Veris E50F5 Installation Instructions

Installation Guide
the FCC Rules. These limits are designed to provide reasonable protection
residential environment. This equipment generates, uses, and can radiate
Power Monitoring
RoHS
Compliant
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
• Follow safe electrical work practices. See NFPA 70E in the USA, or applicable local codes.
• This equipment must only be installed and serviced by qualified electrical personnel.
• Read, understand and follow the instructions before installing this product.
• Turn off all power supplying equipment before working on or inside the equipment.
• Any covers that may be displaced during the installation must be reinstalled before powering the unit.
• Use a properly rated voltage sensing device to confirm power is off. DO NOT DEPEND ON THIS PRODUCT FOR VOLTAGE INDICATION
Failure to follow these instructions will result in death or serious injury.
A qualied person is one who has skills and knowledge related to the construction and operation of this electrical equipment and the installation, and has received safety training to recognize and avoid the hazards involved. NEC2009 Article 100
No responsibility is assumed by Veris Industries for any consequences arising out of the use of this material.
Control system design must consider the potential failure modes of control paths and, for
certain critical control functions, provide a means to acheive a safe state during and after a path failure. Examples of critical control functions are emergency stop and over-travel stop.
TM
E50F2, E50F5
Compact Power and Energy Meters With LON TP/FT-10 Communication
Product Overview
The E50Fx DIN Rail Power Meter provides a solution for measuring energy data with a single device. Inputs include pulse, control power, CT, and 3-phase voltage. The E50Fx supports multiple output options, including solid state phase loss alarm relay contacts (E50F2 only), LON, and data logging (E50F5 only). The LCD screen on the faceplate allows instant output viewing.
The meter is housed in a plastic enclosure suitable for installation on T35 DIN rail according to EN50022. The E50 can be mounted with any orientation over the entire ambient temperature range, either on a DIN rail or in a panel. The meter is not sensitive to CT orientation to reduce installation errors.
Product Identification
Model Description
E50F2 LON output, 1 pulse input , alarm output
E50F5 LON output, data logging, 2 pulse inputs
Specifications
WARNING
LOSS OF CONTROL
∙ Assure that the system will reach a safe state during and after a control path failure. ∙ Separate or redundant control paths must be provided for critical control func tions. ∙ Test the eect of transmission delays or failures of communication links. ∙ Each implementation of equipment using communication links must be individually
and thoroughly tested for proper operation before placing it in service.
Failure to follow these instructions may cause injury, death or equipment damage.
1
For additional information about anticipated transmission delays or failures of the link, refer to
NEMA ICS 1.1 (latest edition). Safety Guidelins for the Application, Installation, and Maintenance of Solid-State Control or its equivalent in your specic country, language, and/or location.
NOTICE
• This product is not intended for life or safety applications.
• Do not install this product in hazardous or classified locations.
• The installer is responsible for conformance to all applicable codes.
• Mount this product inside a suitable fire and electrical enclosure.
FCC PART 15 INFORMATION NOTE: This equipment has been tested by the manufacturer and found to
comply with the limits for a class B digital device, pursuant to part 15 of
against harmful interference when the equipment is operated in a
radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. This device complies with part 15 of the FCC Rules.
Operation is subject to the following two conditions: (1) This device may not cause harmful interference, and (2) this device must accept any interference received, including interference that may cause undesired operation. Modifications to this product without the express authorization of the
manufacturer nullify this statement.
For use in a P ollution D egree 2 or be tter envi ronment on ly. A Pollutio n Degree 2 environment must control conductive pollution and the possibility of condensation or high hum idity. Cons ider the enc losure, th e correc t use of venti lation, the rmal prop erties of the equ ipment, an d the relati onship wi th the envir onment. In stallati on categor y: CAT II or CAT III. P rovide a di sconnec t device to di sconnec t the meter f rom the sup ply source. P lace this de vice in clos e proximit y to the equ ipment and w ithin eas y reach of the oper ator, and mark i t as the disc onnecti ng device. T he disconn ecting de vice shall meet th e relevant r equireme nts of IEC 60 947-1 and IEC 60947-3 and sh all be suit able for the appl ication. I n the US and Can ada, discon nectin g fuse hold ers can be us ed. Provi de overcu rrent prot ection a nd discone cting dev ice for sup ply conduc tors wit h approved current limiting devices suitable for protecting the wiring. If the equipment is used in a manner n ot specie d by the manu facture r, the protec tion prov ided by the d evice may be impaired.
