Veris EP3 Installation Instructions

TM
1.8"
(46 mm)
3.73"
(95 mm)
3.45"
(88 mm)
2.1"
(53 mm)
4.9"
(125 mm)
ENVIRONMENTAL SENSORS
EP3
Electropneumatic Transducer
available
• This product is not intended for life or safety applications.
• Do not install this product in hazardous or classied locations.
• Read and understand the instructions before installing this product.
• Turn off all power supplying equipment before working on it.
• The installer is responsible for conformance to all applicable codes.
INSTALLATION GUIDE
SPECIFICATIONS
Input Power 22-30VDC, 20-30VAC, 47-63 Hz, 150mA max. average, 350mA peak Control Input 4-20mA, (0-10V, 0-5V; jumper selectable), Tri-State, PWM Input Impedance 4-20mA, 250 Ω; 0-5/0-10V, 10 kΩ Manual Override Digital pushbutton adjust, switch selectable mode Alarm Contact 100mA@30VAC/DC (Pressure loss, manual mode, jumper selec table) Accuracy 1% F.S.; combined linearity, hysteresis, repeatability @20°C ambient Temperature Coecient ±0.1%/°C Operational Temperature Range 5°C to 60°C (41° to 14 0°F) Operating Humidity Range 10-90% RH, non-condensing SCIM 523 in3/min@45 psi (8520 cm3/min@310.3 kPa;) 333 in3/min@20 psi (5407 cm3/min@137.9 kPa) Supply Pressure Minimum (0.1 psi plus user F.S. pressure), maximum (45 psig) Control Range User pro grammable zero selectable from 0-25 psi: full scale 0-25 psi Pressure Dierential 0.1 psig (supply to branch) Pressure Indication Electronic, 3½ digit backlit LCD Minimum Tubing Length 15 feet* Port Connection 1/8 i.d. poly tubing Media Connection Clean dry air or inert gas. Not for use with oxygen service
* For shorter tubing runs use the Veris AA45 Pneumatic Capacitor EMC Conformance: EN 61000- 6-3 Class B:2007+A1 2011, EN 61000- 6-1:2007, EN 61000-3-2:2000, EN 61000-3-3:2001 EMC Special Note: connect this produ ct to a DC distribution network or an AC/DC po wer adapter with proper surge protection (EN 6100-6-1:2001 specication requirements).
No responsibility is assumed by Veris Industries for any consequences arising out of the
use of this material.
PRODUCT IDENTIFICATION
Output
EP3
0 = None 3 = Analog out put: 0-10VDC or 4-2 0mA (selectable)
Feedback
3
3 = Pressur e Loss Alarm o r Manual Mode Alarm
Failsafe Option
0 = None 1 = Vent on power fail
US or EU
S = Standard C = CE (CE versions include cov er plat e)
Blank = None 2 = EP Cover Plate
DIMENSIONS
FRONT VIEW - DUST COVER
INSTALLATION
Observe precautions for handling static sensitive devices to avoid damage to the circuitry that is not covered under the factory warranty.
1. Mount the EP3 transducer using the screws provided.
2. Congure the jumpers for desired operation as shown (page 2).
3. Wire the transducer as shown in the wiring diagram (page 3).
4. Attach pressure tubing to the hose barbs. Observe MAIN and BRANCH port labels. Use exible 1/8” I.D. poly tubing for main and branch pneumatic connections.
Main supply pressure must not exceed 45 psig.
SIDE VIEW - DUST COVER
Z203959-0G PAGE 1 ©2013 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com 05132
Alta Labs, Ene rcept, Enspector, Hawk eye, Trustat, Aerospon d, Veris, and the Veris ‘V ’ logo are tradem arks or registe red trademarks o f Veris Industries, L .L.C. in the USA and/or ot her countries.
TM
Auto
Manual
GND
INPUT
24V
CH2
CH1/PWM
OPERATION
MODE
TRISTATE
ALARM
P-LOSS MAN
INPUT VOLTAGE
0-10V 0-5V TRI-PULL-UP
ON OFF
OUTPUT
4-20mA 0-10V
ALARM
Tristate Timing Network FS Point Zero RUN
4-20mA Voltage Tristate
PWM
Network
Control
SETTING
INPUT
+
-
Subtract
Pressure
Add Pressure
4-20mA
Output
0-10V
Output
EP3
CONFIGURATION
Switch/Jumper Description
Input User selectable slide switch: current (4-20 mA), voltage (0-5/0-10
V), Tristate, or PWM (min 0.01-0.60 sec, max 1.0-75.0 sec).
