Venmar Solo 1.5, Solo 2.0, Duo 1.9, Duo 1.2, Duo 1.4 Installer Manual

Page 1
03309-04/10/08
Installer Manual
Ventilation Systems for residential use only
Duo 1.2 (part #: 43710)
Duo 1.4 (part #: 43700)
Duo 1.9 (part #: 45700)
Solo 1.5 (part #: 43720 and 43725)
Solo 2.0 (part #: 45720 and 45725)
VB0013
VB0012
Page 2
2
1.0 SERVICE ............................................................................................4
1.1 3-D Drawing ................................................................................4
1.2 Parts Ordering Chart....................................................................5
1.3 Technical Support ........................................................................5
2.0 SIZING ................................................................................................6
3.0 UNIT TYPE & DEFROST SETTING VS GEOGRAPHICAL LOCATION ..7
4.0 TECHNICAL DATA................................................................................8
4.1 Air Distribution (Normal Operation)..............................................8
4.2 Air Distribution (Defrost and/or Filtration Mode) ..........................8
4.3 Performance Charts ................................................................9-11
4.4 Dimensions ................................................................................12
4.5 Controls and Link Options..........................................................12
4.6 Specifications ............................................................................12
5.0 TYPICAL INSTALLATIONS ..................................................................13
5.1 Fully Ducted System ..................................................................13
5.2 Exhaust Ducted System
(Source Point Ventilation)
..................13
5.3 Simplified
(Volume Ventilation)
..................................................13
6.0 INSTALLATION....................................................................................14
6.1 Locating and Mounting the Unit ................................................14
6.2 Planning of the Ductwork ..........................................................14
6.3 Calculating the Duct Size ..........................................................15
6.3.1 Example Calculation ........................................................15
6.3.2 Example of a Design for a Fully Ducted System ............15
6.4 Installing the Ductwork and Registers ......................................16
6.4.1 Fully Ducted System........................................................16
6.4.2 Exhaust Ducted System (Source Point Ventilation) ........16
6.4.3 Simplified Installation (Volume Ventilation)......................17
6.5 Connecting the Duct to the Unit ................................................18
6.6 Installing the Exterior Hoods ......................................................19
6.7 Connecting the Drain (Solo only) ..............................................20
7.0 CONTROL DEVICES ..........................................................................21
7.1 Main Controls ............................................................................21
7.2 Optional Controls ......................................................................21
7.3 Other Features ..........................................................................22
Page 3
3
Table of Contents (cont’d)
About this Manual
8.0 INSTALLATION OF THE CONTROLS ..................................................22
8.1 Dimensions and Specifications ................................................22
8.2 Installation of the Main Control ..........................................22-23
8.3 Installation of the Wireless Push button and Receiver ............24
8.4 Electrical Connection to Optional Controls ..............................25
8.5 Electrical Connection to the Furnace ......................................25
9.0 WIRING DIAGRAMS ....................................................................26-27
10.0 AIR FLOW BALANCING ................................................................28
11.0 OVERALL VERIFICATION ..................................................................29
11.1 Main Controls ..........................................................................29
11.2 Optional Controls ....................................................................30
12.0 MAINTENANCE / INSTRUCTIONS FOR USER....................................30
13.0 TROUBLESHOOTING ....................................................................31-32
14.0 REFERENCES....................................................................................32
This manual uses the following symbols to emphasize particular information:
NOTE: Indicates supplementary information needed to fully complete an instruction.
WARNING
Identifies an instruction which, if not followed, might cause serious personal injuries including possibility of death.
!
CAUTION
Denotes an instruction which, if not followed, may severely damage the unit and/or its components.
Page 4
4
1.1 3-D DRAWING
1.0 Service
5
Unit shown in normal position.
1
VL0007
Page 5
5
1.2 PARTS ORDERING CHART
1.0 Service (cont’d)
TO ORDER PARTS: Contact your local distributor.
No Description SOLO 1.5 SOLO 2.0 DUO 1.2 DUO 1.4 DUO 1.9
(A) 43720 (A) 45720 43710 43700 45700
(B) 43725 (B) 45725 1 Double Collar Port #2 02257 02257 02257 02257 02257 2 Damper #1 (kit) 12454 12454 12454 12454 12454 3 Damper Rod (kit) 13037 13037 13037 13037 13037 4 Electronic Board & spacers (kit) 13038 13038 13039 13039 13039 5 Thermistor (kit) 12895 12895 12895 12895 12895
6 Door Latches & screws
00886 (2) 00886 (2) 00886 (2) 00886 (2) 00886 (2)
00601 (4) 00601 (4) 00601 (4) 00601 (4) 00601 (4) 7 Damper Actuator Assembly 13734 13734 13734 13734 13734 8 Basic Filter 03308 03308 03308 03308 03308 9 Blower Assembly 12908 12912 12909 12909 12911
10 Square Damper (kit) 13033 13033 13033 13033 13033 11 Top Wheel 02238 02238 02238 02239 02239 12 Motor 12109 12157 12109 12109 12157 13 Bottom Wheel 02240 02240 02239 02239 02240 14 Door Ass’y (including 15 to 17) 13346 13346 13346 13346 13346 15 Door Latches (keeper) 00887 (2) 00887 (2) 00887 (2) 00887 (2) 00887 (2)
& Screws 00601 (4) 00601 (4) 00601 (4) 00601 (4) 00601 (4) 16 Label 03328 03328 03328 03328 03328 17 Hinge Ass’y (kit) 13036 13036 13036 13036 13036 18 Pleated Optional Filter 03316 03316 03316 03316 03316
Charcoal Optional Filter 03315 03315 03315 03315 03315
Electronic Optional Filter 03314 03314 03314 03314 03314 19 Thermal Wheel N/A N/A 13045 13044 13045
20 Recovery Core
(A) 03322 (A) 03322
N/A N/A N/A
(B) 03311 (B) 03311 21 Balancing Double Collar Port 02256 02256 02256 02256 02256 22 Balancing Damper 02253 02253 02253 02253 02253 23 Snap Bushing DP-750 03324 (2) 03324 (2) 03324 (2) 03324 (2) 03324 (2)
& O-Ring 03310 (4) 03310 (4) 03310 (4) 03310 (4) 03310 (4) 24 Drain Connector (kit) 03203 03203 N/A N/A N/A 25 Door Switch (SPST), E69 10A 01825 01825 01825 01825 01825
Please take note that parts not listed are not available; those parts require assembly knowledge that only manufacturer can guarantee.
For assistance, call on weekdays, 8:30 AM to 5:00 PM (Eastern Standard Time).
NOTE: Do not call this number for ordering parts.
Canada & USA: 1-800-649-0372 (toll free)
1.3 TECHNICAL SUPPORT (FOR ASSISTANCE)
Page 6
6
These are the two most common methods used to evaluate the ventilation needs of a house:
CSA F326 and Canadian Building Code:
• High speed: 10 cfm per room 20 cfm for the master bedroom and the basement
• Low speed: 40-60% of high speed
ASHRAE Standard 62-2001:
• 0.35 air change per hour
Refer to ventilation code of your area to determine which method to use.
