Veris E30 Installation Instructions

TM
the user will be required to correct the interference at his own expense.
POWER MONITORING
E30
Panelboard Monitoring System
Other current sensor strip sizes available.
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
• Follow safe electrical work practices. See NFPA 70E in the USA, or applicable local codes.
• This equipment must only be installed and serviced by qualified electrical personnel.
• Read, understand and follow the instructions before installing this product.
• Turn off all power supplying equipment before working on or inside the equipment.
• Use a properly rated voltage sensing device to confirm power is off. DO NOT DEPEND ON THIS PRODUCT FOR VOLTAGE INDICATION
• Only install this product on insulated conductors.
Failure to follow these instructions will result in death or serious injury.
A qualied person is one who has skills and knowledge related to the construction and
operation of this electrical equipment and the installation, and has received safety training to recognize and avoid the hazards involved. NEC2009 Article 100
No responsibility is assumed by Veris Industries for any consequences arising out of the
use of this material.
NOTICE
• This product is not intended for life or safety applications.
• Do not install this product in hazardous or classified locations.
• The installer is responsible for conformance to all applicable codes.
• Mount this product inside a suitable fire and electrical enclosure.
FCC PART 15 INFORMATION NOTE: This equipment has been tested by the manufacturer and found
to comply with the limits for a class A digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful interference in which case
Modifications to this product without the express authorization of Veris Industries nullify this statement.
INSTALLATION GUIDE
SPECIFICATIONS
Inputs:
Accurac y:
Power/Energy IEC 62053-21 Class 1, ANSI C12.1-2008 Volt age ±0.5% of reading 90-277V line-to-neutral
Operation:
Sampling Frequency 2560 Hz Update Rate 1.8 seconds (both panels)
Outputs:
Type Modbus RTU Connection DIP switch-select able 2-wire or 4-wire, RS-485 Address DIP switch-select able address 1 to 247 (in pairs of 2)* Baud Rate DIP switch-select able 9600, 19200, 38400 Parity DIP switch-selectable NONE, ODD, EVEN Communication Format 8-data-bits, 1-start-bit, 1-stop -bit Termination 5-position depluggable connector (TX+ TX- SHIELD TX+/RX+ TX-/RX-) Terminal Block Torque 4.4 to 5.3 in-lb (0.5 to 0.6 N-m)
Mechanical:
Ribbon Cable Suppor t 4 ft. (0.9 m) at ribbon cable ships standard; up to 20 ft. (6 m) available
Environmental:
Operating Temperature Range 0° to 60°C (32° to 140°F) (<95% RH noncondensing) Storage Temperature Range -40° to 70°C (-4 0° to 158°F) Altitude of Operation 3000 m Agency Approvals UL508, EN61010
* See Conguration section for de tails.
TABLE OF CONTENTS
Product Identication 2
Quick Install 2
Operation 2
Dimensions 2
Product Diagram 3
Data Output 3
Blink Codes for Status LED 3
Solid-Core Current Sensor Accuracy 3
Installation 4
Wiring 7
Conguration 8
Default DIP Switch Settings 8
Address Setup 9
Commissioning 10
Recommended Accessories 10
Safety 10
Troubleshooting 11
China RoHS Compliance Information (EFUP Table) 11
Z204998-0N PAGE 1 ©2013 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com 01131
Alta Labs, Ene rcept, Enspector, Hawk eye, Trustat, Aerospon d, Veris, and the Veris ‘V ’ logo are tradem arks or registe red trademarks o f Veris Industries, L .L.C. in the USA and/or ot her countries.
E30
TM
INSTALLATION GUIDE
PRODUCT IDENTIFICATION
Description
E30
A = Advanced B = Interme diate C = Basic
CT Option
0 = 100A, ¾" spacing 1 = 100A, 1" spacing 2 = 100A, 18 mm spacin g
# of CTs
24 = 2 strips wi th 12 sensors each* 36 = 2 strip s with 18 sensors each* 42 = 2 strips w ith 21 sensors each 48 = 4 stri ps with 12 senso rs each* 72 = 4 strip s with 18 sensors each* 84 = 4 stri ps with 21 sensors ea ch
* This option avai lable with 18 mm spacing only.
