the FCC Rules. These limits are designed to provide reasonable protection
residential environment. This equipment generates, uses, and can radiate
Power Monitoring
RoHS
Compliant
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
• Follow safe electrical work practices. See NFPA 70E in the USA, or applicable local codes.
• This equipment must only be installed and serviced by qualified electrical personnel.
• Read, understand and follow the instructions before installing this product.
• Turn off all power supplying equipment before working on or inside the equipment.
• Any covers that may be displaced during the installation must be reinstalled
before powering the unit.
• Use a properly rated voltage sensing device to confirm power is off.
DO NOT DEPEND ON THIS PRODUCT FOR VOLTAGE INDICATION
Failure to follow these instructions will result in death or serious injury.
A qualied person is one who has skills and knowledge related to the construction and
operation of this electrical equipment and the installation, and has received safety
training to recognize and avoid the hazards involved. NEC2009 Article 100
No responsibility is assumed by Veris Industries for any consequences arising out of the
use of this material.
Control system design must consider the potential failure modes of control paths and, for
certain critical control functions, provide a means to acheive a safe state during and after a
path failure. Examples of critical control functions are emergency stop and over-travel stop.
TM
E50F2, E50F5
Compact Power and Energy Meters
With LON TP/FT-10 Communication
Product Overview
The E50Fx DIN Rail Power Meter provides a solution for measuring energy data with a single device. Inputs include
pulse, control power, CT, and 3-phase voltage. The E50Fx supports multiple output options, including solid state
phase loss alarm relay contacts (E50F2 only), LON, and data logging (E50F5 only). The LCD screen on the faceplate
allows instant output viewing.
The meter is housed in a plastic enclosure suitable for installation on T35 DIN rail according to EN50022. The E50 can
be mounted with any orientation over the entire ambient temperature range, either on a DIN rail or in a panel. The
meter is not sensitive to CT orientation to reduce installation errors.
Product Identification
ModelDescription
E50F2LON output, 1 pulse input , alarm output
E50F5LON output, data logging, 2 pulse inputs
Specifications
WARNING
LOSS OF CONTROL
∙ Assure that the system will reach a safe state during and after a control path failure.
∙ Separate or redundant control paths must be provided for critical control func tions.
∙ Test the eect of transmission delays or failures of communication links.
∙ Each implementation of equipment using communication links must be individually
and thoroughly tested for proper operation before placing it in service.
Failure to follow these instructions may cause injury, death or equipment damage.
1
For additional information about anticipated transmission delays or failures of the link, refer to
NEMA ICS 1.1 (latest edition). Safety Guidelins for the Application, Installation, and Maintenance of Solid-State Control or its equivalent in your specic country, language, and/or location.
NOTICE
• This product is not intended for life or safety applications.
• Do not install this product in hazardous or classified locations.
• The installer is responsible for conformance to all applicable codes.
• Mount this product inside a suitable fire and electrical enclosure.
FCC PART 15 INFORMATION
NOTE: This equipment has been tested by the manufacturer and found to
comply with the limits for a class B digital device, pursuant to part 15 of
against harmful interference when the equipment is operated in a
radio frequency energy and, if not installed and used in accordance with
the instruction manual, may cause harmful interference to radio
communications. This device complies with part 15 of the FCC Rules.
Operation is subject to the following two conditions:
(1) This device may not cause harmful interference, and
(2) this device must accept any interference received, including
interference that may cause undesired operation.
Modifications to this product without the express authorization of the
manufacturer nullify this statement.