Example:
2.0 Sizing
1320 ft
2
1320 ft
2
CSA F326
Kitchen (10 cfm) Dining room (10
cfm)
Living room (10
cfm)
family room (10
cfm)
Master bedroom (20
cfm)
Bedroom #1 (10
cfm)
Bedroom #2 (10
cfm)
Bedroom #3 (10
cfm)
Bathroom #1 (10
cfm)
Bathroom #2 (10
cfm)
Bathroom #3 (10
cfm)
Laundry room (10
cfm)
Basement (20 cfm)
Total 150
cfm
ASHRAE Standard 62-1989
Volume of basement 10560 ft
3
Volume of main floor 10560 ft
3
Volume of second floor 10560 ft
3
Total volume 31680 ft
3
x 0.35/h
11090 ft3/h
÷ 60 (min/h)
Total 185 cfm
1320 ft
2
Second floor
Main floor
Basement
Master Bedroom
Bedroom #1
Bathroom
#1
Bedroom #2
Bathroom
#2
Bedroom #3
Basement
VH0021A
Laundry room
Bathroom
Living room
Family room
#3
Kitchen
Dining room
Page 7
7
3.0
Unit Type & Defrost Setting vs Geographical Location
WHITEHORSE
JUNEAU
HAY RIVER
YELLOWKNIFE
Prince Rupert
GRANDE PRAIRIE
FORT MCMURRAY
ZONE A
FORT SMITH
EDMONTON
PRINCE ALBERT
SASKATOON
JASPER
KAMLOOPS
CALGARY
PENTICTON
REGINA
LETHBRIDGE
HELENA
VICTORIA
OLYMPIA
WINNIPEG
SALEM
BOISE
BISMARCK
SALT LAKE CITY
SAULT STE MARIE
ST. PAUL
DES MOINES
MADISON
TIMMINS
HARRISBURG
SACRAMENTO
DENVER
TOPEKA
SUDBURY
TORONTO
DETROIT
INDIANAPOLIS
SANTA FE
SPRINGFIELD
OKLAHOMA CITY
PHOENIX
COLUMBUS
NASHVILLE
ATLANTA
BATON ROUGE
AUSTIN
COLUMBIA
RALEIGH
WASHINGTON
OTTAWA
NORTH BAY
VAL-DOR
CHICOUTIMI
HARTFORD
CHIBOUGAMAU
MONTRÉAL
QUEBEC
BOSTON
GOOSE BAY
LABRADOR CITY
SEPT-ILES
MATANE
GASPÉ
BATHURST
ST-JOHN
HALIFAX
CHARLOTTETOWN
ST JO
ZONE C
ZONE B
RENO
ZONE A Solo is recommended.
Set :”extended defrost”
according to Section 9.
ZONE B Solo is recommended but if a Duo unit is used, it has to
be oversized (because of its high humidity transfer efficiency).
Set “
extended defrost” according to Section 9.
ZONE C Solo or Duo (any models). “Extended defrost” not required
(factory defrost strategy pre-set).
SYMPTOM SOLUTION
(condensation)
Indoor air quality problem DUO
and / or
Excess moisture problem DUO
and/or
Important excess moisture problem SOLO
Q
ZONE B & C SELECTION CHART
NORTH AMERICA
0013 V
VN0001
Page 8
9
8VF0017
8
4.1 AIR DISTRIBUTION (NORMAL OPERATION)
4.2 AIR DISTRIBUTION (DEFROST AND/OR FILTRATION MODE)
4.0 Technical Data
6
SOLO
DUO
STALE AIR FROM BUILDING
SOLO
FILTERED AIR TO BUILDING
DUO
FRESH AIR FROM OUTSIDE
STALE AIR FROM BUILDING
FRESH AIR FROM OUTSIDE
FRESH AIR TO BUILDING
STALE AIR TO OUTSIDE
FRESH AIR TO BUILDING
STALE AIR TO OUTSIDE
STALE AIR FROM BUILDING
FILTERED AIR TO BUILDING
STALE AIR FROM BUILDING
SOLO units
DUO units
Celcius (˚C)
-5
-15
-27
Fahrenheit (˚F)
23
5
-17
Defrosting (min.)
6 6 6
Operation time
(min.)
between each defrost cycle
60 32 20
Defrosting (min.)
10 10 10
Operation time
(min.)
between each defrost cycle
30 20 15
Outside Temperature Defrost Cycles Extended Defrost Cycles
Celcius (˚C)
-5
-15
-27
Fahrenheit (˚F)
23
5
-17
Defrosting (min.)
9 9 9
Operation time
(min.)
between each defrost cycle
60 32 20
Defrosting (min.)
10 10 10
Operation time
(min.)
between each defrost cycle
30 20 15
Outside Temperature Defrost Cycles Extended Defrost Cycles
VF001
VF001
VF001
Page 9
9
4.0 Technical Data (cont’d)
4.3 PERFORMANCE CHARTS
MODEL NUMBER: SOLO 1.5
Electrical requirements: 120 volts, 1.3 amps. Exhaust air transfer ratio: 0.01
External Static Pressure - Pascals
(250 Pascals = 1” of water)
Gross Air Flow -L/s (0.47L/s = 1cfm)
ENERGY PERFORMANCE
Supply Net Average Sensible Recovery Apparent Sensible Latent Recovery Temperature Air Flow Power Efficiency Effectiveness Moisture Transfer °C °F L/s cfm watts % %
0 32 31 66 85 69 81 -0.01 0 32 56 119 124 60 70 -0.01 032
-25 -13 37 78 114 62 80 0.08
-25 -13
Total Recovery Efficiency
35 95 Not tested 35 95
COOLING
HEATING
VENTILATION PERFORMANCE
External Static Net Supply Gross Air Flow
Pressure Air Flow Supply Exhaust
Pa in. w.g. L/s cfm L/s cfm L/s cfm
25 0.1 83 175 83 176 82 175 50 0.2 79 168 80 169 78 165
75 0.3 75 159 75 159 75 158 100 0.4 71 150 71 151 69 146 125 0.5 64 136 64 136 60 127 150 0.6 60 126 60 127 48 103 175 0.7 53 113 53 113 38 80 200 0.8 43 91 43 91 21 45
Supply (l/s) Exhaust (l/s)
External Static Pressure - Pascals
(250 Pascals = 1” of water)
225
200
175
150
125
100
75
50
25
0
05025 75 100 125 150
VG0011
MODEL NUMBER: SOLO 2.0
Electrical requirements: 120 volts, 2.1 amps. Exhaust air transfer ratio: 0.01
VENTILATION PERFORMANCE
External Static Net Supply Gross Air Flow
Pressure Air Flow Supply Exhaust
Pa in. w.g. L/s cfm L/s cfm L/s cfm
25 0.1 110 234 112 237 112 237 50 0.2 104 219 105 223 106 225
75 0.3 98 208 100 211 99 210 100 0.4 89 189 91 192 91 193 125 0.5 84 177 85 180 82 174 150 0.6 71 151 72 153 71 149 175 0.7 64 136 65 138 44 94
ENERGY PERFORMANCE
Supply Net Average Sensible Recovery Apparent Sensible Latent Recovery Temperature Air Flow Power Efficiency Effectiveness Moisture Transfer °C °F L/s cfm watts % %
0 32 56 119 124 60 70 -0.01 0 32 86 182 197 53 62 -0.01
-25 -13 37 78 114 62 80 0.08
-25 -13
Total Recovery Efficiency
35 95 Not tested 35 95
COOLING
HEATING
Supply (l/s) Exhaust (l/s)
Gross Air Flow -L/s (0.47L/s = 1cfm)
225
200
175
150
125
100
75
50
25
0
VG0010
05025 75 100 125
150
Page 10
10
4.3 PERFORMANCE CHARTS (CONTD)
4.0 Technical Data (cont’d)
External Static Pressure - Pascals
(250 Pascals = 1” of water)
225
200
175
150
125
100
75
50
25
0
05025 75 100 125
150
MODEL NUMBER: DUO 1.2
Electrical requirements: 120 volts, 1.4 amps. Exhaust air transfer ratio: 0.01
VENTILATION PERFORMANCE
External Static Net Supply Gross Air Flow
Pressure Air Flow Supply Exhaust
Pa in. w.g. L/s cfm L/s cfm L/s cfm
25 0.1 62 131 62 133 64 137 50 0.2 59 125 60 127 61 130
75 0.3 58 123 58 124 58 123 100 0.4 54 114 55 116 55 117 125 0.5 51 108 52 110 50 107 150 0.6 45 95 45 96 47 99 175 0.7 39 83 39 84 40 85 200 0.8 31 65 31 66 29 62
ENERGY PERFORMANCE
Supply Net Average Sensible Recovery Apparent Sensible Latent Recovery Temperature Air Flow Power Efficiency Effectiveness Moisture Transfer °C °F L/s cfm watts % %
0 32 32 68 108 77 87 0.61 0 32 56 119 156 71 81 0.56 032
-25 -13 51 108 189 66 82 0.69
-25 -13
Total Recovery Efficiency
35 95 31 66 103 75 35 95 55 117 151 69
COOLING
HEATING
Gross Air Flow -L/s (0.47L/s = 1cfm)
Supply (l/s) Exhaust (l/s)
External Static Pressure - Pascals
(250 Pascals = 1” of water)
MODEL NUMBER: DUO 1.4
