the user will be required to correct the interference at his own expense.
POWER MONITORING
E30
Panelboard Monitoring System
Other current sensor
strip sizes available.
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
• Follow safe electrical work practices. See NFPA 70E in the USA, or applicable local codes.
• This equipment must only be installed and serviced by qualified electrical personnel.
• Read, understand and follow the instructions before installing this product.
• Turn off all power supplying equipment before working on or inside the equipment.
• Use a properly rated voltage sensing device to confirm power is off.
DO NOT DEPEND ON THIS PRODUCT FOR VOLTAGE INDICATION
• Only install this product on insulated conductors.
Failure to follow these instructions will result in death or serious injury.
A qualied person is one who has skills and knowledge related to the construction and
operation of this electrical equipment and the installation, and has received safety
training to recognize and avoid the hazards involved. NEC2009 Article 100
No responsibility is assumed by Veris Industries for any consequences arising out of the
use of this material.
NOTICE
• This product is not intended for life or safety applications.
• Do not install this product in hazardous or classified locations.
• The installer is responsible for conformance to all applicable codes.
• Mount this product inside a suitable fire and electrical enclosure.
FCC PART 15 INFORMATION
NOTE: This equipment has been tested by the manufacturer and found
to comply with the limits for a class A digital device, pursuant to part
15 of the FCC Rules. These limits are designed to provide reasonable
protection against harmful interference when the equipment is
operated in a commercial environment. This equipment generates,
uses, and can radiate radio frequency energy and, if not installed and
used in accordance with the instruction manual, may cause harmful
interference to radio communications. Operation of this equipment in
a residential area is likely to cause harmful interference in which case
Modifications to this product without the express authorization of
Veris Industries nullify this statement.
INSTALLATION GUIDE
SPECIFICATIONS
Inputs:
Input Power 90-277VAC, 50/60 Hz
Accurac y:
Power/Energy IEC 62053-21 Class 1, ANSI C12.1-2008
Volt age ±0.5% of reading 90-277V line-to-neutral
Operation:
Sampling Frequency 2560 Hz
Update Rate 1.8 seconds (both panels)
Outputs:
Type Modbus RTU
Connection DIP switch-select able 2-wire or 4-wire, RS-485
Address DIP switch-select able address 1 to 247 (in pairs of 2)*
Baud Rate DIP switch-select able 9600, 19200, 38400
Parity DIP switch-selectable NONE, ODD, EVEN
Communication Format 8-data-bits, 1-start-bit, 1-stop -bit
Termination 5-position depluggable connector
(TX+ TX- SHIELD TX+/RX+ TX-/RX-)
Terminal Block Torque 4.4 to 5.3 in-lb (0.5 to 0.6 N-m)
Mechanical:
Ribbon Cable Suppor t 4 ft. (0.9 m) at ribbon cable ships standard;
up to 20 ft. (6 m) available
Environmental:
Operating Temperature Range 0° to 60°C (32° to 140°F) (<95% RH noncondensing)
Storage Temperature Range -40° to 70°C (-4 0° to 158°F)
Altitude of Operation 3000 m
Agency Approvals UL508, EN61010
Alta Labs, Ene rcept, Enspector, Hawk eye, Trustat, Aerospon d, Veris, and the Veris ‘V ’ logo are tradem arks or registe red trademarks o f Veris Industries, L .L.C. in the USA and/or ot her countries.
E30
TM
INSTALLATION GUIDE
PRODUCT IDENTIFICATION
Description
E30
A = Advanced
B = Interme diate
C = Basic
CT Option
0 = 100A, ¾" spacing
1 = 100A, 1" spacing
2 = 100A, 18 mm spacin g
# of CTs
24 = 2 strips wi th 12 sensors each*
36 = 2 strip s with 18 sensors each*
42 = 2 strips w ith 21 sensors each
48 = 4 stri ps with 12 senso rs each*
72 = 4 strip s with 18 sensors each*
84 = 4 stri ps with 21 sensors ea ch
* This option avai lable with
18 mm spacing only.
