Veris E51C3 Installation Instructions

Installation Guide
the FCC Rules. These limits are designed to provide reasonable protection
residential environment. This equipment generates, uses, and can radiate
Power Monitoring
RoHS
Compliant
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
• Follow safe electrical work practices. See NFPA 70E in the USA, or applicable local codes.
• This equipment must only be installed and serviced by qualified electrical personnel.
• Read, understand and follow the instructions before installing this product.
• Turn off all power supplying equipment before working on or inside the equipment.
• Any covers that may be displaced during the installation must be reinstalled before powering the unit.
• Use a properly rated voltage sensing device to confirm power is off. DO NOT DEPEND ON THIS PRODUCT FOR VOLTAGE INDICATION
Failure to follow these instructions will result in death or serious injury.
A qualied person is one who has skills and knowledge related to the construction and operation of this electrical equipment and the installation, and has received safety training to recognize and avoid the hazards involved. NEC2009 Article 100
No responsibility is assumed by Veris Industries for any consequences arising out of the use of this material.
Control system design must consider the potential failure modes of control paths and, for
certain critical control functions, provide a means to acheive a safe state during and after a path failure. Examples of critical control functions are emergency stop and over-travel stop.
TM
E51C2, E51C3
Compact Bi-Directional
Power and Energy Meter
Product Overview
The E51 DIN Rail Power Meter provides a solution for measuring energy data with a single device. Inputs include Control Power, CTs, and 3-phase voltage. The E51 supports multiple output options, including solid state relay contacts, Modbus (with or without data logging), and pulse. The LCD screen on the faceplate allows instant output viewing.
The E51 Meter is capable of bidirectional metering. Power is monitored in both directions (upstream and downstream from the meter). The meter is housed in a plastic enclosure suitable for installation on T35 DIN rail according to EN50022. The E51 can be mounted either on a DIN rail or in a panel. Observe correct CT orientation
when installing the device.
Product Identification
Model Description Output Data Logging
Pulse RS-485 Alarm
E51C2 Modbus output, full data set
E51C3 Modbus output, data logging
WARNING
LOSS OF CONTROL
∙ Assure that the system will reach a safe state during and after a control path failure. ∙ Separate or redundant control paths must be provided for critical control func tions. ∙ Test the eect of transmission delays or failures of communication links. ∙ Each implementation of equipment using communication links must be individually
and thoroughly tested for proper operation before placing it in service.
Failure to follow these instructions may cause injury, death or equipment damage.
1
For additional information about anticipated transmission delays or failures of the link, refer to
NEMA ICS 1.1 (latest edition). Safety Guidelins for the Application, Installation, and Maintenance of Solid-State Control or its equivalent in your specic country, language, and/or location.
1
NOTICE
• This product is not intended for life or safety applications.
• Do not install this product in hazardous or classified locations.
• The installer is responsible for conformance to all applicable codes.
• Mount this product inside a suitable fire and electrical enclosure.
FCC PART 15 INFORMATION NOTE: This equipment has been tested by the manufacturer and found to
comply with the limits for a class B digital device, pursuant to part 15 of
against harmful interference when the equipment is operated in a
radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. This device complies with part 15 of the FCC Rules.
Operation is subject to the following two conditions: (1) This device may not cause harmful interference, and (2) this device must accept any interference received, including interference that may cause undesired operation. Modifications to this product without the express authorization of the
manufacturer nullify this statement.
For use in a P ollution D egree 2 or be tter envi ronment on ly. A Pollutio n Degree 2 environment must control conductive pollution and the possibility of condensation or high hum idity. Cons ider the enc losure, th e correc t use of venti lation, the rmal prop erties of the equ ipment, an d the relati onship wi th the envir onment. In stallati on categor y: CAT II or CAT III. P rovide a di sconnec t device to di sconnec t the meter f rom the sup ply source. P lace this de vice in clos e proximit y to the equ ipment and w ithin eas y reach of the oper ator, and mark i t as the disc onnecti ng device. T he disconn ecting de vice shall meet th e relevant r equireme nts of IEC 60 947-1 and IEC 60947-3 and sh all be suit able for the appl ication. I n the US and Can ada, discon nectin g fuse hold ers can be us ed. Provi de overcu rrent prot ection a nd discone cting dev ice for sup ply conduc tors wit h approved current limiting devices suitable for protecting the wiring. If the equipment is used in a manner n ot specie d by the manu facture r, the protec tion prov ided by the d evice may be impaired.
ZL00 67-0C Page 1 of 34 ©2013 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com 06131
Alta Labs, E nercept, Ensp ector, Hawkeye, Trus tat, Aerospo nd, Veris, and th e Veris ‘V’ log o are tradema rks or registe red tradema rks of Veris Ind ustries, L. L.C. in the USA and /or other countri es.
Specifications
MEASUREMENT ACCURACY
Real Power and Energy
Reactive Power and Energy
Current
Voltag e
Sample Rate
Data Update Rate
Type of Measurement
Measured AC Voltage
Metering Over-Range
Impedance
Frequency Range
CT Scaling
Measurement Input Range
Impedance
Other companies’ trademarks are hereby acknowledged to belong to their respective owners.
IEC 620 53 -22 Class 0.2S, A NSI C12.20 0.2%
IEC 620 53 -23 Class 2, 2%
0.2% (+ 0.0 05% per ° C deviation from 25°C ) from 1% to 5% of range ;
0.1% (+0.0 05% per °C deviation from 25°C ) from 5% to 100% of range
0.1% (+0.0 05% per °C deviation from 25°C ) from 90 VAC
2520 samples per second; no blind time
1 sec.
True RMS; one to three phase AC system
INPUT VOLTAGE CHARACTERISTICS
Minimum 90 V
UL Maximums: 600 V
+20%
2.5 MΩ
45 to 65 Hz
INPUT CUR RENT CHARACTER ISTICS
Primar y: Adjustable from 5 A to 32,00 0 A
0 to 0.333 VAC or 0 to 1.0 VAC (+20 % over-range)
10.6 kΩ (1/3 V mode) or 32.1 kΩ (1 V mode)
/5 M Ω
L-N
(156 V
L-N
L-L
) for stated accuracy;
L-L
(3 47 V
L-L
); CE Maximums: 3 00 V
L-N
to 600 VAC
L-N
(520 V
L-N
L-L
)
L-L
Installation Guide Power Monitoring EC, EC
TM
Specifications (cont.)
CONTROL POWE R
AC
5 VA max.; 9 0V min.;
DC*
Ride Through Time
Alarm Contacts
Real Energy Pulse Contacts
RS-485 Port
Weight
IP Degree of Protection
(IEC 6 0529 )
Display Characteristics
Terminal Block Screw Torque
Terminal Block Wire Size
Rail
Operating Temperature Range
Storage Temperature Range
Humidity Range
Altitude of Operation
US and Canada
CE
Dielectric Withstand
Conducted and Radiated
Emissions
Conducted and Radiated
Immunity
US and Canada (cULus)
Europe (CE)
UL Maximums: 600 V
3 W max.; U L and CE: 125 to 300 VDC
100 msec at 120 VAC
OUTPUT
N.C., static output ( 30VAC/DC, 100mA max. @ 25°C,
derate 0.56mA per °C above 25°C)
N.O., static output ( 30 VAC/ DC, 100 mA max. @ 25°C,
derate 0.56 mA per ° C above 25°C)
2-wire, 120 0 to 38400 baud, Modbus RTU
MECHAN ICAL CHARACTERI STICS
0.62 lb ( 0.28 kg)
IP40 front display; IP 20 Meter
Back-lit blue LCD
0.37 to 0.44 ft-lb ( 0.5 to 0.6 N ·m )
26 to 14 AWG (0.13 to 2.08 mm2)
T35 ( 35mm ) DIN Rail per EN50022
ENVIRONMENTAL
-30° to 70°C (22° to 158°F )
-4 0° to 85°C (- 40 ° to 185°F )
<95% RH noncondensing
3000 m
METERING CATEGORY
CAT III; for distribution systems up to 3 47 V
CAT III; for distribution systems up to 300 V
Per UL 50 8, EN61010
FCC par t 15 Class B, EN55011/EN61000 Class B (residential and light industrial)
EN61000 Class A ( heavy industrial)
AGENCY APPROVALS
UL508 (open type device) /C SA 22. 2 No. 14- 05
EN6 1010-1:2001
(3 47 V
L-L
* External DC current limiting is required, see fuse recommendations.
); CE Maximums: 3 00 V
L-N
/600 VAC
L-N
L-N
(520 V
L-N
L-L
)
L-L
SunSpec Alliance Interoperability
This meter implements the draft SunSpec 1.0 common elements starting at base 1 address 40001, and the proposed SunSpec 1.1 meter model at 40070 (these addresses are not in Modicon notation). See www.veris.com or www.sunspec.org for copies of these specications.
Specification Compliance
ZL00 67-0C Page 2 of 34 ©2013 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com 06131
Alta Labs, E nercept, Ensp ector, Hawkeye, Trus tat, Aerospo nd, Veris, and th e Veris ‘V’ log o are tradema rks or registe red tradema rks of Veris Ind ustries, L. L.C. in the USA and /or other countri es.
The SunSpec Alliance logo is a trademark or registered trademark of the SunSpec Alliance.
Other companies’ trademarks are hereby acknowledged to belong to their respective owners.
Installation Guide Power Monitoring EC, EC
TM
Table of Contents
Dimensions 4
Application Example 4
Data Outputs 5
Product Diagram 5
Display Screen Diagram 5
Installation 6
Supported System Types 7
Wiring Symbols 7
Wiring 8
Control Power Diagrams 9
Quick Setup Instructions 10
Solid State Pulse Output 11
User Interface Menu Abbreviations Dened 11
User Interface for Data Conguration 12
Alert/Reset Information 13
User Interface for Setup 15
RS-485 Communications 17
Data Logging (E51C3 Only) 17
Modbus Point Map Overview 18
Standard Modbus Default Settings 19
Modbus Point Map 20
SunSpec Register Blocks 30
Troubleshooting 34
China RoHS Compliance Information (EFUP Table) 34
ZL00 67-0C Page 3 of 34 ©2013 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com 06131
Alta Labs, E nercept, Ensp ector, Hawkeye, Trus tat, Aerospo nd, Veris, and th e Veris ‘V’ log o are tradema rks or registe red tradema rks of Veris Ind ustries, L. L.C. in the USA and /or other countri es.
Other companies’ trademarks are hereby acknowledged to belong to their respective owners.
Installation Guide Power Monitoring EC, EC
TM
Dimensions
1.8”
(45mm)
1.9”
(48mm)
2.3”
(59mm)
1.5”
(39mm)
4.2”
(107mm)
3.6”
(91mm)
Bottom View (DIN Mount Option) Bottom View (Screw Mount Option)
2.4 “
(61 mm)
+
0.2 “
(4 mm)
3.6 “
(91 mm)
4.2 “
(107 mm)
3.9“
(99 mm)
4.3 “
(109 mm)
1.2 “
(31 mm)
++
0.3 “
(8 mm)
0.4 “
(10 mm)
Application Example
Main Utility Grid Solar Panels
Imported Power
Exported Power
ZL00 67-0C Page 4 of 34 ©2013 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com 06131
Alta Labs, E nercept, Ensp ector, Hawkeye, Trus tat, Aerospo nd, Veris, and th e Veris ‘V’ log o are tradema rks or registe red tradema rks of Veris Ind ustries, L. L.C. in the USA and /or other countri es.
Other companies’ trademarks are hereby acknowledged to belong to their respective owners.
Installation Guide
kWh
1234.5
Power Monitoring EC, EC
TM
Data Outputs
Product Diagram
Signed Power: Real, Reactive, and Apparent 3-phase total and per phase Real and Apparent Energy Accumulators: Import, Export, and Net; 3-phase total and per phase Reactive Energy Accumulators by Quadrant: 3-phase totals and per phase Congurable for CT & PT ratios, system type, and passwords Diagnostic alerts Current: 3-phase average and per phase Volts: 3-phase average and per phase Line-Line and Line-Neutral Power Factor: 3-phase average and per phase Frequency Power Demand: Most Recent and Peak (Import and Export) Demand Conguration: Fixed, Rolling Block, and External Sync (Modbus only)
Data Logging (E51C3 only)
Real Time Clock: user congurable 10 user congurable log buers: each buer holds 5760 16-bit entries
(User congures which 10 data points are stored in these buers)
User congurable logging interval
(When congured for a 15 minute interval, each buer holds 60 days of data) Continuous and Single Shot logging modes: user selectable Auto write pause: read logs without disabling the meter’s data logging mode
IA
IB
IC
-+-+-
A B C Alarm Energy
+
Phase Loss
Alarm
Pulse
Modbus
OUTPUT
Shield
Display Screen Diagram
- 600V
CE: 90V
L-L
NC NO + - S
+
CONTROL POWER
- 300V
L-N
L-N
0.1A 50/60 Hz
Earth
Control
Power
Two 5-character rows
of display text.
Top row alphanumeric;
Bottom row numeric only
The red Alarm LED lights when
any of the 3 phase voltages
drop below the selected thresh-
old. The green Energy LED lights
momentarily each time the
Energy output pulse is active.