DIMENSIONS
Circuit Board and Mounting Bracket
3.9”
(100 mm)
8.3”
(211 mm)
7.9”
(200 mm)
4.8”
(122 mm)
5.8”
(146 mm)
QUICK INSTALL
Observe precautions for handling static sensitive devices to avoid damage to the circuitry that is not covered under the factory warranty.
Disconnect and lock out power. Use a properly rated voltage sensing device to confirm the power is off.
1. Mount the current sensor strips adjacent to the breaker terminations.
2. Verify that the serial numbers on the current sensor strips match the
serial number on the data acquisition board.
3. Congure communication and addressing parameters using the DIP switches.
4. Mount the data acquisition board in the electrical enclosure.
5. Connect the current sensor strip cables to the main board, observing the 2-strip or 4-strip setup and their orientation (A or B) within the panel.
6. Wire the RS-485 communications.
7. Connect the CTs to the auxiliary inputs and connect them to the main conductors in the enclosure (optional).
8. Wire the control power and voltage taps (E30A and E30B only).
9. Download the free E3x conguration tool from www.veris.com to commission the device for operation.
PRODUCT OVERVIEW
The E30 Series Branch Current Monitor is a device designed to measure the current, voltage, and energy consumption of up to 92 circuits (84 branch circuits, 2 3-phase mains, 2 neutrals) on a single board. It increases the board’s current monitoring capability by combining the functions of two boards into one device.
The E30 consists of a data acquisition board and up to four 21-unit current sensor strips, with eight auxiliary inputs. The strips are mounted on each side of the panel board along the termination points of each breaker. The conductor passes through the appropriate current sensor before terminating at the breaker. Each strip transmits the current data to the data acquisition board.
Ø = 0.2”
(5 mm)
3/4"
option,
21 C Ts
option,
21 C Ts
18 mm option,
21 C Ts
18 mm option,
18 C Ts
7.3”
(184 mm)
8.9”
(288 mm)
Solid-Core Current Sensor Strips
20.3” (516 mm)
1.3”
(33 mm)
2.0”
(50 mm)
0.4” (10 mm) opening
1.2”
(30 mm)
1”
2.0”
(50 mm)
15.7” (399 mm)
2.0”
(50 mm)
1.3”
(32 mm)
0.4” (10 mm) opening
1.7”
(43 mm)
1.3”
(32 mm)
16.4” (417 mm)
0.4” (10 mm) opening
25.0” (635 mm)
0.4” (10 mm) opening
0.7” (18 mm) on center
0.7” (18 mm) on center
slot: 0.25” x 0.5”
(7 x 13mm)
0.75” (19 mm) on center
slot: 0.25” x 0.5”
(7 x 13mm)
1.0” (26 mm) on center
Data is transmitted using an RS-485 Modbus protocol. Each data acquisition board
opening
12.3” (312 mm)
0.7” (18 mm) on center
21.2”
(0.9 mm)
requires two addresses, one for each set of two current sensor strips and four auxiliary inputs. Data is updated roughly every two seconds. As a circuit approaches the user-dened threshold, the E30 activates the alarm indicators.
The E30A measures both current and power for the mains and branch circuits. The E30B measures both current and power for the mains, and current only in each circuit. The E30C measures current only for the mains and branch circuits.
18 mm option,
12 C Ts
1.7”
(43 mm)
1.3”
(32 mm)
0.4” (10 mm)
Z204998-0N PAGE 2 ©2013 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com 01131
Alta Labs, Ene rcept, Enspector, Hawk eye, Trustat, Aerospon d, Veris, and the Veris ‘V ’ logo are tradem arks or registe red trademarks o f Veris Industries, L .L.C. in the USA and/or ot her countries.
21.2”
(0.9 mm)
21.2”
(0.9 mm)
1.75”
(45 mm)
1.1”
(28 mm)
0.8”
(20 mm)
1.2”
(31 mm)
0.8”
(20 mm)
E30
TM
INSTALLATION GUIDE
PRODUCT DIAGRAM
A A
1
B B
8
2
3
4
5
6
1. 50-Pin Ribbon Cable Connectors (Data Acquisition Board): 48-inch (1220
mm) ribbon cables are provided for easy connection of current sensor strips to this point of the data acquisition board. The two connectors on the left are for panelboard 1; the two on the right are for panelboard 2.
Connect current sensor strips to the correct ribbon cable connectors for each panel. The top connector is for Strip A, and the bottom conector is for Strip B.
Verify that the serial numbers on the current sensor strips match the serial number on the data acquisition board.
