Veris GMxA Installation Instructions

TM
ENVIRONMENTAL SENSORS
INSTALLATION GUIDE
GMxA SerieS GMxA SerieS
Carbon Monoxide Monitoring Station
Installer’s Specifications
Supply Power 24VAC/VDC@1.3A Inputs Detect contact closure from G Series relay. Four channels. 24VDC loop Output Form C (SPDT) relay; 5A@30VAC/VDC Sensor Power Output 24VDC, 1A max. Alarm Indicators Four, 10mm Red LED; indicates alarm status Power Indicator Internal Green LED; indicates power supply operation Operating Environment -20° to 50°C (-4° t o 122°F); 0 to 90 % RH non-condensing
QUICK INSTALL
1. Lock out all power supplies prior to installation or ser vice.
NOTICE
• This product is not intended for life or safety applications.
• Do not install this product in hazardous or classified locations.
• Read and understand the instructions before installing this product.
• Turn off all power supplying equipment before working on it.
• The installer is responsible for conformance to all applicable codes.
PRODUCT IDENTIFICATION
GM A
0 = Station On ly 1 = 1 Sensor 2 = 2 Sensor s 3 = 3 Sensor s 4 = 4 Sensor s
N.C. COMM N.O.
CONTACTOR
POWER
Jumper unused Inputs as shown.
N.C. CONTACTOR
VERIS GW/GD SENSOR
(sold separately)
Common Out 0-5V/10V or 4-20mA IN V+ 15-30VDC, 24VAC N.O. Relay N.O. Relay
200
PPM
WIRING DIAGRAM
24VDC/VAC
COMMON
FAN
GMxA
MONITORING
STATION
Note: Position of jumper strip may vary depending on the version ordered.
RELAY
GND
V+
IN
V+
IN
Connect G Series sensors to input terminals as indicated. To ensure proper operation, all unused inputs must be jumpered from (V+) to (IN) as shown in the wiring diagram.
FAN
POWER
5V
10V
OUTPUT
100
2. Select a location for the sensor in a secure area where it will be accessible only to qualied service personnel. The GMxA Series monitoring station should be installed centrally in the parking structure, near the main trac paths, but away from outside air vents and excessive drafts. Mount the unit securely to a wall or column at a height of about 5 ft. (1.52 m) from the oor.
3. Connect only Veris Industries, G Series carbon monoxide sensors to the GMxA monitoring station.
4. Connect only 24VAC/24VDC power to the two-position terminal block as shown in the wiring diagram. Connect a ground wire to the metal case at a mountinig screw or metal conduit tting.
5. Apply power to the unit. A green LED on the circuit board indicates power is applied.
Note: Coverage is NOT dependant on the sensor. Coverage is a function of the buildi ng structure and air ow pat terns. A minimum of on e sensor for 5000 sq. f t. is recommended. Wide open a reas where the air is well mixed may requi re a few sensors.
OPERATION
The GMxA Series monitoring station accepts digital inputs from up to four G Series carbon monoxide sensors. It provides alarm status indication for each input and a normally open Form C (SPDT) fan actuation relay controlling a normally closed fan contactor. If any of the four sensors detect CO levels above 25 ppm, or if a fault is detected, the corresponding alarm status indicator light turns on and the fan relay will activate the fan.
DIMENSIONS
4.9"
(125 mm)
GM CARBON MONOXIDE
MONITOR
ALARM STATUS
1
2
3
4
6.5"
(166 mm)
2.8"
(71 mm)
To provide fail-safe operation, the normally open fan relay contacts must be used with a normally closed motor starter or contactor.
0.5"
(13 mm)
Z201872-0P PAGE 1 ©2010 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com 12101