For use in a P ollution D egree 2 or be tter envi ronment on ly. A Pollutio n Degree 2
environment must control conductive pollution and the possibility of condensation or
high hum idity. Cons ider the enc losure, th e correc t use of venti lation, the rmal prop erties
of the equ ipment, an d the relati onship wi th the envir onment. In stallati on categor y:
CAT II or CAT III. P rovide a di sconnec t device to di sconnec t the meter f rom the sup ply
source. P lace this de vice in clos e proximit y to the equ ipment and w ithin eas y reach of
the oper ator, and mark i t as the disc onnecti ng device. T he disconn ecting de vice shall
meet th e relevant r equireme nts of IEC 60 947-1 and IEC 60947-3 and sh all be suit able for
the appl ication. I n the US and Can ada, discon nectin g fuse hold ers can be us ed. Provi de
overcu rrent prot ection a nd discone cting dev ice for sup ply conduc tors wit h approved
current limiting devices suitable for protecting the wiring. If the equipment is used in a
manner n ot specie d by the manu facture r, the protec tion prov ided by the d evice may
be impaired.
Real Power and Energy
1
Reactive Power and Energy
Current
Volta ge
Sample Rate
Data Update Rate
Type of Measurement
Measured AC Voltage
Metering Over-Range
Impedance
Frequency Range
CT Scaling
Measurement Input Range
Impedance
MEASUREMENT ACCURACY
IEC 620 53 -22 Class 0. 5S, A NSI C12.20 0.5%
IEC 620 53 -23 Class 2, 2%
0.4% (+ 0.015% per °C deviation from 25°C ) from 5% to 100% of range;
0.8% (+0.015% per °C deviation from 25°C ) from 1% to 5% of range
0.4% (+ 0.015% per °C deviation from 25°C ) from 90 V
2520 samples per second
1 sec
True RMS up to 1260 Hz ( 21st harmonic at 60 Hz); One to three phase AC
system
INPUT VO LTAGE CHAR ACTER ISTIC S
Minimum 90 V
UL Maximums: 6 00 V
+20%
2.5 MΩ
45 to 65 Hz
INPUT CUR RENT CHA RACTERISTIC S
Primar y: Adjustable from 5 A to 32,00 0 A
0 to 0.333 VAC or 0 to 1.0 VAC (+20% over- range ), rated for use with Class
1 voltage inputs
Alta Labs, E nercept, Ensp ector, Hawkeye, Trus tat, Aerospo nd, Veris, and th e Veris ‘V’ log o are tradema rks or registe red tradema rks of Veris Ind ustries, L. L.C. in the USA and /or other countri es.
Other companies’ trademarks are hereby acknowledged to belong to their respective owners.
to 600 VAC
L-N
L-L
Installation Guide
Power Monitoring
EF, EF
TM
Specifications
(cont.)
CONTROL POWER
AC
5 VA max.; 9 0 V min.;
UL Maximum: 6 00 V
DC*
3 W max.; U L and CE: 125 to 300 V DC
Ride Through Time
Pulse
Minimum Pul se Width
Alarm Contacts (E50F2 only)
Communication Port
Weight
IP Degree of Prote ction (IEC
60529)
Display Characteristics
Terminal Block Screw Torque
Terminal Block Wire Size
Mounting Rail
Operating Temperature
Storage Temperature
Humidity Range
Altitude of Operation
US and Canada
Dielectric Withstand
Conducted and Radiated
Emissions
Conducted and Radiated
Immunity
Agencies: US and Canada
(cULus)
* External DC current limiting is required. See fuse recommendations.
100 msec at 120 VAC
Solid -State or mechanical contacts (current less than 1 mA)
20 msec
N.C., static output; (30 VAC /DC, 100 mA max. @ 25°C, derate 0.56 mA per
°C above 25°C )
Alta Labs, E nercept, Ensp ector, Hawkeye, Trus tat, Aerospo nd, Veris, and th e Veris ‘V’ log o are tradema rks or registe red tradema rks of Veris Ind ustries, L. L.C. in the USA and /or other countri es.
Other companies’ trademarks are hereby acknowledged to belong to their respective owners.
Alta Labs, E nercept, Ensp ector, Hawkeye, Trus tat, Aerospo nd, Veris, and th e Veris ‘V’ log o are tradema rks or registe red tradema rks of Veris Ind ustries, L. L.C. in the USA and /or other countri es.
