the FCC Rules. These limits are designed to provide reasonable protection
residential environment. This equipment generates, uses, and can radiate
Power Monitoring
RoHS
Compliant
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
• Follow safe electrical work practices. See NFPA 70E in the USA, or applicable local codes.
• This equipment must only be installed and serviced by qualified electrical personnel.
• Read, understand and follow the instructions before installing this product.
• Turn off all power supplying equipment before working on or inside the equipment.
• Any covers that may be displaced during the installation must be reinstalled
before powering the unit.
• Use a properly rated voltage sensing device to confirm power is off.
DO NOT DEPEND ON THIS PRODUCT FOR VOLTAGE INDICATION
Failure to follow these instructions will result in death or serious injury.
A qualied person is one who has skills and knowledge related to the construction and
operation of this electrical equipment and the installation, and has received safety
training to recognize and avoid the hazards involved. NEC2009 Article 100
No responsibility is assumed by Veris Industries for any consequences arising out of the
use of this material.
Control system design must consider the potential failure modes of control paths and, for
certain critical control functions, provide a means to acheive a safe state during and after a
path failure. Examples of critical control functions are emergency stop and over-travel stop.
TM
E51C2, E51C3
Compact Bi-Directional
Power and Energy Meter
Product Overview
The E51 DIN Rail Power Meter provides a solution for measuring energy data with a single device. Inputs include
Control Power, CTs, and 3-phase voltage. The E51 supports multiple output options, including solid state relay
contacts, Modbus (with or without data logging), and pulse. The LCD screen on the faceplate allows instant output
viewing.
The E51 Meter is capable of bidirectional metering. Power is monitored in both directions (upstream and
downstream from the meter). The meter is housed in a plastic enclosure suitable for installation on T35 DIN rail
according to EN50022. The E51 can be mounted either on a DIN rail or in a panel. Observe correct CT orientation
when installing the device.
Product Identification
ModelDescriptionOutputData Logging
PulseRS-485 Alarm
E51C2Modbus output, full data set
E51C3Modbus output, data logging
•••
••••
WARNING
LOSS OF CONTROL
∙ Assure that the system will reach a safe state during and after a control path failure.
∙ Separate or redundant control paths must be provided for critical control func tions.
∙ Test the eect of transmission delays or failures of communication links.
∙ Each implementation of equipment using communication links must be individually
and thoroughly tested for proper operation before placing it in service.
Failure to follow these instructions may cause injury, death or equipment damage.
1
For additional information about anticipated transmission delays or failures of the link, refer to
NEMA ICS 1.1 (latest edition). Safety Guidelins for the Application, Installation, and Maintenance of Solid-State Control or its equivalent in your specic country, language, and/or location.
1
NOTICE
• This product is not intended for life or safety applications.
• Do not install this product in hazardous or classified locations.
• The installer is responsible for conformance to all applicable codes.
• Mount this product inside a suitable fire and electrical enclosure.
FCC PART 15 INFORMATION
NOTE: This equipment has been tested by the manufacturer and found to
comply with the limits for a class B digital device, pursuant to part 15 of
against harmful interference when the equipment is operated in a
radio frequency energy and, if not installed and used in accordance with
the instruction manual, may cause harmful interference to radio
communications. This device complies with part 15 of the FCC Rules.
Operation is subject to the following two conditions:
(1) This device may not cause harmful interference, and
(2) this device must accept any interference received, including
interference that may cause undesired operation.
Modifications to this product without the express authorization of the
manufacturer nullify this statement.
For use in a P ollution D egree 2 or be tter envi ronment on ly. A Pollutio n Degree 2
environment must control conductive pollution and the possibility of condensation or
high hum idity. Cons ider the enc losure, th e correc t use of venti lation, the rmal prop erties
of the equ ipment, an d the relati onship wi th the envir onment. In stallati on categor y:
CAT II or CAT III. P rovide a di sconnec t device to di sconnec t the meter f rom the sup ply
source. P lace this de vice in clos e proximit y to the equ ipment and w ithin eas y reach of
the oper ator, and mark i t as the disc onnecti ng device. T he disconn ecting de vice shall
meet th e relevant r equireme nts of IEC 60 947-1 and IEC 60947-3 and sh all be suit able for
the appl ication. I n the US and Can ada, discon nectin g fuse hold ers can be us ed. Provi de
overcu rrent prot ection a nd discone cting dev ice for sup ply conduc tors wit h approved
current limiting devices suitable for protecting the wiring. If the equipment is used in a
manner n ot specie d by the manu facture r, the protec tion prov ided by the d evice may
be impaired.
Alta Labs, E nercept, Ensp ector, Hawkeye, Trus tat, Aerospo nd, Veris, and th e Veris ‘V’ log o are tradema rks or registe red tradema rks of Veris Ind ustries, L. L.C. in the USA and /or other countri es.
Specifications
MEASUREMENT ACCURACY
Real Power and Energy
Reactive Power and Energy
Current
Voltag e
Sample Rate
Data Update Rate
Type of Measurement
Measured AC Voltage
Metering Over-Range
Impedance
Frequency Range
CT Scaling
Measurement Input Range
Impedance
Other companies’ trademarks are hereby acknowledged to belong to their respective owners.
IEC 620 53 -22 Class 0.2S, A NSI C12.20 0.2%
IEC 620 53 -23 Class 2, 2%
0.2% (+ 0.0 05% per ° C deviation from 25°C ) from 1% to 5% of range ;
0.1% (+0.0 05% per °C deviation from 25°C ) from 5% to 100% of range
0.1% (+0.0 05% per °C deviation from 25°C ) from 90 VAC
FCC par t 15 Class B, EN55011/EN61000 Class B (residential and light
industrial)
EN61000 Class A ( heavy industrial)
AGENCY APPROVALS
UL508 (open type device) /C SA 22. 2 No. 14- 05
EN6 1010-1:2001
(3 47 V
L-L
* External DC current limiting is required, see fuse recommendations.
); CE Maximums: 3 00 V
L-N
/600 VAC
L-N
L-N
(520 V
L-N
L-L
)
L-L
SunSpec Alliance
Interoperability
This meter implements the draft SunSpec 1.0 common elements starting at base 1 address 40001, and the proposed SunSpec 1.1
meter model at 40070 (these addresses are not in Modicon notation). See www.veris.com or www.sunspec.org for copies of these
specications.
Alta Labs, E nercept, Ensp ector, Hawkeye, Trus tat, Aerospo nd, Veris, and th e Veris ‘V’ log o are tradema rks or registe red tradema rks of Veris Ind ustries, L. L.C. in the USA and /or other countri es.
The SunSpec Alliance logo is a trademark or registered trademark of the SunSpec Alliance.
Other companies’ trademarks are hereby acknowledged to belong to their respective owners.
Alta Labs, E nercept, Ensp ector, Hawkeye, Trus tat, Aerospo nd, Veris, and th e Veris ‘V’ log o are tradema rks or registe red tradema rks of Veris Ind ustries, L. L.C. in the USA and /or other countri es.
Other companies’ trademarks are hereby acknowledged to belong to their respective owners.
Installation Guide
Power Monitoring
EC, EC
TM
Dimensions
1.8”
(45mm)
1.9”
(48mm)
2.3”
(59mm)
1.5”
(39mm)
4.2”
(107mm)
3.6”
(91mm)
Bottom View (DIN Mount Option)Bottom View (Screw Mount Option)
Alta Labs, E nercept, Ensp ector, Hawkeye, Trus tat, Aerospo nd, Veris, and th e Veris ‘V’ log o are tradema rks or registe red tradema rks of Veris Ind ustries, L. L.C. in the USA and /or other countri es.
Other companies’ trademarks are hereby acknowledged to belong to their respective owners.
Installation Guide
kWh
1234.5
Power Monitoring
EC, EC
TM
Data Outputs
Product Diagram
Signed Power: Real, Reactive, and Apparent 3-phase total and per phase
Real and Apparent Energy Accumulators: Import, Export, and Net; 3-phase total and per phase
Reactive Energy Accumulators by Quadrant: 3-phase totals and per phase
Congurable for CT & PT ratios, system type, and passwords
Diagnostic alerts
Current: 3-phase average and per phase
Volts: 3-phase average and per phase Line-Line and Line-Neutral
Power Factor: 3-phase average and per phase
Frequency
Power Demand: Most Recent and Peak (Import and Export)
Demand Conguration: Fixed, Rolling Block, and External Sync (Modbus only)
Data Logging (E51C3 only)
Real Time Clock: user congurable
10 user congurable log buers: each buer holds 5760 16-bit entries
(User congures which 10 data points are stored in these buers)
User congurable logging interval
(When congured for a 15 minute interval, each buer holds 60 days of data)
Continuous and Single Shot logging modes: user selectable
Auto write pause: read logs without disabling the meter’s data logging mode
Alta Labs, E nercept, Ensp ector, Hawkeye, Trus tat, Aerospo nd, Veris, and th e Veris ‘V’ log o are tradema rks or registe red tradema rks of Veris Ind ustries, L. L.C. in the USA and /or other countri es.
Other companies’ trademarks are hereby acknowledged to belong to their respective owners.
Installation Guide
Power Monitoring
EC, EC
TM
Installation
Disconnect power prior to installation.
Reinstall any covers that are displaced during the installation before powering the unit.
Mount the meter in an appropriate electrical enclosure near equipment to be monitored.
Do not install on the load side of a Variable Frequency Drive (VFD), aka Variable Speed Drive (VSD)
or Adjustable Frequency Drive (AFD).
Observe correct CT orientation.
The meter can be mounted in two ways: on standard 35 mm DIN rail or screw-mounted to the interior surface of the enclosure.
A. DIN Rail Mounting
1. Attach the mounting clips to the underside of the housing by sliding them into the slots from the inside. The stopping pegs
must face the housing, and the outside edge of the clip must be ush with the outside edge of the housing.
2. Snap the clips onto the DIN rail. See the diagram of the underside of the housing (below).
Clip flush with
outside edge
Snap onto
Insert clips from inside
DIN rail
3. To reduce horizontal shifting across the DIN rail, use two Veris AV02 end stop clips.
B. Screw Mounting
1. Attach the mounting clips to the underside of the housing by sliding them into the slots from the outside. The stopping pegs
must face the housing, and the screw hole must be exposed on the outside of the housing.
2. Use three #8 screws (not supplied) to mount the meter to the inside of the enclosure. See the diagram of the underside of the
Alta Labs, E nercept, Ensp ector, Hawkeye, Trus tat, Aerospo nd, Veris, and th e Veris ‘V’ log o are tradema rks or registe red tradema rks of Veris Ind ustries, L. L.C. in the USA and /or other countri es.
Other companies’ trademarks are hereby acknowledged to belong to their respective owners.