2. Auxiliary Inputs: These 0.333 VAC inputs are used for monitoring the main
breaker or other high amperage source. Inputs on the lef t are for panelboard 1; inputs on the right are for panelboard 2.
3. Control (Mains) Power Connection: Easy 2-wire 90-277 VAC 50/60 Hz
connection.
4. Control Power Fuse: 600 VAC, 500 mA time lag, factory-replaceable.
5. Alive LED: Red/green/amber LEDs. Blink codes are on page 3.
7
2
12
11
10
9
13
DATA OUTPUT
Monitoring at Mains E30A E30B E30C
Current per phase
Max. current per phase
Current demand per phase
Max. current demand per phase
Energy (kWh) per phase
Real Power (kW) per phase
Apparent Power (kVA)
Power factor total *
Power factor per phase
Voltage - L-L and average
Voltage - L-N and average
Frequency (phase A)
Monitoring at Branch Circuit
Current
Max. current
Current demand
Max. current demand
Real power (kW)
Real power (kW) demand
Real power (kW) demand max.
Energy (kWh) per circuit
Power factor
Apparent Power (kVA)
Modbus Alarms
Voltage over/under
Current over/under
6. Voltage Taps: 1, 2, or 3 phase plus neutral connections. For voltage sensing and
* Based on a 3-phase breaker rotation.
power calculations (no voltage taps on the E30C).
7. Communications Address DIP Switches: Each Modbus device must have a
unique address. Switches are binary weighted. Lef t-most switch has a value of 1; right-most switch has a value of 128. Note: the 4-strip model uses 2 addresses.
8. Communications Settings DIP Switch: Congures baud rate, parity, 2/4 wire
communications.
9. RS-485 2 Connection: Used for Modbus serial communications. The Universal
plug accomodates 2 or 4 wire connec tions.
BLINK CODES FOR STATUS LED
Color and Pattern Status Description
Green, once per second Normal operation
Amber, once per second Volts or Amps clipping
Amber, twice per second Invalid rmware image
Amber, three per second Incorrect strips or strip order
Red, solid or blink Diagnostic event detected
10. RS-485 LEDs: The RX LED (closest to DIP switches) indicates the RS-485
is receiving information; the TX LED (farthest from DIP switches) indicates transmission of information.
11. Power LED: Indicates power to main board
12. Current Sensors: Each current sensor is capable of monitoring conductors rated
up to a maximum of 100 amps.
13. 50 Pin Ribbon Cable Connectors (Current Sensor Strips): Connects current
SOLID-CORE CURRENT SENSOR ACCURACY
100A Solid-Core CT
Voltage Rating 300 VAC
Accuracy ±0.5%
Temperature 0° to 60°C
Agency UL508 recognized, EN61010
signal from the sensor strip to the main board via the ribbon connectors.
Z204998-0N PAGE 3 ©2013 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com 01131
Alta Labs, Ene rcept, Enspector, Hawk eye, Trustat, Aerospon d, Veris, and the Veris ‘V ’ logo are tradem arks or registe red trademarks o f Veris Industries, L .L.C. in the USA and/or ot her countries.
E30
TM
INSTALLATION GUIDE
INSTALLATION
Observe precautions for handling static sensitive devices to avoid damage to the circuitry that is not covered under the factory warranty.
Disconnect and lock out power to the electrical panel.
1. Install the current sensor strips in the panel (Figure 1).
2. Arrange the sensor strips in one of the four congurations shown in Figure 2. Adjust orientation of the circuit numbers in the eld during commissioning by writing to Modbus Register 6 or use free conguration software at www.veris. com.
Figure 2
The examples in this g raphic show the 21 current sensor strips strips. The same conguration options a re available for the 18 and 12 strips.
B
A
2
1
5
9
13
17
21
25
29
33
37
41
4
3
6
8
7
10
12
11
14
16
15
18
20
19
22
24
23
26
28
27
30
32
31
34
36
35
38
40
39
42
Top Feed Bottom Feed
Panel 1
A
B
Panel 2
Register 6 Value = 0
(Default)
Figure 1
E30 CURRENT SENSOR STRIP
E30 CURRENT SENSOR STRIP
E30 CURRENT SENSOR STRIP
Current sensors accept a maximum #2 AWG
(0.384” O.D.) wire with THHN insulation.
Use this gauge wire or smaller for 100 A circuits .