Other companies’ trademarks are hereby acknowledged to belong to their respective owners.
Installation Guide
Power Monitoring
EF, EF
TM
Dimensions
1.8”
(45mm)
1.9”
(48mm)
2.3”
(59mm)
1.5”
(39mm)
4.2”
(107mm)
3.6”
(91mm)
Bottom View (DIN Mount Option)Bottom View (Screw Mount Option)
2.4 “
(61 mm)
+
0.2 “
(4 mm)
3.6 “
(91 mm)
4.2 “
(107 mm)
3.9“
(99 mm)
4.3 “
(109 mm)
1.2 “
(31 mm)
++
0.3 “
(8 mm)
0.4 “
(10 mm)
Data Outputs
Full Data Set (FDS)
Power (kW)
Energy (kWh)
Congurable for CT & PT ratios, system type, and passwords
Diagnostic alerts
Current: 3-phase average
Volts: 3-phase average
Current: by phase
Volts: by phase Line-Line and Line-Neutral
Power: Real, Reactive, and Apparent 3-phase total and per phase
Power Factor: 3-phase average and per phase
Frequency
Power Demand: Most Recent and Peak
Demand Conguration: Fixed, Rolling Block, and External Sync
Real Time Clock: user congurable
Data Logging (E50F5 only, includes all FDS outputs plus)
3 user congurable log buers: each buer holds 5760 32-bit entries
(User congures which 3 data points are stored in these buers)
User congurable logging interval
(When congured for a 15 minute interval, each buer holds 60 days of data)
Continuous and Single Shot logging modes: user selectable
Auto write pause: read logs without disabling the meter’s data logging mode
Alta Labs, E nercept, Ensp ector, Hawkeye, Trus tat, Aerospo nd, Veris, and th e Veris ‘V’ log o are tradema rks or registe red tradema rks of Veris Ind ustries, L. L.C. in the USA and /or other countri es.
Other companies’ trademarks are hereby acknowledged to belong to their respective owners.
Installation Guide
Power Monitoring
EF, EF
TM
Product Diagrams
Two 5-character rows
of display text.
Top row alphanumeric;
Bottom row numeric only
The red Alarm LED lights
when any of the 3 phase
voltages drop below the
selected threshold.
E50F2
IA
IB
X2 X1 X2 X1 X2 X1
(X2) A (X1) (X2) B (X1) (X2) C (X1)
1 or 0.333 VAC
CT Inputs
IC
Alarm Output
Pulse Input
+
L-N
- 300V
L-N
–
CONTROL POWER
0.1A 50/60 Hz
EMC Ground
AlarmEnergy
VOLTAGE INPUTS
CAT III 50/60 Hz
ABCN12
VA
UL: 90V
- 600V
CE: 90V
L-N
L-L
VB
VC
Neutral
E50F5
IA
IB
IC
X2 X1 X2 X1 X2 X1
(X2) A (X1) (X2) B (X1) (X2) C (X1)
Pulse Input 1
Pulse Inputs
Pulse Input 2
SERVICE
LON FT
Control
LON FT
Shield
S
Power
Shield
Display Screen
Diagram
12S
SERVICE
+
Two 5-character rows
of display text.
CT Inputs
1 or 0.333 VAC
Top row alphanumeric;
Bottom row numeric only
AlarmEnergy
–
The red Alarm LED lights
when any of the 3 phase
voltages drop below the
VOLTAGE INPUTS
CAT III 50/60 Hz
UL: 90V
L-N
- 600V
CE: 90V
L-L
CONTROL POWER
- 300V
L-N
L-N
0.1A 50/60 Hz
selected threshold.
The green Energy LED lights
when the pulse 1 input
contacts are active or closed.
ABCN12
VA
VB
VC
Neutral
EMC Ground
Control
Power
LCD Screen:Buttons:
Screen Name or Units
Diagnostic Alert:
indicates that one or
more of the alarm
bits (Binary_Objects
1-15) are active.