DIMENSIONS
Circuit Board and Mounting Bracket
3.9”
(100 mm)
8.3”
(211 mm)
7.9”
(200 mm)
4.8”
(122 mm)
5.8”
(146 mm)
QUICK INSTALL
Observe precautions for handling static sensitive
devices to avoid damage to the circuitry that
is not covered under the factory warranty.
Disconnect and lock out power. Use a properly rated
voltage sensing device to confirm the power is off.
1. Mount the current sensor strips adjacent to the breaker terminations.
2. Verify that the serial numbers on the current sensor strips match the
serial number on the data acquisition board.
3. Congure communication and addressing parameters using the DIP switches.
4. Mount the data acquisition board in the electrical enclosure.
5. Connect the current sensor strip cables to the main board, observing the 2-strip or
4-strip setup and their orientation (A or B) within the panel.
6. Wire the RS-485 communications.
7. Connect the CTs to the auxiliary inputs and connect them to the main conductors
in the enclosure (optional).
8. Wire the control power and voltage taps (E30A and E30B only).
9. Download the free E3x conguration tool from www.veris.com to commission the
device for operation.
PRODUCT OVERVIEW
The E30 Series Branch Current Monitor is a device designed to measure the current,
voltage, and energy consumption of up to 92 circuits (84 branch circuits, 2 3-phase
mains, 2 neutrals) on a single board. It increases the board’s current monitoring
capability by combining the functions of two boards into one device.
The E30 consists of a data acquisition board and up to four 21-unit current sensor
strips, with eight auxiliary inputs. The strips are mounted on each side of the panel
board along the termination points of each breaker. The conductor passes through
the appropriate current sensor before terminating at the breaker. Each strip transmits
the current data to the data acquisition board.
Ø = 0.2”
(5 mm)
3/4"
option,
21 C Ts
option,
21 C Ts
18 mm
option,
21 C Ts
18 mm
option,
18 C Ts
7.3”
(184 mm)
8.9”
(288 mm)
Solid-Core Current Sensor Strips
20.3” (516 mm)
1.3”
(33 mm)
2.0”
(50 mm)
0.4” (10 mm)
opening
1.2”
(30 mm)
1”
2.0”
(50 mm)
15.7” (399 mm)
2.0”
(50 mm)
1.3”
(32 mm)
0.4” (10 mm)
opening
1.7”
(43 mm)
1.3”
(32 mm)
16.4” (417 mm)
0.4” (10 mm)
opening
25.0” (635 mm)
0.4” (10 mm)
opening
0.7” (18 mm)
on center
0.7” (18 mm)
on center
slot: 0.25” x 0.5”
(7 x 13mm)
0.75” (19 mm)
on center
slot: 0.25” x 0.5”
(7 x 13mm)
1.0” (26 mm)
on center
Data is transmitted using an RS-485 Modbus protocol. Each data acquisition board
opening
12.3” (312 mm)
0.7” (18 mm)
on center
21.2”
(0.9 mm)
requires two addresses, one for each set of two current sensor strips and four
auxiliary inputs. Data is updated roughly every two seconds. As a circuit approaches
the user-dened threshold, the E30 activates the alarm indicators.
The E30A measures both current and power for the mains and branch circuits. The
E30B measures both current and power for the mains, and current only in each circuit.
The E30C measures current only for the mains and branch circuits.
Alta Labs, Ene rcept, Enspector, Hawk eye, Trustat, Aerospon d, Veris, and the Veris ‘V ’ logo are tradem arks or registe red trademarks o f Veris Industries, L .L.C. in the USA and/or ot her countries.
mm) ribbon cables are provided for easy connection of current sensor strips to
this point of the data acquisition board. The two connectors on the left are for
panelboard 1; the two on the right are for panelboard 2.
Connect current sensor strips to the correct ribbon cable connectors for each
panel. The top connector is for Strip A, and the bottom conector is for Strip B.
Verify that the serial numbers on the current sensor strips match the
serial number on the data acquisition board.
2. Auxiliary Inputs: These 0.333 VAC inputs are used for monitoring the main
breaker or other high amperage source. Inputs on the lef t are for panelboard 1;
inputs on the right are for panelboard 2.
3. Control (Mains) Power Connection: Easy 2-wire 90-277 VAC 50/60 Hz
connection.