Note: the Network Control option is disabled.
Input Voltage* If voltage input is selected, use this jumper to choose 0-5 or 0-10 V.
Tri Pull-up If tristate input is selected, use this jumper to turn the pull-up on
or o.
Alarm Phase loss or manual
Output Use this jumper to select 4-20 mA or 0-10 V output (feedback status
for branch pressure.
Setting User selectable slide switch: Tristate timing (min 1 sec; max 600 sec,
default 60 sec), FS Point (scale point user programmable 0-25 psi), Zero (user programmable 0-25 psig), Run.
Note: the Network option is disabled.
Mode Auto for normal operation; Manual to adjust pressure.
Set this switch last.
* EP3 accepts DC input only. To use with AC input, include a Veris AA49 Triac Adapter in series between the input voltage a nd the EP3.
INSTALLATION GUIDE
Z203959-0G PAGE 2 ©2013 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com 05132
Alta Labs, Ene rcept, Enspector, Hawk eye, Trustat, Aerospon d, Veris, and the Veris ‘V ’ logo are tradem arks or registe red trademarks o f Veris Industries, L .L.C. in the USA and/or ot her countries.
WIRING
GND
INPUT
+24V
CH2
CH1/PWM
4-20mA
0-10V
ALARM CONTACTS
POWER SOURCE
Digital Input (Contact Closure)
0-10V PROCESS METER
BRANCH
TRAP/ FILTER
20-45psi
Regulator
+
-
Analog Out Common
AIR COMPRESSOR
+
-
TM
EP3
INSTALLATION GUIDE
Current/voltage Control, Voltage Output Example
Input switch set to voltage (0-5VDC or 0-10VDC)
• Input volt jumper set to either 0-5VDC or 0-10VDC
• Input switch set to 4-20mA
• Output jumper set to 0-10VDC
AIR COMPRESSOR
Current/voltage Control, Current Output Example
TRAP/
GND
POWER SOURCE
INPUT
+24V
FILTER
CH2
CH1/PWM
BRANCH
4-20mA
0-10V
• Input switch settings same as example 1
• Output jumper set to 4-20mA
ALARM CONTACTS
4-20mA PROCESS METER
20-45psi
Regulator
+
-
Digital Input (Contact Closure)
Analog Out (0-5/0-10/4-20mA) Common
PWM Control Example
GND
-
POWER SOURCE
TRAP/ FILTER
INPUT
+24V
CH2
CH1/PWM
+
PWM CONTACT
• Input switch set to "PWM"
• Tri-State jumper set to "ON"
BRANCH
4-20mA
0-10V
AIR COMPRESSOR
ALARM CONTACTS
AIR COMPRESSOR
20-45psi
Regulator
Z203959-0G PAGE 3 ©2013 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com 05132
Alta Labs, Ene rcept, Enspector, Hawk eye, Trustat, Aerospon d, Veris, and the Veris ‘V ’ logo are tradem arks or registe red trademarks o f Veris Industries, L .L.C. in the USA and/or ot her countries.
Tri-state Control Example
TRAP/
GND
-
POWER SOURCE
INPUT
+
+24V
FILTER
CH2
CH1/PWM
CH1ORCH2
OR
+
-
Pressure
Subtract
TRI-STATE CONTACTS
Add Pressure
20-45psi
Regulator
BRANCH
4-20mA
0-10V
ALARM CONTACTS
• Input switch set to "TRI-STATE"
• Tri-State jumper set to "ON"
TM
SPECIAL INSTRUCTIONS
PWM Mode
To set the minimum pulse value, adjust the Input and Setting switches as shown:
EP3
INPUT
4-20mA Voltage Tristate
PWM
Network
Control
"LO" momentarily appears on the LCD, indicating that the minimum pulse width is
being set. Use the (+) and (-) buttons to increase or decrease this value. To set the
maximum pulse width push both buttons simultaneously. "HI" momentarily appears,
indicating that the maximum pulse width is being set. Push both buttons to toggle
between the "HI" and "LO" settings. To save these settings, move the Setting slide
switch to RUN.