Logo
Numeric Data
♥
Tx
Rx
ERR
Alive Indicator
RS-485 Equipped Units Only:
Transmit Data
Receive Data
Receive Data Error
Alta Labs, E nercept, Ensp ector, Hawkeye, Trus tat, Aerospo nd, Veris, and th e Veris ‘V’ log o are tradema rks or registe red tradema rks of Veris Ind ustries, L. L.C. in the USA and /or other countri es.
Other companies’ trademarks are hereby acknowledged to belong to their respective owners.
Installation Guide
Power Monitoring
EF, EF
TM
Installation
Disconnect power prior to installation.
Reinstall any covers that are displaced during the installation before powering the unit.
Mount the meter in an appropriate electrical enclosure near equipment to be monitored.
Do not install on the load side of a Variable Frequency Drive (VFD), aka Variable Speed Drive (VSD)
or Adjustable Frequency Drive (AFD).
The meter can be mounted in two ways: on standard 35 mm DIN rail or screw-mounted to the interior surface of the enclosure.
A. DIN Rail Mounting
1. Attach the mounting clips to the underside of the housing by sliding them into the slots from the inside. The stopping pegs
must face the housing, and the outside edge of the clip must be ush with the outside edge of the housing.
2. Snap the clips onto the DIN rail. See the diagram of the underside of the housing (below).
Clip flush with
outside edge
Snap onto
Insert clips from inside
DIN rail
3. To reduce horizontal shifting across the DIN rail, use two Veris AV02 end stop clips.
B. Screw Mounting
1. Attach the mounting clips to the underside of the housing by sliding them into the slots from the outside. The stopping pegs
must face the housing, and the screw hole must be exposed on the outside of the housing.
2. Use three #8 screws (not supplied) to mount the meter to the inside of the enclosure. See the diagram of the underside of the
housing (below).
Alta Labs, E nercept, Ensp ector, Hawkeye, Trus tat, Aerospo nd, Veris, and th e Veris ‘V’ log o are tradema rks or registe red tradema rks of Veris Ind ustries, L. L.C. in the USA and /or other countri es.
Other companies’ trademarks are hereby acknowledged to belong to their respective owners.
Installation Guide
Power Monitoring
EF, EF
TM
Supported System
Types
The meter has a number of dierent possible system wiring congurations (see Wiring Diagrams sec tion). To congure the meter,
set the System Type via the User Interface, LON variable cpSystemType. The System Type tells the meter which of its current and
voltage inputs are valid, which are to be ignored, and whether neutral is connec ted. Setting the correct System Type prevents
unwanted energy accumulation on unused inputs, selects the formula to calculate the Theoretical Maximum System Power, and
determines which phase loss algorithm is to be used. The phase loss algorithm is congured as a percentage of the Line-to-Line
System Voltage (except when in System Type 10) and also calculates the expected Line to Neutral voltages for system types that
have Neutral (12 & 40).
Values that are not valid in a particular System Type display as “----” on the User Interface or as QNAN in the LON variables.
CTsVoltage ConnectionsSystem TypePhase Loss MeasurementsWiring
Alta Labs, E nercept, Ensp ector, Hawkeye, Trus tat, Aerospo nd, Veris, and th e Veris ‘V’ log o are tradema rks or registe red tradema rks of Veris Ind ustries, L. L.C. in the USA and /or other countri es.
Other companies’ trademarks are hereby acknowledged to belong to their respective owners.
Installation Guide
Power Monitoring
EF, EF
TM
Wiring
WARNING
RISK OF ELECTRIC SHOCK OR PERMANENT EQUIPMENT DAMAGE
CT negative terminals are referenced to the meter’s neutral and may be at elevated voltages
· Do not contact meter terminals while the unit is connected
· Do not connect or short other circuits to the CT terminals
Failure to follow these instructions may cause injury, death or equipment damage.