Common - 1 or 1/3 VAC Input
Alarm Energy
VOLTAGE INPUTS CAT III 50/60 Hz
A B C N 1 2
VA
UL: 90V
L-N
VB
VC
Neutral
LCD Screen: Buttons:
Screen Name or Units
Alive Indicator
Diagnostic Alert
Logo
Numeric Data
 
 
Tx Rx ERR
Export
Import
Transmit Data Receive Data Receive Data Error
(Left)
Back
(Up)
Select
+
(Right)
Next
(Down)
Select
ZL00 67-0C Page 5 of 34 ©2013 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com 06131
Alta Labs, E nercept, Ensp ector, Hawkeye, Trus tat, Aerospo nd, Veris, and th e Veris ‘V’ log o are tradema rks or registe red tradema rks of Veris Ind ustries, L. L.C. in the USA and /or other countri es.
Other companies’ trademarks are hereby acknowledged to belong to their respective owners.
Installation Guide Power Monitoring EC, EC
TM
Installation
Disconnect power prior to installation.
Reinstall any covers that are displaced during the installation before powering the unit.
Mount the meter in an appropriate electrical enclosure near equipment to be monitored.
Do not install on the load side of a Variable Frequency Drive (VFD), aka Variable Speed Drive (VSD) or Adjustable Frequency Drive (AFD).
Observe correct CT orientation.
The meter can be mounted in two ways: on standard 35 mm DIN rail or screw-mounted to the interior surface of the enclosure.
A. DIN Rail Mounting
1. Attach the mounting clips to the underside of the housing by sliding them into the slots from the inside. The stopping pegs
must face the housing, and the outside edge of the clip must be ush with the outside edge of the housing.
2. Snap the clips onto the DIN rail. See the diagram of the underside of the housing (below).
Clip flush with outside edge
Snap onto
Insert clips from inside
DIN rail
3. To reduce horizontal shifting across the DIN rail, use two Veris AV02 end stop clips.
B. Screw Mounting
1. Attach the mounting clips to the underside of the housing by sliding them into the slots from the outside. The stopping pegs
must face the housing, and the screw hole must be exposed on the outside of the housing.
2. Use three #8 screws (not supplied) to mount the meter to the inside of the enclosure. See the diagram of the underside of the
housing (below).
Insert clips from outside
Screw holes exposed for mounting
ZL00 67-0C Page 6 of 34 ©2013 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com 06131
Alta Labs, E nercept, Ensp ector, Hawkeye, Trus tat, Aerospo nd, Veris, and th e Veris ‘V’ log o are tradema rks or registe red tradema rks of Veris Ind ustries, L. L.C. in the USA and /or other countri es.
Other companies’ trademarks are hereby acknowledged to belong to their respective owners.
Installation Guide Power Monitoring EC, EC
TM
Supported System Types
Number
of wires
Single-Phase Wiring
2 1 A 2 A, N L-N 10 1L + 1n AN 1
2 1 A 2 A, B L- L 11 2L AB 2
3 2 A, B 3 A, B, N L-L with N 12 2L + 1n AB AN, BN AN-BN 3
Three-Phase Wiring
3 3 A, B, C 3 A, B, C Delta 31 3L AB, BC, CA AB-BC-CA 4
4 3 A, B, C 4 A, B, C, N Grounded
The meter has a number of dierent possible system wiring congurations (see Wiring Diagrams section). To congure the meter, set the System Type via the User Interface or Modbus register 130 (if so equipped). The System Type tells the meter which of its current and voltage inputs are valid, which are to be ignored, and if neutral is connected. Setting the correct System Type prevents unwanted energy accumulation on unused inputs, selects the formula to calculate the Theoretical Maximum System Power, and determines which phase loss algorithm is to be used. The phase loss algorithm is congured as a percent of the Line-to-Line System Voltage (except when in System Type 10) and also calculates the expected Line to Neutral voltages for system types that have Neutral (12 & 40).
Values that are not valid in a particular System Type will display as “----” on the User Interface or as QNAN in the Modbus registers.
CTs Voltage Connections System Type Phase Loss Measurements Wiring
Diagram
Qty ID Qty ID Type Modbus
Register 130
40 3L + 1n AB, BC, CA AN, BN, CN AN-BN-CN &
Wye
User Interface:
SETUP>S SYS
VLL VLN Balance Diagram
number
5, 6
AB-BC-CA
Wiring Symbols
To avoid distortion, use parallel wires for control power and voltage inputs.
The following symbols are used in the wiring diagrams on the following pages.
Symbol Description
Voltage Disconnect Switch
Fuse (installer is responsible for ensuring compliance with local requirements. No
fuses are included with the meter.)
Earth ground
X1
Current Transducer
Potential Transformer
Protection containing a voltage disconnect switch with a fuse or disconnect circuit
breaker. The protection device must be rated for the available short-circuit current at the connection point.
CAUTION
RISK OF EQUIPMENT DAMAGE
• This product is designed only for use with 1V or 0.33V current transducers (CTs).
• DO NOT USE CURRENT OUTPUT (e.g. 5A) CTs ON THIS PRODUCT.
• Failure to follow these instructions can result in overheating and permanent equipment damage.
ZL00 67-0C Page 7 of 34 ©2013 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com 06131
Alta Labs, E nercept, Ensp ector, Hawkeye, Trus tat, Aerospo nd, Veris, and th e Veris ‘V’ log o are tradema rks or registe red tradema rks of Veris Ind ustries, L. L.C. in the USA and /or other countri es.
Other companies’ trademarks are hereby acknowledged to belong to their respective owners.
Installation Guide Power Monitoring EC, EC
TM
Wiring
WARNING
RISK OF ELECTRIC SHOCK OR PERMANENT EQUIPMENT DAMAGE
CT negative terminals are referenced to the meter’s neutral and may be at elevated voltages
· Do not contact meter terminals while the unit is connected
· Do not connect or short other circuits to the CT terminals
Failure to follow these instructions may cause injury, death or equipment damage.
Observe correct CT orientation.
Diagram 1: 1-Phase Line-to-Neutral 2- Wire
System 1 CT
N L1
Use System Type 10 (1L + 1n)
X1
X2
A B C N
White
Black
+
-
+
-
+
-
A
B
C
Diagram 2: 1-Phase Line-to-Line 2-Wire
L1 L2
X1
X2
System 1 CT
Use System Type 11 (2L)
White Black
A B C N
+
A
-
+
B
-
+
C
-
Diagram 3: 1-Phase Direct Voltage Connection 2 CT
N
L1 L2
X1
X2
Use System Type 12 (2L + 1n) Use System Type 31 (3L)
A B C N
White
Black
X1
X2
White
Black
+
A
-
+
B
-
+
C
-
Diagram 5: 3-Phase 4-Wire Wye Direct Voltage Input
Connection 3 CT
Use System Type 40 (3L + 1n)
L1N L2 L3
A B C N
X1
X2
X1
X2
X1
X2
White
Black
White
Black
White Black
+
A
-
+
B
-
+
C
-
Diagram 4: 3-Phase 3-Wire 3 CT no PT
L1 L2 L3
A B C N
X1
X1
X2
X2
White
Black
White
X1
X2
Black
White
Black
+
A
-
+
B
-
+
C
-
Diagram 6: 3-Phase 4-Wire Wye Connection 3 CT
3 PT
Use System Type 40 (3L + 1n)
L1N L2 L3
A B C N
X1
X1
X2
X2
X1
X2
White
Black
White
Black
White
Black
+
A
-
+
B
-
+
C
-
ZL00 67-0C Page 8 of 34 ©2013 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com 06131
Alta Labs, E nercept, Ensp ector, Hawkeye, Trus tat, Aerospo nd, Veris, and th e Veris ‘V’ log o are tradema rks or registe red tradema rks of Veris Ind ustries, L. L.C. in the USA and /or other countri es.
Other companies’ trademarks are hereby acknowledged to belong to their respective owners.
Installation Guide Power Monitoring EC, EC
TM
Control Power Diagrams
Direct Connect Control Power (Line to Line)
L1
L2 L3
Line to Line from 90 VAC to 600 VAC (UL) (520 VAC for CE). In
UL installations the lines may be  oating (such as a delta). If any lines are tied to an ear th (such a s a corner grounded
delta), see the Line to Neutral installation limits. In CE
compliant installations, th e lines must be neutral (earth)
referenced at less than 300 VAC
1 2G
L-N
Direct Connect Control Power (DC Control Power)
1 2G
DC Control Power from 125 VDC to 300 VDC
(UL and CE max.)
Direct Connect Control Power (Line to Neutral)
L1N L2 L3
Line to Neutral from 90 VAC to 347 VAC (UL) or 300 VAC (CE)
Control Power Transformer (CPT) Connection
L1N L2 L3
The Control Power Transformer may be wired L-N or L-L. Output to
meet meter input requirements
1 2G
1 2G
Fuse Recommendations
Keep the fuses close to the power source (obey local and national code requirements).
For selecting fuses and circuit breakers, use the following criteria:
• Select current interrupt capacity based on the installation category and fault current capability.
• Select over-current protection with a time delay.
• Select a voltage rating sucient for the input voltage applied.
• Provide overcurrent protection and disconnecting means to protect the wiring. For AC installations, use Veris AH02,
AH03, AH04, or equivalent. For DC installations, provide external circuit protection. Suggested: 0.5 A, time delay fuses.
• The earth connection is required for electromagnetic compatibility (EMC) and is not a protective earth ground.
ZL00 67-0C Page 9 of 34 ©2013 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com 06131
Alta Labs, E nercept, Ensp ector, Hawkeye, Trus tat, Aerospo nd, Veris, and th e Veris ‘V’ log o are tradema rks or registe red tradema rks of Veris Ind ustries, L. L.C. in the USA and /or other countri es.
Other companies’ trademarks are hereby acknowledged to belong to their respective owners.
Installation Guide Power Monitoring EC, EC
TM
Quick Setup Instructions
These instruc tions assume the meter is set to factory defaults. If it has been previously congured, check all optional values.
+
1. Press the
+
or – button repeatedly until SETUP screen appears.
2. to the PASWD screen.
+
3. through the digits. Use the
+
4. Use the
+
or – buttons to selec t the parameter to congure.
+
or – buttons to selec t the password (the default is 00000). Exit the screen to the right.
5. If the unit has an RS-485 interface, the rst Setup screen is S COM (set communications).
+
a. to the ADDR screen and through the address digits. Use the
+
b. to the BAUD screen. Use the
c. to the PAR screen. Use the
+
or – buttons to selec t the baud rate.
+
+
or – buttons to selec t the parity.
+
or – buttons to select the Modbus address.
d. back to the S COM screen.
6.
to the S CT (Set Current Transducer) screen. If this unit does not have an RS-485 port, this will be the rst screen.
+
a. to the CT V screen. Use the
b. to the CT SZ screen and through the digits. Use the
+
or – buttons to selec t the voltage mode Current Transducer output voltage.
+
+
or – buttons to selec t the CT size in amps.
c. back to the S CT screen.
7. – to the S SYS (Set System) screen.
+
a. to the SY STM screen. Use the
+
or – buttons to selec t the System Type (see wiring diagrams).
b. back to the S SYS screen.
8. (Optional) – to the S PT (Set Potential Transformer) screen. If PTs are not used, then skip this step.
+
a. to the RATIO screen and through the digits. Use the
+
or – buttons to selec t the Potential Transformer step down
ratio.
b. back to the S PT screen.
9.
to the S V (Set System Voltage) screen.
+
a. to the VLL (or VLN if system is 1L-1n) screen and through the digits. Use the
+
or – buttons to selec t the Line to Line
System Voltage.
b. back to the S V screen.
10. Use the to exit the setup screen and then S ETU P.
11. Check that the wrench is not displayed on the LCD.
+
a. If the wrench is displayed, use the
+
or – buttons to nd the A LERT screen.
b. through the screens to see which alert is on.
For the full setup instructions, see the conguration instruc tions on the following pages.
ZL00 67-0C Page 10 of 34 ©2013 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com 06131
Alta Labs, E nercept, Ensp ector, Hawkeye, Trus tat, Aerospo nd, Veris, and th e Veris ‘V’ log o are tradema rks or registe red tradema rks of Veris Ind ustries, L. L.C. in the USA and /or other countri es.
Other companies’ trademarks are hereby acknowledged to belong to their respective owners.
Installation Guide Power Monitoring EC, EC
TM
Solid-State Pulse Output
User Interface (UI) Menu Abbreviations Defined
The meter has one normally open (N.O.) KZ Form A output and one normally closed (N.C.) KY solid-state output. One is dedicated to import energy (Wh), and the other to Alarm.
The relay used for the Phase Loss contact is N.C., with closure indicating the presence of an alarm; either loss of phase if the meter is powered, or loss of power if the meter is not. The contacts are open when the meter is powered and no phase loss alarm conditions are present.
The solid state pulse outputs are rated for 30 VAC/DC nom.
Maximum load current is 100 mA at 25°C. Derate
0.56 mA per °C above 25°C.
See the Setup section for conguration
Alarm
* The over-current pro tective device must be rated for the shor t circuit current at the connection point. ** All pulse outpu ts and communication circui ts are only intended to be connec ted to non-hazard ous voltage circuits (SELV or Class 2). Do not connect to hazardous vol tages.
+ – S
Energy Output
information.
The user can set the display mode to either IEC or IEEE notation in the SETUP menu.
