TM
POWER MONITORING
INSTALLATION GUIDE
E682x SERIES
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
• Follow safe electrical work practices. See NFPA 70E in the USA, or applicable local codes.
• This equipment must only be installed and serviced by qualied electrical personnel.
• Read, understand and follow the instructions before installing this product.
• Turn o all power supplying equipment before working on or inside the equipment.
• Use a properly rated voltage sensing device to conrm power is o.
DO NOT DEPEND ON THIS PRODUCT FOR VOLTAGE INDICATION
E682x SERIES
0.333 VAC Solid-Core Current Transducers
Installer’s Specifications
Inputs:
Frequency Range 50/60 Hz
Leads 6’ (1.8 m)
Accurac y:
Accuracy ±0.5% from 5%-120% of rated current
Outputs:
Output at Rated Current 0.333 VAC
Mechanical:
Insulation 60 0 VAC
Environmental:
Operating Temperature Range -40° to 85°C (-4 0° to 185°F)
Storage Temperature Range -50° to 105°C (-58° to 221°F)
Humidity Range 0-95% noncondensing
Altitude of Operation 3 km max.
Installation Categor y Cat III, pollution degree 2
Agency A pprova ls UL61010 -1, EN61010 -1
InstallatIon
Installation must be performed by a qualified electrician.
Disconnect and lock out power to the primary circuit
before installing these current transducers (CTs).
Failure to follow these instructions will result in death or serious injury.
NOTICE
• This product is not intended for life or safety applications.
• Do not install this product in hazardous or classified locations.
• The installer is responsible for conformance to all applicable codes.
• Mount this product inside a suitable fire and electrical enclosure.
Documentation must be consulted where this symbol is used on the product.
This symbol indicates an electrical shock hazard exists.
Always use this product in the manner specied or the protection provided by the
product may be impaired. This product must be installed in an appropriate Fire and
Electrical enclosure per local regulations.
1. Connect the transducer output leads to the meter or device inputs. The white wire
is the X1 lead. Note the labeling on the product indicating the source side, or the
base of the arrow.
2. Run the conductor to be monitored through the CT center and complete
connections.
3. Check wire terminations for tightness.
4. Reconnect power to the panel.
Product IdentIfIcatIon
PART NUMBER DESCRIPTION
E682A051V3 Solid-Core Volt CT, 50A:0.333V, 0.417 in ID, 6 ft leads
E682A101V3 Solid-Core Volt CT, 100A:0.333V, 0.417 in ID, 6 ft leads
E682C201V3 Solid-Core Volt CT, 200A:0.333V, 1.0 in ID, 6 ft leads
E682D401V3 Solid-Core Volt CT, 400A:0.333V, 1.25 in ID, 6 ft leads
Other lead lengths are availa ble. Consult a sales rep for more i nformation.
Z206159- 0A PAGE 1 ©2012 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com 07123
Alta Labs, Enercep t, Enspector, Hawkeye, Trustat, Veris, and the Veris ‘ V’ logo are trademark s or registered tradema rks of Veris Industries, L.L .C. in the USA and /or other count ries.
E682x SERIES
TM
INSTALLATION GUIDE
oPeratIon
The E682x series of 0.333 volt solid-core current transducers provide secondary AC
voltage proportional to the primary (sensed) current. For use with power meters,
data loggers, chart recorders, and other instruments, E682x CTs provide a costeective means to transform electrical service amperages to a voltage compatible
with monitoring equipment.
These products provide basic insulation to 600 VAC between the sensed conductor
and the output leads. For reinforced applications, the sensed conductor must
be provided with appropriate insulation. Reinforced insulation is provided for
applications to 300 VAC between the sensed conductor and the output leads under
UL/IEC/EN 61010-1 rules.
dImensIons
A
C
B
+ +
Ø = E
notes
Accuracy is specied with the primary conductor(s) centered in the CT window.
Do not apply current transducers to circuits having a phase-to-ground/neutral
voltage greater than the stated maximum voltage without applying adequate
additional insulation between the primary conductor and the current transducers.
Veris assumes no responsibility for equipment damage or personal injury caused by
transducers operated on circuits above their published ratings.
#22 AWG Stranded
White Black
1 2
PVC insulation,
UL1015, 600V, 105˚C
0.250” ± 0.050”
(6.35 mm ± 1.27 mm)
L
D
Black
Model L A B C D E
E682A051V3
E682A101V3
E682C201V3
E682D401V3
6’
(1.8 m)
6’
(1.8 m)
6’
(1.8 m)
1.3"
(33 mm)
2.3"
(59 mm)
2.8"
(70 mm)
1.5"
(38 mm)
2.6"
(66 mm)
3.2"
(82 mm)
0.7"
(18 mm)
0.7"
(18 mm)
1.0"
(25 mm)
0.8"
(21 mm)
1.2"
(31 mm)
1.4"
(36 mm)
White
12
0.4"
(10 mm)
1.0"
(25 mm)
1.25"
(31 mm)
Z206159- 0A PAGE 2 ©2012 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com 07123
Alta Labs, Enercep t, Enspector, Hawkeye, Trustat, Veris, and the Veris ‘ V’ logo are trademark s or registered tradema rks of Veris Industries, L.L .C. in the USA and /or other count ries.