Veris EA10 Datasheet

EA10 SERIES
Direct Current String Monitor
DC Monitoring for Combiner Boxes
VERIS INDUSTRIES
EA10
DESCRIPTION
This system includes a communications unit that supplies power and provides Modbus communication. Up to four current sensing modules can connect serially to one communications unit, each with eight DC current sensors, for a total of 32 monitoring nodes. Connect up to 63 communications units in a daisy chain for full system monitoring. All boards can be mounted on standard DIN rail for easy installation.
current monitoring
APPLICATIONS
Renewable energy and string monitors
Industrial monitoring
Data centers
FEATURES
Pulse Reset technology...high immunity to power surges...greater repeatability
over time
Modular construction...connect up to four current sensing modules to one
communications unit...easy to install
Fully encapsulated...robust design is resistant to the elements
Monitors 2016 points total...minimize home run wiring
Up to 1000VDC isolation for high voltage strings
RS-485 Modbus communications...quick commissioning
Wide range DC power requirements...versatility
Fits onto standard 35 mm DIN rail...convenient installation
Amp-hour calculation...read once per day for less network trac
LED indication of faults...quick visible troubleshooting
May be installed in UL1741 systems...smart combiner capability
SPECIFICATIONS
Inputs:
Control Power Class 2/SELV 24VDC to 42VDC Maximum Power Consumption 7W at 32 channels Maximum Current Input Up to 20A per point
Accuracy:
Current 0.5% full scale (combined linearit y, hysteresis, and repeatability)
Outputs:
Communication 2-wire RS-4 85, 1200 to 384 00 baud, Modbus RTU Available Information Current per point, both instantaneous amps & cumulative amp-hours, events Update Rate 2 sec Maximum Measurement Points 8, 16, 24, or 32
Mechanical:
Mounting T35 (35 mm) DIN Rail per EN50022 Terminal Block Wire Size 24 to 12 AWG (0.21 to 3.31 mm2)
Terminal Block Torque 0.37ft-lb(0.5N•m)nominal/0.44ft-lb(0.6N•m)max.
Insulation (from current sensor to control power or RS-485 interface) Up to 1000 VDC (insulate d conductor) Dielectric Strength 10000 VDC
Environmental:
Operating Temperature Range -30° to 75°C (-22° to 167°F) Storage Temperature Range -4 0° to 85°C (-40° to 185°F) Humidity Range <95% RH noncondensing Altitude of Operation 3 km
Agency Approvals:
US and Canada Recognized (cRUus) UL61010-1, Acceptable in UL1741 Combiner Box Europe (CE) EN61010 -1 Installation Category Cat. IV, pollution degree 3
EMC:
Conducted and Radiated Emissions FCC Part 15 Class B, EN55011 / EN6100 0 Class B (residential and light industrial) Conducted and Radiated Immunity EN61000 Class A (heavy industrial)
800.354.8556
+1 503.598.4564
www.veris.com
Maximize Reliability
Minimize Installed Cost
HQ00 01769.C 01131
800.354.8556
Power
20-Pin Connector
+1 503.598.4564
www.veris.com
DIMENSIONAL DRAWING
3.7”
3.9”
(99 mm)
2.8”
(72 mm)
(94 mm)
1.6”
(41 mm)
0.5”
(13 mm)
5.5”
(139 mm)
4.3”
(110 mm)
5.5”
(139 mm)
0.7”
(17.5 mm)
2.4”
(61 mm)
1.0”
(25 mm)
0.8”
(20 mm)
DIN Rail
APPLICATION/WIRING DIAGRAM
Modbus Master RS-485
24 VDC Power Supply
+
S
+
DIP switches
Fuse Block
+
RS-485
(isolated)
S
+
DC Power
EA10 DC Current Sensing Module
StatusTxRx/Error
ORDERING INFORMATION
RoHS
Compliant
MODEL NUMBER OF CTs AMPERAGE RANGE OUTPUT
EA1 0DD0 8B DC curre nt sensing module w ith 8 strings, enc apsulated Up to 20A per CT
EA10HC1AB Communications unit, Modbus RTU, encapsulated, 24
VDC, supp orts up to four E A10DD08 B units (up to 32 strings per communications unit)
EA10 Communications Unit
Summing Block
current monitoring
Modbus RTU
ACCESSORIES
DIN Rail (AV01) and DIN Stop Clip (AV02)
HQ00 01769.C 01131
AV01
AV02
Loading...