Diagram 1: 1-Phase Line-to-Neutral 2- Wire
System 1 CT
N L1
Use System Type 10 (1L + 1n)
X1
X2
A
B
C
N
White
Black
X1
A
X2
X1
B
X2
X1
C
X2
Diagram 3: 1-Phase Direct Voltage Connection 2 CT
N
L1 L2
Use System Type 12 (2L + 1n)Use System Type 31 (3L)
Diagram 2: 1-Phase Line-to-Line 2-Wire
L1 L2
X1
X2
Diagram 4: 3-Phase 3-Wire 3 CT no PT
L1 L2 L3
System 1 CT
Use System Type 11 (2L)
White
Black
A
B
C
N
X1
A
X2
X1
B
X2
X1
C
X2
A
B
C
N
X1
X2
X1
X2
White
Black
White
Black
X1
A
X2
X1
B
X2
X1
C
X2
Diagram 5: 3-Phase 4-Wire Wye Direct Voltage Input
Alta Labs, E nercept, Ensp ector, Hawkeye, Trus tat, Aerospo nd, Veris, and th e Veris ‘V’ log o are tradema rks or registe red tradema rks of Veris Ind ustries, L. L.C. in the USA and /or other countri es.
Other companies’ trademarks are hereby acknowledged to belong to their respective owners.
Installation Guide
Power Monitoring
EF, EF
TM
Control Power
Direct Connect Control Power (Line to Line)
L1
L2 L3
Line to Line from 90 VAC to 600 VAC (UL). In UL installations the
lines may be oating (such as a delta). If any lines are tied to an
earth (such as a corner grounded del ta), see the Line to Neutral
installation limits. In CE compliant installations, the lines must
be neutral (earth) referenced at less than 300 VAC
Direct Connect Control Power (DC Control Power)
1 2G
DC Control Power from 125 VDC to 300 VDC
(UL and CE max.)
Fuse Recommendations
Direct Connect Control Power (Line to Neutral)
1 2G
L-N
L1NL2 L3
Line to Neutral from 90 VAC to 347 VAC (UL) or 300 VAC (CE)
1 2G
Control Power Transformer (CPT) Connection
1 2G
L1NL2 L3
The Control Power Transformer may be wired L-N or L-L. Output to
meet meter input requirements
Keep the fuses close to the power source (obey local and national code requirements).
For selecting fuses and circuit breakers, use the following criteria:
• Select current interrupt capacity based on the installation category and fault current capability.
• Select over-current protection with a time delay.
• Select a voltage rating sucient for the input voltage applied.
• Provide overcurrent protection and disconnecting means to protect the wiring. For AC installations, use Veris AH02,
AH03, AH04, or equivalent. For DC installations, provide external circuit protec tion. Suggested: 0.5 A, time delay fuses.
• The earth connection (G) is required for electromagnetic compatibility (EMC) and is not a protective earth ground.
Alta Labs, E nercept, Ensp ector, Hawkeye, Trus tat, Aerospo nd, Veris, and th e Veris ‘V’ log o are tradema rks or registe red tradema rks of Veris Ind ustries, L. L.C. in the USA and /or other countri es.
Other companies’ trademarks are hereby acknowledged to belong to their respective owners.
Installation Guide
Power Monitoring
EF, EF
TM
Quick Setup
Instructions
These instruc tions assume the meter is set to factory defaults. If it has been previously congured, check all optional values.
A. To Navigate to the Setup screens:
+
+
1. Press
or – repeatedly until SETUP screen appears.
2. Press to get to the PASWD screen.
+
3. Press to move through the digits. Use the
+
or – buttons to enter your password (the default is 00000).
4. Press to move to the rst Setup screen (S CT)
+
+
5. Use
or – to select the parameter screen you want to set.
+
6. After you set the parameters you want, use
+
or – to select the next Setup screen or to exit the Setup screens (return to
SETUP ).