Installation Guide
Power Monitoring
EC, EC
TM
Supported System
Types
Number
of wires
Single-Phase Wiring
21A2A, NL-N101L + 1nAN1
21A2A, BL- L112LAB2
32A, B3A, B, NL-L with N 122L + 1nABAN, BNAN-BN3
Three-Phase Wiring
33A, B, C 3A, B, CDelta313LAB, BC, CAAB-BC-CA4
43A, B, C 4A, B, C, N Grounded
The meter has a number of dierent possible system wiring congurations (see Wiring Diagrams section). To congure the meter,
set the System Type via the User Interface or Modbus register 130 (if so equipped). The System Type tells the meter which of its
current and voltage inputs are valid, which are to be ignored, and if neutral is connected. Setting the correct System Type prevents
unwanted energy accumulation on unused inputs, selects the formula to calculate the Theoretical Maximum System Power,
and determines which phase loss algorithm is to be used. The phase loss algorithm is congured as a percent of the Line-to-Line
System Voltage (except when in System Type 10) and also calculates the expected Line to Neutral voltages for system types that
have Neutral (12 & 40).
Values that are not valid in a particular System Type will display as “----” on the User Interface or as QNAN in the Modbus registers.
CTsVoltage ConnectionsSystem TypePhase Loss MeasurementsWiring
Diagram
QtyIDQtyIDTypeModbus
Register 130
403L + 1nAB, BC, CAAN, BN, CN AN-BN-CN &
Wye
User Interface:
SETUP>S SYS
VLLVLNBalanceDiagram
number
5, 6
AB-BC-CA
Wiring Symbols
To avoid distortion, use parallel wires for control power and voltage inputs.
The following symbols are used in the wiring diagrams on the following pages.
SymbolDescription
Voltage Disconnect Switch
Fuse (installer is responsible for ensuring compliance with local requirements. No
fuses are included with the meter.)
Earth ground
X1
Current Transducer
Potential Transformer
Protection containing a voltage disconnect switch with a fuse or disconnect circuit
breaker. The protection device must be rated for the available short-circuit current at
the connection point.
CAUTION
RISK OF EQUIPMENT DAMAGE
• This product is designed only for use with 1V or 0.33V current
transducers (CTs).
• DO NOT USE CURRENT OUTPUT (e.g. 5A) CTs ON THIS PRODUCT.
• Failure to follow these instructions can result in overheating and
permanent equipment damage.
Alta Labs, E nercept, Ensp ector, Hawkeye, Trus tat, Aerospo nd, Veris, and th e Veris ‘V’ log o are tradema rks or registe red tradema rks of Veris Ind ustries, L. L.C. in the USA and /or other countri es.
Other companies’ trademarks are hereby acknowledged to belong to their respective owners.
Installation Guide
Power Monitoring
EC, EC
TM
Wiring
WARNING
RISK OF ELECTRIC SHOCK OR PERMANENT EQUIPMENT DAMAGE
CT negative terminals are referenced to the meter’s neutral and may be at elevated voltages
· Do not contact meter terminals while the unit is connected
· Do not connect or short other circuits to the CT terminals
Failure to follow these instructions may cause injury, death or equipment damage.
Observe correct CT orientation.
Diagram 1: 1-Phase Line-to-Neutral 2- Wire
System 1 CT
N L1
Use System Type 10 (1L + 1n)
X1
X2
A
B
C
N
White
Black
+
-
+
-
+
-
A
B
C
Diagram 2: 1-Phase Line-to-Line 2-Wire
L1 L2
X1
X2
System 1 CT
Use System Type 11 (2L)
White
Black
A
B
C
N
+
A
-
+
B
-
+
C
-
Diagram 3: 1-Phase Direct Voltage Connection 2 CT
N
L1 L2
X1
X2
Use System Type 12 (2L + 1n)Use System Type 31 (3L)
A
B
C
N
White
Black
X1
X2
White
Black
+
A
-
+
B
-
+
C
-
Diagram 5: 3-Phase 4-Wire Wye Direct Voltage Input
Alta Labs, E nercept, Ensp ector, Hawkeye, Trus tat, Aerospo nd, Veris, and th e Veris ‘V’ log o are tradema rks or registe red tradema rks of Veris Ind ustries, L. L.C. in the USA and /or other countri es.
Other companies’ trademarks are hereby acknowledged to belong to their respective owners.
Installation Guide
Power Monitoring
EC, EC
TM
Control Power
Diagrams
Direct Connect Control Power (Line to Line)
L1
L2 L3
Line to Line from 90 VAC to 600 VAC (UL) (520 VAC for CE). In
UL installations the lines may be oating (such as a delta).
If any lines are tied to an ear th (such a s a corner grounded
delta), see the Line to Neutral installation limits. In CE
compliant installations, th e lines must be neutral (earth)
referenced at less than 300 VAC
1 2G
L-N
Direct Connect Control Power (DC Control Power)
1 2G
DC Control Power from 125 VDC to 300 VDC
(UL and CE max.)
Direct Connect Control Power (Line to Neutral)
L1NL2 L3
Line to Neutral from 90 VAC to 347 VAC (UL) or 300 VAC (CE)
Control Power Transformer (CPT) Connection
L1NL2 L3
The Control Power Transformer may be wired L-N or L-L. Output to
meet meter input requirements
1 2G
1 2G
Fuse Recommendations
Keep the fuses close to the power source (obey local and national code requirements).
For selecting fuses and circuit breakers, use the following criteria:
• Select current interrupt capacity based on the installation category and fault current capability.
• Select over-current protection with a time delay.
• Select a voltage rating sucient for the input voltage applied.
• Provide overcurrent protection and disconnecting means to protect the wiring. For AC installations, use Veris AH02,
AH03, AH04, or equivalent. For DC installations, provide external circuit protection. Suggested: 0.5 A, time delay fuses.
• The earth connection is required for electromagnetic compatibility (EMC) and is not a protective earth ground.
Alta Labs, E nercept, Ensp ector, Hawkeye, Trus tat, Aerospo nd, Veris, and th e Veris ‘V’ log o are tradema rks or registe red tradema rks of Veris Ind ustries, L. L.C. in the USA and /or other countri es.
Other companies’ trademarks are hereby acknowledged to belong to their respective owners.
Installation Guide
Power Monitoring
EC, EC
TM
Quick Setup
Instructions
These instruc tions assume the meter is set to factory defaults. If it has been previously congured, check all optional values.
+
1. Press the
+
or – button repeatedly until SETUP screen appears.
2. to the PASWD screen.
+
3. through the digits. Use the
+
4. Use the
+
or – buttons to selec t the parameter to congure.
+
or – buttons to selec t the password (the default is 00000). Exit the screen to the right.
5. If the unit has an RS-485 interface, the rst Setup screen is S COM (set communications).
+
a. to the ADDR screen and through the address digits. Use the
+
b. to the BAUD screen. Use the
c. to the PAR screen. Use the
+
or – buttons to selec t the baud rate.
+
+
or – buttons to selec t the parity.
+
or – buttons to select the Modbus address.
d. back to the S COM screen.
–
6.
to the S CT (Set Current Transducer) screen. If this unit does not have an RS-485 port, this will be the rst screen.
+
a. to the CT V screen. Use the
b. to the CT SZ screen and through the digits. Use the
+
or – buttons to selec t the voltage mode Current Transducer output voltage.
+
+
or – buttons to selec t the CT size in amps.
c. back to the S CT screen.
7. – to the S SYS (Set System) screen.
+
a. to the SY STM screen. Use the
+
or – buttons to selec t the System Type (see wiring diagrams).
b. back to the S SYS screen.
8. (Optional) – to the S PT (Set Potential Transformer) screen. If PTs are not used, then skip this step.
+
a. to the RATIO screen and through the digits. Use the
+
or – buttons to selec t the Potential Transformer step down
ratio.
b. back to the S PT screen.
–
9.
to the S V (Set System Voltage) screen.
+
a. to the VLL (or VLN if system is 1L-1n) screen and through the digits. Use the
+
or – buttons to selec t the Line to Line
System Voltage.
b. back to the S V screen.
10. Use the to exit the setup screen and then S ETU P.
11. Check that the wrench is not displayed on the LCD.
+
a. If the wrench is displayed, use the
+
or – buttons to nd the A LERT screen.
b. through the screens to see which alert is on.
For the full setup instructions, see the conguration instruc tions on the following pages.
Alta Labs, E nercept, Ensp ector, Hawkeye, Trus tat, Aerospo nd, Veris, and th e Veris ‘V’ log o are tradema rks or registe red tradema rks of Veris Ind ustries, L. L.C. in the USA and /or other countri es.
Other companies’ trademarks are hereby acknowledged to belong to their respective owners.
Installation Guide
Power Monitoring
EC, EC
TM
Solid-State
Pulse Output
User Interface (UI)
Menu Abbreviations
Defined
The meter has one normally open (N.O.) KZ Form
A output and one normally closed (N.C.) KY
solid-state output. One is dedicated to import
energy (Wh), and the other to Alarm.
The relay used for the Phase Loss contact is N.C.,
with closure indicating the presence of an alarm;
either loss of phase if the meter is powered, or
loss of power if the meter is not. The contacts are
open when the meter is powered and no phase
loss alarm conditions are present.
The solid state pulse outputs are rated for 30
VAC/DC nom.
Maximum load current is 100 mA at 25°C. Derate
0.56 mA per °C above 25°C.
See the Setup section for conguration
Alarm
* The over-current pro tective device must be rated for the shor t circuit current at the
connection point.
** All pulse outpu ts and communication circui ts are only intended to be connec ted to
non-hazard ous voltage circuits (SELV or Class 2). Do not connect to hazardous vol tages.
+ – S
EnergyOutput
information.
The user can set the display mode to either IEC or IEEE notation in the SETUP menu.
Alta Labs, E nercept, Ensp ector, Hawkeye, Trus tat, Aerospo nd, Veris, and th e Veris ‘V’ log o are tradema rks or registe red tradema rks of Veris Ind ustries, L. L.C. in the USA and /or other countri es.
Other companies’ trademarks are hereby acknowledged to belong to their respective owners.
