• This product is not intended for life or safety applications.
• Do not install this product in hazardous or classied locations.
• Read and understand the instructions before installing
this product.
• Turn off all power supplying equipment before working on it.
• The installer is responsible for conformance to all applicable codes.
INSTALLATION GUIDE
SPECIFICATIONS
Input Power 22-30VDC, 20-30VAC, 47-63 Hz, 150mA max. average, 350mA peak
Control Input 4-20mA, (0-10V, 0-5V; jumper selectable), Tri-State, PWM
Input Impedance 4-20mA, 250 Ω; 0-5/0-10V, 10 kΩ
Manual Override Digital pushbutton adjust, switch selectable mode
Alarm Contact 100mA@30VAC/DC (Pressure loss, manual mode, jumper selec table)
Accuracy 1% F.S.; combined linearity, hysteresis, repeatability @20°C ambient
Temperature Coecient ±0.1%/°C
Operational Temperature Range 5°C to 60°C (41° to 14 0°F)
Operating Humidity Range 10-90% RH, non-condensing
SCIM 523 in3/min@45 psi (8520 cm3/min@310.3 kPa;)
333 in3/min@20 psi (5407 cm3/min@137.9 kPa)
Supply Pressure Minimum (0.1 psi plus user F.S. pressure), maximum (45 psig)
Control Range User pro grammable zero selectable from 0-25 psi: full scale 0-25 psi
Pressure Dierential 0.1 psig (supply to branch)
Pressure Indication Electronic, 3½ digit backlit LCD
Minimum Tubing Length 15 feet*
Port Connection 1/8 i.d. poly tubing
Media Connection Clean dry air or inert gas. Not for use with oxygen service
* For shorter tubing runs use the Veris AA45 Pneumatic Capacitor
EMC Conformance: EN 61000- 6-3 Class B:2007+A1 2011, EN 61000- 6-1:2007, EN 61000-3-2:2000,
EN 61000-3-3:2001
EMC Special Note: connect this produ ct to a DC distribution network or an AC/DC po wer adapter
with proper surge protection (EN 6100-6-1:2001 specication requirements).
No responsibility is assumed by Veris Industries for any consequences arising out of the
use of this material.
PRODUCT IDENTIFICATION
Output
EP3
0 = None
3 = Analog out put:
0-10VDC or
4-2 0mA
(selectable)
Feedback
3
3 = Pressur e
Loss Alarm o r
Manual Mode
Alarm
FailsafeOption
0 = None
1 = Vent on
power fail
US or EU
S = Standard
C = CE
(CE versions
include cov er
plat e)
Blank = None
2 = EP Cover
Plate
DIMENSIONS
FRONT VIEW - DUST COVER
INSTALLATION
Observe precautions for handling static sensitive
devices to avoid damage to the circuitry that
is not covered under the factory warranty.
1. Mount the EP3 transducer using the screws provided.
2. Congure the jumpers for desired operation as shown (page 2).
3. Wire the transducer as shown in the wiring diagram (page 3).
4. Attach pressure tubing to the hose barbs. Observe MAIN and BRANCH port labels.
Use exible 1/8” I.D. poly tubing for main and branch pneumatic connections.
Alta Labs, Ene rcept, Enspector, Hawk eye, Trustat, Aerospon d, Veris, and the Veris ‘V ’ logo are tradem arks or registe red trademarks o f Veris Industries, L .L.C. in the USA and/or ot her countries.
TM
Auto
Manual
GND
INPUT
24V
CH2
CH1/PWM
OPERATION
MODE
TRISTATE
ALARM
P-LOSS MAN
INPUT VOLTAGE
0-10V 0-5V
TRI-PULL-UP
ON OFF
OUTPUT
4-20mA 0-10V
ALARM
Tristate Timing
Network
FS Point
Zero
RUN
4-20mA
Voltage
Tristate
PWM
Network
Control
SETTING
INPUT
+
-
Subtract
Pressure
Add Pressure
4-20mA
Output
0-10V
Output
EP3
CONFIGURATION
Switch/Jumper Description
InputUser selectable slide switch: current (4-20 mA), voltage (0-5/0-10
V), Tristate, or PWM (min 0.01-0.60 sec, max 1.0-75.0 sec).
Note: the Network Control option is disabled.
Input Voltage*If voltage input is selected, use this jumper to choose 0-5 or 0-10 V.
Tri Pull-upIf tristate input is selected, use this jumper to turn the pull-up on
or o.
AlarmPhase loss or manual
OutputUse this jumper to select 4-20 mA or 0-10 V output (feedback status
Alta Labs, Ene rcept, Enspector, Hawk eye, Trustat, Aerospon d, Veris, and the Veris ‘V ’ logo are tradem arks or registe red trademarks o f Veris Industries, L .L.C. in the USA and/or ot her countries.
WIRING
GND
INPUT
+24V
CH2
CH1/PWM
4-20mA
0-10V
ALARM CONTACTS
POWER
SOURCE
Digital Input
(Contact Closure)
0-10V PROCESS METER
BRANCH
TRAP/
FILTER
20-45psi
Regulator
+
-
Analog Out
Common
AIR COMPRESSOR
+
-
TM
EP3
INSTALLATION GUIDE
Current/voltage Control, Voltage Output Example
• Input switch set to voltage (0-5VDC or 0-10VDC)
• Input volt jumper set to either 0-5VDC or 0-10VDC
Alta Labs, Ene rcept, Enspector, Hawk eye, Trustat, Aerospon d, Veris, and the Veris ‘V ’ logo are tradem arks or registe red trademarks o f Veris Industries, L .L.C. in the USA and/or ot her countries.