B
A
2
1
A
5
B
9
13
17
21
25
29
33
37
41
4
3
6
8
7
10
12
11
14
16
15
18
20
19
22
24
23
26
28
27
30
32
31
34
36
35
38
40
39
42
3
7
11
15
19
23
27
31
35
39
E30 CURRENT SENSOR STRIP
B
1
5
9
13
17
21
25
29
33
37
41
20
2020202020202020
20
20202020202020202020
20
Register 6 Value = 1
Panel 2
B
A
A
B
3
7
11
15
19
23
27
31
35
39
2
1
4
6
5
8
10
9
12
14
13
16
18
17
20
22
21
24
26
25
28
30
29
32
34
33
36
38
37
40
42
41
A
Panel 1
A
B
2
4
6
8
10
12
14
16
18
20
22
24
26
28
30
32
34
36
38
40
42
Single Row: Sequential Single Row: Odd/Even
A
2
4
6
8
10
12
14
16
18
20
22
B
24
26
28
30
32
34
36
38
40
42
Panel 1
A
1
B
3
5
7
9
11
13
15
17
19
21
23
25
27
29
31
33
35
37
39
41
Panel 2
Register 6 Value = 2
A
A
B
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
B
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
A
3
7
11
15
19
23
27
31
35
39
2
B
6
10
14
18
22
26
30
34
38
42
Panel 1
A
1
B
5
9
13
17
21
25
29
33
37
41
4
8
12
16
20
24
28
32
36
40
Register 6 Value = 3
Z204998-0N PAGE 4 ©2013 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com 01131
Alta Labs, Ene rcept, Enspector, Hawk eye, Trustat, Aerospon d, Veris, and the Veris ‘V ’ logo are tradem arks or registe red trademarks o f Veris Industries, L .L.C. in the USA and/or ot her countries.
Panel 2
A
A
B
1
3
5
7
9
11
13
15
17
19
21
23
25
27
29
31
33
35
37
39
41
2
B
4
6
8
10
12
14
16
18
20
22
24
26
28
30
32
34
36
38
40
42
E30
TM
INSTALLATION GUIDE
3. Verify that the serial numbers printed on the current strip and on the data acquisition board match. The board and the strip are sold as a calibrated set.
4. Congure communication and addressing parameters using DIP switches. The E30 requires two addresses, one for each set of two current sensor strips and four auxiliary inputs. See the Conguration section on page 7 for more information.
5. Install the E30 acquisition board mounting bracket in the panel using screws and bolts provided (Figure 3). A grounding connection is located on the mounting bracket, near the lower right corner. Use this stud to ground the bracket when it is mounted on a nonconductive surface.
6. Check the labels on the current sensor strip and on the data acquisition board to make sure the serial numbers match. Additionally, the label indicates which connector to use on the data acquisition board (e.g. connect the strip labeled “Panel 1A” to the top left connector on the board; Figure 4). When the device is powered, if the current sensor strips are installed incorrectly, the Alive LED blinks amber, three times per second. Check the labels and correct the connections.
Figure 4
Serial numbers on bo ard and strips must match.
Connect strips only to the connec tor designated on the label (e.g. 1A).
Figure 3
Panel 1 Panel 2
E30 CURRENT SENSOR STRIP
E30 CURRENT SENSOR STRIP
E30 CURRENT SENSOR STRIP
E30 CURRENT SENSOR STRIP
A
A
Panel 1 Panel 2
B B
7. Connect current sensor ribbon cables to the 50-pin connectors on the main board (Figures 5 and 6). Orient cables so that the red stripe is on the left.
Figure 5
Red Stripe
Align ribbon cable key with
connector keyhole.
Orient ribbon cable so that th e
red stripe is on the lef t side of
the connector.
Figure 6
2-Strip Version
A B
Pane l 1
4-Strip Version
A A
B B
Pane l 2Pane l 1
Panel 2 MainsPanel 1 Mains
Panel 1 uses base Modbus address as set by DI P switches.
Panel 2 uses base + 1 Modbus address as set by DI P switches.
Z204998-0N PAGE 5 ©2013 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com 01131
Alta Labs, Ene rcept, Enspector, Hawk eye, Trustat, Aerospon d, Veris, and the Veris ‘V ’ logo are tradem arks or registe red trademarks o f Veris Industries, L .L.C. in the USA and/or ot her countries.
