminal block may extend up to 1/8” over the height dimensions shown.
0.5"
(13 mm)
2.1"
(54 mm)
2.9"
(74 mm)
(18 mm)
0.7"
3.5"
(89 mm)
1.2"
(31 mm)
2.5" *
(64 mm)
1.0" *
(26 mm)
HOW IT WORKS
The compact split-core H10F current switch monitors a learned load current to detect power loss and electrical overload of fans, blowers, pumps, chillers, or any other critical motor functions. The push-button initiated LEARN MODE allows resetting of the monitored current when the load changes due to system alterations.
LEARN MODE
Unit automatically enters LEARN MODE upon initial power-up
Auto-calibration is achieved by averaging the load current for 30 seconds
During this stage, green and red LEDs blink on/o
STATUS OUTPUT contacts are closed
LEARN MODE may be initiated manually
NORMAL MODE
Initiated after the 30-second learning period, or immediately upon power-up if
sensor has already learned a load
The red LED is o, and the green LED is blinking
STATUS OUTPUT contacts are closed
APPLICATION/WIRING DIAGRAM
Monitoring Fan /Pump Motors for Positive Proof of Flow
CONTACTOR
Insulated conductor only
Motor
ALARM MODE
The ALARM state signals low current, high current, or power loss conditions
Initiated within 1 second when any load current excursion exceeds a nominal
±20%
ALARM will persist until the load current returns to within a nominal ±15% of
the learned current value, or when power is restored to normal
The 5% ALARM-to-NORMAL MODE reentry margin prevents alarm signal
oscillations. This feature is enhanced by a 30 second delay, to insure true nominal load current conditions when returning to NORMAL MODE from an ALARM state
The green LED shuts o, and the red LED blinks
STATUS OUTPUT contacts are open
OPERATING MODES STATUS LEDS STATUS
GREEN RED
LEARN (30 sec s) Alternating Blink On/O Contacts Closed
NORMAL Blink O Contacts Closed
ALARM* O Blink Contacts Open
DDC CONTROLLER
DI
Pump or Fan
OUTPUT
current monitoring
* 1 sec maximum after detection.
ORDERING INFORMATION
MODEL AMPERAGE
RANGE
STATUS OUTPUT NOMINAL TRIP POINT
TARGET RANGE*
RoHS
Compliant
NOMINAL
ALARM RESET
RANGE*
H10F 3.5 - 100A N.O. 1.0A@30VAC/DC ±20% ±15% Split-core
*For best performance, monitor 5A or more current. At currents less than 5A, these ranges are approximate.
1
Listed for use on 75°C insulated conductors.
ACCESSORIES
DIN Rail Clip Set (AH01) DIN Rail (AV01) and DIN Stop Clip (AV02)
HQ00 01757.B 01131
AH01
AV01
HOUSING STATUS
LED
n
UL CE RoHS