Veris CW Installation Instructions

TM
ENVIRONMENTAL SENSORS
INSTALLATION GUIDE
CW SerieS CW SerieS
Wall Mounted Environmental CO2 Sensors
Input Vol tage 20 to 30VDC, 24VAC Analog Output CWL: 4-20mA (clipped and capped)/0-5VDC/0-10VDC (selectable) CWE: 4-20mA (clipped and capped)/0-10VDC (selectable); Sensor Current Draw 100mA max. Operating Temperature Range No humidity option: 0° to 50°C (32° to 122°F) With humidity o ption**: 10° to 35°C (50° to 95°F) Operating Humidity Range 0-95% (noncondensing) Housing Material High impac t ABS plastic
CWL
CWE
NOTICE
• This product is not intended for life or safety applications.
• Do not install this product in hazardous or classified locations.
• Read and understand the instructions before installing this product.
• Turn off all power supplying equipment before working on it.
• The installer is responsible for conformance to all applicable codes.
PRODUCT IDENTIFICATION
WALL DELUXE MODELS:
RH Option
CWL
S
H = RH 2% X = No RH
Options Available
Temp Cal Cert
X = No 1 = 1pt Temp Cal 2 = 2pt Temp Cal
WALL ECONOMY MODELS:
Sensor Type
S
CWE
B = 100R Platinu m, RTD C = 1k Platinum, RTD D = 10k T2, Therm . E = 2.2k, Ther m. F = 3k, Therm . G = 10k CPC, Ther m. H = 10k T3, Therm. J = 10k Dale, Ther m.
Z204903-0M PAGE 1 ©2011 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com 06114
Alta Labs, Enercep t, Enspector, Hawkeye, Trustat, Veris, and the Veris ‘ V’ logo are trademark s or registered tradema rks of Veris Industries, L.L .C. in the USA and /or other count ries.
Temp
Sensor Type
T = Temp X = No (stop here)
Setpoint Slider Value
Option
1 = Push But ton Override * 2 = Set Point Sli der 3 = Push But ton Override*+Set Point Slider
A = Transmitte r B = 100R Platinu m, RTD C = 1k Platinum, RTD D = 10k T2, Therm . E = 2.2k, Ther m. F = 3k, Therm . G = 10k CPC, Ther m. H = 10k T3, Therm.
A = 1k F = 10k G = 20k K = 50k M =10 0k
K = 10k w/11k shunt, Therm. M = 20k NTC, Ther m. N = 1800 ohm, Ther m. R = 10k US, Therm. S = 10k 3A221, Therm. T = 100k, The rm. U = 20k “D”, Therm.
* Note: the Pushbutto n Override feature is not avai lable with temperature transm itter models. Only resistive temp erature models qualify f or this feature.
J = 10k Dale, Ther m. K = 10k w/11k shunt, Therm. M = 20k NTC, Ther m. N = 1800 ohm, Ther m. R = 10k US, Therm. S = 10k 3A221, Therm. T = 100k, The rm. U = 20k “D”, Therm.
CO2 Transmitter: Sensor Type Non-dispersive infrared (NDIR), diusion sampling Output Range CWL: 0-2000 ppm or 0-5000 ppm, user select able; CWE: 0-2000 ppm Accuracy ±30 ppm ±2% of measured value* Repeatability ±20 ppm ±1% of measured value Response Time <60 seconds for 90% step change
RH Transmitter**: HS Sensor Digitally proled thin-lm capacitive (32-bit mathematics); U.S. Pa ten t 5, 84 4,138 Accuracy ±2% from 10 to 80% RH @ 25°C; Multi-point calibration NIST Hysteresis 1.5% typical Linearity Included in Accuracy spec. Stability ±1% @ 20°C (68°F) annually for two years Output Range 0-100% RH Temperature Coecient ±0.1% RH/°C above or below 25°C (typic al)
Temperature (Transmitter)**:
Sensor Type Thermistor Accuracy ±0.5°C (±1°F) typical Resolution 0.1°C (0.2°F) Output Range 10° to 35°C (50° to 95°F)
Relay Contacts**:
1 Form C (on models wit hout setpoint slider option) 1A@30VDC, resistive; 30W max.
Specied accuracy with 24VDC supplied power with rising humid ity. RTD/Thermistors in wall packages are not compensated for internal heating of product. EMC Conformance: EN 61000- 6-3:2001 Class B, EN 61000-6-1:2001, EN 61000-3-2:2000, EN 61000-3-3:2001 EMC Test Methods: CISPR 22:1997(Amended A9:2000, A2:2002), IEC 61000-4-2:2001, IEC 61000-4­3:2002, IEC 61000-4-4:2004, IEC 61000-4-5:2001, IEC 61000-4-6:2004, IEC 61000-4-8:2001, IEC 61000-4-11:2004. EMC Special Note: Connect this produc t to a DC distribution network or an AC/DC powe r adaptor with proper SURGE PROTECTION (EN 61000-6 -1:2001 specication requirements) * Measured at NTP ** Not available on CWE Note: Rough handling and transp ortation may cause a temporary reduction of CO2 sensor accuracy. With time, the ABC function will tun e the readings back to the correct accuracy range. The default tuning speed is li mited to 30 ppm per week.
QUICK INSTALL
1. Select a mounting location away from ventilation sources. The sensor should be mounted on a vertical wall, about 4 1/2 feet above the oor.
2. Ax the backplate to the wall.
3. Wire the device. Refer to wiring diagrams on page 2.
4. Install Cover.
TM
would not be covered under the factory warranty.
4.8"
(122 mm)
1.2"
(30 mm)
3.5"
(89 mm)
CW SERIES
INSTALLATION GUIDE
OPERATION
CW series wall mount CO2 sensors measure the levels of CO2, RH (if equipped), and temperature (if equipped) of air inside a duct. The CO2 sensor operates within accuracy specications for an interval of 5 years and can be eld calibrated. The temperature element is warranted to meet accuracy specications for a period of 5 years. RH equipped models feature a replaceable HS Series humidity element that is warranted to meet accuracy specications for a period of 1 year. To maintain accuracy, all vents must remain clear and free of dust, debris, etc.
DIMENSIONS
INSTALLATION
1. Remove the cover by pressing the tab at the top of the sensor while pulling outward from the top of the cover.
Observe handling precautions for static sensitive devices to avoid damage to the circuitry which
2. Remove the backplate by unfastening the sensor from the bottom of the backplate and pivoting the sensor outward.
3. Punch out desired wire openings in the backplate.
All optional connector blocks are shown here for clarity.
4. Position the sensor vertically on the wall, 4 1/2 feet above the oor. Locate away from windows, vents, and other sources of draft. If possible, do not mount on an external wall, as this might cause inaccurate temperature readings.
5. Mount the backplate onto the wall using the screws provided.
Five screwholes available; use a minimum of two for secure mounting.
All optional connec tor blocks are sho wn here for clarity.
Z204903-0M PAGE 2 ©2011 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com 06114
Alta Labs, Enercep t, Enspector, Hawkeye, Trustat, Veris, and the Veris ‘ V’ logo are trademark s or registered tradema rks of Veris Industries, L.L .C. in the USA and /or other count ries.
TM
CW SERIES
INSTALLATION GUIDE
6. Wire the backplate.
CWL with RH and Temperature Transmitter Options
PWR
COMMON
CO2 OUTPUT
CWL with RH, Thermistor/RTD, Pushbutton Override, and
RH OUTPUT
TEMP OUTPUT
RELAY N.O.
RELAY N.C.
COMMON
Setpoint Slider Options
+
POWER SUPPLY
20-30VDC, 24VAC
-
CONTROL SYSTEM
COMMON
-
CO2 INPUT RH INPUT
TEMP INPUT RELAY N.O. COMMON RELAY N.C.
Note: Connector blocks and h eaders for optional features are no t included with non-option models.
+
POWER SUPPLY
20-30VDC, 24VAC
-
7. Install the sensor onto the backplate.
8. Use the switch to select voltage or current output. For CWL model, see Conguration section on page 4.
9. When installation is complete, install the cover and snap into place.
VO LT
AMP
PWR
CO2 OUTPUT
COMMON
RH OUTPUT
RTD/THERMISTOR/OVERRIDE
RTD/THERMISTOR/OVERRIDE
SLIDER RIGHT
SLIDER LEFT
SLIDER WIPER
CWE
CONTROL SYSTEM
COMMON
-
CO2 INPUT RH INPUT
THERMISTOR/OVERRIDE INPUT
SETPOINT SLIDER INPUT
Note: Relay contacts not available in this conguration.
Note: Connector blocks and h eaders for optional features are no t included with non-option models.
