POWER MONITORING
E30
Panelboard Monitoring System
Other current sensor
strip sizes available.
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
• Follow safe electrical work practices. See NFPA 70E in the USA, or applicable local codes.
• This equipment must only be installed and serviced by qualified electrical personnel.
• Read, understand and follow the instructions before installing this product.
• Turn off all power supplying equipment before working on or inside the equipment.
• Use a properly rated voltage sensing device to confirm power is off.
DO NOT DEPEND ON THIS PRODUCT FOR VOLTAGE INDICATION
• Only install this product on insulated conductors.
Failure to follow these instructions will result in death or serious injury.
A qualied person is one who has skills and knowledge related to the construction and
operation of this electrical equipment and the installation, and has received safety
training to recognize and avoid the hazards involved. NEC2009 Article 100
No responsibility is assumed by Veris Industries for any consequences arising out of the
use of this material.
NOTICE
• This product is not intended for life or safety applications.
• Do not install this product in hazardous or classified locations.
• The installer is responsible for conformance to all applicable codes.
• Mount this product inside a suitable fire and electrical enclosure.
FCC PART 15 INFORMATION
NOTE: This equipment has been tested by the manufacturer and found
to comply with the limits for a class A digital device, pursuant to part
15 of the FCC Rules. These limits are designed to provide reasonable
protection against harmful interference when the equipment is
operated in a commercial environment. This equipment generates,
uses, and can radiate radio frequency energy and, if not installed and
used in accordance with the instruction manual, may cause harmful
interference to radio communications. Operation of this equipment in
a residential area is likely to cause harmful interference in which case
Modifications to this product without the express authorization of
Veris Industries nullify this statement.
INSTALLATION GUIDE
SPECIFICATIONS
Inputs:
Input Power 90-277VAC, 50/60 Hz
Accurac y:
Power/Energy IEC 62053-21 Class 1, ANSI C12.1-2008
Volt age ±0.5% of reading 90-277V line-to-neutral
Operation:
Sampling Frequency 2560 Hz
Update Rate 1.8 seconds (both panels)
Outputs:
Type Modbus RTU
Connection DIP switch-select able 2-wire or 4-wire, RS-485
Address DIP switch-select able address 1 to 247 (in pairs of 2)*
Baud Rate DIP switch-select able 9600, 19200, 38400
Parity DIP switch-selectable NONE, ODD, EVEN
Communication Format 8-data-bits, 1-start-bit, 1-stop -bit
Termination 5-position depluggable connector
(TX+ TX- SHIELD TX+/RX+ TX-/RX-)
Terminal Block Torque 4.4 to 5.3 in-lb (0.5 to 0.6 N-m)
Mechanical:
Ribbon Cable Suppor t 4 ft. (0.9 m) at ribbon cable ships standard;
up to 20 ft. (6 m) available
Environmental:
Operating Temperature Range 0° to 60°C (32° to 140°F) (<95% RH noncondensing)
Storage Temperature Range -40° to 70°C (-4 0° to 158°F)
Altitude of Operation 3000 m
Agency Approvals UL508, EN61010
Alta Labs, Ene rcept, Enspector, Hawk eye, Trustat, Aerospon d, Veris, and the Veris ‘V ’ logo are tradem arks or registe red trademarks o f Veris Industries, L .L.C. in the USA and/or ot her countries.
E30
TM
INSTALLATION GUIDE
PRODUCT IDENTIFICATION
Description
E30
A = Advanced
B = Interme diate
C = Basic
CT Option
0 = 100A, ¾" spacing
1 = 100A, 1" spacing
2 = 100A, 18 mm spacin g
# of CTs
24 = 2 strips wi th 12 sensors each*
36 = 2 strip s with 18 sensors each*
42 = 2 strips w ith 21 sensors each
48 = 4 stri ps with 12 senso rs each*
72 = 4 strip s with 18 sensors each*
84 = 4 stri ps with 21 sensors ea ch
* This option avai lable with
18 mm spacing only.
DIMENSIONS
Circuit Board and Mounting Bracket
3.9”
(100 mm)
8.3”
(211 mm)
7.9”
(200 mm)
4.8”
(122 mm)
5.8”
(146 mm)
QUICK INSTALL
Observe precautions for handling static sensitive
devices to avoid damage to the circuitry that
is not covered under the factory warranty.
Disconnect and lock out power. Use a properly rated
voltage sensing device to confirm the power is off.
1. Mount the current sensor strips adjacent to the breaker terminations.
2. Verify that the serial numbers on the current sensor strips match the
serial number on the data acquisition board.
3. Congure communication and addressing parameters using the DIP switches.
4. Mount the data acquisition board in the electrical enclosure.
5. Connect the current sensor strip cables to the main board, observing the 2-strip or
4-strip setup and their orientation (A or B) within the panel.
6. Wire the RS-485 communications.
7. Connect the CTs to the auxiliary inputs and connect them to the main conductors
in the enclosure (optional).
8. Wire the control power and voltage taps (E30A and E30B only).
9. Download the free E3x conguration tool from www.veris.com to commission the
device for operation.
PRODUCT OVERVIEW
The E30 Series Branch Current Monitor is a device designed to measure the current,
voltage, and energy consumption of up to 92 circuits (84 branch circuits, 2 3-phase
mains, 2 neutrals) on a single board. It increases the board’s current monitoring
capability by combining the functions of two boards into one device.
The E30 consists of a data acquisition board and up to four 21-unit current sensor
strips, with eight auxiliary inputs. The strips are mounted on each side of the panel
board along the termination points of each breaker. The conductor passes through
the appropriate current sensor before terminating at the breaker. Each strip transmits
the current data to the data acquisition board.