Main Menu
IEC IEEE Description
D D Demand
MAX M Maximum Demand
P W Present Real Power
Q VAR Present Reactive Power
S VA Present Apparent Power
A A Amps
UAB, UBC, UAC VAB, VBC, VAC Voltage Line to Line
V VLN Voltage Line to Neutral
PF PF Power Factor
U VLL Voltage Line to Line
HZ HZ Frequency
KSh KVAh Accumulated Apparent
Energy
KQh K VARh Accumulated Reactive
Energy
KPh KWh Accumulated Real Energy
PLOSS PLOSS Phase Loss
LOWPF LOWPF Low Power Factor Error
F ERR F ERR Frequency Error
I OVR I OVR Over Current
V OVR V OVR Over Voltage
IEC IEEE Description
PULSE PULSE kWh Pulse Output Overrun
_PHASE _PHASE Summary Data for 1, 2, or 3
ALERT ALERT Diagnostic Alert Status
INFO INFO Unit Information
MODEL MODEL Model Number
OS OS Operating System
RS RS Reset System
SN SN Serial Number
RESET RESET Reset Data
PASWD PASWD Enter Reset or Setup
ENERG ENERG Reset Energy Accumulators
DEMND DEMND Reset Demand Maximums
 
PULS_ PULS_ Pulse Counter (if equipped)
Q_ Q_ Quadrant 1-4 per IEEE 1459
n n Net
Over-Current Protective
Device* (not supplied)
≤ 100 mA
Main Menu
Power So urce**
~
=
≤ 100 mA
~
=
(conguration error)
active phases
Password
Import
Export
3-30 VDC 6-3 0 VAC
Power So urce**
3-30 VDC 6-3 0 VAC
ZL00 67-0C Page 11 of 34 ©2013 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com 06131
Alta Labs, E nercept, Ensp ector, Hawkeye, Trus tat, Aerospo nd, Veris, and th e Veris ‘V’ log o are tradema rks or registe red tradema rks of Veris Ind ustries, L. L.C. in the USA and /or other countri es.
Other companies’ trademarks are hereby acknowledged to belong to their respective owners.
Installation Guide Power Monitoring EC, EC
User Interface
DEMND
CPHAS
TM
ENRGY
(Export Wh)
PULS2
Pulse Counter 2
for Pulse Value
PULS1
See SETUP > SPULS > Wh/P
(Import Wh)
Pulse Counter 1
_PHAS
KVAh
HZ
Frequency
BPHAS
APHAS
Export
Apparent Energy
Power (S)
M KVA
Export Demand
Maximum Apparent
Power (Q)
MKVAR
Export Demand
Maximum Reactive
Power (P)
M KW
Maximum Real
Export Demand
Power (S)
M KVA
Import Demand
Maximum Apparent
MKVAR
Power (Q)
Import Demand
Maximum Reactive
M KW
IEEE Display Mode
Power (P)
Import Demand
Maximum Real
Present
D KVA
Demand (S)
Apparent Power
C -KWh
C +KWh
C PF
C KVA
CKVAR
C KW
C VLN
B -KWh
B +KWh
B PF
B KVA
BKVAR
B KWB VLN
A -KWh
A +KWh
A PF
A KVA
AKVAR
A KW
A VLN
3 -KWh
Total Export
Total Import
3 +KWh
3 PF
Power Factor
3 KVA
Total Apparent
3KVAR
Total Reactive
3 KW
Total Real
3 VLN
Volts Line-Neutral (V)
Real Energy
Real Energy
(Average of
Active Phases)
Power (S)
Power (Q)
>>> Scroll When Idle >>>
Power (P)
Phases)
(Average of Active
Import
KVAh
Apparent Energy
KVAh
Signed Net
Apparent Energy
Energy
KVAR4
Quadrant 4
Export Reactive
Energy
KVAR3
Quadrant 3
Export Reactive
Energy
KVAR2
Quadrant 2
Import Reactive
Energy
KVAR1
Quadrant 1
Import Reactive
Export
3 -KWh
Real Energy
To:
Present
Demand (Q)
DKVAR
Reactive Power
Present
Real Power
Demand (P)
D KW
SETUP
DEMND
Demand
C VAC
C A
CPHAS
3 Phase
Phase C:
B VBC
B A
BPHAS
Phase B:
2 & 3 Phase
Systems Only
A VAB
A A
APHAS
Phase A:
Systems Only
3 VLL
Phases)
(Average of Active
Volts Line-Line (U)
3 A
Amps (A)
(Average of
Active Phases)
_PHAS
All Systems
Summary Data
1, 2, or 3 Phase
Energy
Import
3 +KWh
3 KWh
ENRGY
and Counters
Accumulators
Real Energy
Signed Net
Real Energy
To:
ALERT
The units for all Power and Energy screens change to preserve resolution as the
accumulated totals increase. For example, energy starts out as Wh, then switches
ZL00 67-0C Page 12 of 34 ©2013 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com 06131
Alta Labs, E nercept, Ensp ector, Hawkeye, Trus tat, Aerospo nd, Veris, and th e Veris ‘V’ log o are tradema rks or registe red tradema rks of Veris Ind ustries, L. L.C. in the USA and /or other countri es.
Other companies’ trademarks are hereby acknowledged to belong to their respective owners.
to kWh, MWh, and eventually GWh as the accumulated value increases.
Installation Guide Power Monitoring EC, EC
User Interface (cont.)
TM
ENRGY
(Export Ph)
PULS2
Pulse Counter 2
for Pulse Value
PULS1
See SETUP > SPULS > Wh/P
(Import Ph)
Pulse Counter 1
_PHAS
Export
HZ
DEMND
CPHAS
BPHAS
APHAS
Frequency
E KSh
Apparent Energy
IEC Display Mode
Power (S)
M KS
Export Demand
Maximum Apparent
Power (Q)
M KQ
Export Demand
Maximum Reactive
Demand
M KP
Power Export
Maximum Real
Power
M KS
Import Demand
Maximum Apparent
Power
M KQ
Import Demand
Maximum Reactive
Demand
M KP
Power Import
Maximum Real
Present
Demand
D KS
Apparent Power
C -KPh
C +KPh
C PF
C KS
C KQ
C KPC V
B -KPh
B +KPh
B PF
B KS
B KQ
B KP
B V
A -KPh
A +KPh
A PF
A KS
A KQ
A KP
A V
3 -KPh
Total Export
Total Import
3 +KPh
3 PF
Power Factor
3 KS
Total Apparent
3 KQ
Total Reactive
3 KP
Total Real
3 V
Volts Line-Neutral (V)
Real Energy
Real Energy
(Average of
Active Phases)
Power (S)
Power (Q)
>>> Scroll When Idle >>>
Power (P)
Phases)
(Average of Active
Import
E KSh
Apparent Energy
E KSh
Signed Net
Apparent Energy
Energy
Q4 Qh
Quadrant 4
Export Reactive
Energy
Q3 Qh
Quadrant 3
Export Reactive
Energy
Q2 Qh
Quadrant 2
Import Reactive
Energy
Q1 Qh
Quadrant 1
Import Reactive
Export
E -KPh
Real Energy
Present
Demand
D KQ
Reactive Power
Present
Demand
Real Power
D KP
To:
SETUP
DEMND
Demand
C U
C A
CPHAS
3 Phase
Phase C:
Volts CA
Systems Only
Phase B:
Volts BC
B U
B A
BPHAS
2 & 3 Phase
Systems Only
A U
A A
APHAS
Phase A:
All Systems
Volts AB
3 U
3 A
_PHAS
Phases)
(Average of Active
Volts Line-Line (U)
Amps (A)
(Average of
Active Phases)
Import
E +KPh
Real Energy
E KPh
Signed Net
Real Energy
To:
ENRGY
ALERT
Energy
and Counters
1, 2, or 3 Phase
Summary Data
Accumulators
The units for all Power and Energy screens change to preserve resolution as the
accumulated totals increase. For example, energy starts out as Wh, then switches
ZL00 67-0C Page 13 of 34 ©2013 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com 06131
Alta Labs, E nercept, Ensp ector, Hawkeye, Trus tat, Aerospo nd, Veris, and th e Veris ‘V’ log o are tradema rks or registe red tradema rks of Veris Ind ustries, L. L.C. in the USA and /or other countri es.
Other companies’ trademarks are hereby acknowledged to belong to their respective owners.
to kWh, MWh, and eventually GWh as the accumulated value increases.
Installation Guide
T
the Reset Password
p menu).
ergy
h, VAh) to 0.
Maximum
, VAR, VA) to the present
to Reset.
lse counters.
Power Monitoring EC, EC
TM
Alert/Reset Information
Alert Status
(check if
Wrench on
LCD)
Unit
Information
Reset
Data
Setup Meter
To: ENRGY
ALERT
INFO
RESET
SETUP
PLOSS
-------­A b C
Phase Loss
A B C
LOWPF
-------­A b C
Low Power Factor
A B C
F ERR
-------­A
Frequency Out
of Range
Display “nOnE” if no alerts
MODEL OS SNRS
Model
Number
Operating
System
System
Back
PASWD
--------
0
0000
Enter Reset
Password
ENERG
--------
rES
Reset Energy
Accumulators to 0
Reset Demand
Maximums to Present
PASWD
--------
0
0000
Enter Setup
Password
A
Reset
DEMND
--------
rES
I OVR
-------­A b C
Over Current
(Clipping)
A B C
Serial
Number
COUNT
Reset Pulse
Counters to 0
--------
rES
V OVR
-------­A b C
Over Voltage
(Clipping)
A B C
INFO
RESET
To Setup
PULSE
-------­ Error
Energy Pulse Output: Error = Overrun Error
ConF = Configuration Error
ALER
PASWD – Enter (configured in the setu ENERG – Reset all En Accumulators (Wh, VAR Press “+” or “-“ to Reset. DEMND – Reset all Demand (W Demand. Hit “+” or “-“ COUNT – Reset the pu Press “+” or “-“ to Reset.
To: DEMND
ZL00 67-0C Page 14 of 34 ©2013 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com 06131
Alta Labs, E nercept, Ensp ector, Hawkeye, Trus tat, Aerospo nd, Veris, and th e Veris ‘V’ log o are tradema rks or registe red tradema rks of Veris Ind ustries, L. L.C. in the USA and /or other countri es.
Other companies’ trademarks are hereby acknowledged to belong to their respective owners.
Installation Guide Power Monitoring EC, EC
UI for Setup
From:
SETUP > PASWD
To Setup p. 2 “SPASS”
Back S COM
RS-485
Output
ADDR
--------
0
01
BAUD
--------
38400
19200
9600 4800 2400 1200
Next
PAR
--------
nOnE
EvEn
Odd
TM
Set Communications Parameters: ADDR - Modbus Address: 1 – 247. + increments the selected (blinking) digit.
- selects the digit to the left. BAUD - Baud Rate: 1200 – 38400 Baud PAR - Parity: Odd, Even, None
+ or to step through the options.
Transformer
Back To SETUP
Back
Current
Back
System
Type
Back
Potential
Transformer
Back
Sytem
Voltage
S CT
S SYS
S PT
S V
CT V
--------
1.0
.33
SYSTM
--------
3L-1n
3L 2L-1n 2L 1L-1n
RATIO
--------
001
V LL
--------
0
0600
.00
Next
Next
Next
CT SZ
--------
00
1
Next
Set System Configuration: SYSTM: + or to step through the following System Type options:
System 3L-1n 40 3 Wye Three Phase: A, B, & C with Neutral (Default). 3L 31 3 Delta Three Phase: A, B & C; no Neutral 2L-1n 12 2 Single Split Phase: A & B with Neutral 2L 11 1 Single Phase: A & B; no Neutral 1L-1n 10 1 Single Phase: A to Neutral
Set Potential Transfomer Ratio: RATIO – Potential transformer step down is RATIO:1. Default is 1:1
(No PT installed). See Install for wiring diagrams. This value must be set before the System Voltage (if used).
Set System Voltage: V LL – The nominal Line to Line Voltage for the system. This is used
by the meter to calculate the theoretical maximum system power, and as the reference voltage for setting the Phase Loss threshold. Maximum is 32000 Volts. For system type 1+N (10), this is a Line to Neutral Voltage, indicated by “V LN”. Note: the meter will reject settings that are not within the meter’s operating range when divided by the PT ratio.
Set Current Transducer: CT V - CT Input Voltage: + or to Select 1.0 or .33V. CT SZ - CT Size: in Amps. Maximum is 32000 Amps.
Reg 130 CTs Description
System Power: MX KW – The theoretical Maximum System Power is calculated by the
meter from the System Voltage, CT size, and System Type. Power Factor is assumed to be unity. The value of System Power is used to determine which combinations of pulse weight and duration are valid and will keep up with the maximum power the meter will see. This value is read only.
Note: Bold is the Default.
Back
S PWR
Sytem
Voltage
To Setup p. 2 “SPLOS”
MX KW
--------
103.92
Next
ZL00 67-0C Page 15 of 34 ©2013 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com 06131
Alta Labs, E nercept, Ensp ector, Hawkeye, Trus tat, Aerospo nd, Veris, and th e Veris ‘V’ log o are tradema rks or registe red tradema rks of Veris Ind ustries, L. L.C. in the USA and /or other countri es.
Other companies’ trademarks are hereby acknowledged to belong to their respective owners.
Installation Guide Power Monitoring EC, EC
UI for Setup (cont.)
