Veris CWV Installation Instructions

TM
4.6"
(116 mm)
3.3"
(84 mm)
1.4"
(36 mm)
(42 mm)
ENVIRONMENTAL SENSORS
CWV SerieS
Environmental CO2 Sensors
NOTICE
• This product is not intended for life or safety applications.
• Do not install this product in hazardous or classied locations.
• Read and understand the instructions before installing this product.
• Turn off all power supplying equipment before working on it.
• The installer is responsible for conformance to all applicable codes.
INSTALLATION GUIDE
Input Vol tage 20 to 30VDC, 24VAC Analog Output #1 4-20mA (clipped & capp ed) or 0-3VDC/0-5VDC/0-10VDC (jumper selectable) Analog Output #2 4-20mA (clipped & capp ed) or 0-3VDC/0-5VDC/0-10VDC (jumper selectable) Sensor Current Draw 200mA Maximum Operating Humidity Range 0-95% RH (noncondensing) Operating Temperature Range 0° to 50°C (32° to 122°F) Housing Material High impac t ABS plastic Relay Contac ts (optional) Form C (SPDT) 1A@30VDC, resistive; 30W ma x.
CO2 Transmitter:
Sensor Type Non-dispersive infrared (NDIR), diusion sampling Measurement Range 0-2000 ppm Accuracy ±40 ppm ±8.5% of measured value Repeatability ±30 ppm ±4.5% of measured value Response Time <60 seconds for 9 0% step change
EMC Conformance: EN 61000- 6-3:2007+A1:2011 Class B, EN 61000-6-1:2007 EMC Special Note: Connect this produc t to a DC distribution network or an AC/DC powe r adaptor with proper surge protection (EN 61000-6-1:2007 specication requirements). RTD/Thermistors are not compensated for internal heating of product.
No responsibility is assumed by Veris Industries for any consequences arising out of the
use of this material.
PRODUCT IDENTIFICATION
Temp/2nd
Output
CWVS
1 = 0-3/5/10VDC an d 4-20 mA 2 = 4-20mA and 4-2 0mA 3 = 0-3/5/10VDC and 0 -3/5/10VD C
MOUNTING
4.6"
(116 mm)
Relay option
X = No relay 1 = Relay
.64”
(16 mm)
Relay option
X = No temp. 1 = Relay B = 100R Pt C = 1k Pt D = 10k T2 E = 2.2k F = 3k H = 10k T3 J = 10k Dale K = 10k with 11kS M = 20k NTC N = 1800 ohm R = 10K US S = 10K 3A1B
3.3"
(84 mm)
Warranty
1 = 1 year 3 = 3 years 5 = 5 years
Housing
Blank = White / gray B = Black
INSTALLATION
1. Select a mounting location with good air circulation. For room installations, mount the sensor 4 ½ feet (1.4 m) above the oor.
2. Remove the cover. Flush mount the CWV on a wall or on a standard US or European single gang junction box.
3. Wire the device. Refer to the wiring diagram.
4. Install the cover.
DIMENSIONS
2.2"
(54 mm)
1.6"
.46"
(12 mm)
Z204905-0F PAGE 1 ©2013 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com 03131
Alta Labs, Ene rcept, Enspector, Hawk eye, Trustat, Aerospon d, Veris, and the Veris ‘V ’ logo are tradem arks or registe red trademarks o f Veris Industries, L .L.C. in the USA and/or ot her countries.
TM
NITROGEN
GAS
Regulator Valve
CW V SERIES
INSTALLATION GUIDE
WIRING
POWER SOURCE
20 to 30 VDC
or
24 VAC
DDC PANEL
COMMON
INPUT mA OR VOLTAGE
INPUT mA OR VOLTAGE
Power
Ground
Output #1
V OUT 1 Relay 2
10
5 3
V OUT 2 Relay 1
10
5 3
Relay 1 output (optional)
Relay 2/temp output (optional)
Output #2 mA or voltage
mA or voltage
Status 800 1000
Status 800 1000
Calibrate
CONFIGURATION
1. If so equipped, select the voltage outputs by jumpering the V Out 1 and/or V Out 2, as indicated at left (10=0-10VDC, 5=0-5VDC, 3=0-3VDC).
2. If so equipped, select the relay mode by jumpering the Relay 1 and/or Relay 2 function blocks, as indicated at left (Status=sensor condition, 800=800ppm CO2 setpoint, 1000=1000ppm CO2 setpoint).
LED INDICATION
Green - Power applied to device
Red - Error condition for false reading, CO2 concentration > 10,000 ppm, insucient power, or improperly calibrated sensor.
The red LED briey illuminates for approximately two seconds when the CWV device is initially powered. It then deluminates, indicating normal sensor operation.
OUTPUT SCALING
CO2 PPM 0-3 Volt Output 0-5 Volt Output 0-10 Volt Output mA Output
Outside 300-500 0.45 to 0.75 0.75 to 1.25 1.5 to 2.5 6.4 to 8
Over Ventilated Under 600 Under 0.9 Under 1.5 Under 3 Under 8.8
Ideal Ventilation 600-900 0.9 to 1.35 1.5 to 2.25 3 to 4.5 8.8 to 11.2
Under Ventilated Over 900 Over 1.35 Over 2.25 Over 4.5 Over 11.2
CALIBRATION PROCESS
1. Remove the cover and connect a hose to the plastic port located on the sensing module.
2. Begin nitrogen gas ow (0 ppm CO2). Use a ow rate of 0.3 to 0.5 liter/minute, using the Veris AA01 Calibration Kit or equivalent.
3. Push and hold down the calibration button for 8 seconds.
4. Release the calibration button and verif y that the analog outputs are at either 4 mA or 0 V. If the outputs are not showing these values, repeat steps 3 and 4.
STEP 1
Calibration Port
Connect hose here
STEP 2
Flow Nitrogen
STEP 3
Push and hold calibration button for 8 seconds
Calibration button
Veris AA01 Calibration Kit
(or equivalent)
Note: Do not breathe on the CO2 sensor during the calibration process.
Z204905-0F PAGE 2 ©2013 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com 03131