Electrical requirements: 120 volts, 1.4 amps. Exhaust air transfer ratio: 0.02
VENTILATION PERFORMANCE
External Static Net Supply Gross Air Flow
Pressure Air Flow Supply Exhaust
Pa in. w.g. L/s cfm L/s cfm L/s cfm
25 0.1 69 145 70 148 78 165 50 0.2 65 137 66 140 72 153
75 0.3 60 127 61 129 65 138 100 0.4 57 120 58 123 60 127 125 0.5 49 104 50 106 49 104 150 0.6 43 91 44 93 42 89 175 0.7 30 64 31 66 31 66 200 0.8 22 46 22 47 23 49
ENERGY PERFORMANCE
Supply Net Average Sensible Recovery Apparent Sensible Latent Recovery Temperature Air Flow Power Efficiency Effectiveness Moisture Transfer °C °F L/s cfm watts % %
0 32 32 68 110 70 80 0.79 0 32 47 100 164 65 74 0.67 0 32 57 121 172 64 72 0.60
-25 -13 29 61 120 64 79 0.65
-25 -13
Total Recovery Efficiency
35 95 31 66 104 69 35 95 57 121 168 61
COOLING
HEATING
Supply (l/s) Exhaust (l/s)
Gross Air Flow -L/s (0.47L/s = 1cfm)
225
200
175
150
125
100
75
50
25
0
VG0009
05025 75 100 125
150
Page 11
11
4.3 PERFORMANCE CHARTS (CONTD)
4.0 Technical Data (cont’d)
MODEL NUMBER: DUO 1.9
Electrical requirements: 120 volts, 2.2 amps. Exhaust air transfer ratio: 0.01
External Static Pressure - Pascals
(250 Pascals = 1” of water)
VENTILATION PERFORMANCE
External Static Net Supply Gross Air Flow
Pressure Air Flow Supply Exhaust
Pa in. w.g. L/s cfm L/s cfm L/s cfm
25 0.1 97 206 98 208 100 233 50 0.2 95 202 96 204 106 224
75 0.3 89 189 90 191 100 211 100 0.4 85 180 86 182 94 199 125 0.5 80 169 81 171 89 189 150 0.6 74 157 75 159 81 173 175 0.7 65 138 66 139 73 156 200 0.8 56 119 57 120 59 125 225 0.9 34 71 34 72 26 56
ENERGY PERFORMANCE
Supply Net Average Sensible Recovery Apparent Sensible Latent Recovery Temperature Air Flow Power Efficiency Effectiveness Moisture Transfer °C °F L/s cfm watts % %
0 32 56 119 156 71 81 0.56 0 32 84 178 230 65 72 0.46 032
-25 -13 51 108 189 66 82 0.69
-25 -13
Total Recovery Efficiency
35 95 55 117 151 69 35 95
COOLING
HEATING
Gross Air Flow -L/s (0.47L/s = 1cfm)
Supply (l/s) Exhaust (l/s)
225
200
175
150
125
100
75
50
25
VG0010
0
05025 75 100 125
150
Page 12
12
4.0 Technical Data (cont’d)
Main controls:
• Venta
• Supra
• Ultima
Optional controls:
• 20/40/60-minute push-button timer
• 20-minute wireless push-button timer
• 60-minute crank timer
• Dehumidistat
Link options:
• Furnace interlock (used with forced air systems)
• Interface for the
Perfect
Climate Comfort Center™
(Honeywell control, W8900)
4.5 CONTROLS AND LINK OPTIONS
4.6 SPECIFICATIONS
Model
Weight Port Diameter
Drain Diameter
Solo 1.5
71 lbs (32 kg)
6” (152 mm)
1/2” (12 mm)
Solo 2.0
73 lbs (33 kg)
6” (152 mm)
1/2” (12 mm)
Duo 1.2
79 lbs (36 kg)
6” (152 mm)
N/A
Duo 1.4
75 lbs (34 kg)
6” (152 mm)
N/A
Duo 1.9
77 lbs (35 kg)
6” (152 mm)
N/A
Installation Chains, springs and hooks (provided with the unit). Motor Speed High and low speed factory set (optional increased or decreased low speed). Electrical supply 120 V, 60 Hz 120 V, 60 Hz 120 V, 60 Hz 120 V, 60 Hz 120 V, 60 Hz Power
150 watts 240 watts 160 watts 160 watts 250 watts
Consumption
4.4 DIMENSIONS
6" (152 mm)
VK0029
30 1/4" (768 mm)
17 1/8" (435 mm)
16 1/2" (419 mm)
Page 13
13
5.0 Typical Installations
(Primarily for homes with radiant hot water or electric baseboard heating. See figure 1.)
Moist, stale air is exhausted from the high humidity areas in the home, such as bathrooms, kitchen and laundry room. Fresh air is supplied to bedrooms and principal living areas.
The use of bathroom fans and a range hood is suggested to exhaust stale air.
Homes with more than one level require at least one exhaust register at the highest level.
5.1 FULLY DUCTED SYSTEM
There are three (3) common installation methods.
*Installations may vary according to the model number and the position (normal or reverse) in which the unit is installed.
figure 1
See 6.4.1 for details
5.2 EXHAUST DUCTED SYSTEM
(SOURCE POINT VENTILATION)
(For homes with forced air heating. See figure 2.)
Moist, stale air is exhausted from the high humidity areas in the home, such as bathrooms, kitchen and laundry room. Fresh air is supplied to the cold air return or the supply duct of the furnace. The use of bathroom fans and a range hood is suggested to exhaust stale air.
Homes with more than one level require at least one exhaust register at the highest level. NOTE: For this type of installation, it is not essential
that the furnace blower runs when the unit is in operation, but we recommend it.
See 6.4.2 for details
figure 2
5.3 SIMPLIFIED
(VOLUME VENTILATION)
(For homes with forced air heating. See figure 3.)
Fresh air and exhaust air flow through the furnace ducts which simplifies the installation.
The use of bathroom fans and a range hood is suggested to exhaust stale air.
NOTE: For this type of installation, the furnace
blower should be running when the unit is in operation.
0007
figure 3
See 6.4.3 for details
VH0002
VH0006
VH
Page 14
6.2 PLANNING OF THE DUCTWORK
14
6.0 Installation
INSPECT THE CONTENTS OF THE BOX
Inspect the exterior of the unit for shipping damage. Ensure that there is no damage to the door, door
latches, door hinges, dampers, duct collars, cabinet, etc.
Inspect the interior of the unit for damage. Ensure that the fan motor assembly, recovery module,
insulation, dampers, damper actuator and condensation tray (Solo) are all intact.
If the unit was damaged during shipping, contact your local distributor. (Claim must be made within 24 hours after delivery.)
Use checklist included with the unit to ensure that no parts are missing.
6.1 LOCATING AND MOUNTING THE UNIT
NOTE:
Please note that the unit can be installed in either the “normal” or “reverse” (upside down)
position.
Choose an appropriate location for the unit:
Within an area of the house where the temperature is above 10°C / 50°F (basement, attic, furnace room, laundry room, etc.).
Away from living areas (dining room, living room, bedroom), if possible.
So as to provide easy access to the interior cabinet and to the control panel on the side of the unit.
Close to an exterior wall, so as to limit the length of the insulated flexi­ble duct to and from the unit.
Close to a drain. If no drain is close by, use a pail to collect run-off. (Solo models only.)
Away from hot chimneys, electrical panel and other fire hazards.
Allow for a power source (standard outlet).