Back To SETUP
To Setup p. 1 “S PWR”
Back
Back
Back
SPLOS
Phase
Loss
SPULS
Pulse
Output
SDMND
Demand
VOLTS
--------
0.1
Wh/P
--------
10000
1000
100
10
INTRV
--------
TM
Set Phase Loss: VOLTS - Phase Loss Voltage: The fraction of the system
voltage below which Phase Loss Alarm is on. For system types with neutral, the Line to Neutral voltage is also
IMBAL
--------
0.2
500 250 100
50 25 10
Next
SEC
--------
0
0900
Next
5
Max PPS
--------
10 20 50
0
mS/P
--------
Next
6 5 4 3 2
1
calculated and tested. If the System Voltage is 600 and the fraction is set to 0.10, then the Phase Loss threshold will be 60 volts. IMBAL - Phase Loss Imbalance: The fractional difference in Line to Line voltages above which Phase Loss Alarm is on. For system types with neutral, the Line to Neutral voltages are also tested. For system types 1+N (10) and 2 (11) , imbalance is not tested.
Set Pulse:
The System Type , CT size, PT Ratio, and System Voltage must all be configured before setting the Pulse Energy. If any of these parameters are changed, the meter will hunt for a new Pulse Duration, but will not change the Pulse Energy. If it cannot find a solution, the meter will display the wrench, show “ConF” in the ALARM -> PULSE screen, and enable Energy pulse output configuration error bit in the Modbus Diagnostic Alert Bitmap (if
1
equipped).
2
Wh/P - Set Pulse Energy: In Watt Hours (& VAR Hours, if
5
present) per Pulse. When moving down to a smaller energy, the meter will not allow the selection if it cannot find a pulse duration that will allow the pulse output to keep up with Theoretical Maximum System Power (see S_PWR screen). When moving up to a larger energy, the meter will jump to the first value where it can find a valid solution. mS/P – Minimum Pulse Duration Time: This read only value is set by the meter to the slowest duration (in mS per closure) that will keep up with the Theoretical Maximum System Power. The open time is greater than or equal to the closure time. The maximum Pulses Per Second (PPS) is shown in yellow.
Set Demand Interval: INTRV - The number of Sub-Intervals (1 to 6) in a Demand Interval.
Default is 1 (block demand). SEC - Sub-Interval length in seconds. Default is 900 (15 minutes). Set to 0 for external sync-to-comms (Modbus units only).
Back
Back
Passwords
To Setup page 1 “S COM”
S DIS
Display
Units
SPASS
Setup
UNITS
--------
IEEE
IEC
Next
SETUP
--------
0
0000
RESET
--------
0
0000
Next
Set Display Units: +/- to switch between:
IEEE – VLL VLN W VAR VA Units. IEC - U V P Q S Units.
Set Passwords: SETUP - The Password to enter the SETUP menu. RESET - The Password to enter the RESET menu.
ZL00 67-0C Page 16 of 34 ©2013 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com 06131
Alta Labs, E nercept, Ensp ector, Hawkeye, Trus tat, Aerospo nd, Veris, and th e Veris ‘V’ log o are tradema rks or registe red tradema rks of Veris Ind ustries, L. L.C. in the USA and /or other countri es.
Other companies’ trademarks are hereby acknowledged to belong to their respective owners.
Installation Guide
Red
Black
Gray
Use 14-24 gauge wire
Power Monitoring EC, EC
TM
RS-485 Communications
Daisy-chaining Devices to the Power Meter
The RS-485 slave port allows the power meter to be connec ted in a daisy chain with up to 63 2-wire devices.
120 Ω terminator on the rst and last
device of the daisy chain
+
S
Shield wire
Notes
• The terminal’s voltage and current ratings are compliant with the requirements of the EIA RS-485 communications standard.
• The RS-485 transceivers are ¼ unit load or less.
• RS-485+ has a 47 k pull up to +5V, and RS-485- has a 47 k pull down to Shield (RS-485 signal ground).
• Wire the RS-485 bus as a daisy chain from device to device, without any stubs. Use 120  termination resistors at each
end of the bus (not included).
• Shield is not internally connected to Earth Ground.
• Connect Shield to Earth Ground somewhere on the RS-485 bus.
For all terminals:
• When tightening terminals, apply the correct torque: 0.37 to 0.44 ft·lb (0.5-0.6 N·m).
• Use 14-24 gauge (2.1-0.2 mm2) wire.
0.37–0.44 ft•lb (0.5–0.6 N•m)
Data Logging (EC only)
The E51C3 includes a data logging feature that records 10 meter parameters, each in its own buer.
Configuration
Use register 150 to set the data logging time subinterval. Writing to the storage buer is triggered by the subinterval timer. The default subinterval is 15 minutes (at a 15 minute interval setting, the buers hold 60 days of data). An external timer can be used over Modbus by setting this register to 0.
Use register 159 to turn on data logging and select either Single Shot or Continuous mode. (default is data logging on, Continuous mode). In Single Shot mode, the meter records data until the buer is full. When the buer is full, the meter stops recording new readings. Data for this time period is kept, but newer energy information is lost. In Continuous mode, the meter continues to record energy data as long as the meter is operating. The buer can only hold 5760 entries at one time, however, so when the number of records exceeds 5760, the oldest entry is deleted to make room for the newest.
Registers 169-178 contain the pointers to 10 data storage buers. Each buer is user-congurable with the Modbus address of the 16-bit data output to be stored. 32-bit data, such as oating point data or 32-bit integer energy accumulators, require two buers. However, the lower 16 bits of an integer energy accumulator can be stored in a single buer (optional).
When the E51C3 is rst installed, the buers contain QNAN data, with a value of 0x8000. This data is considered invalid. If the buer is reset at any point, all entries in the buers are overwritten with this 0x8000 value, indicating that it is invalid. All invalid data is overwritten as the meter lls the buer with new data entries.
Reading Data
Use register 158 to choose which buer to read. When this register value is set to 0, the meter is in data logging mode. Changing this value from 0 to (1 through 10)switches the meter to reading mode and selects a buer to read. Data from the selected buer appears in registers 8000 to 13760.
ZL00 67-0C Page 17 of 34 ©2013 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com 06131
Alta Labs, E nercept, Ensp ector, Hawkeye, Trus tat, Aerospo nd, Veris, and th e Veris ‘V’ log o are tradema rks or registe red tradema rks of Veris Ind ustries, L. L.C. in the USA and /or other countri es.
Other companies’ trademarks are hereby acknowledged to belong to their respective owners.
Installation Guide Power Monitoring EC, EC
TM
Data Logging (EC only, cont.)
Modbus Point Map Overview
Read/Write Collision
If the demand sub-interval timeout occurs while the user is reading a page (register 158 ≠ 0), the log data will be held in RAM until the next demand subinterval. At that time, both the saved data from the previous cycle and the new data will be written to the log, whether the page register has been set back to 0 or not. Error bits in the Log Status Register (160) track these conditions. Subsequent log writes will proceed normally. Provided the log read is concluded in less time than the demand sub-interval, this mechanism handles the occasional collision and prevents the user from reading data as the buer is being updated.
The Log Status Register has additional error ag bits that indicate whether logging has been reset or interrupted (power cycle, etc.) during the previous demand sub-interval, and whether the Real-Time Clock has been changed (re-initialized to default date/ time due to a power-cycle or modied via Modbus commands).
The E51C2 Full Data Set (FDS) model features data outputs such as demand calculations, per phase signed watts VA and VAR, import/export Wh and VAh, and VARh accumulators by quadrant. The E51C3 Data Logging model includes the FDS and adds log conguration registers 155-178 and log buer reading at registers 8000-13760. The meter supports variable CTs and PTs, allowing a much wider range of operation from 90V x 5A up to 32000V x 32000A. To promote this, the meter permits variable scaling of the 16-bit integer registers via the scale registers. The 32-bit oating point registers do not need to be scaled.
Integer registers begin at 001 (0x001). Floats at 257 (0x101). Conguration registers at 129 (0x081). Values not supported in a particular System Type conguration report QNAN (0x8000 in Integer Registers, 0x7FC00000 in Floating Point Registers). Register addresses are in PLC style base 1 notation. Subtrac t 1 from all addresses for the base 0 value used on the Modbus RS-485 link.
Supported Modbus Commands
Note: ID String information varies from model to model. Text shown here is an example.
Command Description
0x03 Read Holding Registers
0x04 Read Input Registers
0x06 Preset Single Register
0x10 Preset Multiple Registers
Report ID
Return string: byte0: address
0x11
0x2B
byte1: 0x11 byte2: #bytes following w/out crc byte3: ID byte = 247 byte4: status = 0xFF if the operating system is used; status = 0x00 if the reset system is used bytes5+: ID string = “Veris Industries E51xx Power Meter Full Data Set” or “Veris Industries E51xx Power Meter - RESET
SYSTEM RUNNING RS Version x.xxx” last 2 bytes: CRC
Read Device Identication, BASIC implementation (0x00, 0x01 and 0x02 data), Conformity Level 1.
Object values: 0x01: “Veris Industries” 0x02: “ E51xx ” 0x03: “Vxx.yyy”, where xx.yyy is the OS version number (reformatted version of the Modbus register #7001, (Firmware
Version, Operating System).
If register #7001 == 12345, then the 0x03 data would be “V12.345”).
Legend
The following table lists the addresses assigned to each data point. For oating point format variables, each data point appears twice because two 16-bit addresses are required to hold a 32-bit oat value. Negative signed integers are 2’s complement.
ZL00 67-0C Page 18 of 34 ©2013 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com 06131
Alta Labs, E nercept, Ensp ector, Hawkeye, Trus tat, Aerospo nd, Veris, and th e Veris ‘V’ log o are tradema rks or registe red tradema rks of Veris Ind ustries, L. L.C. in the USA and /or other countri es.
Other companies’ trademarks are hereby acknowledged to belong to their respective owners.
Installation Guide Power Monitoring EC, EC
TM
Modbus Point Map Overview (cont.)
Standard Modbus Default Settings
R/W
NV Value is stored in non-volatile memor y. The value will still be available if the meter experiences a power loss and reset.
Format
Units Lists the physical units that a register holds.
Scale
Factor
Range Denes the limit of the values that a register can contain.
R=read only R/W=read from either int or oat formats, write only to integer format.
UInt Unsigned 16-bit integer.
SInt Signed 16-bit integer.
ULong Unsigned 32-bit integer; Upper 16-bits (MSR) in lowest-numbered / rst listed register (001/002 = MSR/LSR).
SLong Signed 32-bit integer; Upper 16-bits (MSR) in lowest-numbered / rst listed register (001/002 = MSR/LSR).
Float 32-bit oating point; Upper 16-bits (MSR) in lowest-numbered / rst listed register (257/258 = MSR/LSR). Encoding is
per IEEE standard 754 single precision.
Some Integer values must be multiplied by a constant scale factor (typically a fraction), to be read correctly. This is done to allow
integer numbers to represent fractional numbers.
Setting Value Modbus
Register
Setup Password 00000
Reset Password 00000
System Type 40 (3 + N) Wye 130
CT Primary Ratio (if CTs are not included) 100A 131
CT Secondary Ratio 1V 132
PT Ratio 1:1 (none) 133
System Voltage 600 V L-L 134
Max. Theoretical Power (Analog Output: full scale (20mA or 5V))
Display Mode 1 (IEEE units) 137
Phase Loss 10% of System Voltage (60V ), 25% Phase to Phase Imbalance 142, 143
Pulse Energy 1 (kWh/pulse) 144
Demand: number of sub-intervals per interval 1 (block mode) 149
Demand: sub-interval length 900 sec (15 min) 150
Modbus Address 001
Modbus Baud Rate 19200 baud
Modbus Parity None
Log Read Page 0 158
Logging Conguration Register 0 159
Log Register Pointer 1 3 (Impor t Real Energy MSR) 169
Log Register Pointer 2 4 (Impor t Real Energy LSR) 170
Log Register Pointer 3 5 (Expor t Real Energy MSR) 171
Log Register Pointer 4 6 (Expor t Real Energy LSR) 172
Log Register Pointer 5 29 (Real Demand) 173
Log Register Pointer 6 30 (Reactive Demand) 174
Log Register Pointer 7 31 (Apparent Demand) 175
Log Register Pointer 8 155 (Month/Day) 176
Log Register Pointer 9 156 ( Year/Hour) 177
Log Register Pointer 10 157 (Minutes/Seconds) 178
104 kW 135
ZL00 67-0C Page 19 of 34 ©2013 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com 06131
Alta Labs, E nercept, Ensp ector, Hawkeye, Trus tat, Aerospo nd, Veris, and th e Veris ‘V’ log o are tradema rks or registe red tradema rks of Veris Ind ustries, L. L.C. in the USA and /or other countri es.
Other companies’ trademarks are hereby acknowledged to belong to their respective owners.