B. To Enter the CT (Current Transducer) output voltage and CT size ranges:
1. Navigate to the S CT (Set Current Transducer) Setup screen (see section A above).
+
2. Press to go to the CT V screen. Use
1. 00).
3. Press to go to the CT SZ screen and through the digits. Use
the value and
4. Press to accept the value and go back to the S CT screen.
+
or – to select the voltage mode Current Transducer output voltage (default is
+
+
or – to select the CT size in amps (default is 100). accept
Pulse Contact Inputs
C. To Enter the service type to be monitored:
1. Navigate to the S SYS (Set System) Setup screen (see section A above).
+
2. Press to go to the SYSTM screen. Use
Press to go back to the S SYS screen.
For full setup instructions, see the conguration instructions on the following pages.
The E50F5 has two inputs with pulse accumulators for solid state or mechanical contacts in other sensors, such as water or gas
ow meters. The E50F2 has one pulse input. These inputs are isolated from the measured circuits. The communication signals,
including the shield terminal, are AC-coupled. Use with contacts that do not require current to remove oxidation.
Pulse Input
E50F5 only
4-10 VDC
nominal
+
Contacts
~10 kΩ
+
or – to select the conguration (see wiring diagrams - default is 3L-1N).
Alta Labs, E nercept, Ensp ector, Hawkeye, Trus tat, Aerospo nd, Veris, and th e Veris ‘V’ log o are tradema rks or registe red tradema rks of Veris Ind ustries, L. L.C. in the USA and /or other countri es.
Other companies’ trademarks are hereby acknowledged to belong to their respective owners.
Installation Guide
Red
Black
Gray
Use 14-24 gauge wire
Power Monitoring
EF, EF
TM
Solid State Output
The E50F2 has one normally closed (N.C.) alarm output.* See the Setup section for conguration information.
Over-Current Protective Device**
(not supplied)
≤ 100 mA
Power So urce
~
=
3-30 VDC
6-3 0 VAC
S
Alarm
PulseComm
The solid state pulse outputs are rated for 30 VAC/DC nom.
The maximum load current is 100 mA at 25°C. Derate 0.56 mA per °C above 25°C.
* While the relay used for the Phase Loss contact is normally closed (contacts are closed when the meter is not powered), closure
indicates the presence of an alarm; either loss of phase, when the meter is powered, or loss of power when the meter is not. The
contacts are open when the meter is powered and no phase loss alarm conditions are present.
** The over-current protective device must be rated for the short circuit current at the connection point.
All pulse inputs/outputs and communication circuits are only intended to be connected to non-hazardous circuits (SELV or Class 2).
Do not connect to hazardous voltages.
Lon TP/FT-10
Communications
• Use this meter in either Free Topology or Bus Topology LonWorks network congurations.
• Twisted pair connections to the meter are not polarity sensitive.
• Attach the meter at any point in a Free Topology conguration, but the total network cable length must be less than
500 meters.
• Free Topology congurations require one terminator (Echelon TP/FT-10 Free Topology Terminator or equivalent), which
can be attached at any point in the network.
• In Bus Topology congurations, connect loads sequentially (in a daisy chain), except for stubs, which must be less than
3 meters in length. The total network cable length must be less than 2700 meters.
• Bus Topology congurations require two terminators (Echelon TP/FT -10 Free Topology Terminator or equivalent, one
at at each end of the network.
• The Shield connection is not internally connected to the ground connection on the meter.
LON-FT Shield
For all terminals:
• When tightening terminals, apply the correct torque: 0.37 to 0.44 ft·lb (0.5-0.6 N·m).
Alta Labs, E nercept, Ensp ector, Hawkeye, Trus tat, Aerospo nd, Veris, and th e Veris ‘V’ log o are tradema rks or registe red tradema rks of Veris Ind ustries, L. L.C. in the USA and /or other countri es.
Other companies’ trademarks are hereby acknowledged to belong to their respective owners.