Installation Guide
Power Monitoring
EC, EC
User Interface
DEMND
CPHAS
TM
ENRGY
(Export Wh)
PULS2
Pulse Counter 2
for Pulse Value
PULS1
See SETUP > SPULS > Wh/P
(Import Wh)
Pulse Counter 1
_PHAS
KVAh
HZ
Frequency
BPHAS
APHAS
Export
Apparent Energy
Power (S)
M KVA
Export Demand
Maximum Apparent
Power (Q)
MKVAR
Export Demand
Maximum Reactive
Power (P)
M KW
Maximum Real
Export Demand
Power (S)
M KVA
Import Demand
Maximum Apparent
MKVAR
Power (Q)
Import Demand
Maximum Reactive
M KW
IEEE Display Mode
Power (P)
Import Demand
Maximum Real
Present
D KVA
Demand (S)
Apparent Power
C -KWh
C +KWh
C PF
C KVA
CKVAR
C KW
C VLN
B -KWh
B +KWh
B PF
B KVA
BKVAR
B KWB VLN
A -KWh
A +KWh
A PF
A KVA
AKVAR
A KW
A VLN
3 -KWh
Total Export
Total Import
3 +KWh
3 PF
Power Factor
3 KVA
Total Apparent
3KVAR
Total Reactive
3 KW
Total Real
3 VLN
Volts Line-Neutral (V)
Real Energy
Real Energy
(Average of
Active Phases)
Power (S)
Power (Q)
>>> Scroll When Idle >>>
Power (P)
Phases)
(Average of Active
Import
KVAh
Apparent Energy
KVAh
Signed Net
Apparent Energy
Energy
KVAR4
Quadrant 4
Export Reactive
Energy
KVAR3
Quadrant 3
Export Reactive
Energy
KVAR2
Quadrant 2
Import Reactive
Energy
KVAR1
Quadrant 1
Import Reactive
Export
3 -KWh
Real Energy
To:
Present
Demand (Q)
DKVAR
Reactive Power
Present
Real Power
Demand (P)
D KW
SETUP
DEMND
Demand
C VAC
C A
CPHAS
3 Phase
Phase C:
B VBC
B A
BPHAS
Phase B:
2 & 3 Phase
Systems Only
A VAB
A A
APHAS
Phase A:
Systems Only
3 VLL
Phases)
(Average of Active
Volts Line-Line (U)
3 A
Amps (A)
(Average of
Active Phases)
_PHAS
All Systems
Summary Data
1, 2, or 3 Phase
Energy
Import
3 +KWh
3 KWh
ENRGY
and Counters
Accumulators
Real Energy
Signed Net
Real Energy
To:
ALERT
The units for all Power and Energy screens change to preserve resolution as the
accumulated totals increase. For example, energy starts out as Wh, then switches
Alta Labs, E nercept, Ensp ector, Hawkeye, Trus tat, Aerospo nd, Veris, and th e Veris ‘V’ log o are tradema rks or registe red tradema rks of Veris Ind ustries, L. L.C. in the USA and /or other countri es.
Other companies’ trademarks are hereby acknowledged to belong to their respective owners.
to kWh, MWh, and eventually GWh as the accumulated value increases.
Installation Guide
Power Monitoring
EC, EC
User Interface
(cont.)
TM
ENRGY
(Export Ph)
PULS2
Pulse Counter 2
for Pulse Value
PULS1
See SETUP > SPULS > Wh/P
(Import Ph)
Pulse Counter 1
_PHAS
Export
HZ
DEMND
CPHAS
BPHAS
APHAS
Frequency
E KSh
Apparent Energy
IEC Display Mode
Power (S)
M KS
Export Demand
Maximum Apparent
Power (Q)
M KQ
Export Demand
Maximum Reactive
Demand
M KP
Power Export
Maximum Real
Power
M KS
Import Demand
Maximum Apparent
Power
M KQ
Import Demand
Maximum Reactive
Demand
M KP
Power Import
Maximum Real
Present
Demand
D KS
Apparent Power
C -KPh
C +KPh
C PF
C KS
C KQ
C KPC V
B -KPh
B +KPh
B PF
B KS
B KQ
B KP
B V
A -KPh
A +KPh
A PF
A KS
A KQ
A KP
A V
3 -KPh
Total Export
Total Import
3 +KPh
3 PF
Power Factor
3 KS
Total Apparent
3 KQ
Total Reactive
3 KP
Total Real
3 V
Volts Line-Neutral (V)
Real Energy
Real Energy
(Average of
Active Phases)
Power (S)
Power (Q)
>>> Scroll When Idle >>>
Power (P)
Phases)
(Average of Active
Import
E KSh
Apparent Energy
E KSh
Signed Net
Apparent Energy
Energy
Q4 Qh
Quadrant 4
Export Reactive
Energy
Q3 Qh
Quadrant 3
Export Reactive
Energy
Q2 Qh
Quadrant 2
Import Reactive
Energy
Q1 Qh
Quadrant 1
Import Reactive
Export
E -KPh
Real Energy
Present
Demand
D KQ
Reactive Power
Present
Demand
Real Power
D KP
To:
SETUP
DEMND
Demand
C U
C A
CPHAS
3 Phase
Phase C:
Volts CA
Systems Only
Phase B:
Volts BC
B U
B A
BPHAS
2 & 3 Phase
Systems Only
A U
A A
APHAS
Phase A:
All Systems
Volts AB
3 U
3 A
_PHAS
Phases)
(Average of Active
Volts Line-Line (U)
Amps (A)
(Average of
Active Phases)
Import
E +KPh
Real Energy
E KPh
Signed Net
Real Energy
To:
ENRGY
ALERT
Energy
and Counters
1, 2, or 3 Phase
Summary Data
Accumulators
The units for all Power and Energy screens change to preserve resolution as the
accumulated totals increase. For example, energy starts out as Wh, then switches
Alta Labs, E nercept, Ensp ector, Hawkeye, Trus tat, Aerospo nd, Veris, and th e Veris ‘V’ log o are tradema rks or registe red tradema rks of Veris Ind ustries, L. L.C. in the USA and /or other countri es.
Other companies’ trademarks are hereby acknowledged to belong to their respective owners.
to kWh, MWh, and eventually GWh as the accumulated value increases.
Installation Guide
T
the Reset Password
p menu).
ergy
h, VAh) to 0.
Maximum
, VAR, VA) to the present
to Reset.
lse counters.
Power Monitoring
EC, EC
TM
Alert/Reset
Information
Alert Status
(check if
Wrench on
LCD)
Unit
Information
Reset
Data
Setup
Meter
To: ENRGY
ALERT
INFO
RESET
SETUP
PLOSS
-------A b C
Phase Loss
A B C
LOWPF
-------A b C
Low Power Factor
A B C
F ERR
-------A
Frequency Out
of Range
Display “nOnE” if no alerts
MODELOSSNRS
Model
Number
Operating
System
System
Back
PASWD
--------
0
0000
Enter Reset
Password
ENERG
--------
rES
Reset Energy
Accumulators to 0
Reset Demand
Maximums to Present
PASWD
--------
0
0000
Enter Setup
Password
A
Reset
DEMND
--------
rES
I OVR
-------A b C
Over Current
(Clipping)
A B C
Serial
Number
COUNT
Reset Pulse
Counters to 0
--------
rES
V OVR
-------A b C
Over Voltage
(Clipping)
A B C
INFO
RESET
To Setup
PULSE
------- Error
Energy Pulse Output:
Error = Overrun Error
ConF = Configuration Error
ALER
PASWD – Enter
(configured in the setu
ENERG – Reset all En
Accumulators (Wh, VAR
Press “+” or “-“ to Reset.
DEMND – Reset all
Demand (W
Demand. Hit “+” or “-“
COUNT – Reset the pu
Press “+” or “-“ to Reset.
Alta Labs, E nercept, Ensp ector, Hawkeye, Trus tat, Aerospo nd, Veris, and th e Veris ‘V’ log o are tradema rks or registe red tradema rks of Veris Ind ustries, L. L.C. in the USA and /or other countri es.
Other companies’ trademarks are hereby acknowledged to belong to their respective owners.
Installation Guide
Power Monitoring
EC, EC
UI for Setup
From:
SETUP > PASWD
To Setup p. 2 “SPASS”
BackS COM
RS-485
Output
ADDR
--------
0
01
BAUD
--------
38400
19200
9600
4800
2400
1200
Next
PAR
--------
nOnE
EvEn
Odd
TM
Set Communications Parameters:
ADDR - Modbus Address: 1 – 247.
+ increments the selected (blinking) digit.
- selects the digit to the left.
BAUD - Baud Rate: 1200 – 38400 Baud
PAR - Parity: Odd, Even, None
+ or – to step through the options.
Transformer
Back To SETUP
Back
Current
Back
System
Type
Back
Potential
Transformer
Back
Sytem
Voltage
S CT
S SYS
S PT
S V
CT V
--------
1.0
.33
SYSTM
--------
3L-1n
3L
2L-1n
2L
1L-1n
RATIO
--------
001
V LL
--------
0
0600
.00
Next
Next
Next
CT SZ
--------
00
1
Next
Set System Configuration:
SYSTM: + or – to step through the following System Type options:
System
3L-1n403 Wye Three Phase: A, B, & C with Neutral (Default).
3L313 Delta Three Phase: A, B & C; no Neutral
2L-1n122 Single Split Phase: A & B with Neutral
2L111 Single Phase: A & B; no Neutral
1L-1n101 Single Phase: A to Neutral
Set Potential Transfomer Ratio:
RATIO – Potential transformer step down is RATIO:1. Default is 1:1
(No PT installed). See Install for wiring diagrams. This value must be
set before the System Voltage (if used).
Set System Voltage:
V LL – The nominal Line to Line Voltage for the system. This is used
by the meter to calculate the theoretical maximum system power, and
as the reference voltage for setting the Phase Loss threshold.
Maximum is 32000 Volts. For system type 1+N (10), this is a Line to
Neutral Voltage, indicated by “V LN”. Note: the meter will reject settings
that are not within the meter’s operating range when divided by the PT
ratio.
Set Current Transducer:
CT V - CT Input Voltage: + or – to Select 1.0 or .33V.
CT SZ - CT Size: in Amps. Maximum is 32000 Amps.
Reg 130 CTs Description
System Power:
MX KW – The theoretical Maximum System Power is calculated by the
meter from the System Voltage, CT size, and System Type. Power
Factor is assumed to be unity. The value of System Power is used to
determine which combinations of pulse weight and duration are valid
and will keep up with the maximum power the meter will see. This value
is read only.
Alta Labs, E nercept, Ensp ector, Hawkeye, Trus tat, Aerospo nd, Veris, and th e Veris ‘V’ log o are tradema rks or registe red tradema rks of Veris Ind ustries, L. L.C. in the USA and /or other countri es.
Other companies’ trademarks are hereby acknowledged to belong to their respective owners.
Installation Guide
Power Monitoring
EC, EC
UI for Setup
(cont.)
Back To SETUP
To Setup p. 1 “S PWR”
Back
Back
Back
SPLOS
Phase
Loss
SPULS
Pulse
Output
SDMND
Demand
VOLTS
--------
0.1
Wh/P
--------
10000
1000
100
10
INTRV
--------
TM
Set Phase Loss:
VOLTS - Phase Loss Voltage: The fraction of the system
voltage below which Phase Loss Alarm is on. For system
types with neutral, the Line to Neutral voltage is also
IMBAL
--------
0.2
500
250
100
50
25
10
Next
SEC
--------
0
0900
Next
5
Max
PPS
--------
10
20
50
0
mS/P
--------
Next
6
5
4
3
2
1
calculated and tested. If the System Voltage is 600 and the
fraction is set to 0.10, then the Phase Loss threshold will be
60 volts.