Installation Guide Power Monitoring EC, EC
Modbus Point Map
R/W NV Format Units Scale Range Description
Register
E51C3 Log
E51C2 FDS
Integer Data: Summary of Active Phases
001
002 LSR
003
004 LSR
005
006 LSR
007
008 LSR
009
010 LSR
011
012 LSR
013
014 LSR
015
016 LSR
017
018 LSR
019
020 LSR
021 R SInt kW W -32767 to +32767 Total Instantaneous Real (P) Power
022 R SInt kVAR W 0 to 32767 Total Instantaneous Reactive (Q) Power
023 R UInt kVA W 0 to 32767 Total Instantaneous Apparent (S) Power (vector sum)
024 R SInt Ratio 0.0001 -10000 to +10000 Total Power Factor (total kW / total kVA)
025 R UInt Volt V 0 to 32767 Voltage, L-L (U), average of active phases
026 R UInt Volt V 0 to 32767 Voltage, L-N (V), average of active phases
027 R UInt Amp I 0 to 32767 Current, average of active phases
028 UInt Hz 0.01 4500 to 6500 Frequency
029 R SInt kW W -32767 to +32767 Total Real Power Present Demand
030 SInt kVAR W -32767 to +32767 Total Reactive Power Present Demand
031 R SInt kVA W -32767 to +32767 Total Apparent Power Present Demand
032 R NV SInt kW W -32767 to +32767 Total Real Power Max. Demand
033 R NV SInt kVAR W -32767 to +32767 Total Reactive Power Max. Demand
034 R NV SInt kVA W -32767 to +32767 Total Apparent Power Max. Demand
035 R NV SInt kW W -32767 to +32767 Total Real Power Max. Demand
037 R NV SInt kVA W -32767 to +32767 Total Apparent Power Max. Demand
038 R UInt Reserved, returns 0x8000 (QNAN)
039
040 LSR
041
042 LSR
R NV SLong kWh E
R NV ULong kWh E 0 to 0xFFFFFFFF
R NV ULong kWh E 0 to 0xFFFFFFFF
R NV ULong kVARh E 0 to 0xFFFFFFFF
R NV ULong kVARh E 0 to 0xFFFFFFFF
R NV ULong kVARh E 0 to 0xFFFFFFFF
R NV ULong kVARh E 0 to 0xFFFFFFFF
R NV SLong kVAh E
R NV ULong kVA h E 0 to 0xFFFFFFFF
R NV ULong kVA h E 0 to 0xFFFFFFFF
R NV ULong 0 to 0xFFFFFFFF
R NV ULong 0 to 0xFFFFFFFF
-2147483647 to +2147483647
-2147483647 to +2147483647
Real Energy: Net (Import - Export)
Real Energy: Quadrants 1 & 4 Import
Real Energy: Quadrants 2 & 3 Export
Reactive Energy - Quadrant 1: Lags Import Real Energy (IEC) Inductive (IEEE)
Reactive Energy - Quadrant 2: Leads Export Real Energy (IEC) Inductive (IEEE)
Reactive Energy - Quadrant 3: Lags Export Real Energy (IEC) Capacitive (IEEE)
Reactive Energy - Quadrant 4: Leads Import Real Energy (IEC) Capacitive (IEEE)
Apparent Energy: Net (Import - Export)
Apparent: Quadrants 1 & 4 Import
Apparent: Quadrants 2 & 3 Export
Pulse Counter 1 (Import Real Energy)
Pulse Counter 2 (Export Real Energy)
MSR
MSR
MSR
Accumulated
MSR
MSR
MSR
MSR
MSR
MSR
MSR
MSR
MSR
Import
Export • 036 R NV SInt kVAR W -32767 to +32767 Total Reactive Power Max. Demand
Contact Closure Counters. Valid for both pulse
Real Energy (Ph)
Accumulated
Reactive Energy (Qh):
Quadrants 1 + 2
= Import
Quadrants 3 + 4
= Export
Accumulated
Apparent Energy (Sh):
Import and
Export correspond with Real Energy
inputs and outputs. E51Cx counts are shown in (). See register 144 - Energy Per Pulse for the Wh per pulse count.
Clear via reset
register 129
Reset via register
129
TM
ZL00 67-0C Page 20 of 34 ©2013 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com 06131
Alta Labs, E nercept, Ensp ector, Hawkeye, Trus tat, Aerospo nd, Veris, and th e Veris ‘V’ log o are tradema rks or registe red tradema rks of Veris Ind ustries, L. L.C. in the USA and /or other countri es.
Other companies’ trademarks are hereby acknowledged to belong to their respective owners.
Installation Guide Power Monitoring EC, EC
Modbus Point Map (cont.)
R/W NV Format Units Scale Range Description
Register
E51C3 Log
E51C2 FDS
Integer Data: Per Phase
043
044 LSR
045
046 LSR
047
048 LSR
049
050 LSR
051
052 LSR
053
054 LSR
055
056 LSR
057
058 LSR
059
060 LSR
061
062 LSR
063
064 LSR
065
066 LSR
067
068 LSR
069
070 LSR
071
072 LSR
073
074 LSR
075
076 LSR
077
078 LSR
R NV ULong kWh E 0 to 0xFFFFFFFF
R NV ULong kWh E 0 to 0xFFFFFFFF
R NV ULong kWh E 0 to 0xFFFFFFFF
R NV ULong kWh E 0 to 0xFFFFFFFF
R NV ULong kWh E 0 to 0xFFFFFFFF
R NV ULong kWh E 0 to 0xFFFFFFFF
R NV ULong kVARh E 0 to 0xFFFFFFFF
R NV ULong kVARh E 0 to 0xFFFFFFFF
R NV ULong kVARh E 0 to 0xFFFFFFFF
R NV ULong kVARh E 0 to 0xFFFFFFFF
R NV ULong kVARh E 0 to 0xFFFFFFFF
R NV ULong kVARh E 0 to 0xFFFFFFFF
R NV ULong kVARh E 0 to 0xFFFFFFFF
R NV ULong kVARh E 0 to 0xFFFFFFFF
R NV ULong kVARh E 0 to 0xFFFFFFFF
R NV ULong kVARh E 0 to 0xFFFFFFFF
R NV ULong kVARh E 0 to 0xFFFFFFFF
R NV ULong kVARh E 0 to 0xFFFFFFFF
Accumulated Real Energy,
Phase A
Accumulated Real Energy,
Phase B
Accumulated Real Energy,
Phase C
Accumulated Real Energy,
Phase A
Accumulated Real Energy,
Phase B
Accumulated Real Energy,
Phase C
Accumulated Q1 Reactive
Energy, Phase A
Accumulated Q1 Reactive
Energy, Phase B
Accumulated Q1 Reactive
Energy, Phase C
Accumulated Q2 Reactive
Energy, Phase A
Accumulated Q2 Reactive
Energy, Phase B
Accumulated Q2 Reactive
Energy, Phase C
Accumulated Q3 Reactive
Energy, Phase A
Accumulated Q3 Reactive
Energy, Phase B
Accumulated Q3 Reactive
Energy, Phase C
Accumulated Q4 Reactive
Energy, Phase A
Accumulated Q4 Reactive
Energy, Phase B
Accumulated Q4 Reactive
Energy, Phase C
MSR
MSR
MSR
MSR
MSR
MSR
MSR
MSR
MSR
MSR
MSR
MSR
MSR
MSR
MSR
MSR
MSR
MSR
TM
Import
Accumulated Real
Energy (Ph), per phase
Export
Import
Accumulated
Reactive Energy (Qh), Per Phase
Export
ZL00 67-0C Page 21 of 34 ©2013 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com 06131
Alta Labs, E nercept, Ensp ector, Hawkeye, Trus tat, Aerospo nd, Veris, and th e Veris ‘V’ log o are tradema rks or registe red tradema rks of Veris Ind ustries, L. L.C. in the USA and /or other countri es.
Other companies’ trademarks are hereby acknowledged to belong to their respective owners.
Installation Guide Power Monitoring EC, EC
Modbus Point Map (cont.)
R/W NV Format Units Scale Range Description
Register
E51C3 Log
E51C2 FDS
TM
079
080 LSR
081
082 LSR
083
084 LSR
085
086 LSR
087
088 LSR
089
090 LSR
091 R SInt kW W -32767 to +32767 Real Power (P), Phase A
093 R SInt kW W -32767 to +32767 Real Power (P), Phase C
094 R SInt kVAR W -32767 to +32767 Reactive Power (Q), Phase A
096 R SInt kVAR W -32767 to +32767 Reactive Power (Q), Phase C
097 R UInt kVA W 0 to 32767 Apparent Power (S), Phase A
099 R UInt kVA W 0 to 32767 Apparent Power (S), Phase C
100 R SInt Ratio 0.0001 -10000 to +10000 Power Factor (PF), Phase A
102 R SInt Ratio 0.0001 -10000 to +10000 Power Factor (PF), Phase C
103 R UInt Volt V 0 to 32767 Voltage (U), Phase A-B
105 R UInt Volt V 0 to 32767 Voltage (U), Phase A-C
106 R UInt Volt V 0 to 32767 Voltage (V), Phase A-N
108 R UInt Volt V 0 to 32767 Voltage (V), Phase C-N
109 R UInt Amp I 0 to 32767 Current, Phase A
111 R UInt Amp I 0 to 32767 Current, Phase C
112 R UInt Reserved, Returns 0x8000 (QNAN)
R NV ULong kVA h E 0 to 0xFFFFFFFF
R NV ULong kVA h E 0 to 0xFFFFFFFF
R NV ULong kVA h E 0 to 0xFFFFFFFF
R NV ULong kVA h E 0 to 0xFFFFFFFF
R NV ULong kVA h E 0 to 0xFFFFFFFF
R NV ULong kVA h E 0 to 0xFFFFFFFF
Accumulated Apparent Energy,
Phase A
Accumulated Apparent Energy,
Phase B
Accumulated Apparent Energy,
Phase C
Accumulated Apparent Energy,
Phase A
Accumulated Apparent Energy,
Phase B
Accumulated Apparent Energy,
Phase C
MSR
MSR
MSR
MSR
MSR
MSR
Import
Accumulated
Apparent Energy (Sh), Per Phase
Export
Real Power (P) • 092 R SInt kW W -32767 to +32767 Real Power (P), Phase B
Reactive Power (Q) • 095 R SInt kVAR W -32767 to +32767 Reactive Power (Q), Phase B
Apparent Power (S) • 098 R UInt kVA W 0 to 32767 Apparent Power (S), Phase B
Power Factor (PF) • 101 R SInt Ratio 0.0001 -10000 to +10000 Power Factor (PF), Phase B
Line to Line Voltage (U) • 104 R UInt Volt V 0 to 32767 Voltage (U), Phase B-C
Line to Neutral Voltage ( V) • 107 R UInt Volt V 0 to 32767 Voltage (V), Phase B-N
Current • 110 R UInt Amp I 0 to 32767 Current, Phase B
ZL00 67-0C Page 22 of 34 ©2013 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com 06131
Alta Labs, E nercept, Ensp ector, Hawkeye, Trus tat, Aerospo nd, Veris, and th e Veris ‘V’ log o are tradema rks or registe red tradema rks of Veris Ind ustries, L. L.C. in the USA and /or other countri es.
Other companies’ trademarks are hereby acknowledged to belong to their respective owners.
Installation Guide Power Monitoring EC, EC
Modbus Point Map (cont.)
R/W NV Format Units Scale Range Description
Register
E51C3 Log
E51C2 FDS
Conguration
Reset:
- Write 30078 (0x757E) to clear all Energy Accumulators to 0 (All).
- Write 21211 (0x52DB) to begin new Demand Sub-Interval calculation cycle. Takes eect at the end of the next 1 second calculation cycle. Write no more frequently than every 10 seconds.
129 R/W UInt N/A
10, 11,
130 R/W NV UInt
131 R/W NV UInt Amps 1-32000 CT Ratio – Primary
132 R/W NV UInt 1, 3 CT Ratio – Secondary Interface (1 or 1/3 V, may not be user congurable)
133 R/W NV UInt 100 0.01-320.00
134 R/W NV UInt 82-32000
135 R NV UInt kW W 1-32767
136 R UInt Reserved, always returns 0
137 R/W NV UInt 0,1 Display Units: 0 = IEC (U, V, P, Q, S), 1 = IEEE (default: VLL, VLN, W, VAR, VA)
138 R SInt
139 R SInt Scale Factor V (Voltage)
140 R SInt Scale Factor W (Power)
141 R SInt Scale Factor E (Energy)
12, 31, 40
-4 0.0001
-3 0.001
-2 0.01
-1 0.1 0 1.0 1 10.0 2 100.0 3 1000.0 4 10000.0
- Write 21212 (0x52DC) to reset Max Demand values to Present Demand Values. Takes eect at the end of the next 1 second calculation cycle. Write no more frequently than every 10 seconds.
- Write 16640 (0x4100) to reset Logging (E51C3 only).
- Write 16498 (0x4072) to clear Pulse Counts to zero.
- Read always returns 0.
Single Phase: A + N Single Phase: A + B Single Split Phase: A + B + N 3 phase ∆, A + B + C, no N 3 phase Y, A + B + C + N
PT Ratio: The meter scales this value by 100 (i.e. entering 200 yields a potential transformer ratio of 2:1).
The default is 100 (1.00:1), which is with no PT attached. Set this value before setting the system voltage (below)
System Voltage: This voltage is line to line, unless in system type 10 (register 130), which is line to neutral.
The meter uses this value to calculate the full scale power for the pulse conguration (below), and as full scale for phase loss (register 142). The meter will refuse voltages that are outside the range of 82-660 volts when divided by the PT Ratio (above).
Theoretical Maximum System Power – This read only register is the theoretical maximum power the meter
expects to see on a service. It is calculated by the meter from the System Type (register 130), CT size (register
131), and System Voltage (register 134) and is updated whenever the user changes any of these parameters. It is used to determine the maximum power the pulse outputs can keep up with. This integer register has the same scale as other integer power registers (see register 140 for power scaling).
Scale Factor I (Current)
TM
System Type (See Manual. Note: only the
indicated phases are monitored for Phase Loss)
Current Inputs
Scale Factors
Note: These registers contain a signed
integer, which scales the corresponding integer registers. Floating point registers are not scaled. Scaling is recalculated when the meter conguration is changed.