Real Power and Energy
1
Reactive Power and Energy
Current
Volta ge
Sample Rate
Data Update Rate
Type of Measurement
Measured AC Voltage
Metering Over-Range
Impedance
Frequency Range
CT Scaling
Measurement Input Range
Impedance
MEASUREMENT ACCURACY
IEC 620 53 -22 Class 0. 5S, A NSI C12.20 0.5%
IEC 620 53 -23 Class 2, 2%
0.4% (+ 0.015% per °C deviation from 25°C ) from 5% to 100% of range;
0.8% (+0.015% per °C deviation from 25°C ) from 1% to 5% of range
0.4% (+ 0.015% per °C deviation from 25°C ) from 90 V
2520 samples per second
1 sec
True RMS up to 1260 Hz ( 21st harmonic at 60 Hz); One to three phase AC system
INPUT VO LTAGE CHAR ACTER ISTIC S
Minimum 90 V
UL Maximums: 6 00 V
+20%
2.5 MΩ
45 to 65 Hz
INPUT CUR RENT CHA RACTERISTIC S
Primar y: Adjustable from 5 A to 32,00 0 A
0 to 0.333 VAC or 0 to 1.0 VAC (+20% over- range ), rated for use with Class 1 voltage inputs
10.6 kΩ (1/3 V mode) or 32.1 kΩ (1 V mode)
/5 M Ω
L-N
(156 V
L-N
) for stated accuracy;
L-L
(3 47 V
L-L
L-L
); CE Maximum: 300 V
L-N
L-N
ZL0108-0D Page 1 of 34 ©2013 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com 10131
Alta Labs, E nercept, Ensp ector, Hawkeye, Trus tat, Aerospo nd, Veris, and th e Veris ‘V’ log o are tradema rks or registe red tradema rks of Veris Ind ustries, L. L.C. in the USA and /or other countri es.
Other companies’ trademarks are hereby acknowledged to belong to their respective owners.
to 600 VAC
L-N
L-L
Installation Guide Power Monitoring EF, EF
TM
Specifications (cont.)
CONTROL POWER
AC
5 VA max.; 9 0 V min.;
UL Maximum: 6 00 V
DC*
3 W max.; U L and CE: 125 to 300 V DC
Ride Through Time
Pulse
Minimum Pul se Width
Alarm Contacts (E50F2 only)
Communication Port
Weight
IP Degree of Prote ction (IEC
60529)
Display Characteristics
Terminal Block Screw Torque
Terminal Block Wire Size
Mounting Rail
Operating Temperature
Storage Temperature
Humidity Range
Altitude of Operation
US and Canada
Dielectric Withstand
Conducted and Radiated
Emissions
Conducted and Radiated
Immunity
Agencies: US and Canada
(cULus)
* External DC current limiting is required. See fuse recommendations.
100 msec at 120 VAC
Solid -State or mechanical contacts (current less than 1 mA)
20 msec
N.C., static output; (30 VAC /DC, 100 mA max. @ 25°C, derate 0.56 mA per °C above 25°C )
2-wire, LO N TP/F T-10
MECHAN ICAL CHARACTE RISTIC S
0.62 lb ( 0. 28 kg)
IP40 front display; IP20 M eter
Back-lit blue LCD
0.37 ft-lb ( 0.5 N·m) nominal / 0.44 ft-lb ( 0.6 N· m) max.
24 to 14 AWG (0.2 to 2.1 mm2)
T35 ( 35mm) DIN Rail per EN50022
OPERATING ENVIRONMENT
-30° to 70° C (-22° to 158°F)
-4 0° to 85°C ( - 40 ° to 185°F)
<95% RH (non-condensing)
3 km max.