Hang the unit with the 4 chains and springs provided (see figures 4 and 5).
figure 4
figure 5
figure 6
CAUTION
Make sure the unit is level, with a 1/8’’ (3 mm) tilt backwards (see figure 6).
a) Follow the instructions in Section 6.3 next page to determine the appropriate duct diameters for your
system.
b) Keep it simple. Plan for a minimum number of bends and joints. Keep the length of insulated duct to
a minimum.
c) Do not use wall cavities as ducts. Do not use branch lines smaller than 4” (102 mm) Ø. d) Do not ventilate crawl spaces or cold rooms. Do not attempt to recover the exhaust air from a dryer or
a range hood. This would cause clogging of the recovery module. Use sheet metal for the kitchen exhaust duct.
e) Be sure to plan for at least one exhaust register on the highest lived-in level of the house if it has 2
floors or more.
1/8"
(3 mm)
VD0037
VD0038
VD0039A
level
Page 15
15
6.0 Installation (cont’d)
Use the table below to ensure that the ducts you intend to install will be carrying air flows at or under the recommended values. Avoid installing ducts that will have to carry air flows near the
maximum values and never install a duct if its air flow exceeds the maximum value.
NOTE: Examples 6.2.1 and 6.2.2 use imperial measures.
The same calculation applies to metric measures.
6.3.1 Example of calculation:
Problem: My installation requires two exhaust registers (one for the kitchen, one for the bathroom). I will connect these registers to a main duct which will connect to the unit (high speed performance value of 140 cfm). What size of duct should I use for the main exhaust duct and for the two end branches leading to the registers? (See figure 7.)
Solution: Simplified method.
(For a more detailed method of calculating duct size refer to the
ASHRAE or HRAI HANDBOOK). Main duct:
Table above indicates a 6” Ø duct: recommended air flow: 120 cfm; maximum air flow: 180 cfm. The high speed air flow of 140 cfm is close enough to the recommended value (120) and far enough away from the maximum value (180). Therefore a 6”Ø duct or larger is an appropriate choice for the main exhaust duct.
End branches: Each end branch will have to transport an air flow of 70 cfm (140 divided by 2). Table above indicates a 5ӯ duct: recommended air flow: 75 cfm; maximum air flow: 110 cfm. The high speed air flow of 70 cfm is close enough to the recommended value (75) and far enough away from the maximum value (110). Therefore a 5ӯ duct or larger is an appropriate choice for the 2 end branches.
NOTE: A 4ӯ duct would have been too small because the maximum acceptable value for a 4ӯ
duct is 60 cfm.
6.3 CALCULATING THE DUCT SIZE
end
branches
main branch
6”ø 140 cfm
5”ø
70 cfm
4”(102 mm) 40 cfm 19 l/s 68 m3/h 60 cfm 28 l/s 102 m3/h 5”(127 mm) 75 cfm 35 l/s 127 m3/h 110 cfm 52 l/s 187 m3/h 6”(152 mm) 120 cfm 57 l/s 204 m3/h 180 cfm 85 l/s 306 m3/h 7”(178 mm) 185 cfm 87 l/s 314 m3/h 270 cfm 127 l/s 459 m3/h 8”(203 mm) 260 cfm 123 l/s 442 m
3
/h 380 cfm 179 l/s 645 m3/h
Duct Recommended Maximum
Diameter Air Flow Air Flow
figure 7
6.3.2 Example of a design for a fully ducted system for a unit having a high speed performance of 222 cfm (See figure 8).
4” Ø
42 cfm
6” Ø
129 cfm
5” Ø
65 cfm
5” Ø
6” Ø
93 cfm
5”
6”
7”
7”
6”
6”
6”
4”
4”
4”
4”
4” Ø 42 cfm
6” Ø 84 cfm
6” Ø 96 cfm
6” Ø 138 cfm
7” Ø 222 cfm
7” Ø 222 cfm
VI0003
VI0004
Page 16
16
6.0 Installation (cont’d)
6.4 INSTALLING THE DUCTWORK AND REGISTERS
WARNING
Never install a stale air exhaust register in a room where there is a combustion device, such as a gas furnace, a gas water heater or a fireplace.
!
6.4.1 Fully Ducted System (as illustrated in Section 5.1)
Stale air exhaust ductwork:
Install registers in areas where contaminants are produced: kitchen, bathrooms, laundry room, etc.
Install registers 6 to 12 inches (152 to 305 mm) from the ceiling on an interior wall OR install them in the ceiling.
Install the kitchen register at least 4 feet (1.2 m) from the range.
If possible, measure the velocity of the air flowing through the registers. If the velocity is higher than 400 ft/min. (122 m/min), then the register type is too small. Replace with a larger one.
Fresh air distribution ductwork:
Install registers in bedrooms, dining room, living room and basement.
Install registers either in the ceiling or high on the walls with air flow directed towards the ceiling. (The cooler air will then cross the upper part of the room, and mix with room air before descending to occupant level.)
If a register must be floor installed, direct the air flow up the wall.
6.4.2 Exhaust Ducted System (Source Point Ventilation) (as illustrated in Section 5.2)
Stale air exhaust ductwork: (same as for Fully Ducted System, described on point 6.4.1) Fresh air distribution:
There are two methods for connecting the unit to the furnace:
Method 1: supply side connection
• Cut an opening into the furnace supply duct at least 18 inches (0.5 m) from the furnace.
• Connect this opening to the fresh air distribution port
of the HRV/ERV (use steel duct
, see figure 9).
• Make sure that the HRV/ERV duct forms an elbow inside the furnace ductwork.
• If desired, interlock (synchronize) the furnace blower operation with the HRV/ERV operation. (See Section 8.5).
Method 2: return side connection
• Cut an opening into the furnace return duct not less than 10 feet (3.1m) from the furnace (A+B).
• Connect this opening to the fresh air distribution port of the HRV/ERV (see figure 10).
NOTE:For Method 2, it is not essential that the furnace
blower runs when the unit is in operation, but we recommend it. If desired, synchronize the furnace blower operation with the HRV/ERV operation (see Section 8.5).
WARNING
When performing duct connection to the furnace,
installation must be done in accordance with all
applicable codes and standards.
Please refer to your local building code.
CAUTION
When performing duct connection to the furnace supply duct,
this duct must be sized to support
the additional airflow produced by the ERV/HRV
. Also, use a steel duct. It is recommended that the
ERV/HRV is running when the furnace is in operation to prevent backdrafting inside ERV/HRV.
!
minimum
18” (0.5 m)
Steel duct
figure 9
A+B = not less
than 10’ (3.1 m)
figure 10
VD0172
A
VD0108
B
Page 17
17
6.0 Installation
(cont’d)
6.4.3 Simplified installation
(Volume Ventilation) (as illustrated in Section 5.3)
There are two methods (figures 11 and 12) for connecting the unit to the furnace:
Method 1: return-supply Method 2: return-return
Stale air intake:
• Cut an opening into the furnace return duct (not less than 10 feet (3.1 m) from the furnace).
• Connect this opening to the stale air intake port on the HRV/ERV as shown.
Fresh air distribution: (same instructions as for Method 1 or Method 2, Section 6.4.2).
For Method 2 (return-return) make sure there is a distance of at least 3 feet (0.9 m) between the 2 connections to the furnace. NOTE: For Method 1, it is not essential to synchronize the furnace blower operation with the
unit operation, but we recommend it.
6.4 INSTALLING THE DUCTWORK AND REGISTERS (CONTD)
minimum 3’
(0.9 m)
Steel duct
minimum
18”
(0.5 m)
figure 12
figure 11
CAUTION
If using Method 2, make sure the furnace blower operation is synchronized with the unit operation! See Section 8.5.
WARNING
When performing duct connection to the furnace,
installation must be done in accordance with all
applicable codes and standards.
Please refer to your local building code.
!
A+B = not less
than 10’ (3.1 m)
A+B = not less
than 10’ (3.1 m)
CAUTION
When performing duct connection to the furnace ducts (Method 1),
these ducts must be sized to
support the additional airflow produced by the ERV/HRV
. Also, the supply duct must be a steel duct. It is recommended that the ERV/HRV is running when the furnace is in operation to prevent backdrafting inside ERV/HRV.