4. Control Power Fuse: 600 VAC, 500 mA time lag, factory-replaceable.
5. Alive LED: Red/green/amber LEDs. Blink codes are on page 3.
7
2
12
11
10
9
13
DATA OUTPUT
Monitoring at MainsE30AE30BE30C
Current per phase
Max. current per phase
Current demand per phase
Max. current demand per phase
Energy (kWh) per phase
Real Power (kW) per phase
Apparent Power (kVA)
Power factor total *
Power factor per phase
Voltage - L-L and average
Voltage - L-N and average
Frequency (phase A)
Monitoring at Branch Circuit
Current
Max. current
Current demand
Max. current demand
Real power (kW)
Real power (kW) demand
Real power (kW) demand max.
Energy (kWh) per circuit
Power factor
Apparent Power (kVA)
Modbus Alarms
Voltage over/under
Current over/under
6. Voltage Taps: 1, 2, or 3 phase plus neutral connections. For voltage sensing and
* Based on a 3-phase breaker rotation.
power calculations (no voltage taps on the E30C).
7. Communications Address DIP Switches: Each Modbus device must have a
unique address. Switches are binary weighted. Lef t-most switch has a value of 1;
right-most switch has a value of 128. Note: the 4-strip model uses 2 addresses.
Alta Labs, Ene rcept, Enspector, Hawk eye, Trustat, Aerospon d, Veris, and the Veris ‘V ’ logo are tradem arks or registe red trademarks o f Veris Industries, L .L.C. in the USA and/or ot her countries.
E30
TM
INSTALLATION GUIDE
INSTALLATION
Observe precautions for handling static sensitive
devices to avoid damage to the circuitry that
is not covered under the factory warranty.
Disconnect and lock out power to the electrical panel.
1. Install the current sensor strips in the panel (Figure 1).
2. Arrange the sensor strips in one of the four congurations shown in Figure 2.
Adjust orientation of the circuit numbers in the eld during commissioning by
writing to Modbus Register 6 or use free conguration software at www.veris.
com.
Figure 2
The examples in this g raphic show
the 21 current sensor strips strips.
The same conguration options a re
available for the 18 and 12 strips.
B
A
2
1
5
9
13
17
21
25
29
33
37
41
4
3
6
8
7
10
12
11
14
16
15
18
20
19
22
24
23
26
28
27
30
32
31
34
36
35
38
40
39
42
Top FeedBottom Feed
Panel 1
A
B
Panel 2
Register 6
Value = 0
(Default)
Figure 1
E30 CURRENT SENSOR STRIP
E30 CURRENT SENSOR STRIP
E30 CURRENT SENSOR STRIP
Current sensors accept a maximum #2 AWG
(0.384” O.D.) wire with THHN insulation.
Use this gauge wire or smaller for 100 A circuits .
Alta Labs, Ene rcept, Enspector, Hawk eye, Trustat, Aerospon d, Veris, and the Veris ‘V ’ logo are tradem arks or registe red trademarks o f Veris Industries, L .L.C. in the USA and/or ot her countries.
Panel 2
A
A
B
1
3
5
7
9
11
13
15
17
19
21
23
25
27
29
31
33
35
37
39
41
2
B
4
6
8
10
12
14
16
18
20
22
24
26
28
30
32
34
36
38
40
42
E30
TM
INSTALLATION GUIDE
3. Verify that the serial numbers printed on the current strip and on the data
acquisition board match. The board and the strip are sold as a calibrated set.
4. Congure communication and addressing parameters using DIP switches. The
E30 requires two addresses, one for each set of two current sensor strips and four
auxiliary inputs. See the Conguration section on page 7 for more information.
5. Install the E30 acquisition board mounting bracket in the panel using screws and
bolts provided (Figure 3). A grounding connection is located on the mounting
bracket, near the lower right corner. Use this stud to ground the bracket when it is
mounted on a nonconductive surface.
6. Check the labels on the current sensor strip and on the data acquisition board
to make sure the serial numbers match. Additionally, the label indicates which
connector to use on the data acquisition board (e.g. connect the strip labeled
“Panel 1A” to the top left connector on the board; Figure 4). When the device is
powered, if the current sensor strips are installed incorrectly, the Alive LED blinks
amber, three times per second. Check the labels and correct the connections.