COMPLIANCE INFORMATION
CAT III; for distribution systems up to 347 V
CE
EN61010-1; CAT III; for distribution systems up to 300 V
Per UL 50 8, EN 61010
FCC par t 15 Class B, EN55 011/EN61000 Class B ( residential and light industrial)
EN61000 Class A (heavy industrial)
UL508 (open type device) /CSA 2 2.2 No. 14- 05
INP UT
OUTPUT
(3 47 V
L-L
); CE Maximum: 300 V
L-N
/60 0 VAC
L-N
L-N
L-L
L-N
ZL0108-0D Page 2 of 34 ©2013 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com 10131
Alta Labs, E nercept, Ensp ector, Hawkeye, Trus tat, Aerospo nd, Veris, and th e Veris ‘V’ log o are tradema rks or registe red tradema rks of Veris Ind ustries, L. L.C. in the USA and /or other countri es.
Other companies’ trademarks are hereby acknowledged to belong to their respective owners.
Installation Guide Power Monitoring EF, EF
TM
Table of Contents
Dimensions 4
Data Outputs 4
Product Diagram 5
Display Screen Diagram 5
Installation 6
Supported System Types 7
Wiring Symbols 7
Wiring 8
Control Power 9
Quick Setup Instructions 10
Pulse Contact Inputs 10
Solid State Output 11
LON Communications 11
User Interface Menu Abbreviations Dened 12
User Interface for Data Conguration 13
Alert/Reset Information 14
User Interface for Setup 15
Resources for Download 17
Using the LNS Plugin 17
Conguring and Commissioning Without the Plugin 24
Network Variables 25
Conguration Properties 30
Troubleshooting 34
China RoHS Compliance Information 34
ZL0108-0D Page 3 of 34 ©2013 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com 10131
Alta Labs, E nercept, Ensp ector, Hawkeye, Trus tat, Aerospo nd, Veris, and th e Veris ‘V’ log o are tradema rks or registe red tradema rks of Veris Ind ustries, L. L.C. in the USA and /or other countri es.
Other companies’ trademarks are hereby acknowledged to belong to their respective owners.
Installation Guide Power Monitoring EF, EF
TM
Dimensions
1.8”
(45mm)
1.9”
(48mm)
2.3”
(59mm)
1.5”
(39mm)
4.2”
(107mm)
3.6”
(91mm)
Bottom View (DIN Mount Option) Bottom View (Screw Mount Option)
2.4 “
(61 mm)
+
0.2 “
(4 mm)
3.6 “
(91 mm)
4.2 “
(107 mm)
3.9“
(99 mm)
4.3 “
(109 mm)
1.2 “
(31 mm)
++
0.3 “
(8 mm)
0.4 “
(10 mm)
Data Outputs
Full Data Set (FDS)
Power (kW) Energy (kWh) Congurable for CT & PT ratios, system type, and passwords Diagnostic alerts Current: 3-phase average Volts: 3-phase average Current: by phase Volts: by phase Line-Line and Line-Neutral Power: Real, Reactive, and Apparent 3-phase total and per phase Power Factor: 3-phase average and per phase Frequency Power Demand: Most Recent and Peak Demand Conguration: Fixed, Rolling Block, and External Sync Real Time Clock: user congurable
Data Logging (E50F5 only, includes all FDS outputs plus)
3 user congurable log buers: each buer holds 5760 32-bit entries (User congures which 3 data points are stored in these buers) User congurable logging interval (When congured for a 15 minute interval, each buer holds 60 days of data) Continuous and Single Shot logging modes: user selectable Auto write pause: read logs without disabling the meter’s data logging mode
ZL0108-0D Page 4 of 34 ©2013 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com 10131
Alta Labs, E nercept, Ensp ector, Hawkeye, Trus tat, Aerospo nd, Veris, and th e Veris ‘V’ log o are tradema rks or registe red tradema rks of Veris Ind ustries, L. L.C. in the USA and /or other countri es.
Other companies’ trademarks are hereby acknowledged to belong to their respective owners.