VD0171
A
B
A
B
Page 18
18
6.0 Installation (cont’d)
Insulated flexible duct
Use the following procedure for connecting the insulated flexible duct to the ports on the unit (exhaust to outside and fresh air from outside).
a) Pull back the insulation to expose the flexible duct. b) Connect the interior flexible duct to the port using a duct tie. c) Carefully seal the connection with duct tape. d) Pull the insulation over the joint and tuck it between the inner and outer rings of the double collar. e) Pull the vapor barrier over the insulation and over the outer ring of the double collar. f) Apply duct tape to the joint making an airtight seal.
Avoid compressing the insulation when you pull the tape tightly around the joint. Compressed insulation loses its R value and causes water dripping due to condensation on the exterior surface of the duct.
a) b) c) d), e) f)
Rigid duct:
Use duct tape to connect the rigid ducts to the ports.
Make sure that the 2 balancing dampers are left in a fully open position before
connecting the ducts to
these ports (fresh air distribution port and stale air exhaust port as shown on figure 13).
6.5 CONNECTING THE DUCT TO THE UNIT
CAUTION
Make sure that the vapor barrier on the insulated ducts does not tear during installation to avoid condensation within the duct.
VJ0001
VJ0002
VJ0003
VJ0004
VJ0005
CAUTION
Do not use screws to connect rigid ducts to the ports.
figure 13
VJ0007
Page 19
19
6.0 Installation (cont’d)
6.6 INSTALLING THE EXTERIOR HOODS
Choose an appropriate location for installing the exterior hoods:
a minimum distance of 6 feet (1.8 m) between the hoods to avoid cross-contamination
a minimum distance of 18 inches (457 mm) from the ground
Make sure the intake hood
is at least 6 feet (1.8 m) away from any of the following:
dryer exhaust, high efficiency furnace vent, central vacuum vent
gas meter exhaust, gas barbecue-grill
any exhaust from a combustion source
garbage bin and any other source of contamination
Refer to figure 14 for connecting the insulated duct to the hoods. Place the “FRESH AIR INTAKE” sticker, provided in the installation kit, on corresponding hood. An “Anti-Gust Intake Hood” should be installed in regions where a lot of snow is expected to fall.
VD0028
Exhaust
hood
Optional duct
location
Tape and duct tie
Intake
hood
6ӯ
(152 mm)
18”
(457 mm)
18” (457 mm)
6’
(1.8 m)
6’
(1.8 m)
18”
(457 mm)
figure 14
Page 20
20
6.7 CONNECTING THE DRAIN
(SOLO ONLY)
)
To drain
6.0 Installation (cont’d)
To install the drain fittings, punch the 2 knock-out sections located at the bottom of the unit.
In order to keep the drain pan intact, hand tighten the 2 plastic drain fittings to the unit using the gaskets, washers and
From the inside, install 2 snap bushings on top of the unit. Do not punch the 2
knock-out sections.
Cut 2 sections of plastic tubing, about 12” (305 mm) long and attach them to each drain fitting.
Join the 2 short sections to the “T” junction and main tube as shown.
Make a water trap loop in the tube to prevent the unit from drawing unpleasant odors from the drain source. Make sure this loop is situated BELOW the “T” as shown. This will prevent water from being drawn back up into the unit in case of negative pressure. Run the tube to the floor drain or to an alternative drain pipe or pail. Be sure there is a slight slope for the run-off.
Tie-wrap
12
3
4
5
6
Inside view
Inside view
VO0010
VO0008
12"(305 mm
VO0004
VO0011
VO0005
VO0012
Page 21
21
VENTA model
7.1 MAIN CONTROLS
7.0
Control Devices
SUPRA model
ULTIMA model
MODELS VENTA SUPRA ULTIMA
Off Position X X X Intermittent Exchange (40 min./ OFF -20 min./ON) X X Low Speed Continuous Exchange X X X High Speed Continuous Exchange X X X Intermittent Filtration (40 min./ filtration -20 min./exchange)
X
Low Speed Continuous Filtration X High Speed Continuous Filtration X
Mode Indicator X X Air Exchange Indicator X X Maximum Speed Humidity Control Indicator X X Flashing Maintenance Indicator X X
Sliding Button X
Push Button X X
SWITCHES INDICATORS MODELS
20/40/60-MINUTE PUSH-BUTTON TIMER:
This remote illuminated switch is typically installed in bathrooms, kitchen and laundry room to provide 20, 40 or 60 minutes of high speed ventilation at the push of a button.
20-MINUTE WIRELESS PUSH-BUTTON TIMER:
This remote control provides 20 minutes of high speed ventilation. There is no need for electrical connection between the transmitter and the receiver. The push-button timer can be installed in any room in the house. This type of push-button switch is easy to intall. It is powered from two 3-volt lithium batteries with an expected battery life of up to 3 years.
60-MINUTE CRANK TIMER:
This timer allows up to 60 minutes of high speed operation to be selected from a remote location.
DEHUMIDISTAT:
This optional control helps control maximum humidity level during fall, winter and spring. You will find a relative humidity % scale meant to reduce the window condensation problems.
7.2 OPTIONAL CONTROLS
Page 22
Voltage: 12 volts DC Dimensions: 5” x 5” x 1 3/8”
(127 mm x 127 mm x 35 mm)
INSTRUCTIONS:
1- Determine the location of the control.
The wall control must be installed in a central location on the main floor. Typical locations for these controls are kitchen, main hallways and family room.
2- Remove the button(s) and the cover plate of
the control.
8.2 INSTALLATION OF THE MAIN CONTROL
(V
ENTA
, S
UPRA
& U
LTIMA
)
CAUTION
Never install more than one main control per unit.
22
7.0
Control Devices (cont’d)
7.3 OTHER FEATURES
FURNACE INTERLOCK (for forced air heating system)
The furnace fan can be interlocked so that it will run simultaneously with the ventilation system to ensure proper distribution of fresh air throughout the house.
The Perfect Climate Comfort Center™
With the help of an interface, the operation of your ventilation system can be controlled by
The Perfect
Climate Comfort Center™
(Honeywell control, W8900).
PERMANENT MEMORY
Our electronic controls have a default memory feature in the event of a power outage. Even the date of the last service reminder is maintained as a convenience to the homeowner.
CONTROL UPGRADES
All controls can be used on any unit, so a Venta control can be upgraded to a Supra or an Ultima in the future.
8.1 DIMENSIONS AND SPECIFICATIONS (MAIN CONTROLS)
8.0
Installation of the Controls
FRONT VIEW
SIDE VIEW
Supra or Ultima
Venta
13/8"
(35 mm)
5" (127 mm)
5" (127 mm)
VC0016
VC0026
Page 23
23
3- Install the wall control 60 inches (1.5 m) from the floor and
leave a free space of at least 2 inches (5 cm) to the right of the control to allow user to slide out the control instructions.
Use the template provided in the control box to position the wire hole and the screw holes. Use the screws and the plastic anchors provided in the installation kit to secure the control. (See figure 15)
4- Connect the wires to the main control.
(See figure 16)
5- Make sure the instruction pull-out is in the occupant’s
language. If not, turn it to the other side. (See figure 17)
6- Re-install the cover plate and the buttons.
7- Connect the wires to their corresponding position inside the
electrical compartment. Make sure the connections of the unit and of the wall control correspond exactly. (See figure 18)
8- Connect the optional controls (if applicable) by referring to
Sections 8.3 and 8.4.
9- Do the appropriate connection to the furnace (if applicable) by
referring to Section 8.5.
10- NOTE: If you are in a cold region (zone A or B, as defined in Section 3.0), set up “extended defrost” by
removing jumper JU1F on the main circuit board inside the electrical compartment (see Section 9.0).
11- Plug in the unit and do the “overall verification” of the system as described in Section 11.0.
8.0
Installation of the Controls (cont’d)
Y
VD0026
5
)
8.2 INSTALLATION OF THE MAIN CONTROL (CONTD)
figure 15
figure 16
figure 17
figure 18
VD0025
2" (5 cm
" (1.
