TM
ENVIRONMENTAL SENSORS
G SerieS
Carbon Monoxide Transmitter
and Fan Controller
NOTICE
• This product is not intended for life or safety applications.
• Do not install this product in hazardous or classied locations.
• Read and understand the instructions before installing
this product.
• Turn off all power supplying equipment before working on it.
• The installer is responsible for conformance to all applicable codes.
INSTALLATION GUIDE
SPECIFICATIONS
Input Po wer 15-30VDC /24VAC , 0.3A@24 VAC
Sensor Type Digitally pr oled Metal Oxide Semiconductor (MOS)
Sensor Life 5-10 years typical, replaceable
Detection Range 0 to 200 ppm
Analog Output 3-wire sourcing, 4-20mA or user selec table 0-5V/0-10V (specif y mA or V)
Output Scaling User-selec table 100 ppm F.S. or 200 ppm F.S.
Response Time 2 min 30 sec sample interval cycle
Relay Outpu t N.O. Form A (SPST) 8A@30VAC/VDC; (Use with N.C. contactor)
Relay Setpoint 25 ppm
High Limit Setpoint 100 ppm for 30 minute s
High Limit Alarm Audible, 85 dB, resets below 100 ppm (solid-state contac t for -AS version)
High Limit Contact (-AS Models) 250VAC/DC, 120mA max. Ron 35 Ω
LED Indicator s Solid Green = Normal; Solid Red = Call for ventilation;
Flashing Green = Sensor life has expired; Flashing Red = High-limit alarm
Operating Temperature Range -20° to 50°C (-4° t o 122°F)
Operating Humidity Range 0 to 90% RH non-condensing
Coverage 5000 sq f t typical (465 sq m)
Housing White powder co at over steel
INSTALLATION
1. Lock out all power supplies prior to installation.
No responsibility is assumed by Veris Industries for any consequences arising out of the
use of this material.
PRODUCT IDENTIFICATION
Enclosure
G
D = Duct mo unt
W = Wall mount
0-5/0-10VDC
M = 4-20m A
R = Relay only
Auxiliary Alarm Output Output
A = Auxiliar y Contact
X = None
US or EU
S
= StandardV = Field-s electable,
DIMENSIONS
0.9" dia.
(22 mm)
2.5"
(63 mm)
4.5”
(114 mm)
2.4"
(55 mm)
4"
(102 mm)
2. Select a location for the sensor in a secure area where it will be accessible only
to qualied service personnel. Install the G Series sensor centrally in the parking
structure, near the main trac paths, but away from outside air vents and
excessive drafts. Mount the unit securely to a wall or column at a height of about 5
ft. (1.52 m) from the oor.
3. Connect wiring as shown in the Wiring section. If using a voltage output model,
use the Output jumper to select 0-5 V or 0-10 V.
4. Apply power to the unit. A green LED on the circuit board indicates proper
operation of the power supply.
Coverage is not dependent on the sensor. Coverage is a function of the b uilding structure and air
ow patterns. A minim um of one sensor for 5000 sq. ft. is recommended. Wide open areas whe re
the air is well mixed may require mu ltiple sensors.
5.0"
(127 mm)
Z202025-0P PAGE 1 ©2013 Veris Industries USA 800.354.8556 or +1(0)503.598.4564 / support@veris.com 03131
Alta Labs, Ene rcept, Enspector, Hawk eye, Trustat, Aerospon d, Veris, and the Veris ‘V ’ logo are tradem arks or registe red trademarks o f Veris Industries, L .L.C. in the USA and/or ot her countries.
TM
G SERIES
INSTALLATION GUIDE
PRODUCT OVERVIEW
The G Series carbon monoxide detectors measure CO levels and signal control systems
to provide an inlet of fresh air optimal for the space at a given time. G Series devices
are equipped with a relay contact that closes when the CO level is below 25 ppm
and opens when the CO level is above 25 ppm (when used with a normally closed
contactor). Removal of the sensor, interruption of power, or cut wires cause the relay
circuit to open and start the fan. Minimum relay cycle time is 3 minutes to prevent
fan short-cycling.
Audible Alarm: An 85 dB alarm sounds if the CO level rises above 100 ppm for 30
minutes.
WIRING DIAGRAM
-
-
0-10V/0-5V
or
4-20mA
DDC
SYSTEM
+
+
SENSOR
V in
ALARM
COMM
N.O.
OUT
Out 0-5V/10V or 4-20mA
IN V+ 15-30VDC, 24VAC
Common
N.O. Relay
N.O. Relay
CONTACTOR
POWER
SENSOR DETAIL
200
10V
OUTPUT
PPM
N.C.
CONTACTOR
5V
100
FAN
POWER
TROUBLESHOOTING
Problem Solution
4-20 mA output does not function • Verify that the unit is a 4-20 model.
• Verify that the unit is wired for sourcing output.
Output is half or twice what is
expected
Output is inaccurate or unstable • Allow 96 hours for sensor to burn in and stabilize.
• Verify span jumper is set to desired scale.
• For voltage units, verify jumper is set to desired
voltage output scale.
SERVICE
For any service or installation, consult qualied service personnel. To ensure
continued reliable operation, replace the sensor module every ve years with a Veris
Industries CO sensor replacement module (Veris part number AA09).
Replacement instructions:
1. Disconnect power from the unit.
2. Carefully remove the old sensor module.
3. Install the new module rmly into the socket.
4. Reconnect power to the unit.
5. The replacement sensor requires 96 hours to stabilize after initial power
application.
The sensor module is factory calibrated. No eld calibration is required or possible.
Verify proper operation by observing the LED indicators.
Z202025-0P PAGE 2 ©2013 Veris Industries USA 800.354.8556 or +1(0)503.598.4564 / support@veris.com 03131