Figure 4
Serial numbers on bo ard and strips must match.
Connect strips only to the connec tor designated
on the label (e.g. 1A).
Figure 3
Panel 1Panel 2
E30 CURRENT SENSOR STRIP
E30 CURRENT SENSOR STRIP
E30 CURRENT SENSOR STRIP
E30 CURRENT SENSOR STRIP
A
A
Panel 1Panel 2
BB
7. Connect current sensor ribbon cables to the 50-pin connectors on the main board
(Figures 5 and 6). Orient cables so that the red stripe is on the left.
Figure 5
Red Stripe
Align ribbon cable key with
connector keyhole.
Orient ribbon cable so that th e
red stripe is on the lef t side of
the connector.
Figure 6
2-Strip Version
A
B
Pane l 1
4-Strip Version
AA
BB
Pane l 2Pane l 1
Panel 2 MainsPanel 1 Mains
Panel 1 uses base Modbus address as set by DI P switches.
Panel 2 uses base + 1 Modbus address as set by DI P switches.
Alta Labs, Ene rcept, Enspector, Hawk eye, Trustat, Aerospon d, Veris, and the Veris ‘V ’ logo are tradem arks or registe red trademarks o f Veris Industries, L .L.C. in the USA and/or ot her countries.
E30
I1
I2
I3
IN
I1
I2
I3
IN
±
±
±
±
±
±
±
±
TM
8. Wire RS-485 communications (see diagrams in Wiring section).
9. Connect 0.333VAC CTs to the main conductors by snapping CTs around lines,
observing local codes regarding bending radius (optional; Figure 8).
10. Connect 2-wire 90-277VAC power to main power terminals. Observe polarity. For
the E30A and E30B, connect voltage lines to the voltage taps (Figure 8). Equip
voltage lines with fuses.
Figure 8
CT Input
(0 -0.333 VAC)
INSTALLATION GUIDE
Pane l 2Pane l 1
CT Input
(0 -0.333 VAC)
Figure 7
Panel 1Panel 2
E30 CURRENT SENSOR STRIP
E30 CURRENT SENSOR STRIP
Veris Industries H6810, H6811, H6812 Series with 0.333VAC output.
Call a Veris sales rep if higher amperages a re required.
Alta Labs, Ene rcept, Enspector, Hawk eye, Trustat, Aerospon d, Veris, and the Veris ‘V ’ logo are tradem arks or registe red trademarks o f Veris Industries, L .L.C. in the USA and/or ot her countries.
E30
RX+ TX+
+
TM
WIRING
Disconnect and lock out power before making any wiring connections.
Connect 2-wire or 4-wire Modbus RS-485 daisy chain network (Figures 10 and 11).
INSTALLATION GUIDE
Fig ure 10
SHIELD
RX- TX-
TXTX+
Fi gu re 11
2-Wire4-Wire
Master or Slave
TX+
TX-
RX+
TX+
SHIELD
RX-
TX–
SHLD
SHIELD
1. Mechanically secure the RS-485 cable where it enters the electrical panel.
2. Connect all RS-485 devices in a daisy-chain fashion, and properly terminate the
chain (Figure 12).
3. Shield the RS-485 cable using twisted-pair wire, such as Belden 1120A. Use cable
that is voltage-rated for the installation.
Fi gu re 12
TX+
Master
TX+
TX-
TX–
RX+
SHLD
RX-
SHIELD
TX+
Slave
TX+
TX-
TX–
RX+
SHLD
RX-
SHIELD
2-Wire Example
Belden 1120A or
equivalent
120 Ω terminator
on last device of
daisy chain
4. When tightening terminals, ensure that the correct torque is applied: 0.5 to 0.6
N·m (0.37 to 0.44 ft·lb ) for the connectors on data acquisition board, 0.22 to 0.26
N·m (0.16 to 0.19 ft·lb) for the connectors on the adapter boards (Figure 13).
WARNING: After wiring the RS-485 cable, remove all
scraps of wire or foil shield from the electrical panel.