Installation Guide




Power Monitoring EF, EF
TM
Product Diagrams
Two 5-character rows of display text. Top row alphanumeric; Bottom row numeric only
The red Alarm LED lights when any of the 3 phase voltages drop below the selected threshold.
E50F2
IA
IB
X2 X1 X2 X1 X2 X1
(X2) A (X1) (X2) B (X1) (X2) C (X1)
1 or 0.333 VAC
CT Inputs
IC
Alarm Output
Pulse Input
+
L-N
- 300V
L-N
CONTROL POWER
0.1A 50/60 Hz
EMC Ground
Alarm Energy
VOLTAGE INPUTS CAT III 50/60 Hz
A B C N 1 2
VA
UL: 90V
- 600V
CE: 90V
L-N
L-L
VB
VC
Neutral
E50F5
IA
IB
IC
X2 X1 X2 X1 X2 X1
(X2) A (X1) (X2) B (X1) (X2) C (X1)
Pulse Input 1
Pulse Inputs
Pulse Input 2
SERVICE
LON FT
Control
LON FT
Shield
S
Power
Shield
Display Screen Diagram
1 2 S
SERVICE
+
Two 5-character rows of display text.
CT Inputs
1 or 0.333 VAC
Top row alphanumeric; Bottom row numeric only
Alarm Energy
The red Alarm LED lights when any of the 3 phase voltages drop below the
VOLTAGE INPUTS CAT III 50/60 Hz
UL: 90V
L-N
- 600V
CE: 90V
L-L
CONTROL POWER
- 300V
L-N
L-N
0.1A 50/60 Hz
selected threshold. The green Energy LED lights when the pulse 1 input contacts are active or closed.
A B C N 1 2
VA
VB
VC
Neutral
EMC Ground
Control
Power
LCD Screen: Buttons:
Screen Name or Units
Diagnostic Alert:
indicates that one or
more of the alarm
bits (Binary_Objects
1-15) are active.
Logo
Numeric Data
 
Tx Rx ERR
Alive Indicator
RS-485 Equipped Units Only: Transmit Data Receive Data Receive Data Error
(Left)
Back
(Up)
Select
+
(Right)
Next
(Down)
Select
ZL0108-0D Page 5 of 34 ©2013 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com 10131
Alta Labs, E nercept, Ensp ector, Hawkeye, Trus tat, Aerospo nd, Veris, and th e Veris ‘V’ log o are tradema rks or registe red tradema rks of Veris Ind ustries, L. L.C. in the USA and /or other countri es.
Other companies’ trademarks are hereby acknowledged to belong to their respective owners.
Installation Guide Power Monitoring EF, EF
TM
Installation
Disconnect power prior to installation.
Reinstall any covers that are displaced during the installation before powering the unit.
Mount the meter in an appropriate electrical enclosure near equipment to be monitored.
Do not install on the load side of a Variable Frequency Drive (VFD), aka Variable Speed Drive (VSD) or Adjustable Frequency Drive (AFD).
The meter can be mounted in two ways: on standard 35 mm DIN rail or screw-mounted to the interior surface of the enclosure.
A. DIN Rail Mounting
1. Attach the mounting clips to the underside of the housing by sliding them into the slots from the inside. The stopping pegs must face the housing, and the outside edge of the clip must be ush with the outside edge of the housing.
2. Snap the clips onto the DIN rail. See the diagram of the underside of the housing (below).
Clip flush with outside edge
Snap onto
Insert clips from inside
DIN rail
3. To reduce horizontal shifting across the DIN rail, use two Veris AV02 end stop clips.
B. Screw Mounting
1. Attach the mounting clips to the underside of the housing by sliding them into the slots from the outside. The stopping pegs must face the housing, and the screw hole must be exposed on the outside of the housing.
2. Use three #8 screws (not supplied) to mount the meter to the inside of the enclosure. See the diagram of the underside of the housing (below).
