ENVIRONMENTAL SENSORS
INSTALLATION GUIDE
GMxA SerieS GMxA SerieS
Carbon Monoxide Monitoring Station
Installer’s Specifications
Supply Power 24VAC/VDC@1.3A
Inputs Detect contact closure from G Series relay. Four channels. 24VDC loop
Output Form C (SPDT) relay; 5A@30VAC/VDC
Sensor Power Output 24VDC, 1A max.
Alarm Indicators Four, 10mm Red LED; indicates alarm status
Power Indicator Internal Green LED; indicates power supply operation
Operating Environment -20° to 50°C (-4° t o 122°F); 0 to 90 % RH non-condensing
QUICK INSTALL
1. Lock out all power supplies prior to installation or ser vice.
NOTICE
• This product is not intended for life or safety applications.
• Do not install this product in hazardous or classified locations.
• Read and understand the instructions before installing
this product.
• Turn off all power supplying equipment before working on it.
• The installer is responsible for conformance to all applicable codes.
PRODUCT IDENTIFICATION
GM A
0 = Station On ly
1 = 1 Sensor
2 = 2 Sensor s
3 = 3 Sensor s
4 = 4 Sensor s
N.C.
COMM
N.O.
CONTACTOR
POWER
Jumper
unused Inputs
as shown.
N.C. CONTACTOR
VERIS GW/GD SENSOR
(sold separately)
Common
Out 0-5V/10V or 4-20mA
IN V+ 15-30VDC, 24VAC
N.O. Relay
N.O. Relay
200
PPM
WIRING DIAGRAM
24VDC/VAC
COMMON
FAN
GMxA
MONITORING
STATION
Note: Position of
jumper strip may
vary depending
on the version
ordered.
RELAY
GND
V+
IN
V+
IN
Connect G Series sensors to input terminals as indicated. To ensure proper
operation, all unused inputs must be jumpered from (V+) to (IN) as shown in the
wiring diagram.
FAN
POWER
5V
10V
OUTPUT
100
2. Select a location for the sensor in a secure area where it will be accessible only
to qualied service personnel. The GMxA Series monitoring station should be
installed centrally in the parking structure, near the main trac paths, but away
from outside air vents and excessive drafts. Mount the unit securely to a wall or
column at a height of about 5 ft. (1.52 m) from the oor.
3. Connect only Veris Industries, G Series carbon monoxide sensors to the GMxA
monitoring station.
4. Connect only 24VAC/24VDC power to the two-position terminal block as shown
in the wiring diagram. Connect a ground wire to the metal case at a mountinig
screw or metal conduit tting.
5. Apply power to the unit. A green LED on the circuit board indicates power is
applied.
Note: Coverage is NOT dependant on the sensor. Coverage is a function of the buildi ng structure
and air ow pat terns. A minimum of on e sensor for 5000 sq. f t. is recommended. Wide open a reas
where the air is well mixed may requi re a few sensors.
OPERATION
The GMxA Series monitoring station accepts digital inputs from up to four G Series
carbon monoxide sensors. It provides alarm status indication for each input and a
normally open Form C (SPDT) fan actuation relay controlling a normally closed fan
contactor. If any of the four sensors detect CO levels above 25 ppm, or if a fault is
detected, the corresponding alarm status indicator light turns on and the fan relay
will activate the fan.
DIMENSIONS
4.9"
(125 mm)
GM CARBON MONOXIDE
MONITOR
ALARM STATUS
1
2
3
4
6.5"
(166 mm)
2.8"
(71 mm)
To provide fail-safe operation, the normally open fan relay contacts must be used
with a normally closed motor starter or contactor.