+
POWER SUPPLY
20-30VDC, 24VAC
-
CONTROL SYSTEM
COMMON
-
CO2 INPUT
THERMISTOR/OVERRIDE INPUT
PWR
COMMON
CO2 OUTPUT
RTD/THERMISTOR/OVERRIDE
RTD/THERMISTOR/OVERRIDE
Z204903-0M PAGE 3 ©2011 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com 06114
Alta Labs, Enercep t, Enspector, Hawkeye, Trustat, Veris, and the Veris ‘ V’ logo are trademark s or registered tradema rks of Veris Industries, L.L .C. in the USA and /or other count ries.
TM
ABC Settings (CWE only)
CW SERIES
INSTALLATION GUIDE
ABC CALIBRATION ALGORITHM
ABC (Automatic Baseline Calibration) is a patented self-calibration feature that automatically adjusts the CO2 sensor to compensate for drift. When ABC is enabled, the sensor records the lowest reading within every 24-hour interval and compares these values over a running 7-day or 28-day period. If a statistically signicant amount of drift is detected, the ABC applies an automatic correction factor. This enables the sensor to operate within specications for the 5-year calibration interval.
ON POSITION. Recommended Setting. Use the ON setting for applications where the building is unoccupied within a 24-hour timeframe.
LOW POSITION. Use the LOW setting for buildings occupied 24 hours a day.
OFF POSITION. Not Recommended.
NOTE: After changing the ABC setti ngs, power cycle the unit for changes to take eect.
To set the ABC mode for CWL models, refer to the Conguration section on page 4.
To set the ABC mode for CWE models, position the ABC jumper as shown:
ON LOW
ON
LOW
OFF
ON
LOW
OFF
OFF
ON
LOW
OFF
OUTPUT SCALING
CO2 - Carbon Dioxide Sensor
Output scaling: 0-2000ppm
CO2 PPM 0-5 V Output 0-10 V Output mA
Output
Outside 300-500 0.75 to 1.25 1.5 to 2.5 6.4 to 8
Over Ventilated Under 600 under 1.5 Under 3 Under 8.8
Ideal Ventilation 600-900 1.5 to 2.25 3 to 4.5 8.8 to 11.2
Under Ventilated Over 900 over 2.25 Over 4.5 Over 11.2
RH - Relative Humidity Sensor
Output scaling: 0-100%
T - Temperature Transmitter
Output scaling: 10° to 35°C (50° to 95°F)
To determine temperature from output reading:
1. Compute Total Span from Temperature Range:
Maximum range - Minimum range = Total span ex. 10° to 35°C range: 35 - 10 = 25 Total span
2. Compute Output % of Span from Reading:
(Reading - Minimum Output) / (Maximum output - Minimum output) ex. 11.10 mA reading on 4-20 mA output: (11.10-4) / (20-4) = 7.10 / 16 =
0.444 = 44.4% ex. 4.44v reading on 0-10 V output: (4.44-0) / (10-0) = 4.44 / 10 = 0.444 =
44.4%
3. Compute Temperature:
(Total span x Output % of Span) + Minimum range ex. 44.4% Output, Total Span = 45, range = 50/95: (0.444 x 45) + 50 = 20 + 50 = 70°
Example outputs for selected temperatures:
Temp 4-20 mA 0-10 V 0-5 V
65 9.33 mA 3.33 V 1.67 V
70 11.10 mA 4.44 V 2.22 V
75 12.89 mA 5.56 V 2.78 V
Z204903-0M PAGE 4 ©2011 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com 06114
Alta Labs, Enercep t, Enspector, Hawkeye, Trustat, Veris, and the Veris ‘ V’ logo are trademark s or registered tradema rks of Veris Industries, L.L .C. in the USA and /or other count ries.
TM
PM
PM00150P
O.O
%R H
PM
˚F
XX
IT
ENAD
AM
BDOE
XXX
–+
–0
OU
V+
CX
OE
RX
.X
–+
CA
*:00
WN
XX
SA
CA
OU
CONFIGURATION - CWL ONLY
CW SERIES
INSTALLATION GUIDE
100
*
*INDICATES RELAY STATUS
0
7
XX.
X
CO2/RH/T COMBO MODEL
TOGGLE %RH AND DEGREES
RUN MODE:
0
CO2 ONLY MODEL
CO2/RH COMBO MODEL
0010
.