IMBAL - Phase Loss Imbalance: The fractional difference
in Line to Line voltages above which Phase Loss Alarm is
on. For system types with neutral, the Line to Neutral
voltages are also tested. For system types 1+N (10) and 2
(11) , imbalance is not tested.
Set Pulse:
The System Type , CT size, PT Ratio, and System Voltage must
all be configured before setting the Pulse Energy. If any of these
parameters are changed, the meter will hunt for a new Pulse
Duration, but will not change the Pulse Energy. If it cannot find a
solution, the meter will display the wrench, show “ConF” in the
ALARM -> PULSE screen, and enable Energy pulse output
configuration error bit in the Modbus Diagnostic Alert Bitmap (if
1
equipped).
2
Wh/P - Set Pulse Energy: In Watt Hours (& VAR Hours, if
5
present) per Pulse. When moving down to a smaller energy, the
meter will not allow the selection if it cannot find a pulse duration
that will allow the pulse output to keep up with Theoretical
Maximum System Power (see S_PWR screen). When moving
up to a larger energy, the meter will jump to the first value where
it can find a valid solution.
mS/P – Minimum Pulse Duration Time: This read only value
is set by the meter to the slowest duration (in mS per closure)
that will keep up with the Theoretical Maximum System Power.
The open time is greater than or equal to the closure time. The
maximum Pulses Per Second (PPS) is shown in yellow.
Set Demand Interval:
INTRV - The number of Sub-Intervals (1 to 6) in a Demand Interval.
Default is 1 (block demand).
SEC - Sub-Interval length in seconds. Default is 900 (15 minutes).
Set to 0 for external sync-to-comms (Modbus units only).
Back
Back
Passwords
To Setup page 1 “S COM”
S DIS
Display
Units
SPASS
Setup
UNITS
--------
IEEE
IEC
Next
SETUP
--------
0
0000
RESET
--------
0
0000
Next
Set Display Units: +/- to switch between:
IEEE – VLL VLN W VAR VA Units.
IEC - U V P Q S Units.
Set Passwords:
SETUP - The Password to enter the SETUP menu.
RESET - The Password to enter the RESET menu.
Alta Labs, E nercept, Ensp ector, Hawkeye, Trus tat, Aerospo nd, Veris, and th e Veris ‘V’ log o are tradema rks or registe red tradema rks of Veris Ind ustries, L. L.C. in the USA and /or other countri es.
Other companies’ trademarks are hereby acknowledged to belong to their respective owners.
Installation Guide
Red
Black
Gray
Use 14-24 gauge wire
Power Monitoring
EC, EC
TM
RS-485
Communications
Daisy-chaining Devices to the Power Meter
The RS-485 slave port allows the power meter to be connec ted in a daisy chain with up to 63 2-wire devices.
120 Ω terminator on the rst and last
device of the daisy chain
+
–
S
Shield wire
Notes
• The terminal’s voltage and current ratings are compliant with the requirements of the EIA RS-485 communications
standard.
• The RS-485 transceivers are ¼ unit load or less.
• RS-485+ has a 47 k pull up to +5V, and RS-485- has a 47 k pull down to Shield (RS-485 signal ground).
• Wire the RS-485 bus as a daisy chain from device to device, without any stubs. Use 120 termination resistors at each
end of the bus (not included).
• Shield is not internally connected to Earth Ground.
• Connect Shield to Earth Ground somewhere on the RS-485 bus.
For all terminals:
• When tightening terminals, apply the correct torque: 0.37 to 0.44
ft·lb (0.5-0.6 N·m).
• Use 14-24 gauge (2.1-0.2 mm2) wire.
0.37–0.44 ft•lb
(0.5–0.6 N•m)
Data Logging
(EC only)
The E51C3 includes a data logging feature that records 10 meter parameters, each in its own buer.
Configuration
Use register 150 to set the data logging time subinterval. Writing to the storage buer is triggered by the subinterval timer. The
default subinterval is 15 minutes (at a 15 minute interval setting, the buers hold 60 days of data). An external timer can be used
over Modbus by setting this register to 0.
Use register 159 to turn on data logging and select either Single Shot or Continuous mode. (default is data logging on, Continuous
mode). In Single Shot mode, the meter records data until the buer is full. When the buer is full, the meter stops recording
new readings. Data for this time period is kept, but newer energy information is lost. In Continuous mode, the meter continues
to record energy data as long as the meter is operating. The buer can only hold 5760 entries at one time, however, so when the
number of records exceeds 5760, the oldest entry is deleted to make room for the newest.
Registers 169-178 contain the pointers to 10 data storage buers. Each buer is user-congurable with the Modbus address of the
16-bit data output to be stored. 32-bit data, such as oating point data or 32-bit integer energy accumulators, require two buers.
However, the lower 16 bits of an integer energy accumulator can be stored in a single buer (optional).
When the E51C3 is rst installed, the buers contain QNAN data, with a value of 0x8000. This data is considered invalid. If the
buer is reset at any point, all entries in the buers are overwritten with this 0x8000 value, indicating that it is invalid. All invalid
data is overwritten as the meter lls the buer with new data entries.
Reading Data
Use register 158 to choose which buer to read. When this register value is set to 0, the meter is in data logging mode. Changing
this value from 0 to (1 through 10)switches the meter to reading mode and selects a buer to read. Data from the selected buer
appears in registers 8000 to 13760.
Alta Labs, E nercept, Ensp ector, Hawkeye, Trus tat, Aerospo nd, Veris, and th e Veris ‘V’ log o are tradema rks or registe red tradema rks of Veris Ind ustries, L. L.C. in the USA and /or other countri es.
Other companies’ trademarks are hereby acknowledged to belong to their respective owners.
Installation Guide
Power Monitoring
EC, EC
TM
Data Logging
(EC only, cont.)
Modbus Point Map
Overview
Read/Write Collision
If the demand sub-interval timeout occurs while the user is reading a page (register 158 ≠ 0), the log data will be held in RAM
until the next demand subinterval. At that time, both the saved data from the previous cycle and the new data will be written to
the log, whether the page register has been set back to 0 or not. Error bits in the Log Status Register (160) track these conditions.
Subsequent log writes will proceed normally. Provided the log read is concluded in less time than the demand sub-interval, this
mechanism handles the occasional collision and prevents the user from reading data as the buer is being updated.
The Log Status Register has additional error ag bits that indicate whether logging has been reset or interrupted (power cycle,
etc.) during the previous demand sub-interval, and whether the Real-Time Clock has been changed (re-initialized to default date/
time due to a power-cycle or modied via Modbus commands).
The E51C2 Full Data Set (FDS) model features data outputs such as demand calculations, per phase signed watts VA and VAR,
import/export Wh and VAh, and VARh accumulators by quadrant. The E51C3 Data Logging model includes the FDS and adds log
conguration registers 155-178 and log buer reading at registers 8000-13760. The meter supports variable CTs and PTs, allowing
a much wider range of operation from 90V x 5A up to 32000V x 32000A. To promote this, the meter permits variable scaling of the
16-bit integer registers via the scale registers. The 32-bit oating point registers do not need to be scaled.
Integer registers begin at 001 (0x001). Floats at 257 (0x101). Conguration registers at 129 (0x081). Values not supported in a
particular System Type conguration report QNAN (0x8000 in Integer Registers, 0x7FC00000 in Floating Point Registers). Register
addresses are in PLC style base 1 notation. Subtrac t 1 from all addresses for the base 0 value used on the Modbus RS-485 link.
Supported Modbus Commands
Note: ID String information varies from model to model. Text shown here is an example.
CommandDescription
0x03Read Holding Registers
0x04Read Input Registers
0x06Preset Single Register
0x10Preset Multiple Registers
Report ID
Return string:
byte0: address
0x11
0x2B
byte1: 0x11
byte2: #bytes following w/out crc
byte3: ID byte = 247
byte4: status = 0xFF if the operating system is used; status = 0x00 if the reset system is used
bytes5+: ID string = “Veris Industries E51xx Power Meter Full Data Set” or “Veris Industries E51xx Power Meter - RESET
SYSTEM RUNNING RS Version x.xxx” last 2 bytes: CRC
Object values:
0x01: “Veris Industries”
0x02: “ E51xx ”
0x03: “Vxx.yyy”, where xx.yyy is the OS version number (reformatted version of the Modbus register #7001, (Firmware
Version, Operating System).
If register #7001 == 12345, then the 0x03 data would be “V12.345”).
Legend
The following table lists the addresses assigned to each data point. For oating point format variables, each data point appears
twice because two 16-bit addresses are required to hold a 32-bit oat value. Negative signed integers are 2’s complement.
Alta Labs, E nercept, Ensp ector, Hawkeye, Trus tat, Aerospo nd, Veris, and th e Veris ‘V’ log o are tradema rks or registe red tradema rks of Veris Ind ustries, L. L.C. in the USA and /or other countri es.
Other companies’ trademarks are hereby acknowledged to belong to their respective owners.
Installation Guide
Power Monitoring
EC, EC
TM
Modbus Point Map
Overview (cont.)
Standard Modbus
Default Settings
R/W
NVValue is stored in non-volatile memor y. The value will still be available if the meter experiences a power loss and reset.
Format
UnitsLists the physical units that a register holds.
Scale
Factor
RangeDenes the limit of the values that a register can contain.
R=read only
R/W=read from either int or oat formats, write only to integer format.
Alta Labs, E nercept, Ensp ector, Hawkeye, Trus tat, Aerospo nd, Veris, and th e Veris ‘V’ log o are tradema rks or registe red tradema rks of Veris Ind ustries, L. L.C. in the USA and /or other countri es.
Other companies’ trademarks are hereby acknowledged to belong to their respective owners.