Wire scraps coming into contact with high voltage
conductors could be DANGEROUS!
Alta Labs, Ene rcept, Enspector, Hawk eye, Trustat, Aerospon d, Veris, and the Veris ‘V ’ logo are tradem arks or registe red trademarks o f Veris Industries, L .L.C. in the USA and/or ot her countries.
E30
TM
CONFIGURATION
1. Communications Conguration: Communications parameters for the E30 series
are eld selectable for your convenience. Please see the Product Diagram section
(page 2) for selector location. The following parameters are congurable:
• Baud Rate: 9600, 19200, 38400
• Parity On or O
• Parity: odd or even
• Wiring: two or four
INSTALLATION GUIDE
3. The E30 uses two logical addresses. Panel 1 uses the base address as set on the DIP
switches, and Panel 2 uses this base address + 1. Address the E30 as any whole
number between and including 1-246. Each unit is equipped with a set of 8 DIP
switches for addressing. See below.
=
1
LSBMSB
Bø
B1
Off/
On
Parity
Odd/
Even
Parity
2/4
Wire
Reserved
Example: 2-wire 19200 Baud No Parity (Default Only)
12345678
ooXXX9600
onoXXX1920 0
oonXXX38400
ononXXXReserved
ooXXXNo Parity
onoXXXOdd Parity
oonXXXNo Parity
ononXXXEven Parity
onXXX4-wire RS-
485
oXXX2-wire RS-
485
1 2 4 8 16 32 64 128
4. To determine an address, simply add the values of any switch that is on.
For example:
LSB
Switch number 4 has an ON Value of 8 and switch number 6 has an ON Value of 32.
(8 + 32 = 40). Therefore, the address for Panel 1 is 40, and the address for Panel 2 is
41.
See the Address Setup section (page 8) for a pictorial listing of the rst 63 switch
positions.
DIP Switch Values
=
40
MSB
DEFAULT DIP SWITCH SETTINGS
The E30 includes two DIP switches, as shown below. Switches are shown in their
default positions.
2. Address Conguration: Each Modbus device on a single network must have
a unique address. Set the switch block to assign a unique address before the
device is connected to the Modbus RS-485 network. If an address is selected that
conicts with another device, neither device will be able to communicate.
Alta Labs, Ene rcept, Enspector, Hawk eye, Trustat, Aerospon d, Veris, and the Veris ‘V ’ logo are tradem arks or registe red trademarks o f Veris Industries, L .L.C. in the USA and/or ot her countries.
Alta Labs, Ene rcept, Enspector, Hawk eye, Trustat, Aerospon d, Veris, and the Veris ‘V ’ logo are tradem arks or registe red trademarks o f Veris Industries, L .L.C. in the USA and/or ot her countries.
E30
TM
INSTALLATION GUIDE
COMMISSIONING
1. Reconnect power to the panel.
2. Congure installation mode using Modbus Register 6.
3. Congure CT scaling.
4. Congure alarms.
5. Congure demand.
Download the free E3x conguration tool from www.veris.com to commission the
device for operation.
RECOMMENDED ACCESSORIES
Part IDDescription
CBL008Flat ribbon cable, 50 x 28 AWG, 1.5 ft. (0.45 m)
CBL016Flat ribbon cable, 50 x 28 AWG, 4 ft. (1.2 m)
CBL017Flat ribbon cable, 50 x 28 AWG, 5 ft. (1.5 m)
CBL018Flat ribbon cable, 50 x 28 AWG, 6 ft. (1.8 m)
CBL019Flat ribbon cable, 50 x 28 AWG, 8 ft. (2.4 m)
CBL020Flat ribbon cable, 50 x 28 AWG, 10 ft. (3.0 m)
CBL021Flat ribbon cable, 50 x 28 AWG, 20 ft. (6.1 m)
CBL022Round ribbon cable, 50 x 28 AWG, 4 ft. (1.2 m)
CBL023Round ribbon cable, 50 x 28 AWG, 10 ft. (3 m)
CBL024Round ribbon cable, 50 x 28 AWG, 20 ft. (6 m)
CBL025Flat ribbon cable, 50 x 28 AWG, 2 m
CBL026Flat ribbon cable, 50 x 28 AWG, 4 m
CBL027Flat ribbon cable, 50 x 28 AWG, 6 m
CBL031Round ribbon cable, 50 x 28 AWG, 1.5 ft. (0.45 m)
CBL032Round ribbon cable, 50 x 28 AWG, 2.5 ft. (0.76 m)
AE001E3x MCB cover
AE006E30 CT repair kit
H8932/H8932Network Display
SAFETY
If Veris E30 products are used in installations with circuits higher than the product
ratings, the circuits must be kept segregated per UL508A Sec. 17.5.
