HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
• Follow safe electrical work practices.
See NFPA 70E in the USA, or applicable local codes.
• This equipment must only be installed and serviced by qualified electrical personnel.
• Read, understand and follow the instructions before installing this product.
• Turn off all power supplying equipment before working on or inside the equipment.
• Use a properly rated voltage sensing device to confirm power is off.
DO NOT DEPEND ON THIS PRODUCT FOR VOLTAGE INDICATION
• Only install this product on insulated conductors.
Failure to follow these instructions will result in death or serious injury.
DANGER
CURRENT MONITORING
INSTALLATION GUIDE
EA20 SEriES
pulse reset
technology™
U.S. Pat. #6,160,697; 6,522,517; 7,242,157
RoHS
Compliant
EA20 SEriES
Split-Core Uni-Directional 4-20 mA Output
DC Current Transducer
Installer’s Specifications
Technology Exclusive Puls e Reset Technology™
Amperage Range for State d Accurac y 0.5A to 100, 150, or 200ADC
Sensor Supply Voltage 12 to 24VDC (for currents over 120A,
supply voltage must be at least 15V)
Supply Current 35mA to 110mA*
Insulation Class 1000VDC (insulated conductor)
Temperature Range -30° to 60°C (-2 2° to 14 0°F)
Humidity Range 10-90% RH non-condensing
Output 4-2 0mA
Accuracy ±0.5% full scale, combined linearity, hysteresis, and repeatabilit y
Withstand Current Up to 25,000ADC continuous
Terminal Block Maximum Wire Size 14 AWG
Terminal Block Torque (nominal) 4 in-lbs (0.45 N-m)
Rated Altitude 2000 m
Pollution Degree 2
Installation Category III
* At zero load current: 35 mA; at maximum load current: 55 mA to 110 mA, depending o n supply
voltage.
INSTALLATION
NOTICE
• This product is not intended for life or safety applications.
• Do not install this product in hazardous or classified locations.
• The installer is responsible for conformance to all applicable codes.
• Mount this product inside a suitable fire and electrical enclosure.
For use in a Pollu tion Degree 2 or bet ter environment only. A Pollut ion Degree 2 environme nt must
control conductive pollution and the possibility of condensation or high humidity. Consider the
enclosure, t he correct use of ven tilation, thermal pro perties of the equ ipment, and the relatio nship
with the env ironment. Installat ion category: CAT II or C AT III
PRODUCT IDENTIFICATION
MODEL AMPERAGE RANGE
(DC)
EA20BB010 0-100 A
EA20BB015 0-150 A
EA20BB020 0-200 A
Z206168- 0B PAGE 1 ©2012 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com 01122
Alta Labs, Enercep t, Enspector, Hawkeye, Trustat, Veris, and the Veris ‘ V’ logo are trademark s or registered tradema rks of Veris Industries, L.L .C. in the USA and /or other countri es.
1. Disconnect and lock out power to the conductor to be monitored.
2. Choose a location for the sensor. The monitored conduc tor must pass through the
iris, and the sensor must be at least 1/2” from any conductors, as enclosure can
reach 87°C during operation (at 200A and 60°C ambient temperature). Use wire
rated at a minimum of 90°C.
3. Install the adjustable mounting bracket to the back of the enclosure using the
included screws.
4. Connect 12-24 VDC to the terminals marked Power (+) and Gnd (-).
5. Wire the mA output connections between the sensor and the controller.
6. Snap the sensor over the conductor to be monitored and clip the assembly to the
mounting bracket.
WIRING EXAMPLE
4-20
mA
12–24 VDC
Gnd
Power
–
DIGITAL CONTROL
Power (12-24VDC)
Gnd
4-20 mA input
+
To
Load
DC
Load
TM
SENSED AMPS
4 mA
100 A/150 A/200 A
(depending on model)
0 A
20 mA
SENSOR OUTPUT
EA20 SERIES
INSTALLATION GUIDE
DIMENSIONS
Removable Mounting Bracket
1.0”
3.1”
(79 mm)
Ø = 0.3”
(8 mm)
1.1”
(26 mm)
(25 mm)
0.8”
(21 mm)
2.8”
(70 mm)
2.5”
(64 mm)
3.0”
(76 mm)
Bracket can be mounted
on three sides for added
installation exibility.
Self-gripping
Iris
1.4”
(36 mm)
Use DIN Rail
Mounting clip
(Veris part
number AH01) to
mount on stan-
dard DIN rail.
OPERATION
The EA20 Series of current-sensitive devices monitor DC current (amperage) in
the conductor passing through. These units use Pulse Reset Technology™ with
proven transducer circuitry to produce an output suitable for connection to energy
management systems, building controllers, or other appropriate data acquisition
equipment. The EA20 requires 12-24 VDC (see Specications information) to generate
its output. It comes factory calibrated at a xed span for maximum accuracy (0-100 A,
0-150 A, or 0-200 A, depending on model, see Product Identication).
NOTES
Load Currents Less Than 2 A
Wrap the monitored conductor through the center window and around the sensor
body to produce multiple turns. This increases
the current measured by the transducer.
Program equipment to account for the extra
turns, e.g., if four turns pass through the sensor
(as shown) then divide the reading by 4.
Wrapping may reduce the sensor’s accuracy.
1A
4x
CAUTION
RISK OF EQUIPMENT DAMAGE
• Derate the product’s maximum current for the number of turns
through the sensing window using the following formula.
Rated Max. Amps ÷ Number of Turns = Max. monitored Amps
e.g. : 100A ÷ 4 Turns = 25 Amps max. in monitored conductor
• Failure to follow these instructions can result in overheating
and permanent equipment damage.
High Load Current Monitoring
Do not expose the EA20 to continuous current levels greater than the rated maximum
current (brief current surges and fault currents should not adversely aect the EA20).
SCALING
The EA20 Series is ideal for DC current monitoring where accuracy must be
maintained in the presence of magnetic elds, current spikes, and high fault currents
(e.g. solar panels, electroplating equipment).
The EA20 Series housing oers unprecedented mounting exibility. The mounting
bracket can be attached in three dierent places. Additionally, the bracket is
compatible with the Veris AH01 DIN Rail clip, allowing DIN mounting.
LED INDICATOR BLINK CODES
LED Activity Status Description
Single green Normal operation
Double green Over span
Red/green Over limit
Solid red Overload
TROUBLESHOOTING
Problem Solution
The LED is o and no signal is
produced
The LED is on solid and the
output is at maximum
Verify that supply voltage is applied to PWR (+) and
GND (-) terminals.
Verify that the unit is not attempting to monitor more
than the maximum current range.
Z206168- 0B PAGE 2 ©2012 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com 01122