Installation Guide
Power Monitoring
EC, EC
Modbus Point Map
R/W NV FormatUnitsScaleRangeDescription
Register
E51C3 Log
E51C2 FDS
Integer Data: Summary of Active Phases
•• 001
•• 002LSR
•• 003
•• 004LSR
•• 005
•• 006LSR
•• 007
•• 008LSR
•• 009
•• 010LSR
•• 011
•• 012LSR
•• 013
•• 014LSR
•• 015
•• 016LSR
•• 017
•• 018LSR
•• 019
•• 020LSR
•• 021RSIntkWW-32767 to +32767 Total Instantaneous Real (P) Power
•• 022RSIntkVARW0 to 32767Total Instantaneous Reactive (Q) Power
•• 023RUIntkVAW0 to 32767Total Instantaneous Apparent (S) Power (vector sum)
•• 024RSIntRatio0.0001 -10000 to +10000 Total Power Factor (total kW / total kVA)
•• 025RUIntVoltV0 to 32767Voltage, L-L (U), average of active phases
•• 026RUIntVoltV0 to 32767Voltage, L-N (V), average of active phases
•• 027RUIntAmpI0 to 32767Current, average of active phases
•• 028UIntHz0.014500 to 6500Frequency
•• 029RSIntkWW-32767 to +32767 Total Real Power Present Demand
•• 030SIntkVARW-32767 to +32767 Total Reactive Power Present Demand
•• 031RSIntkVAW-32767 to +32767 Total Apparent Power Present Demand
•• 032RNVSIntkWW-32767 to +32767 Total Real Power Max. Demand
•• 033RNVSIntkVARW-32767 to +32767 Total Reactive Power Max. Demand
•• 034RNVSIntkVAW-32767 to +32767 Total Apparent Power Max. Demand
•• 035RNVSIntkWW-32767 to +32767 Total Real Power Max. Demand
•• 037RNVSIntkVAW-32767 to +32767 Total Apparent Power Max. Demand
•• 038RUIntReserved, returns 0x8000 (QNAN)
•• 039
•• 040LSR
•• 041
•• 042LSR
RNVSLongkWhE
RNVULongkWhE0 to 0xFFFFFFFF
RNVULongkWhE0 to 0xFFFFFFFF
RNVULongkVARhE0 to 0xFFFFFFFF
RNVULongkVARhE0 to 0xFFFFFFFF
RNVULongkVARhE0 to 0xFFFFFFFF
RNVULongkVARhE0 to 0xFFFFFFFF
RNVSLongkVAhE
RNVULongkVA hE0 to 0xFFFFFFFF
RNVULongkVA hE0 to 0xFFFFFFFF
RNVULong0 to 0xFFFFFFFF
RNVULong0 to 0xFFFFFFFF
-2147483647 to
+2147483647
-2147483647 to
+2147483647
Real Energy: Net (Import - Export)
Real Energy: Quadrants 1 & 4
Import
Real Energy: Quadrants 2 & 3
Export
Reactive Energy - Quadrant 1:
Lags Import Real Energy (IEC) Inductive (IEEE)
Reactive Energy - Quadrant 2:
Leads Export Real Energy (IEC) Inductive (IEEE)
Reactive Energy - Quadrant 3:
Lags Export Real Energy (IEC) Capacitive (IEEE)
Reactive Energy - Quadrant 4:
Leads Import Real Energy (IEC) Capacitive (IEEE)
Apparent Energy: Net (Import - Export)
Apparent: Quadrants 1 & 4
Import
Apparent: Quadrants 2 & 3
Export
Pulse Counter 1
(Import Real Energy)
Pulse Counter 2
(Export Real Energy)
MSR
MSR
MSR
Accumulated
MSR
MSR
MSR
MSR
MSR
MSR
MSR
MSR
MSR
Import
Export•• 036RNVSIntkVARW-32767 to +32767 Total Reactive Power Max. Demand
Contact Closure Counters. Valid for both pulse
Real Energy
(Ph)
Accumulated
Reactive Energy
(Qh):
Quadrants 1 + 2
= Import
Quadrants 3 + 4
= Export
Accumulated
Apparent
Energy (Sh):
Import and
Export
correspond
with Real
Energy
inputs and outputs. E51Cx counts are shown in
(). See register 144 - Energy Per Pulse for the
Wh per pulse count.
Alta Labs, E nercept, Ensp ector, Hawkeye, Trus tat, Aerospo nd, Veris, and th e Veris ‘V’ log o are tradema rks or registe red tradema rks of Veris Ind ustries, L. L.C. in the USA and /or other countri es.
Other companies’ trademarks are hereby acknowledged to belong to their respective owners.
Alta Labs, E nercept, Ensp ector, Hawkeye, Trus tat, Aerospo nd, Veris, and th e Veris ‘V’ log o are tradema rks or registe red tradema rks of Veris Ind ustries, L. L.C. in the USA and /or other countri es.
Other companies’ trademarks are hereby acknowledged to belong to their respective owners.
Installation Guide
Power Monitoring
EC, EC
Modbus Point Map (cont.)
R/W NV FormatUnitsScaleRangeDescription
Register
E51C3 Log
E51C2 FDS
TM
•• 079
•• 080LSR
•• 081
•• 082LSR
•• 083
•• 084LSR
•• 085
•• 086LSR
•• 087
•• 088LSR
•• 089
•• 090LSR
•• 091RSIntkWW-32767 to +32767 Real Power (P), Phase A
•• 093RSIntkWW-32767 to +32767 Real Power (P), Phase C
•• 094RSIntkVARW-32767 to +32767 Reactive Power (Q), Phase A
•• 096RSIntkVARW-32767 to +32767 Reactive Power (Q), Phase C
•• 097RUIntkVAW0 to 32767Apparent Power (S), Phase A
•• 099RUIntkVAW0 to 32767Apparent Power (S), Phase C
•• 100RSIntRatio0.0001 -10000 to +10000 Power Factor (PF), Phase A
•• 102RSIntRatio0.0001 -10000 to +10000 Power Factor (PF), Phase C
•• 103RUIntVoltV0 to 32767Voltage (U), Phase A-B
•• 105RUIntVoltV0 to 32767Voltage (U), Phase A-C
•• 106RUIntVoltV0 to 32767Voltage (V), Phase A-N
•• 108RUIntVoltV0 to 32767Voltage (V), Phase C-N
•• 109RUIntAmpI0 to 32767Current, Phase A
•• 111RUIntAmpI0 to 32767Current, Phase C
•• 112RUIntReserved, Returns 0x8000 (QNAN)
RNVULongkVA hE0 to 0xFFFFFFFF
RNVULongkVA hE0 to 0xFFFFFFFF
RNVULongkVA hE0 to 0xFFFFFFFF
RNVULongkVA hE0 to 0xFFFFFFFF
RNVULongkVA hE0 to 0xFFFFFFFF
RNVULongkVA hE0 to 0xFFFFFFFF
Accumulated Apparent Energy,
Phase A
Accumulated Apparent Energy,
Phase B
Accumulated Apparent Energy,
Phase C
Accumulated Apparent Energy,
Phase A
Accumulated Apparent Energy,
Phase B
Accumulated Apparent Energy,
Phase C
MSR
MSR
MSR
MSR
MSR
MSR
Import
Accumulated
Apparent Energy
(Sh), Per Phase
Export
Real Power (P)•• 092RSIntkWW-32767 to +32767 Real Power (P), Phase B
Reactive Power (Q)•• 095RSIntkVARW-32767 to +32767 Reactive Power (Q), Phase B
Apparent Power (S)•• 098RUIntkVAW0 to 32767Apparent Power (S), Phase B
Power Factor (PF)•• 101RSIntRatio0.0001 -10000 to +10000 Power Factor (PF), Phase B
Line to Line Voltage (U)•• 104RUIntVoltV0 to 32767Voltage (U), Phase B-C
Line to Neutral Voltage ( V)•• 107RUIntVoltV0 to 32767Voltage (V), Phase B-N
Alta Labs, E nercept, Ensp ector, Hawkeye, Trus tat, Aerospo nd, Veris, and th e Veris ‘V’ log o are tradema rks or registe red tradema rks of Veris Ind ustries, L. L.C. in the USA and /or other countri es.
Other companies’ trademarks are hereby acknowledged to belong to their respective owners.
Installation Guide
Power Monitoring
EC, EC
Modbus Point Map (cont.)
R/W NV FormatUnitsScaleRangeDescription
Register
E51C3 Log
E51C2 FDS
Conguration
Reset:
- Write 30078 (0x757E) to clear all Energy Accumulators to 0 (All).
- Write 21211 (0x52DB) to begin new Demand Sub-Interval calculation cycle. Takes eect at the end of the
next 1 second calculation cycle. Write no more frequently than every 10 seconds.
•• 129R/WUIntN/A
10,
11,
•• 130R/W NVUInt
•• 131R/W NVUIntAmps1-32000CT Ratio – Primary
•• 132R/W NVUInt1, 3CT Ratio – Secondary Interface (1 or 1/3 V, may not be user congurable)
- Write 21212 (0x52DC) to reset Max Demand values to Present Demand Values. Takes eect at the end of the
next 1 second calculation cycle. Write no more frequently than every 10 seconds.
- Write 16640 (0x4100) to reset Logging (E51C3 only).
- Write 16498 (0x4072) to clear Pulse Counts to zero.
- Read always returns 0.
Single Phase: A + N
Single Phase: A + B
Single Split Phase: A + B + N
3 phase ∆, A + B + C, no N
3 phase Y, A + B + C + N
PT Ratio: The meter scales this value by 100 (i.e. entering 200 yields a potential transformer ratio of 2:1).
The default is 100 (1.00:1), which is with no PT attached. Set this value before setting the system voltage
(below)
System Voltage: This voltage is line to line, unless in system type 10 (register 130), which is line to neutral.
The meter uses this value to calculate the full scale power for the pulse conguration (below), and as full
scale for phase loss (register 142). The meter will refuse voltages that are outside the range of 82-660 volts
when divided by the PT Ratio (above).
Theoretical Maximum System Power – This read only register is the theoretical maximum power the meter
expects to see on a service. It is calculated by the meter from the System Type (register 130), CT size (register
131), and System Voltage (register 134) and is updated whenever the user changes any of these parameters.
It is used to determine the maximum power the pulse outputs can keep up with. This integer register has the
same scale as other integer power registers (see register 140 for power scaling).
Scale Factor I (Current)
TM
System Type
(See Manual. Note: only the
indicated phases are monitored
for Phase Loss)
Current Inputs
Scale Factors
Note: These registers contain a signed
integer, which scales the corresponding
integer registers. Floating point
registers are not scaled. Scaling
is recalculated when the meter
conguration is changed.
Alta Labs, E nercept, Ensp ector, Hawkeye, Trus tat, Aerospo nd, Veris, and th e Veris ‘V’ log o are tradema rks or registe red tradema rks of Veris Ind ustries, L. L.C. in the USA and /or other countri es.
Other companies’ trademarks are hereby acknowledged to belong to their respective owners.
Installation Guide
Power Monitoring
EC, EC
Modbus Point Map (cont.)
R/W NV FormatUnitsScaleRangeDescription
Register
E51C3 Log
E51C2 FDS
•• 142R/W NVUInt%1-99
•• 143R/W NVUInt%1-99
•• 144R/W NVUIntWh
•• 145RNVUIntmsec
•• 146RUInt
10000,
1000,
100,
10
500,
250,
100,
50,
25,
10
Phase Loss Voltage Threshold in percent of system voltage (register
134). Default value is 10 (%). Any phase (as congured in register
130) whose level drops below this threshold triggers a Phase Loss
alert, i.e., if the System voltage is set to 480 V L-L, the L-N voltage
for each phase should be 277 V. When the threshold is set to 10%,
if any phase drops more than 10% below 277 V, (less than 249 V),
or if any L-L voltage drops more than 10% below 480 V (less than
432 V) the corresponding phase loss alarm bit in register 146 will
be true.