0
CO2/T COMBO MODEL
0010
P
CO2
P
PPM
X
CONFIGURATION MODE:
PRESS [ENTER] FOR CONFIGURATION MODE. PRESS PLUS OR MINUS TO CHANGE SETTING.
SPOT
E
O2C
RANGE 500 TO 1500
50PPM INC REMENT
80 0
DDBA
2CO 010
RANGE 10 TO 500
5 PPM INCREMENT
RGEN
A
CO
2
OPTIONS ARE 2000 OR 5000
X
C
XX +X
OPTIONS ARE ON, LOW, OFF
SEE PREVIO US PAGE FOR EXPLANATION
CALIBRATION MODE:
PUSH AND HOLD PLUS AND MINUS FOR 5 SECONDS TO ENTER MODE. PRESS ARROW TO CHANGE OPTION. PUSH ENTER FOR N EXT SELECTIO N.
N
E
R
XX
X
DISPLAYS SERIAL NUMBER
X
X
XX
XXX
DISPLAYS MO DEL NUMBER
F.XS
F
X
LI
XXX
T
º
RANGE IS -5 TO 5°C, 0.1°C INCREMENT
(CO2/temp combo models)
F
FO
%
RANGE -10 TO 10%, 0.1% INCREMENT
O
S
TE
HX
(CO2/temp combo models)
2
C
?
U
40
Z204903-0M PAGE 5 ©2011 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com 06114
Alta Labs, Enercep t, Enspector, Hawkeye, Trustat, Veris, and the Veris ‘ V’ logo are trademark s or registered tradema rks of Veris Industries, L.L .C. in the USA and /or other count ries.
N
SIXT
º
(TEMP MODELS ONLY)
OPTIONS ARE °F or °C
U
T
–1
0
(VOLTAGE MODE ONLY)
OPTIONS: 0-10V OR 0-5V
DEFAULT IS 0-10V
U
T
–2
(mA MODE ONLY)
m
TP
TP
A
X
XLX
OPTIONS ARE YES, NO
L
A
OPTIONS ARE NONE, 0, 400
RI
G
X
XSXX+
KO
?
G
5
Unit will automatically retu rn to run mode
when calibration is complete.
NOTE: This product is factory calibrated. The typical CO2 sensor calibration interval is 5 years , depending on specic site installation factors. A s of the date of this document, compliance with ANSI/ASHRAE 62-2001 requires minimu m on-site accuracy verication intervals of 6 months or per the building operation and maintenance manual. Verif y accuracy using a comparison to a known reference or the CO2 gas calibration kit available from Veris Industries as AA01.
WARNING: CO2 sensor calibration requires gas calibration kit. Performing calibration with out gas kit or at an incorrect gas ow rate will cause erroneous readings.
TM
NITROGEN
GAS
Regulator Valve
NITROGEN
GAS
Regulator Valve
CW SERIES
INSTALLATION GUIDE
CALIBRATION PROCESS: CWL MODELS
1. Remove cover and connect gas cylinder hose to the plastic port located on sensing module. Note: only connect one sensor to the calibration gas cylinder at a time.
800 PPM
70.0 ˚F
2. Start owing nitrogen gas (0 ppm CO2). Use a ow rate of 0.3 to 0.5 liter/minute.
Connect hose
here
CALIBRATION PROCESS: CWE MODELS
1. Remove cover and connect gas cylinder hose to the plastic port located on sensing module. Note: only connect one sensor to the calibration gas cylinder at a time.
LED
indicato r
Connec t
hose here
2. Start owing nitrogen gas (0 ppm CO2). Use a ow rate of 0.3 to 0.5 liter/minute.
3. Calibrate for 5 min. Unit will return to working display when nished.
800 PPM
70.0 ˚F
4. When unit returns to working display, remove hose from calibration port and enter Calibration mode as described on page 3.
3. Push and hold down calibration button until the LED illuminates.
LED indicato r
Connect hose here
Calibration
button
4. Continue owing gas through the sensor until the LED is o. Estimated calibration time is 5 minutes. Remove hose from calibration port when complete.
For more complete calibration instructions using the AA01 Calibration Kit, see the AA01 Installation Guide.
Z204903-0M PAGE 6 ©2011 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com 06114
Alta Labs, Enercep t, Enspector, Hawkeye, Trustat, Veris, and the Veris ‘ V’ logo are trademark s or registered tradema rks of Veris Industries, L.L .C. in the USA and /or other count ries.
Loading...