If the controller receives a pulse that is shorter than the minimum pulse width, the output goes to 0% of the range set with the zero and span settings. If the controller sees a pulse that is the same or longer than the maximum pulse width, the output goes to 100% of the range selected with the zero and span settings.
In this example the minimum pulse width is set to 0.60 sec, the maximum is set to 10 sec, zero is set to 0, and span is set to 10 psi. Assume the controller receives a pulse of 5 sec duration:
Pulse range = 10 sec – 0.60 sec = 9.4 sec
Pressure range = span – zero = 10 – 0 = 10
Output = (5 / 9.4) x 10 = 5.3 psi
Tristate Mode
Traveltime is dened as the contact closure time required to go from zero to full scale. If traveltime is set to 10 seconds and the TRISTATE 1 input is connected to ground for 5 seconds, the output is 50%. If the input is connected to ground for another 5 seconds, the output is 100%. If TRISTATE 2 (the decreasing input) is grounded for 10 seconds, the products output return to 0%.
To set the travel time, adjust the Setting and Input switches as shown:
INPUT
4-20mA Voltage Tristate
PWM
Network
Control
Press the (+) or (-) buttons to increase or decrease the travel time. Minimum travel time is 1 second; maximum is 600 seconds. To save these settings, move the Setting slide switch to RUN. The device's internal counters measure the contact closure time with 100 Hz resolution.
Note: If Tristate input is to be operated by a triac output (Veris AA49), use an AC relay to provide a dry contact closure to the EP3 input.
Tubing Length
Minimum tubing length is 15 feet or an equivalent volume of 2.2 cubic inches. Shorter tubing lengths cause the unit to oscillate.
SETTING
SETTING
Tristate Timing Network FS Point Zero RUN
Tristate Timing Network FS Point Zero RUN
INSTALLATION GUIDE
Analog Output
The output is generated from the branch pressure. It is calculated as follows:
FS = Full Scale Point
Zero = Zero setting
In volt mode:
Pressure = (10 / (FS - Zero)) * Voltage + Zero Voltage = (Pressure - Zero) / (FS - Zero) * 10
In current mode:
Pressure = (FS - Zero) * ((Current - 4) / 16) + Zero Current (in mA) = ((Pressure - Zero) / (FS - Zero)) * 16 + 4
Examples:
Zero setting = 5 psi; Span = 20 psi; Branch pressure = 16 psi Volt mode: Voltage = ((16 - 5) / (20 - 5)) * 10 = 7.33 V Current mode: Current = ((16 - 5) / (20 - 5)) * 16 + 4 = 15.73 mA
Alarms
Auto Mode: Alarm contacts are closed in normal operation and are open when no power is applied or when the device is in an alarm state.
Manual Mode: Alarm contacts are open in manual mode setting and closed for normal operation. Move the P-LOSS/MAN jumper to the manual mode setting. You do not need to power cycle the product af ter moving jumpers or the Auto/Manual switch.
Pressure Loss Alarm: Contacts open when the branch pressure falls and stays below 20% of the desired pressure for a period of 2 minutes.
FS Point and Zero Setting
To set the Zero or FS point, move the SETTING slide switch from Run to Zero or FS point setting, respectively.
SETTING
Tristate Timing Network FS Point Zero RUN
The ‘Set’ icon appears on the LCD. Use the (+) and (-) buttons to increase or decrease the pressure setpoints.
LED Blink Codes
Slow green Normal operation
Slow green with one fast red Manual mode alarm (contacts open)
Slow green with two fast reds Pressure loss alarm active (contacts open)
Slow red SETTINGS slide switch not in Run position
Two fast reds Settings slide switch not in Run position and Alarm
Three fast reds Over-voltage or over-current fault
Four fast reds Over pressure on branch side; over 25 psi.
(contacts open)
SETTING
Tristate Timing Network
or
FS Point Zero RUN
Z203959-0G PAGE 4 ©2013 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com 05132