Insert clips from outside
Screw holes exposed for mounting
ZL0108-0D Page 6 of 34 ©2013 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com 10131
Alta Labs, E nercept, Ensp ector, Hawkeye, Trus tat, Aerospo nd, Veris, and th e Veris ‘V’ log o are tradema rks or registe red tradema rks of Veris Ind ustries, L. L.C. in the USA and /or other countri es.
Other companies’ trademarks are hereby acknowledged to belong to their respective owners.
Installation Guide Power Monitoring EF, EF
TM
Supported System Types
The meter has a number of dierent possible system wiring congurations (see Wiring Diagrams sec tion). To congure the meter, set the System Type via the User Interface, LON variable cpSystemType. The System Type tells the meter which of its current and voltage inputs are valid, which are to be ignored, and whether neutral is connec ted. Setting the correct System Type prevents unwanted energy accumulation on unused inputs, selects the formula to calculate the Theoretical Maximum System Power, and determines which phase loss algorithm is to be used. The phase loss algorithm is congured as a percentage of the Line-to-Line System Voltage (except when in System Type 10) and also calculates the expected Line to Neutral voltages for system types that have Neutral (12 & 40).
Values that are not valid in a particular System Type display as “----” on the User Interface or as QNAN in the LON variables.
CTs Voltage Connections System Type Phase Loss Measurements Wiring
Number of wires
Single-Phase Wiring
2 1 A 2 A, N L-N 10 1L + 1n AN 1
2 1 A 2 A, B L- L 11 2L AB 2
3 2 A, B 3 A, B, N L-L with N 12 2L + 1n AB AN, BN AN-BN 3
Three-Phase Wiring
3 3 A, B, C 3 A, B, C Delta 31 3L AB, BC, CA AB-BC-CA 4
4 3 A, B, C 4 A, B, C, N Grounded
Qty ID Qty ID Type LON variable cpSystemType User Interface:
SETUP>S SYS
40 3L + 1n AB, BC, CA AN, BN, CN AN-BN-CN &
Wye
VLL VLN Balance Diagram
AB-BC-CA
Diagram
number
5, 6
Wiring Symbols
To avoid distortion, use parallel wires for control power and voltage inputs.
The following symbols are used in the wiring diagrams on the following pages.
Symbol Description
Voltage Disconnect Switch
Fuse (installer is responsible for ensuring compliance with local requirements. No
fuses are included with the meter.)
Earth ground
X1
Current Transducer
Potential Transformer
Protection containing a voltage disconnect switch with a fuse or disconnect circuit
breaker. The protection device must be rated for the available short-circuit current at the connection point.
CAUTION
RISK OF EQUIPMENT DAMAGE
• This product is designed only for use with 1V or 0.33V current transducers (CTs).
• DO NOT USE CURRENT OUTPUT (e.g. 5A) CTs ON THIS PRODUCT.
• Failure to follow these instructions can result in overheating and permanent equipment damage.
ZL0108-0D Page 7 of 34 ©2013 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com 10131
Alta Labs, E nercept, Ensp ector, Hawkeye, Trus tat, Aerospo nd, Veris, and th e Veris ‘V’ log o are tradema rks or registe red tradema rks of Veris Ind ustries, L. L.C. in the USA and /or other countri es.
Other companies’ trademarks are hereby acknowledged to belong to their respective owners.
Installation Guide Power Monitoring EF, EF
TM
Wiring
WARNING
RISK OF ELECTRIC SHOCK OR PERMANENT EQUIPMENT DAMAGE
CT negative terminals are referenced to the meter’s neutral and may be at elevated voltages
· Do not contact meter terminals while the unit is connected
· Do not connect or short other circuits to the CT terminals
Failure to follow these instructions may cause injury, death or equipment damage.