VC0061
VE0084
Page 24
CHECKING MEMORY
1. Press and hold the program button for about two seconds until indicator lights, then release (see drawing below).
2. Count the number of indicator blinks. This is the total number of push buttons programmed.
ERASING MEMORY
1. Press the program button and continue to hold it through the count of the push buttons.
2. Continue to hold the button after the count until the indicator blinks one more time (about five seconds after the count).
3. All push buttons programmed into memory will be
erased.
24
INSTRUCTIONS:
1- Determine the location of the receiver illustrated in figure 19.
Important:
• Mount receiver as high as possible for best radio range.
• Don’t mount the receiver or push button directly on metal, concrete or near metal studs. This can decrease radio range by shielding the signal.
• Keep the receiver away from motors, fans and other electrical devices that may cause interference and reduce radio range.
2- Use screws to attach the mounting bracket (see figure 20). 3- Snap the receiver onto the bracket (see figure 20). 4- Pull the antenna straight. 5- Connect the wires referring to Section 8.4. 6- Remove the plastic tab on the push button. 7- Program the memory of the receiver for each push button
(see “Programming Memory” below).
8- Determine the location of the push button. 9- Use the screws to attach the push button mounting bracket (see figure
21).
10- Snap the push button onto bracket.
8.3 INSTALLATION OF THE WIRELESS PUSH BUTTON AND RECEIVER
8.0
Installation of the Controls (cont’d)
PROGRAMMING MEMORY
1. Press and release the program button.
2. Program indicator will light for 3 seconds if there is room in memory for another push button (32 push buttons max.).
3. Within 3 seconds, press the push button. Indicator will flash as signal is received.
4. Repeat the above three steps for each additional push button.
NOTE: The switch on the back of each push button must be set at “INSTANT” position.
NOTE: Do not continue to press button or memo-
NOTE: The receiver can memorize each push button more than once. To prevent duplication of entries, program each push button into receiver only once.
figure 19
figure 20
figure 21
VC0062
VC0063
VC0064
VC0065
VC0066
VC0067
VC0065
Page 25
25
Standard furnace interlock wiring
8.4 ELECTRICAL CONNECTION TO OPTIONAL CONTROLS
8.0
Installation of the Controls (con’d)
D
J1
J3
R
C.
Y
R
S
)
SS
S
0085A
8.5 ELECTRICAL CONNECTION TO THE FURNACE
Alternate furnace interlock wiring
For a furnace connected to cooling system:
On some older thermostats, energizing the “R” and “G” terminals at the furnace has the effect of energiz­ing “Y” at the thermostat and thereby turning on the cooling system. If you identify this type of thermostat, you must use the “alternate furnace interlock wiring”. An additional control relay will then have to be installed.
WARNING
Never connect a 120-volt AC circuit to the terminals of the furnace interlock (standard wiring). Only use the low voltage class 2 circuit of the furnace blower control.
!
RECEIVE
+ - N.O. COM N.
WIRELE
MAIN PC BOAR
PUSH BUTTON
HUMIDIT
VE
NTROL OR
RANK TIME
PUSH-BUTTON SWITCHE
10 SWITCHES MAXIMUM
THERMOSTAT
Y
TERMINALS
HRV CONTROL CONNECTOR
J3
TWO WIRES
I OC OL Y R G BF F
COOLING SYSTEM
FOUR WIRES
TWO WIRES
heating only
W
R
G
C
Y
FURNACE
24-VOLT
TERMINAL BLOCK
VE0010A
W R G
987654321
Unit Control Module
9-PIN AMP PLUG
J1
124
GRAY BROWN
COM
RELAY
COOLING SYSTEM
568
4 WIRES
2 WIRES
heating only
FURNACE
24-VOLT
TERMINAL BLOCK
VE0009A
WRGY
W
R
R
G
C
Y
Y
*FURNACE INTERLOCK RELAY, PART # 12658
THERMOSTAT
TERMINAL
wiring nuts
GREEN
BLUE
2 WIRES
RED
NC NO
*FURNACE INTERLOCK
7
7
93
Page 26
A1
M1
M2
K1
RELAY
K2
RELAY
K5
RELAY
FAN
MOTOR
DAMPER
MOTOR
NEUTRAL
MEDNCHIGH
LOW
J1 6
J1 3
J1 4
J1 9
K4
RELAY
J3 1
J3 2
FURNACE BLOWER INTERLOCK
CLASS 2 CIRCUIT ONLY
ELECTRONIC ASSEMBLY
S1
120V 60Hz
FROM MAIN
J1 2
J1 1
J1 8
VE0018A
26
9.0
Wiring Diagrams
Models: SOLO 1.5 and 2.0
NOTES
1- Controls available. See Section 8.0 (Low voltage only, 12VDC)
2- The factory set wiring for blower speed selection is high and low.
Medium speed can be selected instead of low speed. Disconnect the
RED wire from the motor RED tap and connect it to the motor BLUE tap.
3- If any of the original wire, as supplied, must be replaced, use the
same or equivalent wire.
4- Use the factory supplied protective tubing.
5- The field wiring must comply with applicable codes, ordonnances and
regulations.
6- The furnace fan circuit must be class 2 circuit only.
LINE VOLTAGE
LOW VOLTAGE AND
FIELD WIRE
COLOR CODE
BK BLACK NC NO CONNECTION
BL BLUE O ORANGE
BN BROWN R RED
G GREEN W WHITE
GY GREY Y YELLOW
DEFROST TIME
JUMPERS TABLE MODEL DEFROST/VENTILATION
TYPE MINUTES
23°F 5°F -22°F
JU1A JU1B JU1C JU1D JU1E JU1F JU1G -5°C -15°C -27°C
IN OUT OUT OUT IN IN OUT
43720, 45720
6/60 6/32 6/20
43725, 45725
IN OUT OUT OUT IN OUT OUT
EXTENDED DEFROST
10/30 10/20 10/15
ALL TYPES
FUNCTION TABLE RELAY
MODE K1 K2 K4 K5
Intermittent 0001
Exchange Low 1010
Exchange High 1110
Circulation Low 1011
Circulation High 1111
Defrost Cycle 1111
Off 0001
0 = Relay coil is de-energized
1 = Relay coil is energized
Connection
Logic
WARNING
Risk of electrical shocks. Before performing any maintenance or servicing, always disconnect the unit from its power source.
!
A B C D E F G
2
1
JU 1
. . . .
. . . . . .
. . . .