Note: 277/480 VAC Wye connected (center grounded) power systems operate
within the 300 VAC line to neutral safety rating of the E3x series, and the
operational voltage limit (single-phase connection) as the line to neutral
voltage is 277 VAC in such power systems. Corner-grounded delta 480 VAC
systems would not qualif y, as the actual line to earth voltage is 480 VAC on
each leg, exceeding the E3x ratings.
Note: E3x internal circuitr y (cables and CTs) are not circuits as dened by
UL508A, as they do not extend beyond the E3x itself without further safety/
re isolation.
UL listed under standard 508 as an “open type device.”
Maximum ambient air temperature for use is 60°C.
The E30 Series must be installed in an appropriate electrical and re enclosure per
local regulations.
Installation categor y: CAT III
For use in a Pollution Degree 2 or better environment only.
A Pollution Degree 2 environment must control conductive pollution and the
possibility of condensation or high humidity. Consideration must be given to the
enclosure, the correct use of ventilation, thermal properties of the equipment and the
relationship with the environment.
If the equipment is used in a manner not specied by the manufacturer, the
protection provided by the device may be impaired.
IEC/EN 61010-1
This symbol indicates an electrical shock hazard exists.
Documentation must be consulted where this symbol is used on the
product.
Alta Labs, Ene rcept, Enspector, Hawk eye, Trustat, Aerospon d, Veris, and the Veris ‘V ’ logo are tradem arks or registe red trademarks o f Veris Industries, L .L.C. in the USA and/or ot her countries.
TM
TROUBLESHOOTING
ProblemSolution
Product is not communicating over Modbus daisy chain
RX LED is solid
The main board has a fast ashing amber light
The main board has a slow ashing amber light
The main board has a ashing green light
The main board is a ashing or solid red light
Power factor reading is not as expected
Current reading is not as expected, or reading is on dierent CT
number than expected
Current is reading zero, even when small currents are still owing
through circuit
E3x Cong Tool returns Modbus error on read/write
E30
• Check the unit Modbus address to ensure that each device on the daisy chain has a unique address.
• Check Parity.
• Check the communications wiring.
• Check that the daisy chain is properly terminated.
• Check for reversed polarity on Modbus comms.
• Check for sucient biasing on the Modbus bus. Modbus physical specication calls for 450-650 Ω biasing. This is
usually provided by the master.
• Check that the 1A and 1B CT strips are connected to the left top and left bottom ribbon cable connections; 2A and 2B
must be connected to the right top and right bottom ribbon cable connections (see illustrations in the product install).
• Verify ribbon cable connectors are inserted in the correct orientation.
• If cables are correct, reset main board to re-initialize product.
• Verify serial number on strips matches serial number on main board.
• One or more channels is clipping. This can be caused by a signal greater than 100 A or 277 V L-N, or by a signal with
high THD near the gain stage switching points (1.5 A and 10 A).
• Everything is wired properly and the main board has power.
• Light may be red briey while device powers up.
• If light is red for more the 60 sec. device has encountered a diagnostic event. Contact technical support.
• Verify voltage taps are connected in appropriate phase rotation.
• Verify strip conguration register matches actual strip installation.
• Verify phase rotation of breakers (rmware rev. 1.012 or higher allows for custom rotation if needed).
• Verify strip conguration register matches actual strip installation.
• Verify ribbon cable is fully seated and in the correct orientation.
• The product cuts o at 50 mA, and will set the reporting register to 0 mA for currents near or below this range.
• Verify using the latest release of E3x Cong Tool as older versions may not support all features in current product