Phase Loss Imbalance Threshold in Percent. Default is 25% phase
to phase dierence. For a 3-phase Y (3 + N) system type (40 in
register 130), both Line to Neutral and Line to Line voltages are
tested. In a 3-phase System type (31 in register 130), only Line
to Line voltages are examined. In a single split-phase (2 + N)
system type (12 in register 130), just the line to neutral voltage
are compared.
Wh (& VARh, if equipped)
Energy per Pulse Output
Contact Closure. If the meter
cannot nd a pulse duration
that will keep up with the
max. system power (register
135), it will reject the new
value. Check the meter
conguration and/or try a
larger value.
Pulse Contact Closure Duration
in msec. Read-only. Set to
the slowest duration that will
keep up with the theoretical
max. system power (register
135). The open time ≥ the
closure time, so the max.
pulse rate (pulses per sec)
is the inverse of double the
pulse time.
Error Bitmap. 1 = Active:
Bit 0: Phase A Voltage out of range
Bit 1: Phase B Voltage out of range
Bit 2: Phase C Voltage out of range
Bit 3: Phase A Current out of range
Bit 4: Phase B Current out of range
Bit 5: Phase C Current out of range
Bit 6: Frequency out of the range of 45 to 65 Hz -OR- insucient voltage to determine frequency.
Bit 7: Reserved for future use
Bit 8: Phase Loss A
Bit 9: Phase Loss B
Bit 10: Phase Loss C
Bit 11: Low Power Factor on A with one or more phases having a PF less than 0.5 due to mis-wiring of phases
Bit 12: Low Power Factor on B
Bit 13: Low Power Factor on C
Bit 14: Energy pulse output overrun error. The pulse outputs are unable to keep up with the total real power
(registers 3 and 261/262). To x, increase the pulse energy register (register 144) and reset the energy
accumulators (see reset register 129).
Bit 15: Energy pulse output conguration error (present pulse energy setting may not keep up with the
theoretical max. system power; see register 135). To x, increase the pulse energy (register 144).
kWh (& VARh, if equipped) Pulse Contacts
Note: The kWh pulse contact can keep up with a maximum power (Watts) of
1800000 x Wh pulse weight ÷ contact closure duration (in msec)
Alta Labs, E nercept, Ensp ector, Hawkeye, Trus tat, Aerospo nd, Veris, and th e Veris ‘V’ log o are tradema rks or registe red tradema rks of Veris Ind ustries, L. L.C. in the USA and /or other countri es.
Other companies’ trademarks are hereby acknowledged to belong to their respective owners.
Installation Guide
Power Monitoring
EC, EC
Modbus Point Map (cont.)
R/W NV FormatUnitsScaleRangeDescription
Register
E51C3 Log
E51C2 FDS
•• 147RNVUInt0-32767Count of Energy Accumulator resets
•• 148RUIntReserved (returns 0)
•• 149R/W NVUInt1-6
•• 150R/W NVUIntSeconds0, 10-32767
•• 151R/WUInt1-32767Reserved (returns 0)
•• 152RNVUInt0-32767Power Up Counter.
Number of Sub-Intervals per Demand Interval. Sets the number of sub-intervals that
make a single demand interval. For block demand, set this to 1. Default is 1. When SubInterval Length register #150 is set to 0 (sync-to-comms mode), this register is ignored.
Sub-Interval Length in seconds. For sync-to-comms, set this to 0 and use the reset
register (129) to externally re-start the sub-interval. On the E51C3, this is also the
logging interval.
TM
Demand
Calculation
•• 153RNVUInt0-32767
•• 154RUIntReserved, returns 0
• 155R/W NVUInt
• 156R/W NVUInt
• 157R/W NVUInt
• 158R/W NVUInt0-10
• 159R/W NVUInt
Day /
Month
Hour /
Year
Seconds
/
Minutes
See Bytes
See BytesHour 0-23 (0x00-0x17)
See Bytes Seconds 0-59 (0x00-0x3B)Minutes 0-59 (0x00-0x3B)
Output Conguration. E51C2 and E51C3 units have a NO energy contact and NC (Normally Closed - Form B)
Phase Loss contact, so this register will always return a “0”.
Logging Conguration and Status
Most Significant Byte (MSB) Least Significant Byte (LSB)
Day 1-31 (0x01-0x1F)Month 1-12 (0x01-0x0C)
Logging Read Page Register. Selects which of the Register Logs to read (see registers 169-178). 1-10 are valid
entries that put the meter into log reading mode, temporarily pausing logging. When set to 0 (no variable
selected for reading), normal logging resumes. The meter will buer one set of log entries while in reading
mode if a sub-interval timeout occurs (read/write collision). Default is 0.
Warning: this buered data will be written to the log, and logging will resume on the following sub-interval
timeout whether the page register has been cleared or not, resulting in the appearance of data moving in
the buer during reads. To avoid this, log buer reads should be completed and this register set back to 0 in
less time than the Demand Sub-interval (preferred) or logging should be halted by setting Bit 1 in register
158 (logs may be missed)
Logging Conguration Register (Bit Mapped):
Bit 0: Clear to 0 for Circular log buer mode. Set to 1 for single shot logging mode. Default is 0 (Circular).
Bit 1: Clear to 0 to enable Logging. Set to 1 to halt logging. Default is 0 (Log).
Alta Labs, E nercept, Ensp ector, Hawkeye, Trus tat, Aerospo nd, Veris, and th e Veris ‘V’ log o are tradema rks or registe red tradema rks of Veris Ind ustries, L. L.C. in the USA and /or other countri es.
Other companies’ trademarks are hereby acknowledged to belong to their respective owners.
Installation Guide
Power Monitoring
EC, EC
Modbus Point Map (cont.)
R/W NV FormatUnitsScaleRangeDescription
Register
E51C3 Log
E51C2 FDS
Logging Status Register (Bit Mapped):
Bit 0: Log buer full – Set to 1 when one single shot mode has lled the log buer. In this condition, the
Logged Entry Count will continue to increment. Cleared to 0 when logging is restarted (see reset command
register 129).
Bit 1: Log Buer Read Collision 1 – Set to 1 if the meter tried to save log data while the user was reading the
log (Logging Page Register has been set to something other than 0). On the rst collision, the meter holds
the data until the next sub-interval and then writes the saved data to the log as well as the data for that
interval. This bit is cleared to 0 on the rst demand interval with Logging Page Register = 0.
• 160RNV UInt
• 161RNVUInt0-32767
• 162RNVUInt0-32767
• 163RNVUInt0-32767
• 164
RNVULongkWhE
• 1650-0xFFFFReal Energy Consumption (LSR)
0-0xFFFF
Bit 2: Log Buer Read Collision 2 – Set to 1 on the 2nd attempt to save log data while the user is reading
the log (Logging Page Register is set to something other than 0). At this point the meter ignores the read
condition and does a double write, rst of the values saved from the previous c ycle, and then the present
values. If the read condition is not removed the meter continues to write the log data as it normally would.
This bit is cleared to 0 on the rst demand interval with Logging Page Register = 0.
Bit 3: Logging Reset – The log has been reset during the previous demand sub-interval.
Bit 4: Logging Interrupted – Logging has been interrupted (power cycled, log conguration change, etc.)
during the previous demand sub-interval.
Bit 5: RTC Changed – The real time clock had been changed during the previous demand subinterval.
Bit 6: RTC Reset - The Real Time Clock has been reset to the year 2000 and needs to be re-initialized.
Log Buer Wrap / Missed Log Counter. In continous mode, this counter increments each time the internal
circular log buer wraps and overwrites old data. The total number of logged entries since the last log reset
is: (Register 161 x 5760) + Register 163. In single shot mode this counter is the number of log entries lost
due to the buer being full. The counter is cleared on logging reset.
Max Number of Logging Days. Based on the Sub-Interval Length and the depth of the log buer, this register
shows the maximum number of days that data will be logged following a reset until the Buer is full (Single
Shot Mode) or overwrites old data (Continuous).
Number of Logged Entries since the log buer wrapped or was reset. In single shot mode, this is the total
number of valid entries in the buer. Any entries beyond this will read back as QNAN (0x8000).
Real Energy Consumption
(MSR)
TM
Real Energy (Register 001/002) starting value. Corresponds to when logging
is started, reset, or rolls.
• 166RNVUInt
• 167RNVUInt
• 168RNVUInt
Month /
Day
Year /
Hour
Minutes
/
Seconds
See Bytes
See BytesHour 0-23 (0x00-0x17)
See BytesSeconds 0-59 (0x00-0x3B)Minutes 0-59 (0x00-0x3B)
Most Significant Byte (MSB) Least Significant Byte (LSB)
Day 1-31 (0x01-0x1F)Month 1-12 (0x01-0x0C)
Year 0-199 (0x00-0xC7)
Date & Time of the newest entry in the log.
After a power cycle, resets to:
Day 01 Month 01
Hour 00 Year (20) 00
Alta Labs, E nercept, Ensp ector, Hawkeye, Trus tat, Aerospo nd, Veris, and th e Veris ‘V’ log o are tradema rks or registe red tradema rks of Veris Ind ustries, L. L.C. in the USA and /or other countri es.
Other companies’ trademarks are hereby acknowledged to belong to their respective owners.
Installation Guide
Power Monitoring
EC, EC
Modbus Point Map (cont.)