C1
OPTIONAL
NOTE 5
NOTES 5, 6
OPTIONAL
NOTES 1, 5
WALL CONTROL
WALL CONTROL
WALL CONTROL
BKGRYRBKY
WALL CONTROL
FURNACE BLOWER
INTERLOCK
OVERRIDE SWITCH
OVERRIDE SWITCH
OVERRIDE LED
NOTE 4
1 2
A1
DEFROST
TEMPERATURE
ABCDEFG
JU1
SENSOR
M1
FF IOCOLYRG B
123
456789
J4
T1
R1
NEUTRAL
HIGH
GYOGRBL
X1
1
2
3
GYOGNCR
J3
GY
BN
LOW
BN
MEDIUM
R
7
4
12
FAN MOTOR
(NOTE 2)
BL
BL
9
O
6
3
J1
ELECTRONIC ASSEMBLY
X2 M2
BK
W
BLBLG
123
BLBLG
DAMPER MOTOR
G
POINT
MAIN EARTHING
W1
G
120V 60 Hz
W
LINE
NEUTRAL
NO
COM
NEMA-15P
5-15 PLUG
BK
SWITCH S1
DOOR INTERLOCK
BK
VE0017A
Page 27
27
9.0
Wiring Diagrams (cont’d)
Models: DUO 1.2, 1.4 and 1.9
BKGRYRBKY
NOTE 4
WALL CONTROL
WALL CONTROL
WALL CONTROL
WALL CONTROL
OVERRIDE SWITCH
OVERRIDE SWITCH
OVERRIDE LED
FURNACE BLOWER
INTERLOCK
NOTE 5
NOTE 5
OPTIONAL
NOTE 6
OPTIONAL
THERMAL WHE
ASSEMBLY
GROUND
NEUTRAL
LINE
CAPACITOR
DRIVING MOTOR
RT1
M3
BYPASS THERMAL ACTUATOR
R2 C2
X3
M1
X2 M2
GWR
BK
V
V
123
4
1
2
1
123
1
12
4
7
6
9
3
23
456789
2
3
123
Y
V
BN
NEUTRAL
MEDIUM
HIGH
LOW
FAN MOTOR
X1
GYOGRBL
GYOGNCR
BN
BN
C1
YYG
DAMPER MOTOR
R
V
O
Y
BN
BN
GY
BL
BK
T1
R1
A1
DEFROST
SENSOR
JU1
J4
J1
J2
J3
ABCDEFG
F
F
I
OC
OLY R
G
B
ELECTRONIC ASSEMBLY
MAIN EARTHING
POINT
G
BLBLG
BK
W
COM
120V 60 Hz
W1
G
W
NEMA-15P
5-15 PLUG
BK
DOOR INTERLOCK
SWITCH S1
NO
NEUTRAL
LINE
BK
VE0019A
GROUND
NEUTRAL
LINE
CAPACITOR
DRIVING MOTOR
RT1
M3
BYPASS THERMAL ACTUATOR
R2 C2
X3
GWR
BK
V
V
123
4
GROUND
NEUTRAL
LINE
CAPACITOR
DRIVING MOTOR
RT1
M3
BYPASS THERMAL ACTUATOR
R2/R3
C2
X3
GWR
BK
V
V
123
4
30
30
BODI
NE OR EASTER
N AIR DEVI
CES
SEE BOXES BELOW
JUMPERS TABLE MODEL
JU1A JU1B JU1C JU1D JU1E JU1F JU1G
IN IN OUT OUT IN IN OUT 43700, 45700, 43710
IN IN OUT OUT IN OUT OUT EXTENDED DEFROST
FUNCTION TABLE RELAY DEFROST
MODE K1&K4 K2 K3 K5
Intermittent 0001
Continuous Low 1010
Continuous High 1110K5 active only (-15°C<T<+10°C)
Circulation Low 1001
Circulation High 1101
Defrost Cycle 1101
Off 0001
0 = Relay coil is de-energized
1 = Relay coil is energized
NOTES
1- Controls available. See Section 8.0. (Low voltage only 12VDC)
2- Factory set wiring for blower speed selection is high and medium. Low speed can be selected
instead of medium speed. Disconnect the RED wire from the motor BLUE tap and connect it to
the motor RED tap.
3- If any of the original wire, as supplied, must be replaced, use the same or equivalent wire.
4- Use factory supplied protective tubing.
5- Field wiring must comply with applicable codes, ordonnances and regulations.
6- Furnace fan circuit must be class 2 circuit only.
DRIVING MOTOR DRIVING MOTOR DRIVING MOTOR
CAPACITOR RESISTOR
1.7 uF, 250 VAC 300 Ohms, 7W Bodine
1 uF, 330 VAC 400 Ohms, 10W Eastern Air Devices
1 uF, 250 VAC 800 Ohms, 8W Warner Electric
STANDARD EXTENDED
-5°C 9/60 min 10/30 min
-15°C 9/32 min 10/20 min
-27°C 9/20 min 10/15 min
Connection
Logic
LINE VOLTAGE
LOW VOLTAGE AND
FIELD WIRE
COLOR CODE
BK BLACK NC NO CONNECTION
BL BLUE O ORANGE
BN BROWN R RED
G GREEN-YELLOW V VIOLET
GY GREY W WHITE
Y YELLOW
WARNING
Risk of electrical shocks. Before performing any maintenance or servicing, always disconnect the unit from its power source.
!
A B C D E F G
2
1
JU 1
. . . .
. . . . . .
. . . .
NEUTRAL
J1 2
120V 60Hz
A1
S1
FROM MAIN
J1 1
M1
FAN
MOTOR
LOW
HIGH
NC
J1 6
J1 3
MEDIUM
J1 4
K2
K1
RELAY
RELAY
J1 8
M3
RT1
BYPASS
THERMAL ACTUATOR
J9 1
J1 7
K5 RELAY
DRIVING
J2 1
J1 5
M2
MOTOR
MOTOR
DAMPER
J2 2
FURNACE BLOWER INTERLOCK
K3
J3 1
RELAY
J2 3
K4
CLASS 2 CIRCUIT ONLY
J3 2
ELECTRONIC ASSEMBLY
RELAY
VE0020A
Page 28
28
WHAT YOU NEED TO BALANCE THE UNIT
A magnehelic gauge capable of measuring 0 to 0.5 inch of water (0 to 125 Pa) and 2 plastic tubes.
The balancing chart provided with the unit.
PRELIMINARY STAGES TO BALANCE THE UNIT
Seal all the unit ductwork with tape. Close all windows and doors.
Turn off all exhaust devices such as range hood, dryer and bathroom fans.
Make sure the balancing dampers are fully open.
Make sure all filters are clean (if it is not the first time you balance the unit).
BALANCING PROCEDURE
1. Set the unit to high speed: Make sure that the furnace blower is ON if the installation is in any way connected to the ductwork of the cold air return. If not, leave furnace blower OFF. If the outside temperature is below 0°C / 32°F, make sure the unit is not running in defrost while balancing. (By waiting 10 minutes after plugging the unit in, you are assured that the unit is not in a defrost cycle.) Disconnect the wire of the
bypass damper (Duo only).
2. Place the magnehelic gauge on a level surface and adjust it to zero.
3. Connect tubing from gauge to EXHAUST air flow pressure taps (see diagram). Be sure to connect the tubes to their appropriate
high/low
fittings. If the gauge drops below zero, reverse the tubing connections. NOTE: It is suggested to start with the exhaust air flow reading
because the exhaust has typically more restriction than the fresh air, especially in cases of fully ducted installations or source point ventilation. Place the magnehelic gauge upright and level. Record equivalent AIR FLOW of the reading according to the balancing chart.
4. Move tubing to FRESH air flow pressure taps (see diagram). Adjust the fresh air balancing damper until the fresh air flow is approximately the same as the EXHAUST air flow. If fresh air flow is less than exhaust air flow, then go back and adjust the exhaust balancing damper to equal the fresh air flow.
5. Secure both dampers in place with tape or with a fastening screw.
6. Write the required air flow information on a label and stick it near the unit for future reference (date, maximum speed air flows, your name, phone number and business address). Connect the wire
of the bypass damper (Duo only).
NOTE: The unit is considered balanced even if there is a difference of
+/- 10 cfm or +/- 5 l/s or 17 m
3
/h between the two air flows.
10.0
Air Flow Balancing
SOLO
Fresh air flow
Exhaust air flow
Exhaust air flow
Fresh air flow
NOTE: Always unplug bypass wire while balancing a Duo.
DUO
VP0009
VD0051
VP0010
VP0011
VE0021
VD0052
Page 29
29
VENTA
(6 different control scenarios to be tested)
11.1 MAIN CONTROLS
This procedure allows the installer to verify that all modes of operation are fully functional.
During the verification of a main control, make sure that all optional remote controls are inactive.
