Veris E5x Datasheet

E5x SERIES
Enhanced Power and Energy Meter
Versatile Energy Monitoring Solution
VERIS INDUSTRIES
E50/E51
DESCRIPTION
The E5x Series DIN Rail Meter combines exceptional performance and easy installation to deliver a cost-eective solution for power monitoring applications. The E5x can be installed on standard DIN rail or surface mounted as needed. The Modbus, LON, and BACnet output models oer added exibility for system integration. The data logging capabilit y (E5xC3 and E5xx5) protects data in the event of a power failure. Combinations of serial communication, pulse output, and phase alarms are provided to suit a wide variety of applications.
Additional pulse inputs on E5xHx and E50Fx provide an easy way to incorporate simple ow sensors to track gas, water, steam, or other energy forms using a BACnet or LON system.
The E51 models add a bi-directional monitoring feature designed expressly for
power/energy monitoring
renewable energy applications, allowing measurement of power imported from the utility grid as well as power exported from the renewable energy source (e.g. solar panels). In this way, a facility administrator can track all energy data, ensuring accuracy in billing and crediting. They are also useful for monitoring loads that use regenerative braking.
APPLICATIONS
Energy monitoring in building automation systems
Renewable energy
Energy management
Commercial submetering
Industrial monitoring
Cost allocation
FEATURES
Revenue Grade measurements
ANSI C12.20 0.5% accuracy, IEC 62053-22 Class 0.5S on E50xx or ANSI C12.20
0.2% accuracy, IEC 62053-22 Class 0.2S on E51xx...great for cost allocation
DIN rail or screw mounting options...easy installation
Real energy output and phase loss alarm output on E50Bx and E5xCx models...
one device serves multiple applications
90-600VAC...application versatility with fewer models to stock
Data logging capability (E5xC3 and E5xx5)... ensures long term data retrieval
and safeguards during power failures
Compatible with CTs from 5A to 32000A...wide range of service types
User-enabled password protection...protect from tampering
System integration via Modbus (E5xCx), BACnet MS/TP (E5xHx), or Lonmark-
certied LON FT (E50Fx)...convenient compatibility with existing systems
Native BACnet MS/TP support (no gateway) with serial rates up to
115.2 kbaud (E5xHx)
BTL-certied (E 5xH2)
E51 models: Bi-directional metering (4-quadrant), an essential solution for
solar and other renewable energy applications, measures Import, Export and net energy transfer
CSI approved...eases submission process for California Solar Initiative
E51Cx includes SunSpec compliant common and meter register blocks
SPECIFICATIONS
Inputs:
Control Power, AC 50/60 Hz; 5VA max.; 90V min.; UL Maximums: 600V Control Power, DC 3W max.; UL and CE: 125 to 300VDC (external DC current limiting required)
Voltage Input UL: 90V Current Input Scaling 5A to 32,000A Input Range 0 to 0.333V or 0 to 1V (selectable) Pulse Inputs (E5xHx and E50Fx only) Contact inputs to pulse accumulators (one set with E5xH2 and E50F2; two set s with E5xH5 and E51F5)
Accuracy:
Real Power and Energy E50xx: 0.5% (ANSI C12.20, IEC 62053-22 Class 0.5S); E51xx: 0.2% (ANSI C12.20, IEC 62053-22 Class 0.2S)
Outputs:
All Models (except E5xHx and E50Fx) Real Energy Pulse: N.O. static; Alarm contacts: N.C. static E50Bx Reactive energy pulse 30VAC/DC E5xCx RS-485 2-wire Modbus RTU (1200 baud to 38.4 kbaud) E5xHx RS-485 2-wire BACnet MS/TP (9600 baud to 115.2 kbaud) E50Fx 2-wire LON FT
Mechanical:
Mounting DIN Rail or 3-point screw mount
Environmental:
Operating Temperature Range -30° to 70°C (-22° to 158°F) Storage Temperature Range -40° to 85°C (-4 0° to 185°F) Humidity Range <95% RH noncondensing Agency Approvals UL508, EN61010, California CSI Solar, ANSI C12.20
800.354.8556
Year
5
Warranty
+1 503.598.4564
www.veris.com
HQ0001710.H 09 132
(347V
L-L
to 600V
L-N
); CE Maximum: 300V
L-N
; CE: 90V
L-L
L-N
to 300V
L-N
L-L
800.354.8556
+1 503.598.4564
ORDERING INFORMATION
MEASUREMENT CAPABILITY - FULL DATA SET
Bi-directional Energy Measurements
Power (3-phase total and per phase): Real (kW)
Reactive (kVAR), and Apparent (kVA)
Power Factor: 3-phase average and per phase
Present Power Demand: Real (kW),
Reactive (kVAR), and Apparent (kVA)
Import and Export totals of Present Power Demand:
Real (kW), Reactive (kVAR), and Apparent (kVA)
Peak Power Demand: Real (kW),
Reactive (kVAR), and Apparent (kVA)
Current (3-phase average and per phase)
Voltage: Line-Line and Line-Neutral
(3-phase average and per phase)
Frequency
ANSI 12.20 0.5% accuracy, IEC 62053-22 Class 0.5S
ANSI 12.20 0.2% accuracy, IEC 62053-22 Class 0.2S
Accumulated Net Energy: Real (kWh),
Reactive (kVARh), and Apparent (kVAh)
Accumulated Real Energy by phase (kWh)
Import and Export Accumulators of
Real and Apparent Energy
Reactive Energy Accumulators by Quadrant
(3-phase total and per phase)
Demand Interval Conguration:
Fixed or Rolling Block
Demand Interval Conguration:
External Sync to Comms
DATA LOGGING:
Data Logging: 10 16-Bit Congurable
(can include Date/Time) Data Buers
Data Logging: 3 Timestamped 32-Bit
Congurable Data Buers
Store up to 60 days of readings
at 15-minute intervals
OUTPUTS:
Alarm Output (N.C.)
1 Pulse Output (N.O.)
2 Pulse Outputs (N.O.)
RS-485 Serial (Modbus RTU Protocol)
RS-485 Serial (BACnet MS/TP Protocol)
LON FT Serial (LonTalk Protocol)
INPUTS:
2 Pulse Contact Accumulator Inputs
1 Pulse Contact Accumulator Input
www.veris.com
n
C
e
A
t
B
·
®
·
T
S
E
E
S
I
T
R
I
O
N
T
G
A
L
R
A
O
E51Cx only
E50F2
E50C2
E50B1
n n n n n n n n n n n
n n n n n n n n n n n
n n n n n n n n n n n
n n n n n n n n n n n
n n n n n n n n n n n
n n n n n n n n n n n
n n n n n n n n n n n
n n n n n n n
n n n n n n n n n n n
n n n n n n n n n n n
n n n n n n n n n n n
n n n n n n n n
n
E50C3
n n n n n n n n n n
n n
n n n n n
n n n n
n n n n
E50F5
E50H2
NEW NEW
NEW
n n n
n n n n
n n
n n n
n n n
B
E5xH2 only
E51C2
E50H5
E51C3
n n n n
n n n n
n n n n
n n n n
n n n n
E50Fx only
E51H2
DIMENSIONAL DRAWING
E51H5
2.3”
(59mm)
4.2”
(107mm)
MOUNTING DIAGRAMS
DIN Mount Configuration
3.6 “
(91 mm)
0.2 “
(4 mm)
Screw Mount Configuration
3.9“
(99 mm)
4.3 “
(109 mm)
U013-0012 U013-0013
4.2 “
(107 mm)
2.4 “
(61 mm)
+
1.2 “
(31 mm)
AH04
1.8”
(45mm)
(39mm)
3.6”
(91mm)
++
1.9”
(48mm)
1.5”
0.3 “
(8 mm)
power/energy monitoring
0.4 “
(10 mm)
ACCESSORIES
NEMA 4X enclosure (AE012) Fuse Kits with hi-interrupt capab ility AC Fuses (AH02, AH03, AH04) Split-core and solid-core CTs (H681x, SCT) Replacement mounting clips (AE004)
HQ0001710.H 09 132
DIN Rail (AV01), DIN Rail Stop Cli ps (AV02) Modbus TCP Gateway (U013- 0012) BACnet IP Router (U013-0013) Network Display (H8932, H8936)
AE 012
H8932/H8936
AV01/AV02 (clip styles may vary)