ZL00 67-0C Page 23 of 34 ©2013 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com 06131
Alta Labs, E nercept, Ensp ector, Hawkeye, Trus tat, Aerospo nd, Veris, and th e Veris ‘V’ log o are tradema rks or registe red tradema rks of Veris Ind ustries, L. L.C. in the USA and /or other countri es.
Other companies’ trademarks are hereby acknowledged to belong to their respective owners.
Installation Guide Power Monitoring EC, EC
Modbus Point Map (cont.)
R/W NV Format Units Scale Range Description
Register
E51C3 Log
E51C2 FDS
142 R/W NV UInt % 1-99
143 R/W NV UInt % 1-99
144 R/W NV UInt Wh
145 R NV UInt msec
146 R UInt
10000, 1000, 100, 10
500, 250, 100, 50, 25, 10
Phase Loss Voltage Threshold in percent of system voltage (register
134). Default value is 10 (%). Any phase (as congured in register
130) whose level drops below this threshold triggers a Phase Loss alert, i.e., if the System voltage is set to 480 V L-L, the L-N voltage for each phase should be 277 V. When the threshold is set to 10%, if any phase drops more than 10% below 277 V, (less than 249 V), or if any L-L voltage drops more than 10% below 480 V (less than 432 V) the corresponding phase loss alarm bit in register 146 will be true.
Phase Loss Imbalance Threshold in Percent. Default is 25% phase
to phase dierence. For a 3-phase Y (3 + N) system type (40 in register 130), both Line to Neutral and Line to Line voltages are tested. In a 3-phase  System type (31 in register 130), only Line to Line voltages are examined. In a single split-phase (2 + N) system type (12 in register 130), just the line to neutral voltage are compared.
Wh (& VARh, if equipped)
Energy per Pulse Output Contact Closure. If the meter cannot nd a pulse duration that will keep up with the max. system power (register
135), it will reject the new value. Check the meter conguration and/or try a larger value.
Pulse Contact Closure Duration
in msec. Read-only. Set to the slowest duration that will keep up with the theoretical max. system power (register
135). The open time ≥ the closure time, so the max. pulse rate (pulses per sec) is the inverse of double the pulse time.
Error Bitmap. 1 = Active: Bit 0: Phase A Voltage out of range Bit 1: Phase B Voltage out of range Bit 2: Phase C Voltage out of range Bit 3: Phase A Current out of range Bit 4: Phase B Current out of range Bit 5: Phase C Current out of range Bit 6: Frequency out of the range of 45 to 65 Hz -OR- insucient voltage to determine frequency. Bit 7: Reserved for future use Bit 8: Phase Loss A Bit 9: Phase Loss B Bit 10: Phase Loss C Bit 11: Low Power Factor on A with one or more phases having a PF less than 0.5 due to mis-wiring of phases Bit 12: Low Power Factor on B Bit 13: Low Power Factor on C Bit 14: Energy pulse output overrun error. The pulse outputs are unable to keep up with the total real power
(registers 3 and 261/262). To x, increase the pulse energy register (register 144) and reset the energy accumulators (see reset register 129).
Bit 15: Energy pulse output conguration error (present pulse energy setting may not keep up with the
theoretical max. system power; see register 135). To x, increase the pulse energy (register 144).
kWh (& VARh, if equipped) Pulse Contacts
Note: The kWh pulse contact can keep up with a maximum power (Watts) of
1800000 x Wh pulse weight ÷ contact closure duration (in msec)
Phase Loss Output
Note: The phases tested are determined
by the System Type.
TM
ZL00 67-0C Page 24 of 34 ©2013 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com 06131
Alta Labs, E nercept, Ensp ector, Hawkeye, Trus tat, Aerospo nd, Veris, and th e Veris ‘V’ log o are tradema rks or registe red tradema rks of Veris Ind ustries, L. L.C. in the USA and /or other countri es.
Other companies’ trademarks are hereby acknowledged to belong to their respective owners.
Installation Guide Power Monitoring EC, EC
Modbus Point Map (cont.)
R/W NV Format Units Scale Range Description
Register
E51C3 Log
E51C2 FDS
147 R NV UInt 0-32767 Count of Energy Accumulator resets
148 R UInt Reserved (returns 0)
149 R/W NV UInt 1-6
150 R/W NV UInt Seconds 0, 10-32767
151 R/W UInt 1-32767 Reserved (returns 0)
152 R NV UInt 0-32767 Power Up Counter.
Number of Sub-Intervals per Demand Interval. Sets the number of sub-intervals that
make a single demand interval. For block demand, set this to 1. Default is 1. When Sub­Interval Length register #150 is set to 0 (sync-to-comms mode), this register is ignored.
Sub-Interval Length in seconds. For sync-to-comms, set this to 0 and use the reset
register (129) to externally re-start the sub-interval. On the E51C3, this is also the logging interval.
TM
Demand Calculation
153 R NV UInt 0-32767
154 R UInt Reserved, returns 0
155 R/W NV UInt
156 R/W NV UInt
157 R/W NV UInt
158 R/W NV UInt 0-10
159 R/W NV UInt
Day /
Month
Hour /
Year
Seconds
/ Minutes
See Bytes
See Bytes Hour 0-23 (0x00-0x17)
See Bytes Seconds 0-59 (0x00-0x3B) Minutes 0-59 (0x00-0x3B)
Output Conguration. E51C2 and E51C3 units have a NO energy contact and NC (Normally Closed - Form B)
Phase Loss contact, so this register will always return a “0”.
Logging Conguration and Status
Most Significant Byte (MSB) Least Significant Byte (LSB)
Day 1-31 (0x01-0x1F) Month 1-12 (0x01-0x0C)
Logging Read Page Register. Selects which of the Register Logs to read (see registers 169-178). 1-10 are valid
entries that put the meter into log reading mode, temporarily pausing logging. When set to 0 (no variable selected for reading), normal logging resumes. The meter will buer one set of log entries while in reading mode if a sub-interval timeout occurs (read/write collision). Default is 0.
Warning: this buered data will be written to the log, and logging will resume on the following sub-interval
timeout whether the page register has been cleared or not, resulting in the appearance of data moving in the buer during reads. To avoid this, log buer reads should be completed and this register set back to 0 in less time than the Demand Sub-interval (preferred) or logging should be halted by setting Bit 1 in register 158 (logs may be missed)
Logging Conguration Register (Bit Mapped): Bit 0: Clear to 0 for Circular log buer mode. Set to 1 for single shot logging mode. Default is 0 (Circular). Bit 1: Clear to 0 to enable Logging. Set to 1 to halt logging. Default is 0 (Log).
Year 0-199 (0x00-0xC7)
Date / Time Clock. Following a power cycle,
resets to: Day 01 Month 01 Hour 00 Year (20) 00
ZL00 67-0C Page 25 of 34 ©2013 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com 06131
Alta Labs, E nercept, Ensp ector, Hawkeye, Trus tat, Aerospo nd, Veris, and th e Veris ‘V’ log o are tradema rks or registe red tradema rks of Veris Ind ustries, L. L.C. in the USA and /or other countri es.
Other companies’ trademarks are hereby acknowledged to belong to their respective owners.
Installation Guide Power Monitoring EC, EC
Modbus Point Map (cont.)
R/W NV Format Units Scale Range Description
Register
E51C3 Log
E51C2 FDS
Logging Status Register (Bit Mapped): Bit 0: Log buer full – Set to 1 when one single shot mode has lled the log buer. In this condition, the
Logged Entry Count will continue to increment. Cleared to 0 when logging is restarted (see reset command register 129).
Bit 1: Log Buer Read Collision 1 – Set to 1 if the meter tried to save log data while the user was reading the
log (Logging Page Register has been set to something other than 0). On the rst collision, the meter holds the data until the next sub-interval and then writes the saved data to the log as well as the data for that interval. This bit is cleared to 0 on the rst demand interval with Logging Page Register = 0.
160 R NV UInt
161 R NV UInt 0-32767
162 R NV UInt 0-32767
163 R NV UInt 0-32767
164
R NV ULong kWh E
165 0-0xFFFF Real Energy Consumption (LSR)
0-0xFFFF
Bit 2: Log Buer Read Collision 2 – Set to 1 on the 2nd attempt to save log data while the user is reading
the log (Logging Page Register is set to something other than 0). At this point the meter ignores the read condition and does a double write, rst of the values saved from the previous c ycle, and then the present values. If the read condition is not removed the meter continues to write the log data as it normally would.
This bit is cleared to 0 on the rst demand interval with Logging Page Register = 0. Bit 3: Logging Reset – The log has been reset during the previous demand sub-interval. Bit 4: Logging Interrupted – Logging has been interrupted (power cycled, log conguration change, etc.)
during the previous demand sub-interval. Bit 5: RTC Changed – The real time clock had been changed during the previous demand subinterval. Bit 6: RTC Reset - The Real Time Clock has been reset to the year 2000 and needs to be re-initialized.
Log Buer Wrap / Missed Log Counter. In continous mode, this counter increments each time the internal
circular log buer wraps and overwrites old data. The total number of logged entries since the last log reset
is: (Register 161 x 5760) + Register 163. In single shot mode this counter is the number of log entries lost
due to the buer being full. The counter is cleared on logging reset. Max Number of Logging Days. Based on the Sub-Interval Length and the depth of the log buer, this register
shows the maximum number of days that data will be logged following a reset until the Buer is full (Single
Shot Mode) or overwrites old data (Continuous). Number of Logged Entries since the log buer wrapped or was reset. In single shot mode, this is the total
number of valid entries in the buer. Any entries beyond this will read back as QNAN (0x8000). Real Energy Consumption
(MSR)
TM
Real Energy (Register 001/002) starting value. Corresponds to when logging
is started, reset, or rolls.
166 R NV UInt
167 R NV UInt
168 R NV UInt
Month / Day
Year / Hour
Minutes
/
Seconds
See Bytes
See Bytes Hour 0-23 (0x00-0x17)
See Bytes Seconds 0-59 (0x00-0x3B) Minutes 0-59 (0x00-0x3B)
Most Significant Byte (MSB) Least Significant Byte (LSB)
Day 1-31 (0x01-0x1F) Month 1-12 (0x01-0x0C)
Year 0-199 (0x00-0xC7)
Date & Time of the newest entry in the log.
After a power cycle, resets to: Day 01 Month 01 Hour 00 Year (20) 00
ZL00 67-0C Page 26 of 34 ©2013 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com 06131
Alta Labs, E nercept, Ensp ector, Hawkeye, Trus tat, Aerospo nd, Veris, and th e Veris ‘V’ log o are tradema rks or registe red tradema rks of Veris Ind ustries, L. L.C. in the USA and /or other countri es.
Other companies’ trademarks are hereby acknowledged to belong to their respective owners.
Installation Guide Power Monitoring EC, EC
Modbus Point Map (cont.)
R/W NV Format Units Scale Range Description
Register
E51C3 Log
E51C2 FDS
Log Register 1 –
169 R/W NV UInt
170 R/W NV UInt
171 R/W NV UInt
172 R/W NV UInt
1-42,
173 R/W NV UInt
174 R/W NV UInt
175 R/W NV UInt
176 R/W NV UInt
177 R/W NV UInt
178 R/W NV UInt
257/258 R NV Float kWh Accumulated Real Energy: Net (Import - Export)
259/260 R NV Float kWh
261/262 R Float kWh
263/264 R Float kVARh
265/266 R Float kVARh
267/268 R Float kVARh
269/270 R Float kVARh
271/272 R NV Float k VAh Apparent Energy: Net (Import - Export)
273/274 R NV Float k VAh
275/276 R NV Float k VAh
277/278 R Float kW Total Net Instantaneous Real (P) Power
279/280 R Float kVAR Total Net Instantaneous Reactive (Q) Power
281/282 R Float k VA Total Net Instantaneous Apparent (S) Power
283/284 R Float Ratio 0.0-1.0 Total Power Factor (Total kW / Total kVA)
285/286 R Float Volt Voltage, L-L (U), average of active phases
146, 155-157, 257-336
Floating Point Data: Summary of Active Phases
Default is 3 (Import Real Energy
MSR) Log Register 2 – Default is 4 (Import Real Energy
LSR) Log Register 3 – Default is 5 (Export Real Energy
MSR) Log Register 4 – Default is 6 (Export Real Energy
LSR) Log Register 5 – Default is 29 (Real Demand) Log Register 6 – Default is 30 (Reactive
Demand) Log Register 7 – Default is 31 (Apparent
Demand) Log Register 8 – Default is 155 (Month/Day)
Log Register 9 – Default is 156 (Year/Hour)
Log Register 10 – Default is 157 (Minutes/
Seconds)
Real Energy: Quadrants 1 & 4 Import
Real Energy: Quadrants 2 & 3 Export
Reactive Energy: Quadrant 1 Lags Import Real Energy (IEC) Inductive (IEEE) Reactive Energy: Quadrant 2 Leads Export Real Energy (IEC) Inductive (IEEE) Reactive Energy: Quadrant 3 Lags Export Real Energy (IEC) Capacitive (IEEE)
Reactive Energy: Quadrant 4 Leads Import Real Energy (IEC) Capacitive (IEEE)
Apparent Energy: Quadrants 1 & 4 Import
Apparent Energy: Quadrants 2 & 3 Export
Log Register Selection – Write the number of the 16 bit register to be logged.
