Veris CWE Datasheet

CDE & CWESERIES
Standard Duct and Wall CO2 Sensors
Field-Selectable
VERIS INDUSTRIES
CDE
4-20mA/0-10VDC Output
DESCRIPTION
The CDE and CWE are non-dispersive infrared (NDIR) sensors designed for measuring environmental CO2 concentration in ventilation systems and indoor living spaces. Their measurement range of 0-2000 ppm makes them compliant with ASHRAE and other standards for ventilation control
The CWE/CDE Series provides a user-selectable 4-20mA or 0-10VDC output for versatility. Microprocessor-based digital electronics and a unique self-calibration
algorithm improves long-term stability and accuracy.
APPLICATIONS
Controlling ventilation in response to occupancy
Facilitating compliance with ASHRAE 62.1 standard for air quality
Oce buildings, conference rooms, schools, retail stores, etc.
AIR QUALITY
CWE
FEATURES
Microprocessor-based design increases accuracy and reduces installation time
Non-dispersive infrared technology repeatable to ±20 ppm ±1% of
measured value...high accuracy measurements
Innovative self-calibration algorithm...easy to maintain
5-year calibration interval (recommended)
Low ambient sensitivity
Output 4-20mA/0-10V for exible control system interface
3-year factory warranty from date of purchase
Yea r
SPECIFICATIONS
Input Power 20 to 30VDC/24AC; 100mA Maximum Analog Output 4-20mA (clipped and capped)/0-10VDC (selectable) Operating Temperature Range 0° to 50°C (32° to 122°F) Operating Humidity Range 0 to 95% RH noncondensing Housing Material High impac t ABS plastic Sensor Type Non-dispersive infrared, diusion sampling Output Range 0-2000 ppm Accurac y ±30 ppm ±2% of measured value* Repeatability ±20 ppm ±1% of measured value Response Time <60 seconds for 90% s tep change
RTD/Thermistors in wall housings are not compensated for internal heating of product. EMC Conformance: Low voltage directive 2006/95/EC and EMC directive 2004/108/EC. EMC Special Note: Connect this product to a DC distribution network or an AC/DC power adaptor with proper surge protection (EN 61000-6-1:2007 specication requirements). * Measured at NTP
Note: Roug h handling and transpor tation may cause a temporary red uction of CO2 sensor accuracy. With time, th e ABC function will tune th e readings back to the correct accu racy range. The default tunin g speed is limited to 30 ppm per week.
800.354.8556
3
Warranty
+1 503.598.4564
www.veris.com
HQ00 0174 0.B 01131
800.354.8556
+1 503.598.4564
APPLICATION/WIRING DIAGRAMS
CWE Wall Mount
Power (+24)
CO2 OUT
COMMON
* Note: Connector blocks and h eaders for optional features are not included with non-option models.
N/A
Optional
RTD
RTD
*
DIMENSIONAL DRAWINGS
www.veris.com
CALIBRATION
PUSHBUTTON
LED
CDE Duct Mount
CO2-OUT
V+
GND
CONDUIT ADAPTER (included)
1/2” NPT MALE/FEMALE (included)
CWE Wall Mount
4.8"
(122 mm)
3.5"
(89 mm)
ORDERING INFORMATION
Duct Mount
CDE
(No O ptio ns)
CWE
1.2"
(30 mm)
all models
Wall Mount, Temp. Opti on
Sensor Type
SB = 100R Plati num, RTD SC = 1k Platinum, RTD SD = 10k T2, RTD, Therm istor SE = 2.2k, Ther mistor SF = 3k, Thermi stor SG = 10k CPC, Thermis tor SH = 10k T3, Thermis tor SJ = 10k Da le, Thermistor SK = 10k w/11k shunt, The rmistor SM = 20k NTC, Ther mistor SN = 1800 ohm, Th ermistor SR = 10k US, Thermistor SS = 10k 3A221, Thermist or ST = 100k, Ther mistor SU = 20k “D” The rmistor SW = 10k T2 high accuracy, Thermistor SY = 10k T3 high accuracy, Thermistor SZ = 10k E1, Thermistor
6.7"
(170 mm)
Housing
Blank = Cloud white B = Black
Examp le:
CWE SH B
CDE Duct Mount
10.2"
(258 mm)
3.1"
(78 mm)
2.4"
(61 mm)
7.8"
(97 mm)
Wall Mount, No Temp. Op tion
Housing
CWE
Blank = Cloud white B = Black
ACCESSORIES
Calibration kits and gases (AA01, AA26, AA27, AA28, AA29) Handheld air qua lity testers (1010, 1008, 770) Replacement covers for wall uni ts (AA51, AA51B) Replacement cloud white wall h ousing (AA55)
AA011010
AIR QUALITY
Examp le:
CWE B
AA51/AA51B
AA55
HQ00 0174 0.B 01131