Tri-state Control Example
TRAP/
GND
-
POWER
SOURCE
INPUT
+
+24V
FILTER
CH2
CH1/PWM
CH1ORCH2
OR
+
-
Pressure
Subtract
TRI-STATE CONTACTS
Add Pressure
20-45psi
Regulator
BRANCH
4-20mA
0-10V
ALARM CONTACTS
• Input switch set to "TRI-STATE"
• Tri-State jumper set to "ON"
TM
SPECIAL INSTRUCTIONS
PWM Mode
To set the minimum pulse value, adjust the Input and Setting switches as shown:
EP3
INPUT
4-20mA
Voltage
Tristate
PWM
Network
Control
"LO" momentarily appears on the LCD, indicating that the minimum pulse width is
being set. Use the (+) and (-) buttons to increase or decrease this value. To set the
maximum pulse width push both buttons simultaneously. "HI" momentarily appears,
indicating that the maximum pulse width is being set. Push both buttons to toggle
between the "HI" and "LO" settings. To save these settings, move the Setting slide
switch to RUN.
If the controller receives a pulse that is shorter than the minimum pulse width, the
output goes to 0% of the range set with the zero and span settings. If the controller
sees a pulse that is the same or longer than the maximum pulse width, the output
goes to 100% of the range selected with the zero and span settings.
In this example the minimum pulse width is set to 0.60 sec, the maximum is set to 10
sec, zero is set to 0, and span is set to 10 psi. Assume the controller receives a pulse of
5 sec duration:
Pulse range = 10 sec – 0.60 sec = 9.4 sec
Pressure range = span – zero = 10 – 0 = 10
Output = (5 / 9.4) x 10 = 5.3 psi
Tristate Mode
Traveltime is dened as the contact closure time required to go from zero to full scale.
If traveltime is set to 10 seconds and the TRISTATE 1 input is connected to ground for 5
seconds, the output is 50%. If the input is connected to ground for another 5 seconds,
the output is 100%. If TRISTATE 2 (the decreasing input) is grounded for 10 seconds,
the products output return to 0%.
To set the travel time, adjust the Setting and Input switches as shown:
INPUT
4-20mA
Voltage
Tristate
PWM
Network
Control
Press the (+) or (-) buttons to increase or decrease the travel time. Minimum travel
time is 1 second; maximum is 600 seconds. To save these settings, move the Setting
slide switch to RUN. The device's internal counters measure the contact closure time
with 100 Hz resolution.
Note: If Tristate input is to be operated by a triac output (Veris AA49), use an AC relay
to provide a dry contact closure to the EP3 input.
Tubing Length
Minimum tubing length is 15 feet or an equivalent volume of 2.2 cubic inches.
Shorter tubing lengths cause the unit to oscillate.
SETTING
SETTING
Tristate Timing
Network
FS Point
Zero
RUN
Tristate Timing
Network
FS Point
Zero
RUN
INSTALLATION GUIDE
Analog Output
The output is generated from the branch pressure. It is calculated as follows:
FS = Full Scale Point
Zero = Zero setting
In volt mode:
Pressure = (10 / (FS - Zero)) * Voltage + Zero
Voltage = (Pressure - Zero) / (FS - Zero) * 10
In current mode:
Pressure = (FS - Zero) * ((Current - 4) / 16) + Zero
Current (in mA) = ((Pressure - Zero) / (FS - Zero)) * 16 + 4
Examples:
Zero setting = 5 psi; Span = 20 psi; Branch pressure = 16 psi
Volt mode: Voltage = ((16 - 5) / (20 - 5)) * 10 = 7.33 V
Current mode: Current = ((16 - 5) / (20 - 5)) * 16 + 4 = 15.73 mA
Alarms
Auto Mode: Alarm contacts are closed in normal operation and are open when no
power is applied or when the device is in an alarm state.
Manual Mode: Alarm contacts are open in manual mode setting and closed for
normal operation. Move the P-LOSS/MAN jumper to the manual mode setting. You
do not need to power cycle the product af ter moving jumpers or the Auto/Manual
switch.
Pressure Loss Alarm: Contacts open when the branch pressure falls and stays below
20% of the desired pressure for a period of 2 minutes.
FS Point and Zero Setting
To set the Zero or FS point, move the SETTING slide switch from Run to Zero or FS
point setting, respectively.
SETTING
Tristate Timing
Network
FS Point
Zero
RUN
The ‘Set’ icon appears on the LCD. Use the (+) and (-) buttons to increase or decrease
the pressure setpoints.
LED Blink Codes
Slow greenNormal operation
Slow green with one fast redManual mode alarm (contacts open)
Slow green with two fast redsPressure loss alarm active (contacts open)
Slow redSETTINGS slide switch not in Run position
Two fast redsSettings slide switch not in Run position and Alarm
Three fast redsOver-voltage or over-current fault
Four fast redsOver pressure on branch side; over 25 psi.
Alta Labs, Ene rcept, Enspector, Hawk eye, Trustat, Aerospon d, Veris, and the Veris ‘V ’ logo are tradem arks or registe red trademarks o f Veris Industries, L .L.C. in the USA and/or ot her countries.