To log a 32 bit value (such as accumulators and oating point values) two log registers must be used, one each for the most and least signicant register (MSR & LSR).
Accumulated Real Energy
(Ph)
Accumulated Reactive
Energy (Qh): Quadrants 1+2= Import Quadrants 3+4= Export
Accumulated Apparent
Energy (Sh): Import and
Export correspond with
Real Energy
TM
Clear via register
129
ZL00 67-0C Page 27 of 34 ©2013 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com 06131
Alta Labs, E nercept, Ensp ector, Hawkeye, Trus tat, Aerospo nd, Veris, and th e Veris ‘V’ log o are tradema rks or registe red tradema rks of Veris Ind ustries, L. L.C. in the USA and /or other countri es.
Other companies’ trademarks are hereby acknowledged to belong to their respective owners.
Installation Guide Power Monitoring EC, EC
Modbus Point Map (cont.)
R/W NV Format Units Scale Range Description
Register
E51C3 Log
E51C2 FDS
287/288 R Float Volt Voltage, L-N (V), average of active phases
289/290 R Float Amp Current, average of active phases
291/292 R Float Hz 45.0-65.0 Frequency
293/294 R Float kW Total Real Power Present Demand
295/296 R Float kVAR Total Reactive Power Present Demand
297/298 R Float k VA Total Apparent Power Present Demand
299/300 R NV Float kW Total Real Power Max. Demand
303/304 R NV Float k VA Total Apparent Power Max. Demand
305/306 R NV Float kW Total Real Power Max. Demand
309/310 R NV Float k VA Total Apparent Power Max. Demand
311/312 R Float Reserved, reports QNAN (0x7FC00000)
TM
Import • 301/302 R NV Float kVAR Total Reactive Power Max. Demand
Export • 307/308 R NV Float kVAR Total Reactive Power Max. Demand
313/314 R Float 1 0-4294967040 Pulse Counter 1 (Import Real Energy)
315/316 R Float 1 0-4294967040 Pulse Counter 2 (Export Reactive Energy
Floating Point Data: Per Phase
317/318 R Float kWh Accumulated Real Energy, Phase A
319/320 R Float kWh Accumulated Real Energy, Phase B
321/322 R Float kWh Accumulated Real Energy, Phase C
323/324 R Float kWh Accumulated Real Energy, Phase A
327/328 R Float kWh Accumulated Real Energy, Phase C
329/330 R Float kVARh Accumulated Q1 Reactive Energy, Phase A
331/332 R Float kVARh Accumulated Q1 Reactive Energy, Phase B
333/334 R Float kVARh Accumulated Q1 Reactive Energy, Phase C
335/336 R Float kVARh Accumulated Q2 Reactive Energy, Phase A
339/340 R Float kVARh Accumulated Q2 Reactive Energy, Phase C
341/342 R Float kVARh Accumulated Q3 Reactive Energy, Phase A
343/344 R Float kVARh Accumulated Q3 Reactive Energy, Phase B
345/346 R Float kVARh Accumulated Q3 Reactive Energy, Phase C
347/348 R Float kVARh Accumulated Q4 Reactive Energy, Phase A
351/352 R Float kVARh Accumulated Q4 Reactive Energy, Phase C
353/354 R Float k VAh Accumulated Apparent Energy, Phase A
355/356 R Float k VAh Accumulated Apparent Energy, Phase B
357/358 R Float k VAh Accumulated Apparent Energy, Phase C
359/360 R Float k VAh Accumulated Apparent Energy, Phase A
363/364 R Float k VAh Accumulated Apparent Energy, Phase C
Contact closure counters. Valid for both pulse
inputs and outputs. E51Cx counts are shown
in (). See register 144 for the weight of each
pulse output count. These values are derived
from the 32 bit integer counter and will roll
over to 0 when the integer counters do. Inputs
are user dened.
Import
Accumulated Real Energy (Ph)
Export • 325/326 R Float kWh Accumulated Real Energy, Phase B
Quadrant 1
Import
Quadrant 2 • 337/338 R Float kVARh Accumulated Q2 Reactive Energy, Phase B
Accumulated
Reactive Energy (Qh)
Quadrant 3
Export
Quadrant 4 • 349/350 R Float kVARh Accumulated Q4 Reactive Energy, Phase B
Import
Accumulated Apparent Energy (Sh)
Export • 361/362 R Float k VAh Accumulated Apparent Energy, Phase B
ZL00 67-0C Page 28 of 34 ©2013 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com 06131
Alta Labs, E nercept, Ensp ector, Hawkeye, Trus tat, Aerospo nd, Veris, and th e Veris ‘V’ log o are tradema rks or registe red tradema rks of Veris Ind ustries, L. L.C. in the USA and /or other countri es.
Other companies’ trademarks are hereby acknowledged to belong to their respective owners.
Installation Guide Power Monitoring EC, EC
Modbus Point Map (cont.)
R/W NV Format Units Scale Range Description
Register
E51C3 Log
E51C2 FDS
365/366 R Float kW Real Power, Phase A
369/370 R Float kW Real Power, Phase A
371/372 R Float kVAR Reactive Power, Phase A
375/376 R Float kVAR Reactive Power, Phase A
377/378 R Float k VA Apparent Power, Phase A
381/382 R Float k VA Apparent Power, Phase A
383/384 R Float Ratio 0.0-1.0 Power Factor, Phase A
387/388 R Float Ratio 0.0-1.0 Power Factor, Phase A
389/390 R Float Volt Voltage, Phase A-B
393/394 R Float Volt Voltage, Phase A-C
395/396 R Float Volt Voltage, Phase A-N
399/400 R Float Volt Voltage, Phase C-N
401/402 R Float Amp Current, Phase A
405/406 R Float Amp Current, Phase C
407/408 R Float Reserved, Reports QNAN (0x7FC00000)
Logging Interface
8000 R NV Newest Logged Data Entry
13760 R NV Oldest Logged Data Entry
TM
Real Power (P) • 367/368 R Float kW Real Power, Phase A
Reactive Power (Q) • 373/374 R Float kVAR Reactive Power, Phase A
Apparent Power (S) • 379/380 R Float k VA Apparent Power, Phase A
Power Factor (PF) • 385/386 R Float Ratio 0.0-1.0 Power Factor, Phase A
Line to Line Voltage (U) • 391/392 R Float Volt Voltage, Phase B-C
Line to Neutral (V) • 397/398 R Float Volt Voltage, Phase B-N
Current • 403/404 R Float Amp Current, Phase B
5760 entries total (60 days at a 15 minute sub-interval)(to) (to)
Invalid or Quiet Not A Number (QNAN) conditions are indicated by 0x8000 (negative zero) for 16 bit integers and 0x7FC00000 for 32 bit oating point numbers.
Floating point numbers are encoded per the IEEE 754 32-bit specications.
ZL00 67-0C Page 29 of 34 ©2013 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com 06131
Alta Labs, E nercept, Ensp ector, Hawkeye, Trus tat, Aerospo nd, Veris, and th e Veris ‘V’ log o are tradema rks or registe red tradema rks of Veris Ind ustries, L. L.C. in the USA and /or other countri es.
Other companies’ trademarks are hereby acknowledged to belong to their respective owners.
Installation Guide Power Monitoring EC, EC
TM
SunSpec Register Blocks
This section describes the Modbus registers reserved for SunSpec compliance-related information. See www.sunspec.org for the original specications.
R/W NV Format Units Scale Range SunSpec Name Description
E51C3 Log
E51C2 FDS
• • 40001
• • 40002
• • 40003 R NV UInt 1 C_SunSpec_DID SunSpec common model Device ID
• • 40004 R NV UInt 65 C_SunSpec_Length Length of the common model block
• • 40005 to 40020 R NV String (32) ASCII C_Manufacturer null terminated ASCII text string = “VERIS”
• • 40021 to 40036 R NV String (32) ASCII C_Model null terminated ASCII text string = “E51C_”
• • 40037 to 40044 R NV String (16) ASCII C_Options null terminated ASCII text string
• • 40045 to 40052 R NV String (16) ASCII C_Version null terminated ASCII text string
• • 40053 to 40068 R NV String (32) ASCII C_SerialNumber null terminated ASCII text string
• • 40068 R NV UInt ASCII C_SunSpec_Length Modbus address
• • 40070 R NV UInt 201 to 204 C_SunSpec_DID
• • 40071 R NV UInt 105 C_SunSpec_Length Length of the meter model block
• • 40072 R SInt Amps M_AC_Current_SF -32767 to +32767 M_AC_Current AC Current (sum of active phases)
• • 40073 R SInt Amps M_AC_Current_SF -32767 to +32767 M_AC_Current_A Phase A AC current
• • 40074 R SInt Amps M_AC_Current_SF -32767 to +32767 M_AC_Current_B Phase B AC current
• • 40075 R SInt Amps M_AC_Current_SF -32767 to +32767 M_AC_Current_C Phase C AC current
• • 40076 R NV SInt 1 M_AC_Current_CN AC Current Scale Factor
• • 40077 R SInt Volts M_AC_Voltage_SF -32767 to +32767 M_AC_Voltage_LN Line to Neutral AC voltage (average of active phases)
• • 40078 R SInt Volts M_AC_Voltage_SF -32767 to +32767 M_AC_Voltage_AN Phase A to Neutral AC Voltage
• • 40079 R SInt Volts M_AC_Voltage_SF -32767 to +32767 M_AC_Voltage_BN Phase B to Neutral AC Voltage
• • 40080 R SInt Volts M_AC_Voltage_SF -32767 to +32767 M_AC_Voltage_CN Phase C to Neutral AC Voltage
• • 40081 R SInt Volts M_AC_Voltage_SF -32767 to +32767 M_AC_Voltage_LL Line to Line AC voltage (average of active phases)
• • 40082 R SInt Volts M_AC_Voltage_SF -32767 to +32767 M_AC_Voltage_AB Phase A to Phase B AC Voltage
• • 40083 R SInt Volts M_AC_Voltage_SF -32767 to +32767 M_AC_Voltage_BC Phase B to Phase C AC Voltage
• • 40084 R SInt Volts M_AC_Voltage_SF -32767 to +32767 M_AC_Voltage_CA Phase C to Phase A AC Voltage
• • 40085 R NV SInt 1 M_AC_Voltage_SF AC Voltage Scale Fac tor
• • 40086 R SInt Hertz M_AC_Freq_SF -32767 to +32767 M_AC_Freq AC Frequency
• • 40087 R NV SInt SF 1 M_AC_Freq_SF AC Frequency Scale Factor
Register
R NV ULong
SunSpec 1.0 Common Model
0x5375 6e53
SunSpec 1.1 Integer Meter Model
Identification
Current
Voltage: Line to Neutral
Voltage: Line to Line
Frequency
C_SunSpec_ID
ASCII “SunS”. Identies this as the beginning of a SunSpec Modbus
point
SunSpec Integer meter model device IDs. Meter conguration by
device ID: 201 = single phase (A-N or A-B) meter 202 = split single phase (A-B-N) meter 203 = Wye-connect 3-phase (ABCN) meter 204 = delta-connect 3-phase (ABC) meter
ZL00 67-0C Page 30 of 34 ©2013 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com 06131
Alta Labs, E nercept, Ensp ector, Hawkeye, Trus tat, Aerospo nd, Veris, and th e Veris ‘V’ log o are tradema rks or registe red tradema rks of Veris Ind ustries, L. L.C. in the USA and /or other countri es.
Other companies’ trademarks are hereby acknowledged to belong to their respective owners.
Installation Guide Power Monitoring EC, EC
SunSpec Register Blocks (cont.)