Diagram 1: 1-Phase Line-to-Neutral 2- Wire
System 1 CT
N L1
Use System Type 10 (1L + 1n)
X1
X2
A B C N
White
Black
X1
A
X2 X1
B
X2 X1
C
X2
Diagram 3: 1-Phase Direct Voltage Connection 2 CT
N
L1 L2
Use System Type 12 (2L + 1n) Use System Type 31 (3L)
Diagram 2: 1-Phase Line-to-Line 2-Wire
L1 L2
X1
X2
Diagram 4: 3-Phase 3-Wire 3 CT no PT
L1 L2 L3
System 1 CT
Use System Type 11 (2L)
White
Black
A B C N
X1
A
X2 X1
B
X2 X1
C
X2
A B C N
X1
X2
X1
X2
White
Black
White
Black
X1
A
X2 X1
B
X2 X1
C
X2
Diagram 5: 3-Phase 4-Wire Wye Direct Voltage Input
Connection 3 CT
Use System Type 40 (3L + 1n)
L1N L2 L3
A B C N
X1
X2
X1
X2
X1
X2
White Black
White
Black
White
Black
X1
A
X2 X1
B
X2 X1
C
X2
A B C N
X1
X1
X2
X2
White
Black
White
X1
X2
Black
White
Black
X1
A
X2 X1
B
X2 X1
C
X2
Diagram 6: 3-Phase 4-Wire Wye Connection 3 CT
3 PT
Use System Type 40 (3L + 1n)
L1N L2 L3
A B C N
X1
X1
X2
X2
X1
X2
White Black
White
Black
White Black
X1
A
X2 X1
B
X2 X1
C
X2
ZL0108-0D Page 8 of 34 ©2013 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com 10131
Alta Labs, E nercept, Ensp ector, Hawkeye, Trus tat, Aerospo nd, Veris, and th e Veris ‘V’ log o are tradema rks or registe red tradema rks of Veris Ind ustries, L. L.C. in the USA and /or other countri es.
Other companies’ trademarks are hereby acknowledged to belong to their respective owners.
Installation Guide Power Monitoring EF, EF
TM
Control Power
Direct Connect Control Power (Line to Line)
L1
L2 L3
Line to Line from 90 VAC to 600 VAC (UL). In UL installations the lines may be oating (such as a delta). If any lines are tied to an
earth (such as a corner grounded del ta), see the Line to Neutral installation limits. In CE compliant installations, the lines must
be neutral (earth) referenced at less than 300 VAC
Direct Connect Control Power (DC Control Power)
1 2G
DC Control Power from 125 VDC to 300 VDC
(UL and CE max.)
Fuse Recommendations
Direct Connect Control Power (Line to Neutral)
1 2G
L-N
L1N L2 L3
Line to Neutral from 90 VAC to 347 VAC (UL) or 300 VAC (CE)
1 2G
Control Power Transformer (CPT) Connection
1 2G
L1N L2 L3
The Control Power Transformer may be wired L-N or L-L. Output to
meet meter input requirements
Keep the fuses close to the power source (obey local and national code requirements).
For selecting fuses and circuit breakers, use the following criteria:
• Select current interrupt capacity based on the installation category and fault current capability.
• Select over-current protection with a time delay.
• Select a voltage rating sucient for the input voltage applied.
• Provide overcurrent protection and disconnecting means to protect the wiring. For AC installations, use Veris AH02,
AH03, AH04, or equivalent. For DC installations, provide external circuit protec tion. Suggested: 0.5 A, time delay fuses.
• The earth connection (G) is required for electromagnetic compatibility (EMC) and is not a protective earth ground.
ZL0108-0D Page 9 of 34 ©2013 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com 10131
Alta Labs, E nercept, Ensp ector, Hawkeye, Trus tat, Aerospo nd, Veris, and th e Veris ‘V’ log o are tradema rks or registe red tradema rks of Veris Ind ustries, L. L.C. in the USA and /or other countri es.
Other companies’ trademarks are hereby acknowledged to belong to their respective owners.
Installation Guide Power Monitoring EF, EF
TM
Quick Setup Instructions
These instruc tions assume the meter is set to factory defaults. If it has been previously congured, check all optional values.
A. To Navigate to the Setup screens:
+
+
1. Press
or – repeatedly until SETUP screen appears.
2. Press to get to the PASWD screen.
+
3. Press to move through the digits. Use the
+
or – buttons to enter your password (the default is 00000).
4. Press to move to the rst Setup screen (S CT)
+
+
5. Use
or – to select the parameter screen you want to set.
