Veris E5xxxA Datasheet

E5xxxA SERIES
Enhanced Power and Energy Meter, Built-in Integrator and Power Supply
Versatile Monitoring Solution When Used With U018 Rope Style CTs (sold separately)
VERIS INDUSTRIES
U018 Series
(sold separately)
E50xxxA/E51xxxA
DESCRIPTION
The E5xxxA Series DIN Rail Meter combines exceptional metering per formance with a built-in integrator and power supply to deliver a cost-eec tive, easily installed solution for power monitoring applications. Multiple communication protocol options oer added exibility for system integration.
E5xxxA devices work exclusively with Veris U018 series rope CTs for fast connection. The rope style CTs allow convenient installation in tight spaces.
The data logging capability (E5xC3A and E5xx5A) protects data in the event of a power failure. Dierent devices in the series oer serial communication, pulse output, and phase alarms to suit a wide variety of applications.
The E51xxA models add a bi-directional monitoring feature designed expressly for
power/energy monitoring
renewable energy applications, allowing measurement of power imported from the utility grid as well as power exported from the renewable energy source.
APPLICATIONS
Energy monitoring in building automation systems
Renewable energy
Energy management
Commercial submetering
Industrial monitoring
Cost allocation
FEATURES
Integrator and power supply for the CTs are built into the meter...fewer devices
to purchase and faster installation
Revenue Grade measurements
ANSI C12.20 0.5% accuracy, IEC 62053-22 Class 0.5S on E50xxA or ANSI C12.20
0.2% accuracy, IEC 62053-22 Class 0.2S on E51xxA...great for cost allocation
DIN rail or screw mounting options...easy installation
Real energy output and phase loss alarm output on E50BxA and E5xCxA
models...one device serves multiple applications
90-600VAC...application versatility with fewer models to stock
Data logging capability (E5xC3A and E5xx5A)... ensures long term data retrieval
and safeguards during power failures
Designed to work exclusively with U018 Series rope CTs, 20 to 5000A range...
easy connection
User-enabled password protection...protec t from tampering
System integration via Modbus (E5xCxA), BACnet MS/TP (E5xHxA), or Lonmark-
certied LON FT (E50FxA)...convenient compatibility with existing systems
Native BACnet MS/TP support (no gateway) with serial rates up to
115.2 kbaud (E5xHxA)
E51 models: Bi-directional metering (4-quadrant), an essential solution for
solar and other renewable energy applications, measures Import, Export and net energy transfer
CSI approved...eases submission process for California Solar Initiative
E51CxA includes SunSpec compliant common and meter register blocks
SPECIFICATIONS
Inputs:
Control Power, AC 50/60 Hz; 5VA max.; 90V min.; UL Maximums: 600V Control Power, DC 3W max.; UL and CE: 125 to 300VDC (external DC current limiting required)
Voltage Input UL: 90V Current Input Scaling 20A to 5000A Input Range U018 series rope st yle CTs only (CTs must be rated for connection to Class 1 voltage inputs) Pulse Inputs (E5xHxA and E50FxA only) Contact inputs to pulse accumulators (one set with E5xH2A and E50F2A; t wo sets with E5xH5A and E51F5A)
Accuracy:
Real Power and Energy E50xx A: 0.5% (ANSI C12.20, IEC 62053-22 Class 0.5S); E51xxA: 0.2% (ANSI C12.20, IEC 62053-22 Class 0.2S)
Outputs:
All Models (except E5xHxA and E50FxA) Real Energy Pulse: N.O. static; Alarm contacts: N.C. static E50BxA Reactive energy pulse 30VAC/DC E5xCxA RS-485 2-wire Modbus RTU (1200 baud to 38.4 kbaud) E5xHxA RS-485 2-wire BACnet MS/TP (9600 baud to 115.2 kbaud) E50FxA 2-wire LON FT
Mechanical:
Mounting DIN Rail or 3-point screw mount
Environmental:
Operating Temperature Range -30° to 70°C (-22° to 158°F) Storage Temperature Range -40° to 85°C (-40° to 185°F) Humidity Range <95% RH noncondensing Agency Approvals UL508, EN61010, California CSI Solar, ANSI C12.20
800.354.8556
Year
5
Warranty
+1 503.598.4564
www.veris.com
HQ000 4397.B 0 9131
(347V
L-L
to 600V
L-N
); CE Maximums: 300V
L-N
; CE: 90V
L-L
to 300V
L-N
L-N
L-N
800.354.8556
+1 503.598.4564
www.veris.com
ORDERING INFORMATION
MEASUREMENT CAPABILITY - FULL DATA SET
Bi-directional Energy Measurements
Power (3-phase total and per phase): Real (kW)
Reactive (kVAR), and Apparent (kVA)
Power Factor: 3-phase average and per phase
Present Power Demand: Real (kW),
Reactive (kVAR), and Apparent (kVA)
Import and Export totals of Present Power Demand:
Real (kW), Reactive (kVAR), and Apparent (kVA)
Peak Power Demand: Real (kW),
Reactive (kVAR), and Apparent (kVA)
Current (3-phase average and per phase)
Voltage: Line-Line and Line-Neutral
(3-phase average and per phase)
Frequency
ANSI C12.20 0.5% accuracy, IEC 62053-22 Class 0.5S
ANSI C12.20 0.2% accuracy, IEC 62053-22 Class 0.2S
Accumulated Net Energy: Real (kWh),
Reactive (kVARh), and Apparent (kVAh)
Accumulated Real Energy by phase (kWh)
Import and Export Accumulators of
Real and Apparent Energy
Reactive Energy Accumulators by Quadrant
(3-phase total and per phase)
Demand Interval Conguration:
Fixed or Rolling Block
Demand Interval Conguration:
External Sync to Comms
DATA LOGGING:
Data Logging: 10 16-Bit Congurable
(can include Date/Time) Data Buers
Data Logging: 3 Timestamped 32-Bit
Congurable Data Buers
Store up to 60 days of readings
at 15-minute intervals
OUTPUTS:
Alarm Output (N.C.)
1 Pulse Output (N.O.)
2 Pulse Outputs (N.O.)
RS-485 Serial (Modbus RTU Protocol)
RS-485 Serial (BACnet MS/TP Protocol)
LON FT Serial (LonTalk Protocol)
INPUTS:
2 Pulse Contact Accumulator Inputs
1 Pulse Contact Accumulator Input
REQUIRED CTs
MODEL DESCRIPTION
U018-0001 CT, Rope, 12 in, 5000A
U018-0002 CT, Rope, 18 in, 5000A
U018-0003 CT, Rope, 24 in, 5000A
U018-0004 CT, Rope, 36 in, 5000A
RoHS
Compliant
E51CxA only
E50F2A
E50C2A
E50B1A
n n n n n n n n n n n
n n n n n n n n n n n
n n n n n n n n n n n
n n n n n n n n n n n
n n n n n n n n n n n
n n n n n n n n n n n
n n n n n n n n n n n
n n n n n n n
n n n n n n n n n n n
n n n n n n n n n n n
n n n n n n n n n n n
n n n n n n n n
n
E50C3A
n n n n n n n n n n
n n
n n n n n
n n n n
n n n n
E50F5A
E50H2A
comi ng
soon
n n n
n n
n n n
n n n
E50H5A
comi ng
n n n n
E50FxA only
E51C2A
E51C3A
E51H2A
soon
n n n n
n n n n
n n n n
n n n n
n n n n
comi ng
soon
ACCESSORIES
NEMA 4X enclosure (AE012) Fuse Kits with hi-interrupt capab ility AC Fuses (AH02, AH03, AH04) DIN Rail (AV01), DIN Rail Stop Cli ps (AV02) Modbus TCP Gateway (U013- 0012) BACnet IP Router (U013-0013)
DIMENSIONAL DRAWING
E51H5A
2.3”
(59mm)
4.2”
(107mm)
MOUNTING DIAGRAMS
DIN Mount Configuration
3.6 “
(91 mm)
0.2 “
(4 mm)
Screw Mount Configuration
3.9“
(99 mm)
4.3 “
(109 mm)
U018 Series
4.2 “
(107 mm)
2.4 “
(61 mm)
+
(31 mm)
U013-0012U013-0013
AE 012
1.2 “
1.8”
(45mm)
1.9”
(48mm)
1.5”
(39mm)
3.6”
(91mm)
++
0.3 “
(8 mm)
0.4 “
(10 mm)
AH04
AV01/AV02 (clip styles may vary)
power/energy monitoring
HQ000 4397.B 0 9131
Loading...