Veris EP3 Installation Instructions

TM
1.8"
(46 mm)
3.73"
(95 mm)
3.45"
(88 mm)
2.1"
(53 mm)
4.9"
(125 mm)
ENVIRONMENTAL SENSORS
EP3
Electropneumatic Transducer
available
• This product is not intended for life or safety applications.
• Do not install this product in hazardous or classied locations.
• Read and understand the instructions before installing this product.
• Turn off all power supplying equipment before working on it.
• The installer is responsible for conformance to all applicable codes.
INSTALLATION GUIDE
SPECIFICATIONS
Input Power 22-30VDC, 20-30VAC, 47-63 Hz, 150mA max. average, 350mA peak Control Input 4-20mA, (0-10V, 0-5V; jumper selectable), Tri-State, PWM Input Impedance 4-20mA, 250 Ω; 0-5/0-10V, 10 kΩ Manual Override Digital pushbutton adjust, switch selectable mode Alarm Contact 100mA@30VAC/DC (Pressure loss, manual mode, jumper selec table) Accuracy 1% F.S.; combined linearity, hysteresis, repeatability @20°C ambient Temperature Coecient ±0.1%/°C Operational Temperature Range 5°C to 60°C (41° to 14 0°F) Operating Humidity Range 10-90% RH, non-condensing SCIM 523 in3/min@45 psi (8520 cm3/min@310.3 kPa;) 333 in3/min@20 psi (5407 cm3/min@137.9 kPa) Supply Pressure Minimum (0.1 psi plus user F.S. pressure), maximum (45 psig) Control Range User pro grammable zero selectable from 0-25 psi: full scale 0-25 psi Pressure Dierential 0.1 psig (supply to branch) Pressure Indication Electronic, 3½ digit backlit LCD Minimum Tubing Length 15 feet* Port Connection 1/8 i.d. poly tubing Media Connection Clean dry air or inert gas. Not for use with oxygen service
* For shorter tubing runs use the Veris AA45 Pneumatic Capacitor EMC Conformance: EN 61000- 6-3 Class B:2007+A1 2011, EN 61000- 6-1:2007, EN 61000-3-2:2000, EN 61000-3-3:2001 EMC Special Note: connect this produ ct to a DC distribution network or an AC/DC po wer adapter with proper surge protection (EN 6100-6-1:2001 specication requirements).
No responsibility is assumed by Veris Industries for any consequences arising out of the
use of this material.
PRODUCT IDENTIFICATION
Output
EP3
0 = None 3 = Analog out put: 0-10VDC or 4-2 0mA (selectable)
Feedback
3
3 = Pressur e Loss Alarm o r Manual Mode Alarm
Failsafe Option
0 = None 1 = Vent on power fail
US or EU
S = Standard C = CE (CE versions include cov er plat e)
Blank = None 2 = EP Cover Plate
DIMENSIONS
FRONT VIEW - DUST COVER
INSTALLATION
Observe precautions for handling static sensitive devices to avoid damage to the circuitry that is not covered under the factory warranty.
1. Mount the EP3 transducer using the screws provided.
2. Congure the jumpers for desired operation as shown (page 2).
3. Wire the transducer as shown in the wiring diagram (page 3).
4. Attach pressure tubing to the hose barbs. Observe MAIN and BRANCH port labels. Use exible 1/8” I.D. poly tubing for main and branch pneumatic connections.
Main supply pressure must not exceed 45 psig.
SIDE VIEW - DUST COVER
Z203959-0G PAGE 1 ©2013 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com 05132
Alta Labs, Ene rcept, Enspector, Hawk eye, Trustat, Aerospon d, Veris, and the Veris ‘V ’ logo are tradem arks or registe red trademarks o f Veris Industries, L .L.C. in the USA and/or ot her countries.
TM
Auto
Manual
GND
INPUT
24V
CH2
CH1/PWM
OPERATION
MODE
TRISTATE
ALARM
P-LOSS MAN
INPUT VOLTAGE
0-10V 0-5V TRI-PULL-UP
ON OFF
OUTPUT
4-20mA 0-10V
ALARM
Tristate Timing Network FS Point Zero RUN
4-20mA Voltage Tristate
PWM
Network
Control
SETTING
INPUT
+
-
Subtract
Pressure
Add Pressure
4-20mA
Output
0-10V
Output
EP3
CONFIGURATION
Switch/Jumper Description
Input User selectable slide switch: current (4-20 mA), voltage (0-5/0-10
V), Tristate, or PWM (min 0.01-0.60 sec, max 1.0-75.0 sec).
Note: the Network Control option is disabled.
Input Voltage* If voltage input is selected, use this jumper to choose 0-5 or 0-10 V.
Tri Pull-up If tristate input is selected, use this jumper to turn the pull-up on
or o.
Alarm Phase loss or manual
Output Use this jumper to select 4-20 mA or 0-10 V output (feedback status
for branch pressure.
Setting User selectable slide switch: Tristate timing (min 1 sec; max 600 sec,
default 60 sec), FS Point (scale point user programmable 0-25 psi), Zero (user programmable 0-25 psig), Run.
Note: the Network option is disabled.
Mode Auto for normal operation; Manual to adjust pressure.
Set this switch last.
* EP3 accepts DC input only. To use with AC input, include a Veris AA49 Triac Adapter in series between the input voltage a nd the EP3.
INSTALLATION GUIDE
Z203959-0G PAGE 2 ©2013 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com 05132
Alta Labs, Ene rcept, Enspector, Hawk eye, Trustat, Aerospon d, Veris, and the Veris ‘V ’ logo are tradem arks or registe red trademarks o f Veris Industries, L .L.C. in the USA and/or ot her countries.
Loading...
+ 2 hidden pages