+
6. After you set the parameters you want, use
+
or – to select the next Setup screen or to exit the Setup screens (return to
SETUP ).
B. To Enter the CT (Current Transducer) output voltage and CT size ranges:
1. Navigate to the S CT (Set Current Transducer) Setup screen (see section A above).
+
2. Press to go to the CT V screen. Use
1. 00).
3. Press to go to the CT SZ screen and through the digits. Use
the value and
4. Press to accept the value and go back to the S CT screen.
+
or – to select the voltage mode Current Transducer output voltage (default is
+
+
or – to select the CT size in amps (default is 100). accept
Pulse Contact Inputs
C. To Enter the service type to be monitored:
1. Navigate to the S SYS (Set System) Setup screen (see section A above).
+
2. Press to go to the SYSTM screen. Use
Press to go back to the S SYS screen.
For full setup instructions, see the conguration instructions on the following pages.
The E50F5 has two inputs with pulse accumulators for solid state or mechanical contacts in other sensors, such as water or gas ow meters. The E50F2 has one pulse input. These inputs are isolated from the measured circuits. The communication signals, including the shield terminal, are AC-coupled. Use with contacts that do not require current to remove oxidation.
Pulse Input
E50F5 only
4-10 VDC
nominal
+
Contacts
~10 kΩ
+
or – to select the conguration (see wiring diagrams - default is 3L-1N).
SComm
Output
Comm
Ground
Equivalent
Circuit
ZL0108-0D Page 10 of 34 ©2013 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com 10131
Alta Labs, E nercept, Ensp ector, Hawkeye, Trus tat, Aerospo nd, Veris, and th e Veris ‘V’ log o are tradema rks or registe red tradema rks of Veris Ind ustries, L. L.C. in the USA and /or other countri es.
Other companies’ trademarks are hereby acknowledged to belong to their respective owners.
Installation Guide
Red
Black
Gray
Use 14-24 gauge wire
Power Monitoring EF, EF
TM
Solid State Output
The E50F2 has one normally closed (N.C.) alarm output.* See the Setup section for conguration information.
Over-Current Protective Device**
(not supplied)
≤ 100 mA
Power So urce
~
=
3-30 VDC 6-3 0 VAC
S
Alarm
Pulse Comm
The solid state pulse outputs are rated for 30 VAC/DC nom.
The maximum load current is 100 mA at 25°C. Derate 0.56 mA per °C above 25°C.
* While the relay used for the Phase Loss contact is normally closed (contacts are closed when the meter is not powered), closure indicates the presence of an alarm; either loss of phase, when the meter is powered, or loss of power when the meter is not. The contacts are open when the meter is powered and no phase loss alarm conditions are present.
** The over-current protective device must be rated for the short circuit current at the connection point.
All pulse inputs/outputs and communication circuits are only intended to be connected to non-hazardous circuits (SELV or Class 2). Do not connect to hazardous voltages.
Lon TP/FT-10 Communications
• Use this meter in either Free Topology or Bus Topology LonWorks network congurations.
• Twisted pair connections to the meter are not polarity sensitive.
• Attach the meter at any point in a Free Topology conguration, but the total network cable length must be less than
500 meters.
• Free Topology congurations require one terminator (Echelon TP/FT-10 Free Topology Terminator or equivalent), which can be attached at any point in the network.
• In Bus Topology congurations, connect loads sequentially (in a daisy chain), except for stubs, which must be less than 3 meters in length. The total network cable length must be less than 2700 meters.
• Bus Topology congurations require two terminators (Echelon TP/FT -10 Free Topology Terminator or equivalent, one at at each end of the network.
• The Shield connection is not internally connected to the ground connection on the meter.
LON-FT Shield
For all terminals:
• When tightening terminals, apply the correct torque: 0.37 to 0.44 ft·lb (0.5-0.6 N·m).
• Use 14-24 gauge (2.1-0.2 mm2) wire.
0.37–0.44 ft•lb (0.5–0.6 N•m)
ZL0108-0D Page 11 of 34 ©2013 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com 10131