Ø = 0.2”
(5 mm)
3/4"
option,
21 C Ts
option,
21 C Ts
18 mm
option,
21 C Ts
18 mm
option,
18 C Ts
7.3”
(184 mm)
8.9”
(288 mm)
Solid-Core Current Sensor Strips
20.3” (516 mm)
1.3”
(33 mm)
2.0”
(50 mm)
0.4” (10 mm)
opening
1.2”
(30 mm)
1”
2.0”
(50 mm)
15.7” (399 mm)
2.0”
(50 mm)
1.3”
(32 mm)
0.4” (10 mm)
opening
1.7”
(43 mm)
1.3”
(32 mm)
16.4” (417 mm)
0.4” (10 mm)
opening
25.0” (635 mm)
0.4” (10 mm)
opening
0.7” (18 mm)
on center
0.7” (18 mm)
on center
slot: 0.25” x 0.5”
(7 x 13mm)
0.75” (19 mm)
on center
slot: 0.25” x 0.5”
(7 x 13mm)
1.0” (26 mm)
on center
Data is transmitted using an RS-485 Modbus protocol. Each data acquisition board
opening
12.3” (312 mm)
0.7” (18 mm)
on center
21.2”
(0.9 mm)
requires two addresses, one for each set of two current sensor strips and four
auxiliary inputs. Data is updated roughly every two seconds. As a circuit approaches
the user-dened threshold, the E30 activates the alarm indicators.
The E30A measures both current and power for the mains and branch circuits. The
E30B measures both current and power for the mains, and current only in each circuit.
The E30C measures current only for the mains and branch circuits.
Alta Labs, Ene rcept, Enspector, Hawk eye, Trustat, Aerospon d, Veris, and the Veris ‘V ’ logo are tradem arks or registe red trademarks o f Veris Industries, L .L.C. in the USA and/or ot her countries.
mm) ribbon cables are provided for easy connection of current sensor strips to
this point of the data acquisition board. The two connectors on the left are for
panelboard 1; the two on the right are for panelboard 2.
Connect current sensor strips to the correct ribbon cable connectors for each
panel. The top connector is for Strip A, and the bottom conector is for Strip B.
Verify that the serial numbers on the current sensor strips match the
serial number on the data acquisition board.
2. Auxiliary Inputs: These 0.333 VAC inputs are used for monitoring the main
breaker or other high amperage source. Inputs on the lef t are for panelboard 1;
inputs on the right are for panelboard 2.
3. Control (Mains) Power Connection: Easy 2-wire 90-277 VAC 50/60 Hz
connection.
4. Control Power Fuse: 600 VAC, 500 mA time lag, factory-replaceable.
5. Alive LED: Red/green/amber LEDs. Blink codes are on page 3.
7
2
12
11
10
9
13
DATA OUTPUT
Monitoring at MainsE30AE30BE30C
Current per phase
Max. current per phase
Current demand per phase
Max. current demand per phase
Energy (kWh) per phase
Real Power (kW) per phase
Apparent Power (kVA)
Power factor total *
Power factor per phase
Voltage - L-L and average
Voltage - L-N and average
Frequency (phase A)
Monitoring at Branch Circuit
Current
Max. current
Current demand
Max. current demand
Real power (kW)
Real power (kW) demand
Real power (kW) demand max.
Energy (kWh) per circuit
Power factor
Apparent Power (kVA)
Modbus Alarms
Voltage over/under
Current over/under
6. Voltage Taps: 1, 2, or 3 phase plus neutral connections. For voltage sensing and
* Based on a 3-phase breaker rotation.
power calculations (no voltage taps on the E30C).
7. Communications Address DIP Switches: Each Modbus device must have a
unique address. Switches are binary weighted. Lef t-most switch has a value of 1;
right-most switch has a value of 128. Note: the 4-strip model uses 2 addresses.
Alta Labs, Ene rcept, Enspector, Hawk eye, Trustat, Aerospon d, Veris, and the Veris ‘V ’ logo are tradem arks or registe red trademarks o f Veris Industries, L .L.C. in the USA and/or ot her countries.
E30
TM
INSTALLATION GUIDE
INSTALLATION
Observe precautions for handling static sensitive
devices to avoid damage to the circuitry that
is not covered under the factory warranty.
Disconnect and lock out power to the electrical panel.
1. Install the current sensor strips in the panel (Figure 1).
2. Arrange the sensor strips in one of the four congurations shown in Figure 2.
Adjust orientation of the circuit numbers in the eld during commissioning by
writing to Modbus Register 6 or use free conguration software at www.veris.
com.
Figure 2
The examples in this g raphic show
the 21 current sensor strips strips.
The same conguration options a re
available for the 18 and 12 strips.
B
A
2
1
5
9
13
17
21
25
29
33
37
41
4
3
6
8
7
10
12
11
14
16
15
18
20
19
22
24
23
26
28
27
30
32
31
34
36
35
38
40
39
42
Top FeedBottom Feed
Panel 1
A
B
Panel 2
Register 6
Value = 0
(Default)
Figure 1
E30 CURRENT SENSOR STRIP
E30 CURRENT SENSOR STRIP
E30 CURRENT SENSOR STRIP
Current sensors accept a maximum #2 AWG
(0.384” O.D.) wire with THHN insulation.
Use this gauge wire or smaller for 100 A circuits .
Alta Labs, Ene rcept, Enspector, Hawk eye, Trustat, Aerospon d, Veris, and the Veris ‘V ’ logo are tradem arks or registe red trademarks o f Veris Industries, L .L.C. in the USA and/or ot her countries.
Panel 2
A
A
B
1
3
5
7
9
11
13
15
17
19
21
23
25
27
29
31
33
35
37
39
41
2
B
4
6
8
10
12
14
16
18
20
22
24
26
28
30
32
34
36
38
40
42
Loading...
+ 7 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.