R/W NV FormatUnitsScaleRangeDescription
Register
E51C3 Log
E51C2 FDS
Log Register 1 –
• 169R/W NVUInt
• 170R/W NVUInt
• 171R/W NVUInt
• 172R/W NVUInt
1-42,
• 173R/W NVUInt
• 174R/W NVUInt
• 175R/W NVUInt
• 176R/W NVUInt
• 177R/W NVUInt
• 178R/W NVUInt
•• 257/258 RNVFloatkWhAccumulated Real Energy: Net (Import - Export)
•• 259/260 RNVFloatkWh
•• 261/262 RFloatkWh
•• 263/264 RFloatkVARh
•• 265/266 RFloatkVARh
•• 267/268 RFloatkVARh
•• 269/270 RFloatkVARh
•• 271/272 RNVFloatk VAhApparent Energy: Net (Import - Export)
•• 273/274 RNVFloatk VAh
•• 275/276 RNVFloatk VAh
•• 277/278 RFloatkWTotal Net Instantaneous Real (P) Power
•• 279/280 RFloatkVARTotal Net Instantaneous Reactive (Q) Power
•• 281/282 RFloatk VATotal Net Instantaneous Apparent (S) Power
•• 283/284 RFloatRatio0.0-1.0Total Power Factor (Total kW / Total kVA)
•• 285/286 RFloatVoltVoltage, L-L (U), average of active phases
146,
155-157,
257-336
Floating Point Data: Summary of Active Phases
Default is 3 (Import Real Energy
MSR)
Log Register 2 –
Default is 4 (Import Real Energy
LSR)
Log Register 3 –
Default is 5 (Export Real Energy
MSR)
Log Register 4 –
Default is 6 (Export Real Energy
LSR)
Log Register 5 –
Default is 29 (Real Demand)
Log Register 6 –
Default is 30 (Reactive
Demand)
Log Register 7 –
Default is 31 (Apparent
Demand)
Log Register 8 –
Default is 155 (Month/Day)
Log Register 9 –
Default is 156 (Year/Hour)
Log Register 10 –
Default is 157 (Minutes/
Seconds)
Real Energy: Quadrants 1 & 4
Import
Real Energy: Quadrants 2 & 3
Export
Reactive Energy: Quadrant 1
Lags Import Real Energy (IEC) Inductive (IEEE)
Reactive Energy: Quadrant 2
Leads Export Real Energy (IEC) Inductive (IEEE)
Reactive Energy: Quadrant 3
Lags Export Real Energy (IEC) Capacitive (IEEE)
Reactive Energy: Quadrant 4
Leads Import Real Energy (IEC) Capacitive (IEEE)
Apparent Energy: Quadrants 1 & 4
Import
Apparent Energy: Quadrants 2 & 3
Export
Log Register Selection – Write the number of the 16 bit register to be logged.
To log a 32 bit value (such as accumulators and oating point values) two
log registers must be used, one each for the most and least signicant
register (MSR & LSR).
Accumulated Real Energy
(Ph)
Accumulated Reactive
Energy (Qh):
Quadrants 1+2= Import
Quadrants 3+4= Export
Alta Labs, E nercept, Ensp ector, Hawkeye, Trus tat, Aerospo nd, Veris, and th e Veris ‘V’ log o are tradema rks or registe red tradema rks of Veris Ind ustries, L. L.C. in the USA and /or other countri es.
Other companies’ trademarks are hereby acknowledged to belong to their respective owners.
Installation Guide
Power Monitoring
EC, EC
Modbus Point Map (cont.)
R/W NV FormatUnitsScaleRangeDescription
Register
E51C3 Log
E51C2 FDS
•• 287/288 RFloatVoltVoltage, L-N (V), average of active phases
•• 289/290 RFloatAmpCurrent, average of active phases
•• 291/292 RFloatHz45.0-65.0Frequency
•• 293/294 RFloatkWTotal Real Power Present Demand
•• 295/296 RFloatkVARTotal Reactive Power Present Demand
•• 297/298 RFloatk VATotal Apparent Power Present Demand
•• 299/300 RNVFloatkWTotal Real Power Max. Demand
•• 303/304 RNVFloatk VATotal Apparent Power Max. Demand
•• 305/306 RNVFloatkWTotal Real Power Max. Demand
•• 309/310 RNVFloatk VATotal Apparent Power Max. Demand
Alta Labs, E nercept, Ensp ector, Hawkeye, Trus tat, Aerospo nd, Veris, and th e Veris ‘V’ log o are tradema rks or registe red tradema rks of Veris Ind ustries, L. L.C. in the USA and /or other countri es.
Other companies’ trademarks are hereby acknowledged to belong to their respective owners.
Installation Guide
Power Monitoring
EC, EC
Modbus Point Map (cont.)
R/W NV FormatUnitsScaleRangeDescription
Register
E51C3 Log
E51C2 FDS
•• 365/366 RFloatkWReal Power, Phase A
•• 369/370 RFloatkWReal Power, Phase A
•• 371/372 RFloatkVARReactive Power, Phase A
•• 375/376 RFloatkVARReactive Power, Phase A
•• 377/378 RFloatk VAApparent Power, Phase A
•• 381/382 RFloatk VAApparent Power, Phase A
•• 383/384 RFloatRatio0.0-1.0Power Factor, Phase A
•• 387/388 RFloatRatio0.0-1.0Power Factor, Phase A
Real Power (P)•• 367/368 RFloatkWReal Power, Phase A
Reactive Power (Q)•• 373/374 RFloatkVARReactive Power, Phase A
Apparent Power (S)•• 379/380 RFloatk VAApparent Power, Phase A
Power Factor (PF)•• 385/386 RFloatRatio0.0-1.0Power Factor, Phase A
Line to Line Voltage (U)•• 391/392 RFloatVoltVoltage, Phase B-C
Line to Neutral (V)•• 397/398 RFloatVoltVoltage, Phase B-N
Current•• 403/404 RFloatAmpCurrent, Phase B
5760 entries total (60 days at a 15 minute sub-interval)(to)(to)
Invalid or Quiet Not A Number (QNAN) conditions are indicated by 0x8000 (negative zero) for 16 bit integers and 0x7FC00000 for 32 bit oating point numbers.
Floating point numbers are encoded per the IEEE 754 32-bit specications.
Alta Labs, E nercept, Ensp ector, Hawkeye, Trus tat, Aerospo nd, Veris, and th e Veris ‘V’ log o are tradema rks or registe red tradema rks of Veris Ind ustries, L. L.C. in the USA and /or other countri es.
Other companies’ trademarks are hereby acknowledged to belong to their respective owners.
Installation Guide
Power Monitoring
EC, EC
TM
SunSpec Register Blocks
This section describes the Modbus registers reserved for SunSpec compliance-related information. See www.sunspec.org for
the original specications.
R/W NV Format UnitsScaleRangeSunSpec NameDescription
E51C3 Log
E51C2 FDS
• • 40001
• • 40002
• • 40003RNVUInt1C_SunSpec_DIDSunSpec common model Device ID
• • 40004RNVUInt65C_SunSpec_Length Length of the common model block
• • 40005 to 40020 RNVString (32) ASCIIC_Manufacturernull terminated ASCII text string = “VERIS”
• • 40021 to 40036 RNVString (32) ASCIIC_Modelnull terminated ASCII text string = “E51C_”
• • 40037 to 40044 RNVString (16) ASCIIC_Optionsnull terminated ASCII text string
• • 40045 to 40052 RNVString (16) ASCIIC_Versionnull terminated ASCII text string
• • 40053 to 40068 RNVString (32) ASCIIC_SerialNumbernull terminated ASCII text string
• • 40071RNVUInt105C_SunSpec_Length Length of the meter model block
• • 40072RSIntAmps M_AC_Current_SF-32767 to +32767 M_AC_CurrentAC Current (sum of active phases)
• • 40073RSIntAmps M_AC_Current_SF-32767 to +32767 M_AC_Current_APhase A AC current
• • 40074RSIntAmps M_AC_Current_SF-32767 to +32767 M_AC_Current_BPhase B AC current
• • 40075RSIntAmps M_AC_Current_SF-32767 to +32767 M_AC_Current_CPhase C AC current
• • 40076RNVSInt1M_AC_Current_CN AC Current Scale Factor
• • 40077RSIntVoltsM_AC_Voltage_SF-32767 to +32767 M_AC_Voltage_LN Line to Neutral AC voltage (average of active phases)
• • 40078RSIntVoltsM_AC_Voltage_SF-32767 to +32767 M_AC_Voltage_AN Phase A to Neutral AC Voltage
• • 40079RSIntVoltsM_AC_Voltage_SF-32767 to +32767 M_AC_Voltage_BN Phase B to Neutral AC Voltage
• • 40080RSIntVoltsM_AC_Voltage_SF-32767 to +32767 M_AC_Voltage_CN Phase C to Neutral AC Voltage
• • 40081RSIntVoltsM_AC_Voltage_SF-32767 to +32767 M_AC_Voltage_LLLine to Line AC voltage (average of active phases)
• • 40082RSIntVoltsM_AC_Voltage_SF-32767 to +32767 M_AC_Voltage_AB Phase A to Phase B AC Voltage
• • 40083RSIntVoltsM_AC_Voltage_SF-32767 to +32767 M_AC_Voltage_BC Phase B to Phase C AC Voltage
• • 40084RSIntVoltsM_AC_Voltage_SF-32767 to +32767 M_AC_Voltage_CA Phase C to Phase A AC Voltage
• • 40085RNVSInt1M_AC_Voltage_SF AC Voltage Scale Fac tor
• • 40086RSIntHertzM_AC_Freq_SF-32767 to +32767 M_AC_FreqAC Frequency
• • 40087RNVSIntSF1M_AC_Freq_SFAC Frequency Scale Factor
Register
RNVULong
SunSpec 1.0 Common Model
0x5375
6e53
SunSpec 1.1 Integer Meter Model
Identification
Current
Voltage: Line to Neutral
Voltage: Line to Line
Frequency
C_SunSpec_ID
ASCII “SunS”. Identies this as the beginning of a SunSpec Modbus
point
SunSpec Integer meter model device IDs. Meter conguration by
device ID:
201 = single phase (A-N or A-B) meter
202 = split single phase (A-B-N) meter
203 = Wye-connect 3-phase (ABCN) meter
204 = delta-connect 3-phase (ABC) meter
Alta Labs, E nercept, Ensp ector, Hawkeye, Trus tat, Aerospo nd, Veris, and th e Veris ‘V’ log o are tradema rks or registe red tradema rks of Veris Ind ustries, L. L.C. in the USA and /or other countri es.
Other companies’ trademarks are hereby acknowledged to belong to their respective owners.
Installation Guide
Power Monitoring
EC, EC
SunSpec Register Blocks (cont.)