E30
I1
I2
I3
IN
I1
I2
I3
IN
±
±
±
±
±
±
±
±
TM
8. Wire RS-485 communications (see diagrams in Wiring section).
9. Connect 0.333VAC CTs to the main conductors by snapping CTs around lines, observing local codes regarding bending radius (optional; Figure 8).
10. Connect 2-wire 90-277VAC power to main power terminals. Observe polarity. For the E30A and E30B, connect voltage lines to the voltage taps (Figure 8). Equip voltage lines with fuses.
Figure 8
CT Input
(0 -0.333 VAC)
INSTALLATION GUIDE
Pane l 2Pane l 1
CT Input
(0 -0.333 VAC)
Figure 7
Panel 1 Panel 2
E30 CURRENT SENSOR STRIP
E30 CURRENT SENSOR STRIP
Veris Industries H6810, H6811, H6812 Series with 0.333VAC output.
Call a Veris sales rep if higher amperages a re required.
E30 CURRENT SENSOR STRIP
E30 CURRENT SENSOR STRIP
Recommended CT:
Available in 100A max. to 2400A max.
Set up Modbus registers 115-118 for CT scaling.
Use base + 1 address for Panel 2 setup.
Figure 9
V2/N
90 -277 VAC
V1
V1 V2 V3 N
L - L L - N
Line to Line (L-L) Voltage: 150 to 480 VAC
Line to Neutral (L-N) voltage: 90 to 277 VAC
Voltage taps are shared by both panels.
Z204998-0N PAGE 6 ©2013 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com 01131
Alta Labs, Ene rcept, Enspector, Hawk eye, Trustat, Aerospon d, Veris, and the Veris ‘V ’ logo are tradem arks or registe red trademarks o f Veris Industries, L .L.C. in the USA and/or ot her countries.
E30
RX+ TX+
+
TM
WIRING
Disconnect and lock out power before making any wiring connections.
Connect 2-wire or 4-wire Modbus RS-485 daisy chain network (Figures 10 and 11).
INSTALLATION GUIDE
Fig ure 10
SHIELD RX- TX-
TX­TX+
Fi gu re 11
2-Wire 4-Wire
Master or Slave
TX+
TX-
RX+
TX+
SHIELD
RX-
TX–
SHLD
SHIELD
1. Mechanically secure the RS-485 cable where it enters the electrical panel.
2. Connect all RS-485 devices in a daisy-chain fashion, and properly terminate the chain (Figure 12).
3. Shield the RS-485 cable using twisted-pair wire, such as Belden 1120A. Use cable that is voltage-rated for the installation.
Fi gu re 12
TX+
Master
TX+
TX-
TX–
RX+
SHLD
RX-
SHIELD
TX+
Slave
TX+
TX-
TX–
RX+
SHLD
RX-
SHIELD
2-Wire Example
Belden 1120A or
equivalent
120 Ω terminator
on last device of
daisy chain
4. When tightening terminals, ensure that the correct torque is applied: 0.5 to 0.6 N·m (0.37 to 0.44 ft·lb ) for the connectors on data acquisition board, 0.22 to 0.26 N·m (0.16 to 0.19 ft·lb) for the connectors on the adapter boards (Figure 13).
WARNING: After wiring the RS-485 cable, remove all scraps of wire or foil shield from the electrical panel. Wire scraps coming into contact with high voltage conductors could be DANGEROUS!
Not Used
Fi gu re 13
– +
Z204998-0N PAGE 7 ©2013 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com 01131
Alta Labs, Ene rcept, Enspector, Hawk eye, Trustat, Aerospon d, Veris, and the Veris ‘V ’ logo are tradem arks or registe red trademarks o f Veris Industries, L .L.C. in the USA and/or ot her countries.
E30
TM
CONFIGURATION
1. Communications Conguration: Communications parameters for the E30 series are eld selectable for your convenience. Please see the Product Diagram section (page 2) for selector location. The following parameters are congurable:
• Baud Rate: 9600, 19200, 38400
• Parity On or O
• Parity: odd or even
• Wiring: two or four
INSTALLATION GUIDE
3. The E30 uses two logical addresses. Panel 1 uses the base address as set on the DIP switches, and Panel 2 uses this base address + 1. Address the E30 as any whole number between and including 1-246. Each unit is equipped with a set of 8 DIP switches for addressing. See below.