11.0
Overall Verification
Set the slider Set dehumidistat Results expected
switch to dial to fan speed / damper 1 off maximum counterclockwise motor off / closed 2 off maximum clockwise motor off / closed 3 min. maximum counterclockwise low speed / open 4 min. maximum clockwise high speed / open 5 max. maximum counterclockwise high speed / open 6 max. maximum clockwise high speed / open
Set air supply Set dehumidistat
Results expected
control to dial to
Fan Exchange Max speed
speed indicator indicator
(A)(B)
1 off maximum counterclockwise off *off off 2 off maximum clockwise off *off off 3 min. maximum counterclockwise low on off 4 min. maximum clockwise high on on 5 max. maximum counterclockwise high on off 6 max. maximum clockwise high on on
7 intermittent maximum counterclockwise
off 40 min *off 40 min off
low 20 min on 20 min off
8 intermittent maximum clockwise high on on
SUPRA
(8 different control scenarios to be tested)
ULTIMA
(14 different control scenarios to be tested)
Set air supply Set dehumidistat
Results expected
control to dial to
Fan Exchange Max speed
speed indicator indicator
(A)(B)
1 off maximum counterclockwise off *off off 2 off maximum clockwise off *off off 3 min. (green light) maximum counterclockwise low on off 4 min. (green light) maximum clockwise high on on 5 min. (red light) maximum counterclockwise low *off off 6 min. (red light) maximum clockwise high on on 7 max. (green light) maximum counterclockwise high on off 8 max. (green light) maximum clockwise high on on 9 max. (red light) maximum counterclockwise high *off off 10 max. (red light) maximum clockwise high on on
11
intermittent
maximum counterclockwise
off / 40 min. *off / 40 min. off
(green light) low / 20 min. on / 20 min. off
12
intermittent
maximum counterclockwise high on on
(green light)
13
intermittent
maximum counterclockwise
low / 20 min. on / 20 min. off
(red light) high / 40 min .*off / 40 min. off
14
intermittent
maximum counterclockwise high on on
(red light)
*The dampers are closed when
the exchange indicator is off.
*The dampers are closed when
the exchange indicator is off.
A
B
B
A
Page 30
20-MINUTE WIRELESS PUSH-BUTTON TIMER:
Activate the push button.
Results expected:
1. Indicator light goes “ON” while activating the push button.
2. Motor speed: high for 20 minutes.
3. Supra or Ultima wall con­trols: Air exchange indicator light goes “ON”.
NOTE:
To stop activation, push one more time.
60-MINUTE CRANK TIMER:
Activate the timer.
Results expected:
1. Motor speed: high for up to 60 minutes.
2. Supra or Ultima wall controls: Air exchange indicator light goes “ON”.
11.2 OPTIONAL CONTROLS
First, turn OFF the main control device before checking the remote optional controls.
30
11.0
Overall Verification (cont’d)
20/40/60-MINUTE PUSH-BUTTON TIMER:
Activate the push button. Within 2 seconds, push one time for 20 minutes, two times for 40 minutes or three times for a
60-minute activation.
Results expected:
1. Motor speed: high for 20, 40 or 60 minutes.
2. Indicator light goes “ON” and flashes every 5 seconds (one time to indicate a 20-minute operation, two times for a 40-minute, and three times for a 60-minute operation).
3. Supra or Ultima wall controls: Air exchange indicator light goes “ON”.
NOTE: To stop activation, push one more time.
DEHUMIDISTAT:
Turn dial to the maximum clock-
wise position (20%).
Result expected:
1. Motor speed changes to high.
• Review with the user the steps required for the regular maintenance of her/his ventilation
system. These steps are described in detail in the user manual:
• Warn the user of the necessity to rebalance the system following a major house renovation or follow-
ing the installation of any extra registers.
• Make sure the user understands how to use the main control as described in the user manual.
12.0
Maintenance / Instructions for User
FOUR TIMES A YEAR:
Inspect the intake hood, and clean if needed.
Clean the filters.
Clean the interior of the cabinet and clean the door.
Clean the condensation tray and inspect the drain tubing (SOLO only).
ONCE A YEAR:
Clean the recovery module (core or thermal wheel).
Clean the blades of the blower wheels if needed.
WARNING
Risk of electrical shocks. Before performing any maintenance or servicing, always disconnect the unit from its power source.
!
CAUTION
Do not oil the motor. It is already permanently lubricated.
20 min.
40 min.
60 min.
VC0007
VC0006
TURN
OFF
PAST
20
10
20
30
60
40
50
VC0017
Page 31
31
Problems Possible causes You should try this
1. Unit doesn't work. • The circuit board may • Unplug the unit. Disconnect the main
be defective. control and the optional(s) contol(s)
(If need be). Jump B and G terminals. Plug the unit. If the motor runs on high speed and the damper opens, the circuit board is not defective.
.
2. The damper actuator • The 9-pin connector may • Unplug the unit and check to make sure all the crimp
does not work. have a loose connection. connections are secured. Check the damper actuator
connections as well.
• The damper actuator may be • Feed 120 V directly to the damper actuator. If the defective. problem persists, replace the damper actuator.
• The circuit board may be • Replace the circuit board if the problem is not solved by defective. the above.
3. The wall control does • Erratic operation of the • Unplug the unit. Wait 30 seconds. Plug it back in. not work control every 8 seconds. OR the indicators flash. • The wires may be in reverse • Ensure that the color coded wires have been connected
position. to their appropriate places.
• The wires may be broken. • Inspect every wire and replace any that are damaged.
• There may be a short-circuit. • With the help of a multimeter, check for continuity.
• The wire in the wall OR the • Jump “B” and “G” (BLACK and GREEN). If unit switches wall control may be defective. to high speed, remove the wall control and test it right
beside the unit using another shorter wire. If the wall control works there, change the wire. If it doesn’t, change the wall control.
• The circuit board may • If the unit does not switch to high speed, replace the be defective. circuit board.
4. The dehumidistat • The dehumidistat or push • Jump the OL and OC terminals. If the does not work OR button may be defective. unit switches to high speed, remove the the 20/40/60-min. dehumidistat or push button and test it push-button timer right beside the unit using another shorter does not work OR its wire. If it works there, change the wire. indicator light does not If it doesn’t, change the dehumidistat or stay on. the push button.
Start-up troubleshooting:
NOTE: Be sure to unplug and inspect the unit before proceeding with these steps.
13.0
Troubleshooting
B G
VE0082
VE0081
OL OC
Page 32
32
Problems Possible causes You should try this
5. 20-min. wireless push • Plastic tab on batteries has not • Remove the tab, program memory of receiver and try button timer doesn’t work. been removed from push button. again (see Section 8.3).
• Poor location for push button • Use 1/4” to 1/2” wood shims to move off the surface or and/or receiver. try different locations.
• Light indicator flashes while • Low batteries. Open push button casing and change activating the push button. batteries. (Refer to user manual.)
• Push button batteries are dead. • Open push button casing and change batteries.
(Refer to user manual.)
• Push button not properly • Re-program the memory of the receiver (refer to programmed in receiver or the Section 8.3). switch on the back of the push button is not at “instant” position.
• Receiver not properly wired. • Ensure that the wires have been connected to their
appropriate places (see Section 8.4).
• The wires may be broken. • Inspect every wire and replace any that are damaged.
• There may be a short-circuit. • With the help of a multimeter, check for continuity.
6. The defrost cycle • Ice deposits may be hindering • Remove the ice. does not work the damper operation. (the fresh air duct is frozen OR the fresh air •The damper rod or the port • Inspect these parts and replace if necessary. distributed is very cold damper itself may be broken. OR the “AIR EXCHANGE” light flashes). • The damper actuator may • Plug in the unit and select “MIN” or “MAX”. Press the
be defective. door switch and see if the port damper opens. If it doesn’t
open, feed 120V directly to the damper actuator. If the
port damper still doesn’t open, replace the damper
actuator.
• The circuit board may • Unplug the unit. Unplug the defrost sensor wire (see J4 be defective. on electrical diagram Section 9.0). Plug the unit back in.
Select “MIN” and make sure the unit is adjusted for low speed operation (turn all dehumidistats maximum counterclockwise).
Wait 3 minutes. The unit should switch to high speed and the damper at the fresh air intake port should close (defrost mode). If this doesn’t happen, then replace the circuit board.
• The thermistor may be • If the defrost mode works well after having disconnected defective. the thermistor wire (above test), this means the thermistor
is probably defective. You should replace it.
13.0
Troubleshooting (cont’d)
14.0
References
D
• HVI, “Installation Manual for Heat Recovery Ventilators”, 1987 edition.
• ASHRAE 1984 Systems Handbook, chapter 11, “Air Distribution Design for Small Heating and Cooling Systems”.
R 2000
Venmar Quality
Assurance
LISTE
Loading...