CDE & CWESERIES
Standard Duct and Wall
CO2 Sensors
Field-Selectable
VERIS INDUSTRIES
CDE
4-20mA/0-10VDC Output
DESCRIPTION
The CDE and CWE are non-dispersive infrared (NDIR) sensors designed for measuring
environmental CO2 concentration in ventilation systems and indoor living spaces.
Their measurement range of 0-2000 ppm makes them compliant with ASHRAE and
other standards for ventilation control
The CWE/CDE Series provides a user-selectable 4-20mA or 0-10VDC output for
versatility. Microprocessor-based digital electronics and a unique self-calibration
algorithm improves long-term stability and accuracy.
APPLICATIONS
● Controlling ventilation in response to occupancy
● Facilitating compliance with ASHRAE 62.1 standard for air quality
● Oce buildings, conference rooms, schools, retail stores, etc.
AIR QUALITY
CWE
FEATURES
● Microprocessor-based design increases accuracy and reduces installation time
● Non-dispersive infrared technology repeatable to ±20 ppm ±1% of
measured value...high accuracy measurements
● Innovative self-calibration algorithm...easy to maintain
● 5-year calibration interval (recommended)
● Low ambient sensitivity
● Output 4-20mA/0-10V for exible control system interface
● 3-year factory warranty from date of purchase
Yea r
SPECIFICATIONS
Input Power 20 to 30VDC/24AC; 100mA Maximum
Analog Output 4-20mA (clipped and capped)/0-10VDC (selectable)
Operating Temperature Range 0° to 50°C (32° to 122°F)
Operating Humidity Range 0 to 95% RH noncondensing
Housing Material High impac t ABS plastic
Sensor Type Non-dispersive infrared, diusion sampling
Output Range 0-2000 ppm
Accurac y ±30 ppm ±2% of measured value*
Repeatability ±20 ppm ±1% of measured value
Response Time <60 seconds for 90% s tep change
RTD/Thermistors in wall housings are not compensated for internal heating of product.
EMC Conformance: Low voltage directive 2006/95/EC and EMC directive 2004/108/EC.
EMC Special Note: Connect this product to a DC distribution network or an AC/DC power adaptor with proper surge protection (EN 61000-6-1:2007 specication requirements).
* Measured at NTP
Note: Roug h handling and transpor tation may cause a temporary red uction of CO2 sensor accuracy. With time, th e ABC function will tune th e readings back to the correct accu racy range. The default tunin g speed is limited
to 30 ppm per week.
800.354.8556
3
Warranty
+1 503.598.4564
www.veris.com
HQ00 0174 0.B 01131
800.354.8556
+1 503.598.4564
APPLICATION/WIRING DIAGRAMS
CWE Wall Mount
Power (+24)
CO2 OUT
COMMON
* Note: Connector blocks and h eaders for optional
features are not included with non-option models.
N/A
Optional
RTD
RTD
*
DIMENSIONAL DRAWINGS
www.veris.com
CALIBRATION
PUSHBUTTON
LED
CDE Duct Mount
CO2-OUT
V+
GND
CONDUIT ADAPTER
(included)
1/2” NPT MALE/FEMALE
(included)
CWE Wall Mount
4.8"
(122 mm)
3.5"
(89 mm)
ORDERING INFORMATION
Duct Mount
CDE
(No O ptio ns)
CWE
1.2"
(30 mm)
all models
Wall Mount, Temp. Opti on
Sensor Type
SB = 100R Plati num, RTD
SC = 1k Platinum, RTD
SD = 10k T2, RTD, Therm istor
SE = 2.2k, Ther mistor
SF = 3k, Thermi stor
SG = 10k CPC, Thermis tor
SH = 10k T3, Thermis tor
SJ = 10k Da le, Thermistor
SK = 10k w/11k shunt, The rmistor
SM = 20k NTC, Ther mistor
SN = 1800 ohm, Th ermistor
SR = 10k US, Thermistor
SS = 10k 3A221, Thermist or
ST = 100k, Ther mistor
SU = 20k “D” The rmistor
SW = 10k T2 high accuracy, Thermistor
SY = 10k T3 high accuracy, Thermistor
SZ = 10k E1, Thermistor
6.7"
(170 mm)
Housing
Blank = Cloud white
B = Black
Examp le:
CWE SH B
CDE Duct Mount
10.2"
(258 mm)
3.1"
(78 mm)
2.4"
(61 mm)
7.8"
(97 mm)
Wall Mount, No Temp. Op tion
Housing
CWE
Blank = Cloud white
B = Black
ACCESSORIES
Calibration kits and gases (AA01, AA26, AA27, AA28, AA29)
Handheld air qua lity testers (1010, 1008, 770)
Replacement covers for wall uni ts (AA51, AA51B)
Replacement cloud white wall h ousing (AA55)
AA011010
AIR QUALITY
Examp le:
CWE B
AA51/AA51B
AA55
HQ00 0174 0.B 01131