TM
ACCESSORIES
INSTALLATION GUIDE
AH07
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
• Follow safe electrical work practices. See NFPA 70E in the USA, or applicable local codes.
• This equipment must only be installed and serviced by qualied electrical personnel.
• Read, understand and follow the instructions before installing this product.
• Turn o all power supplying equipment before working on or inside the equipment.
• Use a properly rated voltage sensing device to conrm power is o.
DO NOT DEPEND ON THIS PRODUCT FOR VOLTAGE INDICATION
Failure to follow these instructions will result in death or serious injury.
AH07
RS-485 to RS-232 Converter
OPERATION
The AH07 converts the RS-485 output signal from a 2-wire power meter into a signal
compatible with a host device that has an RS-232 port (e.g. PC, data acquisition
device). Up to 31 RS-485 devices can be daisy chained to a single AH07 converter. The
host device acts as the power supply. The AH07 requires DTR and RTS connected to
the power supply for operation.
DIMENSIONS
2.6”
(67 mm)
1.3”
(32 mm)
NOTICE
• This product is not intended for life or safety applications.
• Do not install this product in hazardous or classified locations.
• The installer is responsible for conformance to all applicable codes.
WIRING
• The terminal’s voltage and current ratings are compatible with the
requirements of the EIA RS-485 communications standard.
• Maximum baud rate is 19.2 kB.
Host Device with
RS-232 connection
port
(PC or data
collection device)
+
-
S
INSTALLATION
1. Disconnect power to the power meter and the host device.
2. Connect the AH07 to the RS-232 port on the host device.
3. Wire the rst meter to the AH07 slave port. Observe +, –, and S polarity as shown
below. Use a 120Ω terminator between + and – (provided with the AH07).
4. If desired, daisy chain up to 31 meters or other 2-wire RS-485 devices (only
4 devices shown below). Terminate the nal device in the chain with a 120Ω
terminator.
Shielded cable suitable for panel
voltage and conditions
Up to 31 RS-485 devices in a daisy chain
120Ω terminator on
the AH07 converter
and the
last device of the daisy
chain
+
–
S
Shield wire
Z204942- 0C PAGE 1 ©2011 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com 07111