=
1
LSB MSB
Bø
B1
Off/
On
Parity
Odd/ Even
Parity
2/4
Wire
Reserved
Example: 2-wire 19200 Baud No Parity (Default Only)
1 2 3 4 5 6 7 8
o o X X X 9600
on o X X X 1920 0
o on X X X 38400
on on X X X Reserved
o o X X X No Parity
on o X X X Odd Parity
o on X X X No Parity
on on X X X Even Parity
on X X X 4-wire RS-
485
o X X X 2-wire RS-
485
1 2 4 8 16 32 64 128
4. To determine an address, simply add the values of any switch that is on.
For example:
LSB
Switch number 4 has an ON Value of 8 and switch number 6 has an ON Value of 32.
(8 + 32 = 40). Therefore, the address for Panel 1 is 40, and the address for Panel 2 is
41.
See the Address Setup section (page 8) for a pictorial listing of the rst 63 switch positions.
DIP Switch Values
=
40
MSB
DEFAULT DIP SWITCH SETTINGS
The E30 includes two DIP switches, as shown below. Switches are shown in their default positions.
2. Address Conguration: Each Modbus device on a single network must have a unique address. Set the switch block to assign a unique address before the device is connected to the Modbus RS-485 network. If an address is selected that conicts with another device, neither device will be able to communicate.
Comms Address Comms Settings
Z204998-0N PAGE 8 ©2013 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com 01131
Alta Labs, Ene rcept, Enspector, Hawk eye, Trustat, Aerospon d, Veris, and the Veris ‘V ’ logo are tradem arks or registe red trademarks o f Veris Industries, L .L.C. in the USA and/or ot her countries.
ADDRESS SETUP
E30
TM
INSTALLATION GUIDE
DO NOT
USE ZERO
1 2 3 4 5 6 7 8 9 10
11 12 13 14 15 16 17 18 19 20 21
22 23 24 25 26 27 28 29 30 31 32
33 34 35 36 37 38 39 40 41 42 43
44 45 46 47 48 49 50 51 52 53 54
55 56 57 58 59 60 61 62 63 246
......
Z204998-0N PAGE 9 ©2013 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com 01131
Alta Labs, Ene rcept, Enspector, Hawk eye, Trustat, Aerospon d, Veris, and the Veris ‘V ’ logo are tradem arks or registe red trademarks o f Veris Industries, L .L.C. in the USA and/or ot her countries.
E30
TM
INSTALLATION GUIDE
COMMISSIONING
1. Reconnect power to the panel.
2. Congure installation mode using Modbus Register 6.
3. Congure CT scaling.
4. Congure alarms.
5. Congure demand.
Download the free E3x conguration tool from www.veris.com to commission the device for operation.
RECOMMENDED ACCESSORIES
Part ID Description
CBL008 Flat ribbon cable, 50 x 28 AWG, 1.5 ft. (0.45 m)
CBL016 Flat ribbon cable, 50 x 28 AWG, 4 ft. (1.2 m)
CBL017 Flat ribbon cable, 50 x 28 AWG, 5 ft. (1.5 m)
CBL018 Flat ribbon cable, 50 x 28 AWG, 6 ft. (1.8 m)
CBL019 Flat ribbon cable, 50 x 28 AWG, 8 ft. (2.4 m)
CBL020 Flat ribbon cable, 50 x 28 AWG, 10 ft. (3.0 m)
CBL021 Flat ribbon cable, 50 x 28 AWG, 20 ft. (6.1 m)
CBL022 Round ribbon cable, 50 x 28 AWG, 4 ft. (1.2 m)
CBL023 Round ribbon cable, 50 x 28 AWG, 10 ft. (3 m)
CBL024 Round ribbon cable, 50 x 28 AWG, 20 ft. (6 m)
CBL025 Flat ribbon cable, 50 x 28 AWG, 2 m
CBL026 Flat ribbon cable, 50 x 28 AWG, 4 m
CBL027 Flat ribbon cable, 50 x 28 AWG, 6 m
CBL031 Round ribbon cable, 50 x 28 AWG, 1.5 ft. (0.45 m)
CBL032 Round ribbon cable, 50 x 28 AWG, 2.5 ft. (0.76 m)
AE001 E3x MCB cover
AE006 E30 CT repair kit
H8932/H8932 Network Display
SAFETY
If Veris E30 products are used in installations with circuits higher than the product ratings, the circuits must be kept segregated per UL508A Sec. 17.5.