R/W NV Format UnitsScaleRangeSunSpec NameDescription
E51C3 Log
E51C2 FDS
• • 40088RSIntWatts M_AC_Power_SF-32767 to +32767 M_AC_PowerTotal Real Power (sum of active phases)
• • 40089RSIntWatts M_AC_Power_SF-32767 to +32767 M_AC_Power_APhase A AC Real Power
• • 40090RSIntWatts M_AC_Power_SF-32767 to +32767 M_AC_Power_BPhase B AC Real Power
• • 40091RSIntWatts M_AC_Power_SF-32767 to +32767 M_AC_Power_CPhase A AC Real Power
• • 40092RNVSIntSF1M_AC_Power_SFAC Real Power Scale Factor
• • 40093RSInt
• • 40094RSInt
• • 40095RSInt
• • 40096RSInt
• • 40097RNVSIntSF1M_AC_VA_SFAC Apparent Power Scale Factor
• • 40098RSIntVARM_AC_VAR_SF-32767 to +32767 M_AC_VARTotal AC Reactive Power (sum of active phases)
• • 40099RSIntVARM_AC_VAR_SF-32767 to +32767 M_AC_VAR_APhase A AC Reactive Power
• • 40100RSIntVARM_AC_VAR_SF-32767 to +32767 M_AC_VAR_BPhase B AC Reactive Power
• • 40101RSIntVARM_AC_VAR_SF-32767 to +32767 M_AC_VAR_CPhase A AC Reactive Power
• • 40102RNVSIntSF1M_AC_VAR_SFAC Reactive Power Scale Factor
• • 40103RSInt%M_AC_PF_SF-32767 to +32767 M_AC_PFAverage Power Factor (average of active phases)
• • 40104RSInt%M_AC_PF_SF-32767 to +32767 M_AC_PF_APhase A Power Fac tor
• • 40105RSInt%M_AC_PF_SF-32767 to +32767 M_AC_PF_BPhase B Power Factor
• • 40106RSInt%M_AC_PF_SF-32767 to +32767 M_AC_PF_CPhase A Power Factor
• • 40107RNVSIntSF1M_AC_PF_SFAC Power Factor Scale Factor
• • 40108
• • 40109
• • 40110
• • 40111
• • 40112
• • 40113
• • 40114
• • 40115
• • 40116
• • 40117
• • 40118
• • 40119
• • 40120
• • 40121
• • 40122
• • 40123
• • 40124RNVSFSF1M_Energy_W_SFReal Energy Scale Factor
Register
RNVULong
RNVULong
RNVULong
RNVULong
RNVULong
RNVULong
RNVULong
RNVULong
Power
Real Power
Volt-
M_AC_VA_SF-32767 to +32767 M_AC_VATotal AC Apparent Power (sum of active phases)
Amps
Volt-
M_AC_VA_SF-32767 to +32767 M_AC_VA_APhase A AC Apparent Power
Amps
Volt-
M_AC_VA_SF-32767 to +32767 M_AC_VA_BPhase B AC Apparent Power
Amps
Volt-
M_AC_VA_SF-32767 to +32767 M_AC_VA_CPhase A AC Apparent Power
Amps
Watt-
M_Energy_W_SF0x0 to 0xFFFFFFFF M_Exported_WTotal Exported Real Energy
hours
Watt-
M_Energy_W_SF0x0 to 0xFFFFFFFF M_Exported_W_APhase A Exported Real Energy
hours
Watt-
M_Energy_W_SF0x0 to 0xFFFFFFFF M_Exported_W_BPhase B Exported Real Energy
hours
Watt-
M_Energy_W_SF0x0 to 0xFFFFFFFF M_Exported_W_CPhase C Exported Real Energy
hours
Watt-
M_Energy_W_SF0x0 to 0xFFFFFFFF M_Imported_WTotal Imported Real Energy
hours
Watt-
M_Energy_W_SF0x0 to 0xFFFFFFFF M_Imported_W_A Phase A Imported Real Energy
hours
Watt-
M_Energy_W_SF0x0 to 0xFFFFFFFF M_Imported_W_B Phase B Imported Real Energy
hours
Watt-
M_Energy_W_SF0x0 to 0xFFFFFFFF M_Imported_W_C Phase C Imported Real Energy
Alta Labs, E nercept, Ensp ector, Hawkeye, Trus tat, Aerospo nd, Veris, and th e Veris ‘V’ log o are tradema rks or registe red tradema rks of Veris Ind ustries, L. L.C. in the USA and /or other countri es.
Other companies’ trademarks are hereby acknowledged to belong to their respective owners.
Installation Guide
Power Monitoring
EC, EC
SunSpec Register Blocks (cont.)
R/W NV Format UnitsScaleRangeSunSpec NameDescription
E51C3 Log
E51C2 FDS
• • 40125
• • 40126
• • 40127
• • 40128
• • 40129
• • 40130
• • 40131
• • 40132
• • 40133
• • 40134
• • 40135
• • 40136
• • 40137
• • 40138
• • 40139
• • 40140
• • 40141RNVUIntSF1M_Energy_VA_SFReal Energy Scale Factor
• • 40142
• • 40143
• • 40144
• • 40145
• • 40146
• • 40147
• • 40148
• • 40149
• • 40150
• • 40151
• • 40152
• • 40153
• • 40154
• • 40155
• • 40156
• • 40157
• • 40158
• • 40159
• • 40160
• • 40161
• • 40162
• • 40163
• • 40164
• • 40165
• • 40166
• • 40167
Register
RNVULong
RNVULong
RNVULong
RNVULong
RNVULong
RNVULong
RNVULong
RNVULong
RNVULong
RNVULong
RNVULong
RNVULong
RNVULong
RNVULong
RNVULong
RNVULong
RNVULong
RNVULong
RNVULong
RNVULong
RNVULong
Apparent Energy
VA-
M_Energy_VA_SF0x0 to 0xFFFFFFFF M_Exported_VATotal Exported Apparent Energy
hours
VA-
M_Energy_VA_SF0x0 to 0xFFFFFFFF M_Exported_VA_A Phase A Exported Apparent Energy
hours
VA-
M_Energy_VA_SF0x0 to 0xFFFFFFFF M_Exported_VA_B Phase B Exported Apparent Energy
hours
VA-
M_Energy_VA_SF0x0 to 0xFFFFFFFF M_Exported_VA_C Phase C Exported Apparent Energy
hours
VA-
M_Energy_VA_SF0x0 to 0xFFFFFFFF M_Imported_VATotal Imported Apparent Energy
hours
VA-
M_Energy_VA_SF0x0 to 0xFFFFFFFF M_Imported_VA_A Phase A Imported Apparent Energy
hours
VA-
M_Energy_VA_SF0x0 to 0xFFFFFFFF M_Imported_VA_B Phase B Imported Apparent Energy
hours
VA-
M_Energy_VA_SF0x0 to 0xFFFFFFFF M_Imported_VA_C Phase C Imported Apparent Energy
hours
Reactive Energy
VAR-
M_Energy_VAR_SF0x0 to 0xFFFFFFFF M_Import_VARh_Q1 Quadrant 1: Total Imported Reactive Energy
hours
VAR-
M_Energy_VAR_SF0x0 to 0xFFFFFFFF
hours
VAR-
M_Energy_VAR_SF0x0 to 0xFFFFFFFF
hours
VAR-
M_Energy_VAR_SF0x0 to 0xFFFFFFFF
hours
VAR-
M_Energy_VAR_SF0x0 to 0xFFFFFFFF M_Import_VARh_Q2 Quadrant 2: Total Imported Reactive Energy
hours
VAR-
M_Energy_VAR_SF0x0 to 0xFFFFFFFF
hours
VAR-
M_Energy_VAR_SF0x0 to 0xFFFFFFFF
hours
VAR-
M_Energy_VAR_SF0x0 to 0xFFFFFFFF
hours
VAR-
M_Energy_VAR_SF0x0 to 0xFFFFFFFF M_Export_VARh_Q3 Quadrant 3: Total Exported Reactive Energy
hours
VAR-
M_Energy_VAR_SF0x0 to 0xFFFFFFFF
hours
VAR-
M_Energy_VAR_SF0x0 to 0xFFFFFFFF
hours
VAR-
M_Energy_VAR_SF0x0 to 0xFFFFFFFF
hours
VAR-
M_Energy_VAR_SF0x0 to 0xFFFFFFFF M_Export_VARh_Q4 Quadrant 4: Total Exported Reactive Energy
hours
M_Import_VARh_
Q1A
M_Import_VARh_
Q1B
M_Import_VARh_
Q1C
M_Import_VARh_
Q2A
M_Import_VARh_
Q2B
M_Import_VARh_
Q2C
M_Export_VARh_
Q3A
M_Export_VARh_
Q3B
M_Export_VARh_
Q3C
Phase A - Quadrant 1: Total Imported Reactive Energy
Phase B - Quadrant 1: Total Imported Reactive Energy
Phase C - Quadrant 1: Total Imported Reactive Energy
Phase A - Quadrant 2: Total Imported Reactive Energy
Phase B - Quadrant 2: Total Imported Reactive Energy
Phase C - Quadrant 2: Total Imported Reactive Energy
Phase A - Quadrant 3: Total Exported Reactive Energy
Phase B - Quadrant 3: Total Exported Reactive Energy
Phase C - Quadrant 3: Total Exported Reactive Energy
Alta Labs, E nercept, Ensp ector, Hawkeye, Trus tat, Aerospo nd, Veris, and th e Veris ‘V’ log o are tradema rks or registe red tradema rks of Veris Ind ustries, L. L.C. in the USA and /or other countri es.
Other companies’ trademarks are hereby acknowledged to belong to their respective owners.
Installation Guide
Power Monitoring
EC, EC
SunSpec Register Blocks (cont.)
R/W NV Format UnitsScaleRangeSunSpec NameDescription
E51C3 Log
E51C2 FDS
Register
TM
• • 40168
• • 40169
• • 40170
• • 40171
• • 40172
• • 40173
• • 40174RNVUIntSF1M_Energy_VA_SFReactive Energy Scale Factor
• • 40175
RNVULong
RNVULong
RNVULong
VAR-
M_Energy_VAR_SF0x0 to 0xFFFFFFFF
hours
VAR-
M_Energy_VAR_SF0x0 to 0xFFFFFFFF
hours
VAR-
M_Energy_VAR_SF0x0 to 0xFFFFFFFF
hours
Events
M_Export_VARh_
Q4A
M_Export_VARh_
Q4B
M_Export_VARh_
Q4C
M_EventsBit Map. See M_EVENT_ags. 0 = no event
Phase A - Quadrant 4: Total Exported Reactive Energy
Phase B - Quadrant 4: Total Exported Reactive Energy
Phase C - Quadrant 4: Total Exported Reactive Energy
EventBitDescription
M_EVENT_Power_Failure0x00000004Loss of power or phase
Alta Labs, E nercept, Ensp ector, Hawkeye, Trus tat, Aerospo nd, Veris, and th e Veris ‘V’ log o are tradema rks or registe red tradema rks of Veris Ind ustries, L. L.C. in the USA and /or other countri es.
Other companies’ trademarks are hereby acknowledged to belong to their respective owners.
Installation Guide
Power Monitoring
EC, EC
TM
Troubleshooting
ProblemCauseSolution
The maintenance wrench
icon appears in the power
meter display.
The display is blank after
applying control power
to the meter.
The data displayed is
inaccurate.
Cannot communicate
with power meter from
a remote personal
computer.
Sign of one phase (real
power) is incorrect
There is a problem
with the inputs to the
power meter.
The meter is not
receiving adequate
power.
Incorrect setup valuesVerify the values entered for power meter setup parameters (CT and PT ratings,
Incorrect voltage inputs Check power meter voltage input terminals to verify adequate voltage.
Alta Labs, E nercept, Ensp ector, Hawkeye, Trus tat, Aerospo nd, Veris, and th e Veris ‘V’ log o are tradema rks or registe red tradema rks of Veris Ind ustries, L. L.C. in the USA and /or other countri es.
Other companies’ trademarks are hereby acknowledged to belong to their respective owners.
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.