R/W NV Format Units Scale Range SunSpec Name Description
E51C3 Log
E51C2 FDS
• • 40088 R SInt Watts M_AC_Power_SF -32767 to +32767 M_AC_Power Total Real Power (sum of active phases)
• • 40089 R SInt Watts M_AC_Power_SF -32767 to +32767 M_AC_Power_A Phase A AC Real Power
• • 40090 R SInt Watts M_AC_Power_SF -32767 to +32767 M_AC_Power_B Phase B AC Real Power
• • 40091 R SInt Watts M_AC_Power_SF -32767 to +32767 M_AC_Power_C Phase A AC Real Power
• • 40092 R NV SInt SF 1 M_AC_Power_SF AC Real Power Scale Factor
• • 40093 R SInt
• • 40094 R SInt
• • 40095 R SInt
• • 40096 R SInt
• • 40097 R NV SInt SF 1 M_AC_VA_SF AC Apparent Power Scale Factor
• • 40098 R SInt VAR M_AC_VAR_SF -32767 to +32767 M_AC_VAR Total AC Reactive Power (sum of active phases)
• • 40099 R SInt VAR M_AC_VAR_SF -32767 to +32767 M_AC_VAR_A Phase A AC Reactive Power
• • 40100 R SInt VAR M_AC_VAR_SF -32767 to +32767 M_AC_VAR_B Phase B AC Reactive Power
• • 40101 R SInt VAR M_AC_VAR_SF -32767 to +32767 M_AC_VAR_C Phase A AC Reactive Power
• • 40102 R NV SInt SF 1 M_AC_VAR_SF AC Reactive Power Scale Factor
• • 40103 R SInt % M_AC_PF_SF -32767 to +32767 M_AC_PF Average Power Factor (average of active phases)
• • 40104 R SInt % M_AC_PF_SF -32767 to +32767 M_AC_PF_A Phase A Power Fac tor
• • 40105 R SInt % M_AC_PF_SF -32767 to +32767 M_AC_PF_B Phase B Power Factor
• • 40106 R SInt % M_AC_PF_SF -32767 to +32767 M_AC_PF_C Phase A Power Factor
• • 40107 R NV SInt SF 1 M_AC_PF_SF AC Power Factor Scale Factor
• • 40108
• • 40109
• • 40110
• • 40111
• • 40112
• • 40113
• • 40114
• • 40115
• • 40116
• • 40117
• • 40118
• • 40119
• • 40120
• • 40121
• • 40122
• • 40123
• • 40124 R NV SF SF 1 M_Energy_W_SF Real Energy Scale Factor
Register
R NV ULong
R NV ULong
R NV ULong
R NV ULong
R NV ULong
R NV ULong
R NV ULong
R NV ULong
Power
Real Power
Volt-
M_AC_VA_SF -32767 to +32767 M_AC_VA Total AC Apparent Power (sum of active phases)
Amps
Volt-
M_AC_VA_SF -32767 to +32767 M_AC_VA_A Phase A AC Apparent Power
Amps
Volt-
M_AC_VA_SF -32767 to +32767 M_AC_VA_B Phase B AC Apparent Power
Amps
Volt-
M_AC_VA_SF -32767 to +32767 M_AC_VA_C Phase A AC Apparent Power
Amps
Watt-
M_Energy_W_SF 0x0 to 0xFFFFFFFF M_Exported_W Total Exported Real Energy
hours
Watt-
M_Energy_W_SF 0x0 to 0xFFFFFFFF M_Exported_W_A Phase A Exported Real Energy
hours
Watt-
M_Energy_W_SF 0x0 to 0xFFFFFFFF M_Exported_W_B Phase B Exported Real Energy
hours
Watt-
M_Energy_W_SF 0x0 to 0xFFFFFFFF M_Exported_W_C Phase C Exported Real Energy
hours
Watt-
M_Energy_W_SF 0x0 to 0xFFFFFFFF M_Imported_W Total Imported Real Energy
hours
Watt-
M_Energy_W_SF 0x0 to 0xFFFFFFFF M_Imported_W_A Phase A Imported Real Energy
hours
Watt-
M_Energy_W_SF 0x0 to 0xFFFFFFFF M_Imported_W_B Phase B Imported Real Energy
hours
Watt-
M_Energy_W_SF 0x0 to 0xFFFFFFFF M_Imported_W_C Phase C Imported Real Energy
hours
Apparent Power
Reactive Power
Power Factor
Accumulated Energy
Real Energy
TM
ZL00 67-0C Page 31 of 34 ©2013 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com 06131
Alta Labs, E nercept, Ensp ector, Hawkeye, Trus tat, Aerospo nd, Veris, and th e Veris ‘V’ log o are tradema rks or registe red tradema rks of Veris Ind ustries, L. L.C. in the USA and /or other countri es.
Other companies’ trademarks are hereby acknowledged to belong to their respective owners.
Installation Guide Power Monitoring EC, EC
SunSpec Register Blocks (cont.)
R/W NV Format Units Scale Range SunSpec Name Description
E51C3 Log
E51C2 FDS
• • 40125
• • 40126
• • 40127
• • 40128
• • 40129
• • 40130
• • 40131
• • 40132
• • 40133
• • 40134
• • 40135
• • 40136
• • 40137
• • 40138
• • 40139
• • 40140
• • 40141 R NV UInt SF 1 M_Energy_VA_SF Real Energy Scale Factor
• • 40142
• • 40143
• • 40144
• • 40145
• • 40146
• • 40147
• • 40148
• • 40149
• • 40150
• • 40151
• • 40152
• • 40153
• • 40154
• • 40155
• • 40156
• • 40157
• • 40158
• • 40159
• • 40160
• • 40161
• • 40162
• • 40163
• • 40164
• • 40165
• • 40166
• • 40167
Register
R NV ULong
R NV ULong
R NV ULong
R NV ULong
R NV ULong
R NV ULong
R NV ULong
R NV ULong
R NV ULong
R NV ULong
R NV ULong
R NV ULong
R NV ULong
R NV ULong
R NV ULong
R NV ULong
R NV ULong
R NV ULong
R NV ULong
R NV ULong
R NV ULong
Apparent Energy
VA-
M_Energy_VA_SF 0x0 to 0xFFFFFFFF M_Exported_VA Total Exported Apparent Energy
hours
VA-
M_Energy_VA_SF 0x0 to 0xFFFFFFFF M_Exported_VA_A Phase A Exported Apparent Energy
hours
VA-
M_Energy_VA_SF 0x0 to 0xFFFFFFFF M_Exported_VA_B Phase B Exported Apparent Energy
hours
VA-
M_Energy_VA_SF 0x0 to 0xFFFFFFFF M_Exported_VA_C Phase C Exported Apparent Energy
hours
VA-
M_Energy_VA_SF 0x0 to 0xFFFFFFFF M_Imported_VA Total Imported Apparent Energy
hours
VA-
M_Energy_VA_SF 0x0 to 0xFFFFFFFF M_Imported_VA_A Phase A Imported Apparent Energy
hours
VA-
M_Energy_VA_SF 0x0 to 0xFFFFFFFF M_Imported_VA_B Phase B Imported Apparent Energy
hours
VA-
M_Energy_VA_SF 0x0 to 0xFFFFFFFF M_Imported_VA_C Phase C Imported Apparent Energy
hours
Reactive Energy
VAR-
M_Energy_VAR_SF 0x0 to 0xFFFFFFFF M_Import_VARh_Q1 Quadrant 1: Total Imported Reactive Energy
hours
VAR-
M_Energy_VAR_SF 0x0 to 0xFFFFFFFF
hours
VAR-
M_Energy_VAR_SF 0x0 to 0xFFFFFFFF
hours
VAR-
M_Energy_VAR_SF 0x0 to 0xFFFFFFFF
hours
VAR-
M_Energy_VAR_SF 0x0 to 0xFFFFFFFF M_Import_VARh_Q2 Quadrant 2: Total Imported Reactive Energy
hours
VAR-
M_Energy_VAR_SF 0x0 to 0xFFFFFFFF
hours
VAR-
M_Energy_VAR_SF 0x0 to 0xFFFFFFFF
hours
VAR-
M_Energy_VAR_SF 0x0 to 0xFFFFFFFF
hours
VAR-
M_Energy_VAR_SF 0x0 to 0xFFFFFFFF M_Export_VARh_Q3 Quadrant 3: Total Exported Reactive Energy
hours
VAR-
M_Energy_VAR_SF 0x0 to 0xFFFFFFFF
hours
VAR-
M_Energy_VAR_SF 0x0 to 0xFFFFFFFF
hours
VAR-
M_Energy_VAR_SF 0x0 to 0xFFFFFFFF
hours
VAR-
M_Energy_VAR_SF 0x0 to 0xFFFFFFFF M_Export_VARh_Q4 Quadrant 4: Total Exported Reactive Energy
hours
M_Import_VARh_
Q1A
M_Import_VARh_
Q1B
M_Import_VARh_
Q1C
M_Import_VARh_
Q2A
M_Import_VARh_
Q2B
M_Import_VARh_
Q2C
M_Export_VARh_
Q3A
M_Export_VARh_
Q3B
M_Export_VARh_
Q3C
Phase A - Quadrant 1: Total Imported Reactive Energy
Phase B - Quadrant 1: Total Imported Reactive Energy
Phase C - Quadrant 1: Total Imported Reactive Energy
Phase A - Quadrant 2: Total Imported Reactive Energy
Phase B - Quadrant 2: Total Imported Reactive Energy
Phase C - Quadrant 2: Total Imported Reactive Energy
Phase A - Quadrant 3: Total Exported Reactive Energy
Phase B - Quadrant 3: Total Exported Reactive Energy
Phase C - Quadrant 3: Total Exported Reactive Energy
TM
ZL00 67-0C Page 32 of 34 ©2013 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com 06131
Alta Labs, E nercept, Ensp ector, Hawkeye, Trus tat, Aerospo nd, Veris, and th e Veris ‘V’ log o are tradema rks or registe red tradema rks of Veris Ind ustries, L. L.C. in the USA and /or other countri es.
Other companies’ trademarks are hereby acknowledged to belong to their respective owners.
Installation Guide Power Monitoring EC, EC
SunSpec Register Blocks (cont.)
R/W NV Format Units Scale Range SunSpec Name Description
E51C3 Log
E51C2 FDS
Register
TM
• • 40168
• • 40169
• • 40170
• • 40171
• • 40172
• • 40173
• • 40174 R NV UInt SF 1 M_Energy_VA_SF Reactive Energy Scale Factor
• • 40175
R NV ULong
R NV ULong
R NV ULong
VAR-
M_Energy_VAR_SF 0x0 to 0xFFFFFFFF
hours
VAR-
M_Energy_VAR_SF 0x0 to 0xFFFFFFFF
hours
VAR-
M_Energy_VAR_SF 0x0 to 0xFFFFFFFF
hours
Events
M_Export_VARh_
Q4A
M_Export_VARh_
Q4B
M_Export_VARh_
Q4C
M_Events Bit Map. See M_EVENT_ags. 0 = no event
Phase A - Quadrant 4: Total Exported Reactive Energy
Phase B - Quadrant 4: Total Exported Reactive Energy
Phase C - Quadrant 4: Total Exported Reactive Energy
Event Bit Description
M_EVENT_Power_Failure 0x00000004 Loss of power or phase
M_EVENT_Under_Voltage 0x00000008 Voltage below threshold (phase loss)
M_EVENT_Low_PF 0x00000010 Power factor below threshold (can
• • 40176
R NV ULong Flags
M_EVENT_Over_Current 0x00000020 Current input over threshold (out of
M_EVENT_Over_Voltage 0x00000040 Voltage input over threshold (out of
M_EVENT_Missing_Sensor 0x00000080 Sensor not connected (not supported)
M_EVENT_Reserved1-8 0x00000100 to
0x00008000
M_EVENT_OEM1-15 0x7FFF000 Reserved for OEMs (not used)
indicate misassociated voltage and current inputs in 3-phase systems)
measurement range)
measurement range)
Reserved for future SunSpec use
End of SunSpec Block
• • 40177 R NV UInt 0xFFFF
• • 40178 R NV UInt 0x0000
C_SunSpec_DID = 0xFFFF Uniquely identies this as the last SunSpec block
C_SunSpec_Length = 0 Last block has no length
ZL00 67-0C Page 33 of 34 ©2013 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com 06131
Alta Labs, E nercept, Ensp ector, Hawkeye, Trus tat, Aerospo nd, Veris, and th e Veris ‘V’ log o are tradema rks or registe red tradema rks of Veris Ind ustries, L. L.C. in the USA and /or other countri es.
Other companies’ trademarks are hereby acknowledged to belong to their respective owners.
Installation Guide Power Monitoring EC, EC
TM
Troubleshooting
Problem Cause Solution
The maintenance wrench
icon appears in the power meter display.
The display is blank after
applying control power to the meter.
The data displayed is
inaccurate.
Cannot communicate
with power meter from a remote personal computer.
Sign of one phase (real
power) is incorrect
There is a problem
with the inputs to the power meter.
The meter is not
receiving adequate power.
Incorrect setup values Verify the values entered for power meter setup parameters (CT and PT ratings,
Incorrect voltage inputs Check power meter voltage input terminals to verify adequate voltage.
Power meter is wired
improperly.
Power meter address is
incorrect.
Power meter baud rate
is incorrect.
Communications
lines are improperly connected.
CT orientation reversed Remove CT, reverse orientation, reconnect (qualied personnel only)
See the Alert sub-menu or the Diagnostic Alert Modbus Register 146
Verify that the meter control power are receiving the required voltage. Verify that the heart icon is blinking. Check the fuse.
system type, etc.). See the Setup section.
Check all CTs and PTs to verify correct connection to the same service, CT and PT
polarity, and adequate powering. See the Wiring Diagrams section for more information.
Verify that the meter is correctly addressed (see Setup section).
Verify that the baud rate of the meter matches that of all other devices on its
communications link (see Setup section).
Verify the power meter communications connections (see the Communications
section).
Verify the terminating resistors are properly installed on both ends of a chain of units.
Units in the middle of a chain should not have a terminator.
Verify the shield ground is connected between all units.
China RoHSCompliance Information (EFUPTable)
产品中有毒有害物质或元素的名称及含量Substances
部件名称
铅 (Pb) 汞 (Hg) 镉 (Cd) 六价铬 (Cr(VI)) 多溴联苯(PBB) 多溴二苯醚(PBDE)
电子线路板 X O O O O O
O = 表示该有毒有害物质在该部件所有均质材料中的含量均在 SJ/T11363-2006 标准规定的限量要求以下. X = 表示该有毒有害物质至少在该部件的某一均质材料中的含量超出SJ/T11363-2006标准规定的限量要求.
Z000057-0A
ZL00 67-0C Page 34 of 34 ©2013 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com 06131
Alta Labs, E nercept, Ensp ector, Hawkeye, Trus tat, Aerospo nd, Veris, and th e Veris ‘V’ log o are tradema rks or registe red tradema rks of Veris Ind ustries, L. L.C. in the USA and /or other countri es.
Other companies’ trademarks are hereby acknowledged to belong to their respective owners.
Loading...