Note: 277/480 VAC Wye connected (center grounded) power systems operate within the 300 VAC line to neutral safety rating of the E3x series, and the operational voltage limit (single-phase connection) as the line to neutral voltage is 277 VAC in such power systems. Corner-grounded delta 480 VAC systems would not qualif y, as the actual line to earth voltage is 480 VAC on each leg, exceeding the E3x ratings.
Note: E3x internal circuitr y (cables and CTs) are not circuits as dened by UL508A, as they do not extend beyond the E3x itself without further safety/ re isolation.
UL listed under standard 508 as an “open type device.”
Maximum ambient air temperature for use is 60°C.
The E30 Series must be installed in an appropriate electrical and re enclosure per local regulations.
Installation categor y: CAT III
For use in a Pollution Degree 2 or better environment only.
A Pollution Degree 2 environment must control conductive pollution and the possibility of condensation or high humidity. Consideration must be given to the enclosure, the correct use of ventilation, thermal properties of the equipment and the relationship with the environment.
If the equipment is used in a manner not specied by the manufacturer, the protection provided by the device may be impaired.
IEC/EN 61010-1
This symbol indicates an electrical shock hazard exists.
Documentation must be consulted where this symbol is used on the product.
Z204998-0N PAGE 10 ©2013 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com 01131
Alta Labs, Ene rcept, Enspector, Hawk eye, Trustat, Aerospon d, Veris, and the Veris ‘V ’ logo are tradem arks or registe red trademarks o f Veris Industries, L .L.C. in the USA and/or ot her countries.
TM
TROUBLESHOOTING
Problem Solution
Product is not communicating over Modbus daisy chain
RX LED is solid
The main board has a fast ashing amber light
The main board has a slow ashing amber light
The main board has a ashing green light
The main board is a ashing or solid red light
Power factor reading is not as expected
Current reading is not as expected, or reading is on dierent CT
number than expected
Current is reading zero, even when small currents are still owing
through circuit
E3x Cong Tool returns Modbus error on read/write
E30
Check the unit Modbus address to ensure that each device on the daisy chain has a unique address.
Check Parity.
Check the communications wiring.
Check that the daisy chain is properly terminated.
Check for reversed polarity on Modbus comms.
Check for sucient biasing on the Modbus bus. Modbus physical specication calls for 450-650 Ω biasing. This is
usually provided by the master.
Check that the 1A and 1B CT strips are connected to the left top and left bottom ribbon cable connections; 2A and 2B must be connected to the right top and right bottom ribbon cable connections (see illustrations in the product install).
Verify ribbon cable connectors are inserted in the correct orientation.
If cables are correct, reset main board to re-initialize product.
Verify serial number on strips matches serial number on main board.
One or more channels is clipping. This can be caused by a signal greater than 100 A or 277 V L-N, or by a signal with
high THD near the gain stage switching points (1.5 A and 10 A).
Everything is wired properly and the main board has power.
Light may be red briey while device powers up.
If light is red for more the 60 sec. device has encountered a diagnostic event. Contact technical support.
Verify voltage taps are connected in appropriate phase rotation.
Verify strip conguration register matches actual strip installation.
Verify phase rotation of breakers (rmware rev. 1.012 or higher allows for custom rotation if needed).
Verify strip conguration register matches actual strip installation.
Verify ribbon cable is fully seated and in the correct orientation.
The product cuts o at 50 mA, and will set the reporting register to 0 mA for currents near or below this range.
Verify using the latest release of E3x Cong Tool as older versions may not support all features in current product
rmware. Latest version is available on our website http://www.veris.com/modbus.aspx
INSTALLATION GUIDE
CHINA ROHS COMPLIANCE INFORMATION (EFUP TABLE)
产品中有毒有害物质或元素的名称及含量Substances
部件名称
铅 (Pb) 汞 (Hg) 镉 (Cd) 六价铬 (Cr(VI)) 多溴联苯(PBB) 多溴二苯醚(PBDE)
电子线路板 X O O O O O
O = 表示该有毒有害物质在该部件所有均质材料中的含量均在 SJ/T11363-2006 标准规定的限量要求以下. X = 表示该有毒有害物质至少在该部件的某一均质材料中的含量超出SJ/T11363-2006标准规定的限量要求.
Z000057-0A
Z204998-0N PAG E 11 ©2013 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com 01131